Professional Documents
Culture Documents
Polycab EHV Power Cable IEC 1
Polycab EHV Power Cable IEC 1
Polycab offers Extra high Voltage Cable with Copper as well as Aluminum conductor in the range of 66
KV to 220 KV for underground installation for 3 Phase AC circuit. Polycab’s rich experience and advance
technology made the cable superior to use for a service life of 40 years. These cables are mainly used
to supply power from the power station to distribution unit or substation.
Polycab has set up it’s largest High Voltage cable manufacturing plant in Halol, Gujarat districts near
Mumbai invested in state-of the art machines like Maillifer, Scolz, John Royale along with a most
modern testing facility. The plant is equipped with high automation for material feeding to avoid
contamination and electrical failure as well as high speed stranding machines for classic conductor
preparation.
CONDUCTOR
In house developed high conductive Copper or Aluminum is used for EHV Cable for highest degree of
transmission. Polycab supplies two types of coductors: Stranded compacted round and stranded
segmental Milliken conductor beyond 800 Sq.mm.
The large conductor divides into no. of segments followed by converging spirally to form a circular
conductor. The Combination of segmental structure suppress the skin effect and proximity effect
resulting low conductor resistance and improving the current rating capacity.
Upon request Polycab can supply water tight conductor with improved design.
CONDUCTOR SCREEN
The conductor screen consists of an extruded layer of semiconducting thermosetting compound which
completely covers the whole surface of the conductor and firmly bonded to the XLPE insulation layer.
A non hygroscopic semiconducting tape may be applied on the conductor if required.
INSULATION
In-house developed high insulation resistance cross-linked polyethylene thermoset insulation
compound.
Shield: Copper wires / Aluminium wires / Aluminium corrugated sheath / lead (or) lead alloy sheath
to carry fault current, semiconducting tape may be applied for wire shielding
Outer Sheath: In-house developed thermoplastic High Density polyethylene compound having low
emission of smoke and corrosive gases when exposed to fire, semiconducting layer may be applied.
POLYCAB HV CS+PAL IEC 60840 38/66 kV (72.5 kV) - POLYCAB HV CS+PAL IEC 60840 64/110 kV (123 kV) -
Copper Conductor Copper Conductor
POLYCAB HV CS+PAL IEC 60840 76/132 kV (145 kV) - POLYCAB HV CS+PAL IEC 60840 127/220 kV (245 kV)
Copper Conductor - Copper Conductor
POLYCAB HV CS+PB IEC 60840 38/66 kV (72.5 kV) - POLYCAB HV CS+PB IEC 60840 64/110 kV (123 kV) -
Copper Conductor Copper Conductor
POLYCAB HV CS+PB IEC 60840 76/132 kV (145 kV) - POLYCAB HV CS+PB IEC 60840 127/220 kV (245 kV) -
Copper Conductor Copper Conductor
POLYCAB HV AL.COR IEC 60840 38/66 kV (72.5 kV) - POLYCAB HV AL.COR IEC 60840 64/110 kV (123 kV) -
Copper Conductor Copper Conductor
POLYCAB HV AL.COR IEC 60840 76/132 kV (145 kV) - POLYCAB HV AL.COR IEC 60840 127/220 kV (245 kV)
Copper Conductor - Copper Conductor
POLYCAB HV PB IEC 60840 38/66 kV (72.5 kV) - POLYCAB HV PB IEC 60840 64/110 kV (123 kV) -
Copper Conductor Copper Conductor
POLYCAB HV PB IEC 60840 76/132 kV (145 kV) - POLYCAB HV PB IEC 60840 127/220 kV (245 kV) -
Copper Conductor Copper Conductor
POLYCAB HV CS+PAL IEC 60840 38/66 kV (72.5 kV) - POLYCAB HV CS+PAL IEC 60840 64/110 kV (123 kV) -
Aluminium Conductor Aluminium Conductor
POLYCAB HV CS+PAL IEC 60840 76/132 kV (145 kV) - POLYCAB HV CS+PAL IEC 60840 127/220 kV (245 kV)
Aluminium Conductor - Aluminium Conductor
POLYCAB HV CS+PB IEC 60840 38/66 kV (72.5 kV) - POLYCAB HV CS+PB IEC 60840 64/110 kV (123 kV) -
Aluminium Conductor Aluminium Conductor
POLYCAB HV CS+PB IEC 60840 76/132 kV (145 kV) - POLYCAB HV CS+PB IEC 60840 127/220 kV (245 kV) -
Aluminium Conductor Aluminium Conductor
POLYCAB HV AL.COR IEC 60840 38/66 kV (72.5 kV) - POLYCAB HV AL.COR IEC 60840 64/110 kV (123 kV) -
Aluminium Conductor Aluminium Conductor
POLYCAB HV AL.COR IEC 60840 76/132 kV (145 kV) - POLYCAB HV AL.COR IEC 60840 127/220 kV (245 kV)
Aluminium Conductor - Aluminium Conductor
POLYCAB HV PB IEC 60840 38/66 kV (72.5 kV) - POLYCAB HV PB IEC 60840 64/110 kV (123 kV) -
Aluminium Conductor Aluminium Conductor
POLYCAB HV PB IEC 60840 76/132 kV (145 kV) - POLYCAB HV PB IEC 60840 127/220 kV (245 kV) -
Aluminium Conductor Aluminium Conductor
POLYCAB HV CS+PAL IEC 60840 38/66 kV (72.5 kV)
HV Cable with Copper Conductor, Copper Screen and Poly Al. laminated
Outstanding Features
• High life
• UV resistance
• Longitudinal water resistant
• Radial water resistant
Application
POLYCAB HV 38/66 KV (72.5 kV) XLPE insulated cable with copper conductor is suitable to use in high voltage
transmission for external and direct burial applications in power network system.
Voltage Rating Bending Radius: 20D
Nominal Voltage: 38/66 kV (72.5 kV) : D is overall diameter of cable
ELECTRICAL CHARACTERISTICS:
Core Max. DC Max. AC Approx. Approx. Star Approx. Surge Cable Zero Cable Zero Cable Zero
Cross Resistance Resistance Star Impedance Capacitance Impedance sequence sequence sequence
sectional at 20˚C at 90˚C Reactance Resistance Reactance Impedance
Area
mm2 Ω/km Ω/km Ω/km Ω/km µF/km Ω Ω/km Ω/km Ω/km
240 0.0754 0.0973 0.133 0.165 0.19 47 0.156 0.0781 0.174
300 0.0601 0.0782 0.128 0.150 0.21 44 0.141 0.0735 0.159
400 0.0470 0.0620 0.123 0.138 0.22 42 0.128 0.0687 0.145
500 0.0366 0.0494 0.118 0.128 0.25 39 0.118 0.0639 0.134
630 0.0283 0.0397 0.113 0.120 0.27 37 0.110 0.0598 0.125
800 0.0221 0.0327 0.109 0.114 0.29 35 0.105 0.0562 0.119
1000 0.0176 0.0279 0.106 0.110 0.32 32 0.101 0.0530 0.114
1200 0.0151 0.0206 0.102 0.104 0.35 30 0.095 0.0497 0.107
1400 0.0129 0.0181 0.100 0.102 0.38 29 0.0933 0.0481 0.105
1600 0.0113 0.0162 0.0987 0.100 0.40 28 0.0918 0.0465 0.103
1800 0.0101 0.0149 0.0973 0.0984 0.41 27 0.0907 0.0454 0.101
2000 0.0090 0.0137 0.0957 0.0967 0.43 27 0.0898 0.0441 0.100
2500 0.0072 0.0119 0.0928 0.0936 0.47 25 0.0882 0.0417 0.0976
POLYCAB HV CS+PAL IEC 60840 38/66 kV (72.5 kV)
HV Cable with Copper Conductor, Copper Screen and Poly. Al laminated
CURRENT RATING:
Core Cross Continuous current ratings for 3 single core cables, Short Circuit
sectional Area single ended bonded Rating for
1 Sec.
In ground In air
Supply frequency 50 Hz
Maximum conductor temperature 90°C
Ambient air temperature 40°C
Ground temperature 30°C
Depth of laying 1000 m
Thermal resistivity of soil 1.5 K.m/W
POLYCAB HV CS+PAL IEC 60840 64/110 kV (123 kV)
HV Cable with Copper Conductor, Copper Screen and Poly Al. laminated
Outstanding Features
• High life
• UV resistance
• Longitudinal water resistant
• Radial water resistant
Application
POLYCAB HV 64/110 KV (123 kV) XLPE insulated cable with copper conductor is suitable to use in high voltage
transmission for external and direct burial applications in power network system.
Voltage Rating Bending Radius: 20D
Nominal Voltage: 64/110 kV (123 kV) : D is overall diameter of cable
ELECTRICAL CHARACTERISTICS:
Core Max. DC Max. AC Approx. Approx. Star Approx. Surge Cable Zero Cable Zero Cable Zero
Cross Resistance Resistance Star Impedance Capacitance Impedance sequence sequence sequence
sectional at 20˚C at 90˚C Reactance Resistance Reactance Impedance
Area
mm2 Ω/km Ω/km Ω/km Ω/km µF/km Ω Ω/km Ω/km Ω/km
240 0.0754 0.0972 0.144 0.174 0.15 55 0.156 0.0900 0.180
300 0.0601 0.0781 0.138 0.159 0.16 52 0.141 0.0851 0.165
400 0.0470 0.0618 0.133 0.147 0.17 50 0.128 0.0798 0.151
500 0.0366 0.0491 0.128 0.137 0.19 46 0.118 0.0744 0.139
630 0.0283 0.0393 0.122 0.128 0.20 44 0.110 0.0697 0.130
800 0.0221 0.0322 0.118 0.122 0.22 41 0.105 0.0656 0.124
1000 0.0176 0.0273 0.114 0.117 0.24 39 0.101 0.0617 0.118
1200 0.0151 0.0205 0.110 0.112 0.26 37 0.0953 0.0582 0.112
1400 0.0129 0.0179 0.108 0.109 0.28 35 0.0933 0.0560 0.109
1600 0.0113 0.0161 0.105 0.106 0.29 34 0.0918 0.0541 0.107
1800 0.0101 0.0147 0.104 0.105 0.30 33 0.0907 0.0527 0.105
2000 0.0090 0.0135 0.102 0.103 0.32 32 0.0898 0.0512 0.103
2500 0.0072 0.0117 0.0987 0.0994 0.35 30 0.0882 0.0483 0.101
POLYCAB HV CS+PAL IEC 60840 64/110 kV (123 kV)
HV Cable with Copper Conductor, Copper Screen and Poly Al. laminated
CURRENT RATING:
Core Cross Continuous current ratings for 3 single core cables, Short Circuit
sectional Area single ended bonded Rating for
1 Sec.
In ground In air
Supply frequency 50 Hz
Maximum conductor temperature 90°C
Ambient air temperature 40°C
Ground temperature 30°C
Depth of laying 1000 m
Thermal resistivity of soil 1.5 K.m/W
POLYCAB HV CS+PAL IEC 60840 76/132 kV (145 kV)
HV Cable with Copper Conductor, Copper Screen and Poly Al. laminated
Outstanding Features
• High life
• UV resistance
• Longitudinal water resistant
• Radial water resistant
Application
POLYCAB HV 76/132 KV (145 kV) XLPE insulated cable with copper conductor is suitable to use in high voltage
transmission for external and direct burial applications in power network system.
Voltage Rating Bending Radius: 20D
Nominal Voltage: 76/132 kV (145 kV) : D is overall diameter of cable
ELECTRICAL CHARACTERISTICS:
Core Max. DC Max. AC Approx. Approx. Star Approx. Surge Cable Zero Cable Zero Cable Zero
Cross Resistance Resistance Star Impedance Capacitance Impedance sequence sequence sequence
sectional at 20˚C at 90˚C Reactance Resistance Reactance Impedance
Area
mm2 Ω/km Ω/km Ω/km Ω/km µF/km Ω Ω/km Ω/km Ω/km
300 0.0601 0.0780 0.143 0.163 0.15 55 0.141 0.0896 0.167
400 0.0470 0.0617 0.137 0.150 0.16 52 0.128 0.0841 0.153
500 0.0366 0.0491 0.131 0.140 0.17 50 0.118 0.0785 0.142
630 0.0283 0.0392 0.126 0.132 0.19 46 0.110 0.0736 0.132
800 0.0221 0.0321 0.122 0.126 0.20 44 0.105 0.0693 0.126
1000 0.0176 0.0272 0.117 0.120 0.22 41 0.101 0.0653 0.120
1200 0.0151 0.0205 0.113 0.115 0.24 39 0.0953 0.0615 0.113
1400 0.0129 0.0179 0.110 0.111 0.25 37 0.0933 0.0592 0.110
1600 0.0113 0.0160 0.108 0.109 0.27 36 0.0918 0.0572 0.108
1800 0.0101 0.0147 0.106 0.107 0.28 35 0.0907 0.0557 0.106
2000 0.0090 0.0135 0.105 0.106 0.29 34 0.0898 0.0540 0.105
2500 0.0072 0.0116 0.101 0.102 0.31 32 0.0882 0.0510 0.102
POLYCAB HV CS+PAL IEC 60840 76/132 kV (145 kV)
HV Cable with Copper Conductor, Copper Screen and Poly Al. laminated
CURRENT RATING:
Core Cross Continuous current ratings for 3 single core cables, Short Circuit
sectional Area single ended bonded Rating for
1 Sec.
In ground In air
Supply frequency 50 Hz
Maximum conductor temperature 90°C
Ambient air temperature 40°C
Ground temperature 30°C
Depth of laying 1000 m
Thermal resistivity of soil 1.5 K.m/W
POLYCAB HV CS+PAL IEC 62067 127/220 kV (245 kV)
HV Cable with Copper Conductor, Copper Screen and Poly Al. laminated
Outstanding Features
• High life
• UV resistance
• Longitudinal water resistant
• Radial water resistant
Application
POLYCAB HV 127/220 KV (245 kV) XLPE insulated cable with copper conductor is suitable to use in high
voltage transmission for external and direct burial applications in power network system.
Voltage Rating Bending Radius: 20D
Nominal Voltage: 127/220 kV (245 kV) : D is overall diameter of cable
ELECTRICAL CHARACTERISTICS:
Core Max. DC Max. AC Approx. Approx. Star Approx. Surge Cable Zero Cable Zero Cable Zero
Cross Resistance Resistance Star Impedance Capacitance Impedance sequence sequence sequence
sectional at 20˚C at 90˚C Reactance Resistance Reactance Impedance
Area
mm2 Ω/km Ω/km Ω/km Ω/km µF/km Ω Ω/km Ω/km Ω/km
400 0.0470 0.0616 0.152 0.164 0.12 63 0.111 0.0999 0.149
500 0.0366 0.0488 0.145 0.153 0.13 60 0.101 0.0936 0.138
630 0.0283 0.0389 0.139 0.144 0.14 56 0.0934 0.0880 0.128
800 0.0221 0.0317 0.134 0.138 0.15 53 0.0878 0.0831 0.121
1000 0.0176 0.0267 0.129 0.132 0.17 49 0.0839 0.0783 0.115
1200 0.0151 0.0203 0.124 0.126 0.18 47 0.0785 0.0739 0.108
1400 0.0129 0.0177 0.121 0.122 0.19 45 0.0764 0.0711 0.104
1600 0.0113 0.0159 0.119 0.120 0.20 43 0.0750 0.0687 0.102
1800 0.0101 0.0145 0.117 0.118 0.21 42 0.0739 0.0672 0.0999
2000 0.0090 0.0133 0.115 0.116 0.21 42 0.0729 0.0653 0.0979
2500 0.0072 0.0113 0.111 0.112 0.23 39 0.0714 0.0616 0.0943
POLYCAB HV CS+PAL IEC 62067 127/220 kV (245 kV)
HV Cable with Copper Conductor, Copper Screen and Poly Al. laminated
CURRENT RATING:
Core Cross Continuous current ratings for 3 single core cables, Short Circuit
sectional Area single ended bonded Rating for
1 Sec.
In ground In air
Supply frequency 50 Hz
Maximum conductor temperature 90°C
Ambient air temperature 40°C
Ground temperature 30°C
Depth of laying 1000 m
Thermal resistivity of soil 1.5 K.m/W
POLYCAB HV CS+PB IEC 60840 38/66 kV (72.5 kV)
HV Cable with Copper Conductor, Copper Screen and Lead Sheath
Outstanding Features
• High life
• UV resistance
• Longitudinal water resistant
• Radial water resistant
Application
POLYCAB HV 38/66 KV (72.5 kV) XLPE insulated cable with copper conductor is suitable to use in high voltage
transmission for external and direct burial applications in power network system.
Voltage Rating Bending Radius: 20D
Nominal Voltage: 38/66 kV (72.5 kV) : D is overall diameter of cable
ELECTRICAL CHARACTERISTICS:
Core Max. DC Max. AC Approx. Approx. Star Approx. Surge Cable Zero Cable Zero Cable Zero
Cross Resistance Resistance Star Impedance Capacitance Impedance sequence sequence sequence
sectional at 20˚C at 90˚C Reactance Resistance Reactance Impedanc
Area e
CURRENT RATING:
Core Cross Continuous current ratings for 3 single core cables, Short Circuit
sectional Area single ended bonded Rating for
1 Sec.
In ground In air
Supply frequency 50 Hz
Maximum conductor temperature 90°C
Ambient air temperature 40°C
Ground temperature 30°C
Depth of laying 1000 m
Thermal resistivity of soil 1.5 K.m/W
POLYCAB HV CS+PB IEC 60840 64/110 kV (123 kV)
HV Cable with Copper Conductor, Copper Screen and Lead Sheath
Outstanding Features
• High life
• UV resistance
• Longitudinal water resistant
• Radial water resistant
Application
POLYCAB HV 64/110 KV (123 kV) XLPE insulated cable with copper conductor is suitable to use in high voltage
transmission for external and direct burial applications in power network system.
Voltage Rating Bending Radius: 20D
Nominal Voltage: 64/110 kV (123 kV) : D is overall diameter of cable
ELECTRICAL CHARACTERISTICS:
Core Max. DC Max. AC Approx. Approx. Star Approx. Surge Cable Zero Cable Zero Cable Zero
Cross Resistance Resistance Star Impedance Capacitance Impedance sequence sequence sequence
sectional at 20˚C at 90˚C Reactance Resistance Reactance Impedance
Area
mm2 Ω/km Ω/km Ω/km Ω/km µF/km Ω Ω/km Ω/km Ω/km
240 0.0754 0.0972 0.147 0.176 0.15 56 0.171 0.0927 0.195
300 0.0601 0.0780 0.142 0.162 0.16 53 0.156 0.0878 0.179
400 0.0470 0.0618 0.136 0.149 0.17 51 0.145 0.0825 0.167
500 0.0366 0.0491 0.131 0.140 0.19 47 0.138 0.0771 0.158
630 0.0283 0.0392 0.126 0.132 0.20 45 0.131 0.0722 0.150
800 0.0221 0.0321 0.121 0.125 0.22 42 0.128 0.0681 0.145
1000 0.0176 0.0272 0.117 0.120 0.24 39 0.128 0.0642 0.143
1200 0.0151 0.0205 0.113 0.115 0.26 37 0.125 0.0604 0.139
1400 0.0129 0.0179 0.110 0.111 0.28 35 0.126 0.0583 0.139
1600 0.0113 0.0160 0.108 0.109 0.29 34 0.128 0.0565 0.140
1800 0.0101 0.0147 0.106 0.107 0.30 34 0.129 0.0550 0.140
2000 0.0090 0.0135 0.104 0.105 0.32 32 0.130 0.0534 0.141
2500 0.0072 0.0116 0.101 0.102 0.35 30 0.135 0.0504 0.144
POLYCAB HV CS+PB IEC 60840 64/110 kV (123 kV)
HV Cable with Copper Conductor, Copper Screen and Lead Sheath
CURRENT RATING:
Core Cross Continuous current ratings for 3 single core cables, Short Circuit
sectional Area single ended bonded Rating for
1 Sec.
In ground In air
Supply frequency 50 Hz
Maximum conductor temperature 90°C
Ambient air temperature 40°C
Ground temperature 30°C
Depth of laying 1000 m
Thermal resistivity of soil 1.5 K.m/W
POLYCAB HV CS+PB IEC 60840 76/132 kV (145 kV)
HV Cable with Copper Conductor, Copper Screen and Lead Sheath
Outstanding Features
• High life
• UV resistance
• Longitudinal water resistant
• Radial water resistant
Application
POLYCAB HV 76/132 KV (145 kV) XLPE insulated cable with copper conductor is suitable to use in high voltage
transmission for external and direct burial applications in power network system.
Voltage Rating Bending Radius: 20D
Nominal Voltage: 76/132 kV (145 kV) : D is overall diameter of cable
ELECTRICAL CHARACTERISTICS:
Core Max. DC Max. AC Approx. Approx. Star Approx. Surge Cable Zero Cable Zero Cable Zero
Cross Resistance Resistance Star Impedance Capacitance Impedance sequence sequence sequence
sectional at 20˚C at 90˚C Reactance Resistance Reactance Impedance
Area
mm2 Ω/km Ω/km Ω/km Ω/km µF/km Ω Ω/km Ω/km Ω/km
300 0.0601 0.0780 0.146 0.166 0.15 56 0.159 0.0922 0.184
400 0.0470 0.0617 0.140 0.153 0.16 53 0.148 0.0867 0.172
500 0.0366 0.0490 0.134 0.143 0.17 50 0.139 0.0810 0.161
630 0.0283 0.0391 0.129 0.135 0.19 47 0.134 0.0760 0.154
800 0.0221 0.0320 0.124 0.128 0.20 44 0.131 0.0717 0.149
1000 0.0176 0.0271 0.120 0.123 0.22 42 0.130 0.0675 0.146
1200 0.0151 0.0204 0.115 0.117 0.24 39 0.128 0.0637 0.143
1400 0.0129 0.0178 0.113 0.114 0.25 38 0.130 0.0615 0.144
1600 0.0113 0.0160 0.111 0.112 0.27 36 0.131 0.0595 0.144
1800 0.0101 0.0146 0.109 0.110 0.28 35 0.131 0.0579 0.143
2000 0.0090 0.0134 0.107 0.108 0.29 34 0.132 0.0562 0.143
2500 0.0072 0.0115 0.103 0.104 0.31 33 0.141 0.0531 0.151
POLYCAB HV CS+PB IEC 60840 76/132 kV (145 kV)
HV Cable with Copper Conductor, Copper Screen and Lead Sheath
CURRENT RATING:
Core Cross Continuous current ratings for 3 single core cables, Short Circuit
sectional Area single ended bonded Rating for
1 Sec.
In ground In air
Supply frequency 50 Hz
Maximum conductor temperature 90°C
Ambient air temperature 40°C
Ground temperature 30°C
Depth of laying 1000 m
Thermal resistivity of soil 1.5 K.m/W
POLYCAB HV CS+PB IEC 62067 127/220 kV (245 kV)
HV Cable with Copper Conductor, Copper Screen and Lead Sheath
Outstanding Features
• High life
• UV resistance
• Longitudinal water resistant
• Radial water resistant
Application
POLYCAB HV 127/220 KV (245 kV) XLPE insulated cable with copper conductor is suitable to use in high
voltage transmission for external and direct burial applications in power network system.
