V1379-E-DS-001_70769796

You might also like

Download as doc, pdf, or txt
Download as doc, pdf, or txt
You are on page 1of 6

Data Sheet

Control Cabinets

RIG/PLANT REFERENCE REFERENCE DESCRIPTION


Pride No 1 V1379 Mud Control Systems
ADDITIONAL CODE SDRL CODE TOTAL PGS
6.2 6 This document contains proprietary and confidential National Oilwell Norway AS
information which belongs to National Oilwell Varco; it is P.O. Box 168
REMARKS loaned for limited purposes only and remains the property
of National Oilwell Varco. Reproduction, in whole or in N-1371 ASKER
part; or use of this design or distribution of this information NORWAY
MAIN TAG NUMBER DISCIPLINE to others is not permitted without the express written
consent of National Oilwell Varco. This document is to be
returned to National Oilwell Varco upon request and in Phone +47 64 00 50 00
CLIENT PO NUMBER any event upon completion of the use for which it was Fax +47 66 90 23 53
loaned.
© Copyright National Oilwell Varco - 2009

CLIENT DOCUMENT NUMBER DOCUMENT NUMBER REV

V1379-E-DS-001 0

www.nov.com
Document number V1379-E-DS-001
Revision 0
Page 2 of 6

REVISION HISTORY

0 10.03.2009 For Information TOHE INLO TOHE


Rev Date (dd.mm.yyyy) Reason for issue Prepared Checked Approved

CHANGE DESCRIPTION

Revision Change description


0

www.nov.com
Document number V1379-E-DS-001
Revision 0
Page 3 of 6

TABLE OF CONTENTS

1 PLC / IO CABINETS........................................................................................................4
2 RIO CABINETS................................................................................................................5
3 MCC CABINET................................................................................................................ 6

www.nov.com
Document number V1379-E-DS-001
Revision 0
Page 4 of 6

1 PLC / IO CABINETS

INSTRUMENT
CONTROL CABINET
DATASHEET
TAG RELATED TO THIS DATASHEET:

Tag number 3D29704 / 3D21705


Description PLC Cabinet / IO cabinets

Drawing reference: V1379-MCS-G0001 / 0002 AND 0005 / 0006

DESCRIPTION: UNIT REQUIREMENTS NOTE MANUFACTURER DATA NOTE

GENERAL:

1 Manufacturer: NATIONAL OILWELL NORWAY


2 Manufacturer model no.:
3 Mounting: FLOOR
4 Dimensions (l x d x h): mm 800 x 800 x 2100
5 Weight: kg Approx. 250

ENCLOSURE:

6 Hazardous area: NON HAZARDOUS


7 Ex classification: N.A.
8 Degree of Protection (IEC 529): IP43
9 Material: SHEET STEEL
10 External painting: RAL 7035
11 Transport: TOP MOUNTED LIFTING LUGS
12 Access: FRONT
13 Rack/section size:
14 Cable entries: BOTTOM
15 Ventilation: FAN / FILTER
16 Lighting: YES
17 Power outlets: SERVICE OUTLETS
18 Bonding: YES

ELECTRICAL DATA:

19 Nom. voltage: V AC 220


20 Nom. frequency: Hz 60
21 Nom. power cons. non UPS: VA N.A.
22 Max. power cons. non UPS: VA N.A.
21 Nom. power cons. UPS: VA 800
22 Max. power cons. UPS: VA 1500
23 Heat dissipation: W 200
24 Minimum rated breaker: A 10
25 Short circuit current: kA N.A.
26 Earthing systems: PE, IE

ENVIRONMENT DATA:

27 Operating ambient temperature: deg C 0 - +40

28 Humidity: % LESS THAN 50% NON


CONDENSING
29 Environment: DRY AND CLEAN

NOTES:

www.nov.com
Document number V1379-E-DS-001
Revision 0
Page 5 of 6

2 RIO CABINETS

INSTRUMENT
CONTROL CABINET
DATASHEET
TAG RELATED TO THIS DATASHEET:

Tag number 3D21706 / 707 AND 3D24708


Description RIO cabinets

Drawing reference: V1379-MCS-G0007 // 0010 AND 0014 / 0015

DESCRIPTION: UNIT REQUIREMENTS NOTE MANUFACTURER DATA NOTE

GENERAL:

1 Manufacturer: NATIONAL OILWELL NORWAY


2 Manufacturer model no.:
3 Mounting: FLOOR
4 Dimensions (l x d x h): mm 800 x 600 x 2200
5 Weight: kg Approx. 250

ENCLOSURE:

6 Hazardous area: HAZARDOUS ZONE 2


7 Ex classification: II 3 G EEx nA de (ia) IIC T4
8 Degree of Protection (IEC 529): IP 56
9 Material: STAINLESS STEEL
10 External painting: N.A.
11 Transport: TOP MOUNTED LIFTING LUGS
12 Access: FRONT
13 Rack/section size:
14 Cable entries: BOTTOM
15 Ventilation: N.A.
16 Lighting: NO
17 Power outlets: NO
18 Bonding: YES

ELECTRICAL DATA:

19 Nom. voltage: V AC 220


20 Nom. frequency: Hz 60
21 Nom. power cons. non UPS: VA N.A.
22 Max. power cons. non UPS: VA N.A.
21 Nom. power cons. UPS: VA 500
22 Max. power cons. UPS: VA 1000
23 Heat dissipation: W 200
24 Minimum rated breaker: A 10
25 Short circuit current: kA N.A.
26 Earthing systems: PE, IE, IS

ENVIRONMENT DATA:

27 Operating ambient temperature: deg C 0 - +40

28 Humidity: % LESS THAN 50% NON


CONDENSING
29 Environment: DRY AND CLEAN

NOTES:

www.nov.com
Document number V1379-E-DS-001
Revision 0
Page 6 of 6

3 MCC CABINET

INSTRUMENT
CONTROL CABINET
DATASHEET
TAG RELATED TO THIS DATASHEET:

Tag number 3D23709


Description MCC cabinet

Drawing reference: V1379-MCS-G0003 / 0004

DESCRIPTION: UNIT REQUIREMENTS NOTE MANUFACTURER DATA NOTE

GENERAL:

1 Manufacturer: NATIONAL OILWELL NORWAY


2 Manufacturer model no.:
3 Mounting: FLOOR
4 Dimensions (l x d x h): mm 1200 x 800 x 2100
5 Weight: kg Approx. 325

ENCLOSURE:

6 Hazardous area: NON HAZARDOUS


7 Ex classification: N.A.
8 Degree of Protection (IEC 529): IP43
9 Material: SHEET STEEL
10 External painting: RAL 7035
11 Transport: TOP MOUNTED LIFTING LUGS
12 Access: FRONT
13 Rack/section size:
14 Cable entries: BOTTOM
15 Ventilation: FAN / FILTER
16 Lighting: YES
17 Power outlets: SERVICE OUTLETS
18 Bonding: YES

ELECTRICAL DATA:

19 Nom. voltage: V AC 440 / 3PH x 2


20 Nom. frequency: Hz 60
21 Nom. power cons. non UPS: VA N.A.
22 Max. power cons. non UPS: VA N.A.
21 Nom. power cons. UPS: VA N.A.
22 Max. power cons. UPS: VA N.A.
23 Heat dissipation: W 800
24 Minimum rated breaker: A 16 + 50
25 Short circuit current: kA N.A.
26 Earthing systems: PE

ENVIRONMENT DATA:

27 Operating ambient temperature: deg C 0 - +40

28 Humidity: % LESS THAN 50% NON


CONDENSING
29 Environment: DRY AND CLEAN

NOTES: