Professional Documents
Culture Documents
Handouts-for-Design-of-Anchor-Bolts-in-Accordance-with-ACI-318-19-1684527395938
Handouts-for-Design-of-Anchor-Bolts-in-Accordance-with-ACI-318-19-1684527395938
Agenda
Introduction
Typical construction
Relevant provisions of IBC
ACI 318 Chapter 17
Resisting tension loads
Resisting shear
Combined loading
Comprehensive design example
Conclusion, final Q&A
1
Anchor Bolts:
Typical Construction
The Name
Traditional: ‘Anchor Bolts’
AISC: ‘Anchor Rods’ (vs. steel-to-steel structural bolts)
AISC COSP considers anchor rods and embedments that
receive structural steel elements to be structural steel
The Function
Extend from column base plate into concrete foundation to:
Stabilize structure during erection
Typical Construction
OSHA Safety and Health Standards for the Construction Industry, 29 CFR 1926 Part R, Safety Standards for Steel
4 Erection, Paragraph 1926.755(a)(2)
2
Typical Construction
Anchor Bolts
Headed anchors are preferred today
Do not use L, J bolts when calculated tension exists*
“A heavy-hex nut or forged head is adequate to develop the
concrete shear cone.” (AISC 360-22, -16, -10, -05 Comm. J9)
*See the discussion in AISCM 14th and 13th editions, p. 14-10.
Typical Construction
Anchor Bolts: Load Transfer to Column
Nonshrink
grout
Structural steel,
with grout MBS, no grout
3
Typical Construction
PLATE WASHER
BOTTOM NUT
Typical Construction
4
Typical Construction
Anchor Bolt Materials, Cont’d
Nuts: ASTM F1554 for req’ts
Strongest: ASTM A563 (typ. used for HS bolts). Heat-
treated, so careful with welding to them… best to use
adhesive (threadlocker) or damage the treads of treaded
rods than to tack weld
Nuts and their threads exceed strength of rod (ASD
0.375Fu in 14th and 13th ed’s. vs. 0.33Fu in 9th ed.)
Washers: ASTM A36 stock
ASTM F435 washers are typ. too thin
5
Relevant Provisions of IBC
IBC-12 Table 1908.2: Representative Values
¾” bolts, min. 5” embed., 9” spacing