Voltage Rating Bending Radius: 20D
Nominal Voltage: 127/220 kV (245 kV) : D is overall diameter of cable
ELECTRICAL CHARACTERISTICS:
Core Max. DC Max. AC Approx. Approx. Star Approx. Surge Cable Zero Cable Zero Cable Zero
Cross Resistance Resistance Star Impedance Capacitance Impedance sequence sequence sequence
sectional at 20˚C at 90˚C Reactance Resistance Reactance Impedance
Area
mm2 Ω/km Ω/km Ω/km Ω/km µF/km Ω Ω/km Ω/km Ω/km
400 0.0470 0.0615 0.154 0.166 0.12 64 0.130 0.102 0.165
500 0.0366 0.0488 0.148 0.156 0.13 60 0.122 0.0959 0.155
630 0.0283 0.0388 0.142 0.147 0.14 57 0.115 0.0902 0.146
800 0.0221 0.0316 0.136 0.140 0.15 54 0.111 0.0852 0.140
1000 0.0176 0.0266 0.131 0.134 0.17 50 0.109 0.0804 0.135
1200 0.0151 0.0203 0.126 0.128 0.18 47 0.107 0.0760 0.131
1400 0.0129 0.0177 0.123 0.124 0.19 45 0.106 0.0731 0.129
1600 0.0113 0.0158 0.121 0.122 0.20 44 0.108 0.0707 0.129
1800 0.0101 0.0145 0.119 0.120 0.21 42 0.108 0.0691 0.128
2000 0.0090 0.0132 0.117 0.118 0.21 42 0.111 0.0672 0.130
2500 0.0072 0.0113 0.113 0.114 0.23 40 0.115 0.0635 0.131
POLYCAB HV CS+PB IEC 62067 127/220 kV (245 kV)
HV Cable with Copper Conductor, Copper Screen and Lead Sheath
CURRENT RATING:
Core Cross Continuous current ratings for 3 single core cables, Short Circuit
sectional Area single ended bonded Rating for
1 Sec.
In ground In air
Supply frequency 50 Hz
Maximum conductor temperature 90°C
Ambient air temperature 40°C
Ground temperature 30°C
Depth of laying 1000 m
Thermal resistivity of soil 1.5 K.m/W
POLYCAB HV AL.COR IEC 60840 38/66 kV (72.5 kV)
HV Cable with Copper Conductor, Aluminium Corrugated Sheath
``
Outstanding Features
• High life
• UV resistance
• Longitudinal water resistant
• Radial water resistant
Application
POLYCAB HV 38/66 KV (72.5 kV) XLPE insulated cable with Copper conductor is suitable to use in high voltage
transmission for external and direct burial applications in power network system.
Voltage Rating Bending Radius: 20D
Nominal Voltage: 38/66 kV (72.5 kV) : D is overall diameter of cable
ELECTRICAL CHARACTERISTICS:
Core Max. DC Max. AC Approx. Approx. Star Approx. Surge Cable Zero Cable Zero Cable Zero
Cross Resistance Resistance Star Impedance Capacitance Impedance sequence sequence sequence
sectional at 20˚C at 90˚C Reactance Resistance Reactance Impedance
Area
mm2 Ω/km Ω/km Ω/km Ω/km µF/km Ω Ω/km Ω/km Ω/km
240 0.0754 0.0972 0.145 0.175 0.19 49 0.166 0.0883 0.188
300 0.0601 0.0780 0.140 0.160 0.21 46 0.150 0.0836 0.172
400 0.0470 0.0618 0.134 0.148 0.22 44 0.135 0.0782 0.156
500 0.0366 0.0491 0.128 0.137 0.25 40 0.125 0.0726 0.145
630 0.0283 0.0393 0.123 0.129 0.27 38 0.115 0.0679 0.134
800 0.0221 0.0322 0.118 0.122 0.29 36 0.107 0.0638 0.125
1000 0.0176 0.0274 0.114 0.117 0.32 34 0.103 0.0598 0.119
1200 0.0151 0.0205 0.110 0.112 0.35 32 0.0980 0.0560 0.113
1400 0.0129 0.0179 0.107 0.108 0.38 30 0.0949 0.0540 0.109
1600 0.0113 0.0161 0.105 0.106 0.40 29 0.0904 0.0522 0.104
1800 0.0101 0.0147 0.104 0.105 0.41 28 0.0864 0.0511 0.100
2000 0.0090 0.0135 0.102 0.103 0.43 28 0.0829 0.0496 0.0966
2500 0.0072 0.0116 0.0992 0.0999 0.47 26 0.0765 0.0469 0.0897
POLYCAB HV AL.COR IEC 60840 38/66 kV (72.5 kV)
HV Cable with Copper Conductor, Aluminium Corrugated Sheath
CURRENT RATING:
Core Cross Continuous current ratings for 3 single core cables, Short Circuit
sectional Area single ended bonded Rating for
1 Sec.
In ground In air
Supply frequency 50 Hz
Maximum conductor temperature 90°C
Ambient air temperature 40°C
Ground temperature 30°C
Depth of laying 1000 m
Thermal resistivity of soil 1.5 K.m/W
POLYCAB HV AL.COR IEC 60840 64/110 kV (123 kV)
HV Cable with Copper Conductor, Aluminium Corrugated Sheath
``
Outstanding Features
• High life
• UV resistance
• Longitudinal water resistant
• Radial water resistant
Application
POLYCAB HV 64/110 KV (123 kV) XLPE insulated cable with Copper conductor is suitable to use in high voltage
transmission for external and direct burial applications in power network system.
Voltage Rating Bending Radius: 20D
Nominal Voltage: 64/110 kV (123 kV) : D is overall diameter of cable
ELECTRICAL CHARACTERISTICS:
Core Max. DC Max. AC Approx. Approx. Star Approx. Surge Cable Zero Cable Zero Cable Zero
Cross Resistance Resistance Star Impedance Capacitance Impedance sequence sequence sequence
sectional at 20˚C at 90˚C Reactance Resistance Reactance Impedance
Area
mm2 Ω/km Ω/km Ω/km Ω/km µF/km Ω Ω/km Ω/km Ω/km
240 0.0754 0.0972 0.154 0.182 0.15 57 0.16 0.0985 0.188
300 0.0601 0.0780 0.148 0.167 0.16 54 0.145 0.0932 0.172
400 0.0470 0.0617 0.142 0.155 0.17 52 0.131 0.0874 0.157
500 0.0366 0.0490 0.136 0.145 0.19 48 0.12 0.0816 0.145
630 0.0283 0.0391 0.130 0.136 0.20 45 0.113 0.0763 0.136
800 0.0221 0.0320 0.125 0.129 0.22 43 0.106 0.0718 0.128
1000 0.0176 0.0270 0.121 0.124 0.24 40 0.101 0.0675 0.121
1200 0.0151 0.0204 0.117 0.119 0.26 38 0.0905 0.0638 0.111
1400 0.0129 0.0178 0.114 0.115 0.28 36 0.0855 0.0615 0.105
1600 0.0113 0.0160 0.112 0.113 0.29 35 0.0817 0.0595 0.101
1800 0.0101 0.0146 0.110 0.111 0.30 34 0.0784 0.0579 0.0975
2000 0.0090 0.0134 0.108 0.109 0.32 33 0.0754 0.0562 0.094
2500 0.0072 0.0115 0.105 0.106 0.35 31 0.07 0.0531 0.0879
POLYCAB HV AL.COR IEC 60840 64/110 kV (123 kV)
HV Cable with Copper Conductor, Aluminium Corrugated Sheath
CURRENT RATING:
Core Cross Continuous current ratings for 3 single core cables, Short Circuit
sectional Area single ended bonded Rating for
1 Sec.
In ground In air
Supply frequency 50 Hz
Maximum conductor temperature 90°C
Ambient air temperature 40°C
Ground temperature 30°C
Depth of laying 1000 m
Thermal resistivity of soil 1.5 K.m/W
POLYCAB HV AL.COR IEC 60840 76/132 kV (145 kV)
HV Cable with Copper Conductor, Aluminium Corrugated Sheath
``
Outstanding Features
• High life
• UV resistance
• Longitudinal water resistant
• Radial water resistant
Application
POLYCAB HV 76/132 KV (145 kV) XLPE insulated cable with Copper conductor is suitable to use in high voltage
transmission for external and direct burial applications in power network system.
Voltage Rating Bending Radius: 20D
Nominal Voltage: 76/132 kV (145 kV) : D is overall diameter of cable
ELECTRICAL CHARACTERISTICS:
Core Max. DC Max. AC Approx. Approx. Star Approx. Surge Cable Zero Cable Zero Cable Zero
Cross Resistance Resistance Star Impedance Capacitance Impedance sequence sequence sequence
sectional at 20˚C at 90˚C Reactance Resistance Reactance Impedance
Area
mm2 Ω/km Ω/km Ω/km Ω/km µF/km Ω Ω/km Ω/km Ω/km
300 0.0601 0.0779 0.151 0.170 0.15 57 0.144 0.0969 0.174
400 0.0470 0.0616 0.145 0.158 0.16 54 0.131 0.0910 0.160
500 0.0366 0.0489 0.139 0.147 0.17 51 0.120 0.0850 0.147
630 0.0283 0.0390 0.133 0.139 0.19 47 0.111 0.0797 0.137
800 0.0221 0.0319 0.128 0.132 0.20 45 0.105 0.0751 0.129
1000 0.0176 0.0269 0.124 0.127 0.22 42 0.0963 0.0710 0.120
1200 0.0151 0.0204 0.119 0.121 0.24 40 0.0869 0.0669 0.110
1400 0.0129 0.0178 0.117 0.118 0.25 39 0.0821 0.0644 0.104
1600 0.0113 0.0159 0.114 0.115 0.27 37 0.0785 0.0623 0.100
1800 0.0101 0.0146 0.112 0.113 0.28 36 0.0755 0.0606 0.0968
2000 0.0090 0.0133 0.111 0.112 0.29 35 0.0726 0.0589 0.0935
2500 0.0072 0.0114 0.107 0.108 0.31 33 0.0675 0.0556 0.0875
POLYCAB HV AL.COR IEC 60840 76/132 kV (145 kV)
HV Cable with Copper Conductor, Aluminium Corrugated Sheath
CURRENT RATING:
Core Cross Continuous current ratings for 3 single core cables, Short Circuit
sectional Area single ended bonded Rating for
1 Sec.
In ground In air
Supply frequency 50 Hz
Maximum conductor temperature 90°C
Ambient air temperature 40°C
Ground temperature 30°C
Depth of laying 1000 m
Thermal resistivity of soil 1.5 K.m/W
POLYCAB HV AL.COR IEC 62067 127/220 kV (245 kV)
HV Cable with Copper Conductor, Aluminium Corrugated Sheath
``
Outstanding Features
• High life
• UV resistance
• Longitudinal water resistant
• Radial water resistant
Application
POLYCAB HV 127/220 KV (245 kV) XLPE insulated cable with Copper conductor is suitable to use in high
voltage transmission for external and direct burial applications in power network system.
Voltage Rating Bending Radius: 20D
Nominal Voltage: 127/220 kV (245 kV) : D is overall diameter of cable
ELECTRICAL CHARACTERISTICS:
Core Max. DC Max. AC Approx. Approx. Star Approx. Surge Cable Zero Cable Zero Cable Zero
Cross Resistance Resistance Star Impedance Capacitance Impedance sequence sequence sequence
sectional at 20˚C at 90˚C Reactance Resistance Reactance Impedance
Area
mm2 Ω/km Ω/km Ω/km Ω/km µF/km Ω Ω/km Ω/km Ω/km
400 0.0470 0.0615 0.157 0.169 0.12 65 0.113 0.104 0.154
500 0.0366 0.0487 0.150 0.158 0.13 61 0.102 0.0977 0.141
630 0.0283 0.0388 0.144 0.149 0.14 57 0.0943 0.0919 0.132
800 0.0221 0.0316 0.139 0.143 0.15 54 0.0885 0.0868 0.124
1000 0.0176 0.0266 0.133 0.136 0.17 50 0.0841 0.0817 0.117
1200 0.0151 0.0203 0.129 0.131 0.18 48 0.0757 0.0772 0.108
1400 0.0129 0.0177 0.125 0.126 0.19 46 0.0719 0.0743 0.103
1600 0.0113 0.0158 0.123 0.124 0.20 44 0.0688 0.0719 0.0995
1800 0.0101 0.0144 0.121 0.122 0.21 43 0.0660 0.0703 0.0964
2000 0.0090 0.0132 0.119 0.120 0.21 42 0.0637 0.0683 0.0934
2500 0.0072 0.0112 0.115 0.116 0.23 40 0.0595 0.0646 0.0878
POLYCAB HV AL.COR IEC 62067 127/220 kV (245 kV)
HV Cable with Copper Conductor, Aluminium Corrugated Sheath
CURRENT RATING:
Core Cross Continuous current ratings for 3 single core cables, Short Circuit
sectional Area single ended bonded Rating for
1 Sec.
In ground In air
Supply frequency 50 Hz
Maximum conductor temperature 90°C
Ambient air temperature 40°C
Ground temperature 30°C
Depth of laying 1000 m
Thermal resistivity of soil 1.5 K.m/W
POLYCAB HV PB IEC 60840 38/66 kV (72.5 kV)
HV Cable with Copper Conductor, Lead Sheath
Outstanding Features
• High life
• UV resistance
• Longitudinal water resistant
• Radial water resistant
Application
POLYCAB HV 38/66 KV (72.5 kV) XLPE insulated cable with copper conductor is suitable to use in high voltage
transmission for external and direct burial applications in power network system.
Voltage Rating Bending Radius: 20D
Nominal Voltage: 38/66 kV (72.5 kV) : D is overall diameter of cable
ELECTRICAL CHARACTERISTICS:
Core Max. DC Max. AC Approx. Approx. Star Approx. Surge Cable Zero Cable Zero Cable Zero
Cross Resistance Resistance Star Impedance Capacitance Impedance sequence sequence sequence
sectional at 20˚C at 90˚C Reactance Resistance Reactance Impedance
Area
mm2 Ω/km Ω/km Ω/km Ω/km µF/km Ω Ω/km Ω/km Ω/km
240 0.0754 0.0973 0.137 0.168 0.19 48 0.166 0.0809 0.185
300 0.0601 0.0781 0.132 0.153 0.21 45 0.152 0.0763 0.170
400 0.0470 0.0619 0.127 0.141 0.22 43 0.141 0.0716 0.158
500 0.0366 0.0493 0.121 0.131 0.25 39 0.132 0.0668 0.148
630 0.0283 0.0395 0.117 0.123 0.27 37 0.126 0.0625 0.141
800 0.0221 0.0325 0.113 0.118 0.29 35 0.122 0.0589 0.135
1000 0.0176 0.0277 0.109 0.112 0.32 33 0.121 0.0555 0.133
1200 0.0151 0.0206 0.105 0.107 0.35 31 0.117 0.0521 0.128
1400 0.0129 0.0180 0.103 0.105 0.38 29 0.118 0.0505 0.128
1600 0.0113 0.0162 0.101 0.102 0.40 28 0.119 0.0489 0.129
1800 0.0101 0.0148 0.0998 0.101 0.41 28 0.120 0.0477 0.129
2000 0.0090 0.0136 0.0982 0.0991 0.43 27 0.122 0.0464 0.131
2500 0.0072 0.0118 0.0954 0.0961 0.47 25 0.126 0.0440 0.133
POLYCAB HV PB IEC 60840 38/66 kV (72.5 kV)
HV Cable with Copper Conductor, Lead Sheath
CURRENT RATING:
Core Cross Continuous current ratings for 3 single core cables, Short Circuit
sectional Area single ended bonded Rating for
1 Sec.
In ground In air
Supply frequency 50 Hz
Maximum conductor temperature 90°C
Ambient air temperature 40°C
Ground temperature 30°C
Depth of laying 1000 m
Thermal resistivity of soil 1.5 K.m/W
POLYCAB HV PB IEC 60840 64/110 kV (123 kV)
HV Cable with Copper Conductor, Lead Sheath
Outstanding Features
• High life
• UV resistance
• Longitudinal water resistant
• Radial water resistant
Application
POLYCAB HV 64/110 KV (123 kV) XLPE insulated cable with copper conductor is suitable to use in high voltage
transmission for external and direct burial applications in power network system.
Voltage Rating Bending Radius: 20D
Nominal Voltage: 64/110 kV (123 kV) : D is overall diameter of cable
ELECTRICAL CHARACTERISTICS:
Core Max. DC Max. AC Approx. Approx. Star Approx. Surge Cable Zero Cable Zero Cable Zero
Cross Resistance Resistance Star Impedance Capacitance Impedance sequence sequence sequence
sectional at 20˚C at 90˚C Reactance Resistance Reactance Impedance
Area
mm2 Ω/km Ω/km Ω/km Ω/km µF/km Ω Ω/km Ω/km Ω/km
240 0.0754 0.0972 0.147 0.176 0.15 56 0.171 0.0927 0.195
300 0.0601 0.0780 0.142 0.162 0.16 53 0.156 0.0878 0.179
400 0.0470 0.0618 0.136 0.149 0.17 51 0.145 0.0825 0.167
500 0.0366 0.0491 0.131 0.140 0.19 47 0.138 0.0771 0.158
630 0.0283 0.0392 0.126 0.132 0.20 45 0.131 0.0722 0.150
800 0.0221 0.0321 0.121 0.125 0.22 42 0.128 0.0681 0.145
1000 0.0176 0.0272 0.117 0.120 0.24 39 0.128 0.0642 0.143
1200 0.0151 0.0205 0.113 0.115 0.26 37 0.125 0.0604 0.139
1400 0.0129 0.0179 0.110 0.111 0.28 35 0.126 0.0583 0.139
1600 0.0113 0.0160 0.108 0.109 0.29 34 0.128 0.0565 0.140
1800 0.0101 0.0147 0.106 0.107 0.30 34 0.129 0.0550 0.140
2000 0.0090 0.0135 0.104 0.105 0.32 32 0.130 0.0534 0.141
2500 0.0072 0.0116 0.101 0.102 0.35 30 0.135 0.0504 0.144
POLYCAB HV PB IEC 60840 64/110 kV (123 kV)
HV Cable with Copper Conductor, Lead Sheath
CURRENT RATING:
Core Cross Continuous current ratings for 3 single core cables, Short Circuit
sectional Area single ended bonded Rating for
1 Sec.
In ground In air
Supply frequency 50 Hz
Maximum conductor temperature 90°C
Ambient air temperature 40°C
Ground temperature 30°C
Depth of laying 1000 m
Thermal resistivity of soil 1.5 K.m/W
POLYCAB HV PB IEC 60840 76/132 kV (145 kV)
HV Cable with Copper Conductor, Lead Sheath
Outstanding Features
• High life
• UV resistance
• Longitudinal water resistant
• Radial water resistant
Application
POLYCAB HV 76/132 KV (145 kV) XLPE insulated cable with copper conductor is suitable to use in high voltage
transmission for external and direct burial applications in power network system.
Voltage Rating Bending Radius: 20D
Nominal Voltage: 76/132 kV (145 kV) : D is overall diameter of cable
ELECTRICAL CHARACTERISTICS:
Core Max. DC Max. AC Approx. Approx. Star Approx. Surge Cable Zero Cable Zero Cable Zero
Cross Resistance Resistance Star Impedance Capacitance Impedance sequence sequence sequence
sectional at 20˚C at 90˚C Reactance Resistance Reactance Impedance
Area
mm2 Ω/km Ω/km Ω/km Ω/km µF/km Ω Ω/km Ω/km Ω/km
300 0.0601 0.0780 0.146 0.166 0.15 56 0.159 0.0922 0.184
400 0.0470 0.0617 0.140 0.153 0.16 53 0.148 0.0867 0.172
500 0.0366 0.0490 0.134 0.143 0.17 50 0.139 0.0810 0.161
630 0.0283 0.0391 0.129 0.135 0.19 47 0.134 0.0760 0.154
800 0.0221 0.0320 0.124 0.128 0.20 44 0.131 0.0717 0.149
1000 0.0176 0.0271 0.120 0.123 0.22 42 0.130 0.0675 0.146
1200 0.0151 0.0204 0.115 0.117 0.24 39 0.128 0.0637 0.143
1400 0.0129 0.0178 0.113 0.114 0.25 38 0.130 0.0615 0.144
1600 0.0113 0.0160 0.111 0.112 0.27 36 0.131 0.0595 0.144
1800 0.0101 0.0146 0.109 0.110 0.28 35 0.131 0.0579 0.143
2000 0.0090 0.0134 0.107 0.108 0.29 34 0.132 0.0562 0.143
2500 0.0072 0.0115 0.103 0.104 0.31 33 0.141 0.0531 0.151
POLYCAB HV PB IEC 60840 76/132 kV (145 kV)
HV Cable with Copper Conductor, Lead Sheath
CURRENT RATING:
Core Cross Continuous current ratings for 3 single core cables, Short Circuit
sectional Area single ended bonded Rating for
1 Sec.
In ground In air
Supply frequency 50 Hz
Maximum conductor temperature 90°C
Ambient air temperature 40°C
Ground temperature 30°C
Depth of laying 1000 m
Thermal resistivity of soil 1.5 K.m/W
POLYCAB HV PB IEC 62067 127/220 kV (245 kV)
HV Cable with Copper Conductor, Lead Sheath
Outstanding Features
• High life
• UV resistance
• Longitudinal water resistant
• Radial water resistant
Application
POLYCAB HV 127/220 KV (245 kV) XLPE insulated cable with copper conductor is suitable to use in high
voltage transmission for external and direct burial applications in power network system.
Voltage Rating Bending Radius: 20D
Nominal Voltage: 127/220 kV (245 kV) : D is overall diameter of cable
ELECTRICAL CHARACTERISTICS:
Core Max. DC Max. AC Approx. Approx. Star Approx. Surge Cable Zero Cable Zero Cable Zero
Cross Resistance Resistance Star Impedance Capacitance Impedance sequence sequence sequence
sectional at 20˚C at 90˚C Reactance Resistance Reactance Impedance
Area
mm2 Ω/km Ω/km Ω/km Ω/km µF/km Ω Ω/km Ω/km Ω/km
400 0.0470 0.0615 0.154 0.166 0.12 64 0.130 0.102 0.165
500 0.0366 0.0488 0.148 0.156 0.13 60 0.122 0.0959 0.155
630 0.0283 0.0388 0.142 0.147 0.14 57 0.115 0.0902 0.146
800 0.0221 0.0316 0.136 0.140 0.15 54 0.111 0.0852 0.140
1000 0.0176 0.0266 0.131 0.134 0.17 50 0.109 0.0804 0.135
1200 0.0151 0.0203 0.126 0.128 0.18 47 0.107 0.0760 0.131
1400 0.0129 0.0177 0.123 0.124 0.19 45 0.106 0.0731 0.129
1600 0.0113 0.0158 0.121 0.122 0.20 44 0.108 0.0707 0.129
1800 0.0101 0.0145 0.119 0.120 0.21 42 0.108 0.0691 0.128
2000 0.0090 0.0132 0.117 0.118 0.21 42 0.111 0.0672 0.130
2500 0.0072 0.0113 0.113 0.114 0.23 40 0.115 0.0635 0.131
POLYCAB HV PB IEC 62067 127/220 kV (245 kV)
HV Cable with Copper Conductor, Lead Sheath
CURRENT RATING:
Core Cross Continuous current ratings for 3 single core cables, Short Circuit
sectional Area single ended bonded Rating for
1 Sec.
In ground In air
Supply frequency 50 Hz
Maximum conductor temperature 90°C
Ambient air temperature 40°C
Ground temperature 30°C
Depth of laying 1000 m
Thermal resistivity of soil 1.5 K.m/W
POLYCAB HV CS+PAL IEC 60840 38/66 kV (72.5 kV)
HV Cable with Aluminium Conductor, Copper Screen and Poly Al. laminated
Outstanding Features
• High life
• UV resistance
• Longitudinal water resistant
• Radial water resistant
Application
POLYCAB HV 38/66 KV (72.5 kV) XLPE insulated cable with Aluminium conductor is suitable to use in high
voltage transmission for external and direct burial applications in power network system.
Voltage Rating Bending Radius: 20D
Nominal Voltage: 38/66 kV (72.5 kV) : D is overall diameter of cable
ELECTRICAL CHARACTERISTICS:
Core Max. DC Max. AC Approx. Approx. Star Approx. Surge Cable Zero Cable Zero Cable Zero
Cross Resistance Resistance Star Impedance Capacitance Impedance sequence sequence sequence
sectional at 20˚C at 90˚C Reactance Resistance Reactance Impedance
Area
mm2 Ω/km Ω/km Ω/km Ω/km µF/km Ω Ω/km Ω/km Ω/km
400 0.0778 0.101 0.123 0.159 0.22 42 0.158 0.0687 0.172
500 0.0605 0.0793 0.118 0.142 0.25 39 0.141 0.0639 0.155
630 0.0469 0.0625 0.114 0.130 0.27 37 0.128 0.0602 0.141
800 0.0367 0.0501 0.110 0.121 0.29 35 0.118 0.0564 0.131
1000 0.0291 0.0412 0.106 0.114 0.32 32 0.111 0.0530 0.123
1200 0.0247 0.0322 0.102 0.107 0.35 30 0.104 0.0497 0.115
1400 0.0212 0.0278 0.100 0.104 0.38 29 0.101 0.0481 0.112
1600 0.0186 0.0245 0.0987 0.102 0.40 28 0.0980 0.0465 0.108
1800 0.0165 0.0219 0.0973 0.0997 0.41 27 0.0959 0.0454 0.106
2000 0.0149 0.0200 0.0957 0.0978 0.43 27 0.0944 0.0441 0.104
2500 0.0127 0.0174 0.0928 0.0944 0.47 25 0.0922 0.0417 0.101
POLYCAB HV CS+PAL IEC 60840 38/66 kV (72.5 kV)
HV Cable with Aluminium Conductor, Copper Screen and Poly. Al laminated
CURRENT RATING:
Core Cross Continuous current ratings for 3 single core cables, Short Circuit
sectional Area single ended bonded Rating for
1 Sec.
In ground In air
Supply frequency 50 Hz
Maximum conductor temperature 90°C
Ambient air temperature 40°C
Ground temperature 30°C
Depth of laying 1000 m
Thermal resistivity of soil 1.5 K.m/W
POLYCAB HV CS+PAL IEC 60840 64/110 kV (123 kV)
HV Cable with Aluminium Conductor, Copper Screen and Poly Al. laminated
Outstanding Features
• High life
• UV resistance
• Longitudinal water resistant
• Radial water resistant
Application
POLYCAB HV 64/110 KV (123 kV) XLPE insulated cable with Aluminium conductor is suitable to use in high
voltage transmission for external and direct burial applications in power network system.
Voltage Rating Bending Radius: 20D
Nominal Voltage: 64/110 kV (123 kV) : D is overall diameter of cable
ELECTRICAL CHARACTERISTICS:
Core Max. DC Max. AC Approx. Approx. Star Approx. Surge Cable Zero Cable Zero Cable Zero
Cross Resistance Resistance Star Impedance Capacitance Impedance sequence sequence sequence
sectional at 20˚C at 90˚C Reactance Resistance Reactance Impedance
Area
mm2 Ω/km Ω/km Ω/km Ω/km µF/km Ω Ω/km Ω/km Ω/km
400 0.0778 0.101 0.133 0.167 0.17 50 0.158 0.0798 0.177
500 0.0605 0.0791 0.128 0.150 0.19 46 0.141 0.0744 0.159
630 0.0469 0.0622 0.123 0.138 0.20 44 0.128 0.0702 0.146
800 0.0367 0.0498 0.118 0.128 0.22 41 0.118 0.0658 0.135
1000 0.0291 0.0408 0.114 0.121 0.24 39 0.111 0.0617 0.127
1200 0.0247 0.0321 0.110 0.115 0.26 37 0.104 0.0582 0.119
1400 0.0212 0.0277 0.108 0.111 0.28 35 0.101 0.0560 0.115
1600 0.0186 0.0244 0.105 0.108 0.29 34 0.098 0.0541 0.112
1800 0.0165 0.0218 0.104 0.106 0.30 33 0.0959 0.0527 0.109
2000 0.0149 0.0199 0.102 0.104 0.32 32 0.0944 0.0512 0.107
2500 0.0127 0.0172 0.0987 0.100 0.35 30 0.0922 0.0483 0.104
POLYCAB HV CS+PAL IEC 60840 64/110 kV (123 kV)
HV Cable with Aluminium Conductor, Copper Screen and Poly. Al laminated
CURRENT RATING:
Core Cross Continuous current ratings for 3 single core cables, Short Circuit
sectional Area single ended bonded Rating for
1 Sec.
In ground In air
Supply frequency 50 Hz
Maximum conductor temperature 90°C
Ambient air temperature 40°C
Ground temperature 30°C
Depth of laying 1000 m
Thermal resistivity of soil 1.5 K.m/W
POLYCAB HV CS+PAL IEC 60840 76/132 kV (145 kV)
HV Cable with Aluminium Conductor, Copper Screen and Poly Al. laminated
Outstanding Features
• High life
• UV resistance
• Longitudinal water resistant
• Radial water resistant
Application
POLYCAB HV 76/132 KV (145 kV) XLPE insulated cable with Aluminium conductor is suitable to use in high
voltage transmission for external and direct burial applications in power network system.
Voltage Rating Bending Radius: 20D
Nominal Voltage: 76/132 kV (145 kV) : D is overall diameter of cable
ELECTRICAL CHARACTERISTICS:
Core Max. DC Max. AC Approx. Approx. Star Approx. Surge Cable Zero Cable Zero Cable Zero
Cross Resistance Resistance Star Impedance Capacitance Impedance sequence sequence sequence
sectional at 20˚C at 90˚C Reactance Resistance Reactance Impedance
Area
mm2 Ω/km Ω/km Ω/km Ω/km µF/km Ω Ω/km Ω/km Ω/km
400 0.0778 0.101 0.137 0.170 0.16 52 0.158 0.0841 0.179
500 0.0605 0.0791 0.131 0.153 0.17 50 0.141 0.0785 0.161
630 0.0469 0.0622 0.127 0.141 0.19 46 0.128 0.0741 0.148
800 0.0367 0.0498 0.122 0.132 0.20 44 0.118 0.0695 0.137
1000 0.0291 0.0408 0.117 0.124 0.22 41 0.111 0.0653 0.129
1200 0.0247 0.0321 0.113 0.117 0.24 39 0.104 0.0615 0.121
1400 0.0212 0.0277 0.110 0.113 0.25 37 0.101 0.0592 0.117
1600 0.0186 0.0244 0.108 0.111 0.27 36 0.098 0.0572 0.113
1800 0.0165 0.0218 0.106 0.108 0.28 35 0.0959 0.0557 0.111
2000 0.0149 0.0199 0.105 0.107 0.29 34 0.0944 0.0540 0.109
2500 0.0127 0.0172 0.101 0.102 0.31 32 0.0922 0.0510 0.105
POLYCAB HV CS+PAL IEC 60840 76/132 kV (145 kV)
HV Cable with Aluminium Conductor, Copper Screen and Poly. Al laminated
CURRENT RATING:
Core Cross Continuous current ratings for 3 single core cables, Short Circuit
sectional Area single ended bonded Rating for
1 Sec.
In ground In air
Supply frequency 50 Hz
Maximum conductor temperature 90°C
Ambient air temperature 40°C
Ground temperature 30°C
Depth of laying 1000 m
Thermal resistivity of soil 1.5 K.m/W
POLYCAB HV CS+PAL IEC 62067 127/220 kV (245 kV)
HV Cable with Aluminium Conductor, Copper Screen and Poly Al. laminated
Outstanding Features
• High life
• UV resistance
• Longitudinal water resistant
• Radial water resistant
Application
POLYCAB HV 127/220 KV (245 kV) XLPE insulated cable with Aluminium conductor is suitable to use in high
voltage transmission for external and direct burial applications in power network system.
Voltage Rating Bending Radius: 20D
Nominal Voltage: 127/220 kV (245 kV) : D is overall diameter of cable
ELECTRICAL CHARACTERISTICS:
Core Max. DC Max. AC Approx. Approx. Star Approx. Surge Cable Zero Cable Zero Cable Zero
Cross Resistance Resistance Star Impedance Capacitance Impedance sequence sequence sequence
sectional at 20˚C at 90˚C Reactance Resistance Reactance Impedance
Area
mm2 Ω/km Ω/km Ω/km Ω/km µF/km Ω Ω/km Ω/km Ω/km
400 0.0778 0.101 0.152 0.182 0.12 63 0.141 0.0999 0.173
500 0.0605 0.0789 0.145 0.165 0.13 60 0.124 0.0936 0.155
630 0.0469 0.0619 0.140 0.153 0.14 56 0.111 0.0886 0.142
800 0.0367 0.0494 0.134 0.143 0.15 53 0.101 0.0834 0.131
1000 0.0291 0.0403 0.129 0.135 0.17 49 0.0941 0.0783 0.122
1200 0.0247 0.0320 0.124 0.128 0.18 47 0.0872 0.0739 0.114
1400 0.0212 0.0275 0.121 0.124 0.19 45 0.0838 0.0711 0.110
1600 0.0186 0.0243 0.119 0.121 0.20 43 0.0812 0.0687 0.106
1800 0.0165 0.0216 0.117 0.119 0.21 42 0.0791 0.0672 0.104
2000 0.0149 0.0197 0.115 0.117 0.21 42 0.0775 0.0653 0.101
2500 0.0127 0.0170 0.111 0.112 0.23 39 0.0753 0.0616 0.0973
POLYCAB HV CS+PAL IEC 62067 127/220 kV (245 kV)
HV Cable with Aluminium Conductor, Copper Screen and Poly. Al laminated
CURRENT RATING:
Core Cross Continuous current ratings for 3 single core cables, Short Circuit
sectional Area single ended bonded Rating for
1 Sec.
In ground In air
Supply frequency 50 Hz
Maximum conductor temperature 90°C
Ambient air temperature 40°C
Ground temperature 30°C
Depth of laying 1000 m
Thermal resistivity of soil 1.5 K.m/W
POLYCAB HV CS+PB IEC 60840 38/66 kV (72.5 kV)
HV Cable with Aluminium Conductor, Copper Screen and Lead Sheath
Outstanding Features
• High life
• UV resistance
• Longitudinal water resistant
• Radial water resistant
Application
POLYCAB HV 38/66 KV (72.5 kV) XLPE insulated cable with Aluminium conductor is suitable to use in high
voltage transmission for external and direct burial applications in power network system.
Voltage Rating Bending Radius: 20D
Nominal Voltage: 38/66 kV (72.5 kV) : D is overall diameter of cable
ELECTRICAL CHARACTERISTICS:
Core Max. DC Max. AC Approx. Approx. Star Approx. Surge Cable Zero Cable Zero Cable Zero
Cross Resistance Resistance Star Impedance Capacitance Impedance sequence sequence sequence
sectional at 20˚C at 90˚C Reactance Resistance Reactance Impedance
Area
mm2 Ω/km Ω/km Ω/km Ω/km µF/km Ω Ω/km Ω/km Ω/km
400 0.0778 0.101 0.127 0.162 0.22 43 0.171 0.0716 0.185
500 0.0605 0.0792 0.121 0.145 0.25 39 0.155 0.0668 0.169
630 0.0469 0.0624 0.117 0.133 0.27 37 0.143 0.0629 0.156
800 0.0367 0.0500 0.113 0.124 0.29 35 0.136 0.0591 0.148
1000 0.0291 0.0410 0.109 0.116 0.32 33 0.131 0.0555 0.142
1200 0.0247 0.0321 0.105 0.110 0.35 31 0.126 0.0521 0.136
1400 0.0212 0.0277 0.103 0.107 0.38 29 0.125 0.0505 0.135
1600 0.0186 0.0245 0.101 0.104 0.4 28 0.126 0.0489 0.135
1800 0.0165 0.0219 0.0998 0.102 0.41 28 0.125 0.0477 0.134
2000 0.0149 0.0199 0.0982 0.100 0.43 27 0.126 0.0464 0.134
2500 0.0127 0.0173 0.0954 0.0970 0.47 25 0.130 0.0440 0.137
POLYCAB HV CS+PB IEC 60840 38/66 kV (72.5 kV)
HV Cable with Aluminium Conductor, Copper Screen and Lead Sheath
CURRENT RATING:
Core Cross Continuous current ratings for 3 single core cables, Short Circuit
sectional Area single ended bonded Rating for
1 Sec.
In ground In air
Supply frequency 50 Hz
Maximum conductor temperature 90°C
Ambient air temperature 40°C
Ground temperature 30°C
Depth of laying 1000 m
Thermal resistivity of soil 1.5 K.m/W
POLYCAB HV CS+PB IEC 60840 64/110 kV (123 kV)
HV Cable with Aluminium Conductor, Copper Screen and Lead Sheath
Outstanding Features
• High life
• UV resistance
• Longitudinal water resistant
• Radial water resistant
Application
POLYCAB HV 64/110 KV (123 kV) XLPE insulated cable with Aluminium conductor is suitable to use in high
voltage transmission for external and direct burial applications in power network system.
Voltage Rating Bending Radius: 20D
Nominal Voltage: 64/110 kV (123 kV) : D is overall diameter of cable
ELECTRICAL CHARACTERISTICS:
Core Max. DC Max. AC Approx. Approx. Star Approx. Surge Cable Zero Cable Zero Cable Zero
Cross Resistance Resistance Star Impedance Capacitance Impedance sequence sequence sequence
sectional at 20˚C at 90˚C Reactance Resistance Reactance Impedance
Area
mm2 Ω/km Ω/km Ω/km Ω/km µF/km Ω Ω/km Ω/km Ω/km
400 0.0778 0.101 0.136 0.169 0.17 51 0.175 0.0825 0.193
500 0.0605 0.0791 0.131 0.153 0.19 47 0.161 0.0771 0.179
630 0.0469 0.0621 0.126 0.140 0.20 45 0.149 0.0727 0.166
800 0.0367 0.0497 0.121 0.131 0.22 42 0.142 0.0683 0.158
1000 0.0291 0.0407 0.117 0.124 0.24 39 0.138 0.0642 0.152
1200 0.0247 0.0320 0.113 0.117 0.26 37 0.133 0.0604 0.146
1400 0.0212 0.0276 0.110 0.113 0.28 35 0.133 0.0583 0.145
1600 0.0186 0.0244 0.108 0.111 0.29 34 0.134 0.0565 0.145
1800 0.0165 0.0218 0.106 0.108 0.30 34 0.134 0.0550 0.145
2000 0.0149 0.0198 0.104 0.106 0.32 32 0.134 0.0534 0.144
2500 0.0127 0.0172 0.101 0.102 0.35 30 0.139 0.0504 0.148
POLYCAB HV CS+PB IEC 60840 64/110 kV (123 kV)
HV Cable with Aluminium Conductor, Copper Screen and Lead Sheath
CURRENT RATING:
Core Cross Continuous current ratings for 3 single core cables, Short Circuit
sectional Area single ended bonded Rating for
1 Sec.
In ground In air
Supply frequency 50 Hz
Maximum conductor temperature 90°C
Ambient air temperature 40°C
Ground temperature 30°C
Depth of laying 1000 m
Thermal resistivity of soil 1.5 K.m/W
POLYCAB HV CS+PB IEC 60840 76/132 kV (145 kV)
HV Cable with Aluminium Conductor, Copper Screen and Lead Sheath
Outstanding Features
• High life
• UV resistance
• Longitudinal water resistant
• Radial water resistant
Application
POLYCAB HV 76/132 KV (145 kV) XLPE insulated cable with Aluminium conductor is suitable to use in high
voltage transmission for external and direct burial applications in power network system.
Voltage Rating Bending Radius: 20D
Nominal Voltage: 76/132 kV (145 kV) : D is overall diameter of cable
ELECTRICAL CHARACTERISTICS:
Core Max. DC Max. AC Approx. Approx. Star Approx. Surge Cable Zero Cable Zero Cable Zero
Cross Resistance Resistance Star Impedance Capacitance Impedance sequence sequence sequence
sectional at 20˚C at 90˚C Reactance Resistance Reactance Impedance
Area
mm2 Ω/km Ω/km Ω/km Ω/km µF/km Ω Ω/km Ω/km Ω/km
400 0.0778 0.101 0.140 0.173 0.16 53 0.178 0.0867 0.198
500 0.0605 0.0790 0.134 0.156 0.17 50 0.162 0.0810 0.181
630 0.0469 0.0621 0.130 0.144 0.19 47 0.152 0.0766 0.170
800 0.0367 0.0496 0.125 0.134 0.20 45 0.145 0.0719 0.162
1000 0.0291 0.0406 0.120 0.127 0.22 42 0.140 0.0675 0.155
1200 0.0247 0.0320 0.115 0.119 0.24 39 0.137 0.0637 0.151
1400 0.0212 0.0276 0.113 0.116 0.25 38 0.138 0.0615 0.151
1600 0.0186 0.0244 0.111 0.114 0.27 36 0.137 0.0595 0.149
1800 0.0165 0.0217 0.109 0.111 0.28 35 0.137 0.0579 0.149
2000 0.0149 0.0198 0.107 0.109 0.29 34 0.137 0.0562 0.148
2500 0.0127 0.0171 0.103 0.104 0.31 33 0.145 0.0531 0.154
POLYCAB HV CS+PB IEC 60840 76/132 kV (145 kV)
HV Cable with Aluminium Conductor, Copper Screen and Lead Sheath
CURRENT RATING:
Core Cross Continuous current ratings for 3 single core cables, Short Circuit
sectional Area single ended bonded Rating for
1 Sec.
In ground In air
Supply frequency 50 Hz
Maximum conductor temperature 90°C
Ambient air temperature 40°C
Ground temperature 30°C
Depth of laying 1000 m
Thermal resistivity of soil 1.5 K.m/W
POLYCAB HV CS+PB IEC 62067 127/220 kV (245 kV)
HV Cable with Aluminium Conductor, Copper Screen and Lead Sheath
Outstanding Features
• High life
• UV resistance
• Longitudinal water resistant
• Radial water resistant
Application
POLYCAB HV 127/220 KV (245 kV) XLPE insulated cable with Aluminium conductor is suitable to use in high
voltage transmission for external and direct burial applications in power network system.
Voltage Rating Bending Radius: 20D
Nominal Voltage: 127/220 kV (245 kV) : D is overall diameter of cable
ELECTRICAL CHARACTERISTICS:
Core Max. DC Max. AC Approx. Approx. Star Approx. Surge Cable Zero Cable Zero Cable Zero
Cross Resistance Resistance Star Impedance Capacitance Impedance sequence sequence sequence
sectional at 20˚C at 90˚C Reactance Resistance Reactance Impedance
Area
mm2 Ω/km Ω/km Ω/km Ω/km µF/km Ω Ω/km Ω/km Ω/km
400 0.0778 0.101 0.154 0.184 0.12 64 0.160 0.102 0.190
500 0.0605 0.0789 0.148 0.168 0.13 60 0.145 0.0959 0.174
630 0.0469 0.0619 0.142 0.155 0.14 57 0.132 0.0908 0.160
800 0.0367 0.0493 0.137 0.146 0.15 54 0.124 0.0855 0.151
1000 0.0291 0.0402 0.131 0.137 0.17 50 0.119 0.0804 0.144
1200 0.0247 0.0319 0.126 0.130 0.18 47 0.116 0.0760 0.139
1400 0.0212 0.0275 0.123 0.126 0.19 45 0.114 0.0731 0.135
1600 0.0186 0.0242 0.121 0.123 0.20 44 0.114 0.0707 0.134
1800 0.0165 0.0216 0.119 0.121 0.21 42 0.114 0.0691 0.133
2000 0.0149 0.0196 0.117 0.119 0.21 42 0.115 0.0672 0.133
2500 0.0127 0.0169 0.113 0.114 0.23 40 0.119 0.0635 0.135
POLYCAB HV CS+PB IEC 62067 127/220 kV (245 kV)
HV Cable with Aluminium Conductor, Copper Screen and Lead Sheath
CURRENT RATING:
Core Cross Continuous current ratings for 3 single core cables, Short Circuit
sectional Area single ended bonded Rating for
1 Sec.
In ground In air
Supply frequency 50 Hz
Maximum conductor temperature 90°C
Ambient air temperature 40°C
Ground temperature 30°C
Depth of laying 1000 m
Thermal resistivity of soil 1.5 K.m/W
POLYCAB HV AL.COR IEC 60840 38/66 kV (72.5 kV)
HV Cable with Aluminium Conductor, Aluminium Corrugated Sheath
``
Outstanding Features
• High life
• UV resistance
• Longitudinal water resistant
• Radial water resistant
Application
POLYCAB HV 38/66 KV (72.5 kV) XLPE insulated cable with Aluminium conductor is suitable to use in high
voltage transmission for external and direct burial applications in power network system.
Voltage Rating Bending Radius: 20D
Nominal Voltage: 38/66 kV (72.5 kV) : D is overall diameter of cable
ELECTRICAL CHARACTERISTICS:
Core Max. DC Max. AC Approx. Approx. Star Approx. Surge Cable Zero Cable Zero Cable Zero
Cross Resistance Resistance Star Impedance Capacitance Impedance sequence sequence sequence
sectional at 20˚C at 90˚C Reactance Resistance Reactance Impedance
Area
mm2 Ω/km Ω/km Ω/km Ω/km µF/km Ω Ω/km Ω/km Ω/km
400 0.0778 0.101 0.134 0.168 0.22 44 0.165 0.0782 0.183
500 0.0605 0.0791 0.128 0.150 0.25 40 0.148 0.0726 0.165
630 0.0469 0.0622 0.123 0.138 0.27 38 0.133 0.0684 0.150
800 0.0367 0.0498 0.118 0.128 0.29 36 0.121 0.0640 0.137
1000 0.0291 0.0408 0.114 0.121 0.32 34 0.113 0.0598 0.128
1200 0.0247 0.0321 0.110 0.115 0.35 32 0.107 0.0560 0.121
1400 0.0212 0.0277 0.107 0.111 0.38 30 0.102 0.0540 0.115
1600 0.0186 0.0244 0.105 0.108 0.40 29 0.0966 0.0522 0.110
1800 0.0165 0.0218 0.104 0.106 0.41 28 0.0916 0.0511 0.105
2000 0.0149 0.0199 0.102 0.104 0.43 28 0.0875 0.0496 0.101
2500 0.0127 0.0172 0.0992 0.101 0.47 26 0.0805 0.0469 0.0932
POLYCAB HV AL.COR IEC 60840 38/66 kV (72.5 kV)
HV Cable with Aluminium Conductor, Aluminium Corrugated Sheath
CURRENT RATING:
Core Cross Continuous current ratings for 3 single core cables, Short Circuit
sectional Area single ended bonded Rating for
1 Sec.
In ground In air
Supply frequency 50 Hz
Maximum conductor temperature 90°C
Ambient air temperature 40°C
Ground temperature 30°C
Depth of laying 1000 m
Thermal resistivity of soil 1.5 K.m/W
POLYCAB HV AL.COR IEC 60840 64/110 kV (123 kV)
HV Cable with Aluminium Conductor, Aluminium Corrugated Sheath
Outstanding Features
• High life
• UV resistance
• Longitudinal water resistant
• Radial water resistant
Application
POLYCAB HV 64/110 KV (123 kV) XLPE insulated cable with Aluminium conductor is suitable to use in high
voltage transmission for external and direct burial applications in power network system.
Voltage Rating Bending Radius: 20D
Nominal Voltage: 64/110 kV (123 kV) : D is overall diameter of cable
ELECTRICAL CHARACTERISTICS:
Core Max. DC Max. AC Approx. Approx. Star Approx. Surge Cable Zero Cable Zero Cable Zero
Cross Resistance Resistance Star Impedance Capacitance Impedance sequence sequence sequence
sectional at 20˚C at 90˚C Reactance Resistance Reactance Impedance
Area
mm2 Ω/km Ω/km Ω/km Ω/km µF/km Ω Ω/km Ω/km Ω/km
400 0.0778 0.101 0.142 0.174 0.17 52 0.161 0.0874 0.183
500 0.0605 0.0790 0.136 0.157 0.19 48 0.143 0.0816 0.165
630 0.0469 0.0620 0.130 0.144 0.20 46 0.131 0.0768 0.152
800 0.0367 0.0496 0.125 0.134 0.22 43 0.120 0.0720 0.140
1000 0.0291 0.0405 0.121 0.128 0.24 40 0.111 0.0675 0.130
1200 0.0247 0.0320 0.117 0.121 0.26 38 0.0993 0.0638 0.118
1400 0.0212 0.0276 0.114 0.117 0.28 36 0.0928 0.0615 0.111
1600 0.0186 0.0243 0.112 0.115 0.29 35 0.0879 0.0595 0.106
1800 0.0165 0.0217 0.110 0.112 0.30 34 0.0836 0.0579 0.102
2000 0.0149 0.0197 0.108 0.110 0.32 33 0.0800 0.0562 0.0978
2500 0.0127 0.0171 0.105 0.106 0.35 31 0.0740 0.0531 0.0911
POLYCAB HV AL.COR IEC 60840 64/110 kV (123 kV)
HV Cable with Aluminium Conductor, Aluminium Corrugated Sheath
CURRENT RATING:
Core Cross Continuous current ratings for 3 single core cables, Short Circuit
sectional Area single ended bonded Rating for
1 Sec.
In ground In air
Supply frequency 50 Hz
Maximum conductor temperature 90°C
Ambient air temperature 40°C
Ground temperature 30°C
Depth of laying 1000 m
Thermal resistivity of soil 1.5 K.m/W
POLYCAB HV AL.COR IEC 60840 76/132 kV (145 kV)
HV Cable with Aluminium Conductor, Aluminium Corrugated Sheath
``
Outstanding Features
• High life
• UV resistance
• Longitudinal water resistant
• Radial water resistant
Application
POLYCAB HV 76/132 KV (145 kV) XLPE insulated cable with Aluminium conductor is suitable to use in high
voltage transmission for external and direct burial applications in power network system.
Voltage Rating Bending Radius: 20D
Nominal Voltage: 76/132 kV (145 kV) : D is overall diameter of cable
ELECTRICAL CHARACTERISTICS:
Core Max. DC Max. AC Approx. Approx. Star Approx. Surge Cable Zero Cable Zero Cable Zero
Cross Resistance Resistance Star Impedance Capacitance Impedance sequence sequence sequence
sectional at 20˚C at 90˚C Reactance Resistance Reactance Impedance
Area
mm2 Ω/km Ω/km Ω/km Ω/km µF/km Ω Ω/km Ω/km Ω/km
300 0.100 0.129 0.151 0.199 0.15 57 0.184 0.0967 0.208
400 0.0778 0.101 0.145 0.177 0.16 54 0.161 0.0910 0.185
500 0.0605 0.0790 0.139 0.160 0.17 51 0.143 0.0850 0.166
630 0.0469 0.0620 0.134 0.148 0.19 47 0.129 0.0802 0.152
800 0.0367 0.0495 0.129 0.138 0.20 45 0.118 0.0753 0.140
1000 0.0291 0.0404 0.124 0.130 0.22 42 0.107 0.0710 0.128
1200 0.0247 0.0320 0.119 0.123 0.24 40 0.0956 0.0669 0.117
1400 0.0212 0.0276 0.117 0.120 0.25 39 0.0894 0.0644 0.110
1600 0.0186 0.0243 0.114 0.117 0.27 37 0.0847 0.0623 0.105
1800 0.0165 0.0217 0.112 0.114 0.28 36 0.0807 0.0606 0.101
2000 0.0149 0.0197 0.111 0.113 0.29 35 0.0772 0.0589 0.0971
2500 0.0127 0.0170 0.107 0.108 0.31 33 0.0715 0.0556 0.0906
POLYCAB HV AL.COR IEC 60840 76/132 kV (145 kV)
HV Cable with Aluminium Conductor, Aluminium Corrugated Sheath
CURRENT RATING:
Core Cross Continuous current ratings for 3 single core cables, Short Circuit
single ended bonded Rating for
sectional Area 1 Sec.
In ground In air
Supply frequency 50 Hz
Maximum conductor temperature 90°C
Ambient air temperature 40°C
Ground temperature 30°C
Depth of laying 1000 m
Thermal resistivity of soil 1.5 K.m/W
POLYCAB HV AL.COR IEC 62067 127/220 kV (245 kV)
HV Cable with Aluminium Conductor, Aluminium Corrugated Sheath
``
Outstanding Features
• High life
• UV resistance
• Longitudinal water resistant
• Radial water resistant
Application
POLYCAB HV 127/220 KV (145 kV) XLPE insulated cable with Aluminium conductor is suitable to use in high
voltage transmission for external and direct burial applications in power network system.
Voltage Rating Bending Radius: 20D
Nominal Voltage: 127/220 kV (145 kV) : D is overall diameter of cable
ELECTRICAL CHARACTERISTICS:
Core Max. DC Max. AC Approx. Approx. Star Approx. Surge Cable Zero Cable Zero Cable Zero
Cross Resistance Resistance Star Impedance Capacitance Impedance sequence sequence sequence
sectional at 20˚C at 90˚C Reactance Resistance Reactance Impedance
Area
mm2 Ω/km Ω/km Ω/km Ω/km µF/km Ω Ω/km Ω/km Ω/km
400 0.0778 0.101 0.157 0.187 0.12 65 0.143 0.104 0.177
500 0.0605 0.0789 0.150 0.169 0.13 61 0.125 0.0977 0.159
630 0.0469 0.0618 0.145 0.158 0.14 57 0.112 0.0925 0.145
800 0.0367 0.0493 0.139 0.147 0.15 54 0.102 0.0870 0.134
1000 0.0291 0.0401 0.133 0.139 0.17 50 0.0944 0.0817 0.125
1200 0.0247 0.0319 0.129 0.133 0.18 48 0.0845 0.0772 0.114
1400 0.0212 0.0275 0.125 0.128 0.19 46 0.0792 0.0743 0.109
1600 0.0186 0.0242 0.123 0.125 0.20 44 0.0750 0.0719 0.104
1800 0.0165 0.0216 0.121 0.123 0.21 43 0.0712 0.0703 0.100
2000 0.0149 0.0196 0.119 0.121 0.21 42 0.0683 0.0683 0.0966
2500 0.0127 0.0169 0.115 0.116 0.23 40 0.0635 0.0646 0.0906
POLYCAB HV AL.COR IEC 62067 127/220 kV (245 kV)
HV Cable with Aluminium Conductor, Aluminium Corrugated Sheath
CURRENT RATING:
Core Cross Continuous current ratings for 3 single core cables, Short Circuit
sectional Area single ended bonded Rating for
1 Sec.
In ground In air
Supply frequency 50 Hz
Maximum conductor temperature 90°C
Ambient air temperature 40°C
Ground temperature 30°C
Depth of laying 1000 m
Thermal resistivity of soil 1.5 K.m/W
POLYCAB HV PB IEC 60840 38/66 kV (72.5 kV)
HV Cable with Aluminium Conductor, Lead Sheath
Outstanding Features
• High life
• UV resistance
• Longitudinal water resistant
• Radial water resistant
Application
POLYCAB HV 38/66 KV (72.5 kV) XLPE insulated cable with Aluminium conductor is suitable to use in high
voltage transmission for external and direct burial applications in power network system.
Voltage Rating Bending Radius: 20D
Nominal Voltage: 38/66 kV (72.5 kV) : D is overall diameter of cable
ELECTRICAL CHARACTERISTICS:
Core Max. DC Max. AC Approx. Approx. Star Approx. Surge Cable Zero Cable Zero Cable Zero
Cross Resistance Resistance Star Impedance Capacitance Impedance sequence sequence sequence
sectional at 20˚C at 90˚C Reactance Resistance Reactance Impedance
Area
mm2 Ω/km Ω/km Ω/km Ω/km µF/km Ω Ω/km Ω/km Ω/km
400 0.0778 0.101 0.127 0.162 0.22 43 0.171 0.0716 0.185
500 0.0605 0.0792 0.121 0.145 0.25 39 0.155 0.0668 0.169
630 0.0469 0.0624 0.117 0.133 0.27 37 0.143 0.0629 0.156
800 0.0367 0.0500 0.113 0.124 0.29 35 0.136 0.0591 0.148
1000 0.0291 0.0410 0.109 0.116 0.32 33 0.131 0.0555 0.142
1200 0.0247 0.0321 0.105 0.110 0.35 31 0.126 0.0521 0.136
1400 0.0212 0.0277 0.103 0.107 0.38 29 0.125 0.0505 0.135
1600 0.0186 0.0245 0.101 0.104 0.4 28 0.126 0.0489 0.135
1800 0.0165 0.0219 0.0998 0.102 0.41 28 0.125 0.0477 0.134
2000 0.0149 0.0199 0.0982 0.100 0.43 27 0.126 0.0464 0.134
2500 0.0127 0.0173 0.0954 0.0970 0.47 25 0.130 0.0440 0.137
POLYCAB HV PB IEC 60840 38/66 kV (72.5 kV)
HV Cable with Aluminium Conductor, Lead Sheath
CURRENT RATING:
Core Cross Continuous current ratings for 3 single core cables, Short Circuit
sectional Area single ended bonded Rating for
1 Sec.
In ground In air
Supply frequency 50 Hz
Maximum conductor temperature 90°C
Ambient air temperature 40°C
Ground temperature 30°C
Depth of laying 1000 m
Thermal resistivity of soil 1.5 K.m/W
POLYCAB HV PB IEC 60840 64/110 kV (123 kV)
HV Cable with Aluminium Conductor, Lead Sheath
Outstanding Features
• High life
• UV resistance
• Longitudinal water resistant
• Radial water resistant
Application
POLYCAB HV 64/110 KV (123 kV) XLPE insulated cable with Aluminium conductor is suitable to use in high
voltage transmission for external and direct burial applications in power network system.
Voltage Rating Bending Radius: 20D
Nominal Voltage: 64/110 kV (123 kV) : D is overall diameter of cable
ELECTRICAL CHARACTERISTICS:
Core Max. DC Max. AC Approx. Approx. Star Approx. Surge Cable Zero Cable Zero Cable Zero
Cross Resistance Resistance Star Impedance Capacitance Impedance sequence sequence sequence
sectional at 20˚C at 90˚C Reactance Resistance Reactance Impedance
Area
mm2 Ω/km Ω/km Ω/km Ω/km µF/km Ω Ω/km Ω/km Ω/km
400 0.0778 0.101 0.136 0.169 0.17 51 0.175 0.0825 0.193
500 0.0605 0.0791 0.131 0.153 0.19 47 0.161 0.0771 0.179
630 0.0469 0.0621 0.126 0.140 0.20 45 0.149 0.0727 0.166
800 0.0367 0.0497 0.121 0.131 0.22 42 0.142 0.0683 0.158
1000 0.0291 0.0407 0.117 0.124 0.24 39 0.138 0.0642 0.152
1200 0.0247 0.0320 0.113 0.117 0.26 37 0.133 0.0604 0.146
1400 0.0212 0.0276 0.110 0.113 0.28 35 0.133 0.0583 0.145
1600 0.0186 0.0244 0.108 0.111 0.29 34 0.134 0.0565 0.145
1800 0.0165 0.0218 0.106 0.108 0.30 34 0.134 0.0550 0.145
2000 0.0149 0.0198 0.104 0.106 0.32 32 0.134 0.0534 0.144
2500 0.0127 0.0172 0.101 0.102 0.35 30 0.139 0.0504 0.148
POLYCAB HV PB IEC 60840 64/110 kV (123 kV)
HV Cable with Aluminium Conductor, Lead Sheath
CURRENT RATING:
Core Cross Continuous current ratings for 3 single core cables, Short Circuit
sectional Area single ended bonded Rating for
1 Sec.
In ground In air
Supply frequency 50 Hz
Maximum conductor temperature 90°C
Ambient air temperature 40°C
Ground temperature 30°C
Depth of laying 1000 m
Thermal resistivity of soil 1.5 K.m/W
POLYCAB HV PB IEC 60840 76/132 kV (145 kV)
HV Cable with Aluminium Conductor, Lead Sheath
Outstanding Features
• High life
• UV resistance
• Longitudinal water resistant
• Radial water resistant
Application
POLYCAB HV 76/132 KV (145 kV) XLPE insulated cable with Aluminium conductor is suitable to use in high
voltage transmission for external and direct burial applications in power network system.
Voltage Rating Bending Radius: 20D
Nominal Voltage: 76/132 kV (145 kV) : D is overall diameter of cable
ELECTRICAL CHARACTERISTICS:
Core Max. DC Max. AC Approx. Approx. Star Approx. Surge Cable Zero Cable Zero Cable Zero
Cross Resistance Resistance Star Impedance Capacitance Impedance sequence sequence sequence
sectional at 20˚C at 90˚C Reactance Resistance Reactance Impedance
Area
mm2 Ω/km Ω/km Ω/km Ω/km µF/km Ω Ω/km Ω/km Ω/km
400 0.0778 0.101 0.140 0.173 0.16 53 0.178 0.0867 0.198
500 0.0605 0.0790 0.134 0.156 0.17 50 0.162 0.0810 0.181
630 0.0469 0.0621 0.130 0.144 0.19 47 0.152 0.0766 0.170
800 0.0367 0.0496 0.125 0.134 0.20 45 0.145 0.0719 0.162
1000 0.0291 0.0406 0.120 0.127 0.22 42 0.140 0.0675 0.155
1200 0.0247 0.0320 0.115 0.119 0.24 39 0.137 0.0637 0.151
1400 0.0212 0.0276 0.113 0.116 0.25 38 0.138 0.0615 0.151
1600 0.0186 0.0244 0.111 0.114 0.27 36 0.137 0.0595 0.149
1800 0.0165 0.0217 0.109 0.111 0.28 35 0.137 0.0579 0.149
2000 0.0149 0.0198 0.107 0.109 0.29 34 0.137 0.0562 0.148
2500 0.0127 0.0171 0.103 0.104 0.31 33 0.145 0.0531 0.154
POLYCAB HV PB IEC 60840 76/132 kV (145 kV)
HV Cable with Aluminium Conductor, Lead Sheath
CURRENT RATING:
Core Cross Continuous current ratings for 3 single core cables, Short Circuit
sectional Area single ended bonded Rating for
1 Sec.
In ground In air
Supply frequency 50 Hz
Maximum conductor temperature 90°C
Ambient air temperature 40°C
Ground temperature 30°C
Depth of laying 1000 m
Thermal resistivity of soil 1.5 K.m/W
POLYCAB HV PB IEC 62067 127/220 kV (245 kV)
HV Cable with Aluminium Conductor, Lead Sheath
Outstanding Features
• High life
• UV resistance
• Longitudinal water resistant
• Radial water resistant
Application
POLYCAB HV 127/220 KV (245 kV) XLPE insulated cable with Aluminium conductor is suitable to use in high
voltage transmission for external and direct burial applications in power network system.
Voltage Rating Bending Radius: 20D
Nominal Voltage: 127/220 kV (245 kV) : D is overall diameter of cable
ELECTRICAL CHARACTERISTICS:
Core Max. DC Max. AC Approx. Approx. Star Approx. Surge Cable Zero Cable Zero Cable Zero
Cross Resistance Resistance Star Impedance Capacitance Impedance sequence sequence sequence
sectional at 20˚C at 90˚C Reactance Resistance Reactance Impedance
Area
mm2 Ω/km Ω/km Ω/km Ω/km µF/km Ω Ω/km Ω/km Ω/km
400 0.0778 0.101 0.154 0.184 0.12 64 0.160 0.102 0.190
500 0.0605 0.0789 0.148 0.168 0.13 60 0.145 0.0959 0.174
630 0.0469 0.0619 0.142 0.155 0.14 57 0.132 0.0908 0.160
800 0.0367 0.0493 0.137 0.146 0.15 54 0.124 0.0855 0.151
1000 0.0291 0.0402 0.131 0.137 0.17 50 0.119 0.0804 0.144
1200 0.0247 0.0319 0.126 0.130 0.18 47 0.116 0.0760 0.139
1400 0.0212 0.0275 0.123 0.126 0.19 45 0.114 0.0731 0.135
1600 0.0186 0.0242 0.121 0.123 0.20 44 0.114 0.0707 0.134
1800 0.0165 0.0216 0.119 0.121 0.21 42 0.114 0.0691 0.133
2000 0.0149 0.0196 0.117 0.119 0.21 42 0.115 0.0672 0.133
2500 0.0127 0.0169 0.113 0.114 0.23 40 0.119 0.0635 0.135
POLYCAB HV PB IEC 62067 127/220 kV (245 kV)
HV Cable with Aluminium Conductor, Lead Sheath
CURRENT RATING:
Core Cross Continuous current ratings for 3 single core cables, Short Circuit
sectional Area single ended bonded Rating for
1 Sec.
In ground In air
Supply frequency 50 Hz
Maximum conductor temperature 90°C
Ambient air temperature 40°C
Ground temperature 30°C
Depth of laying 1000 m
Thermal resistivity of soil 1.5 K.m/W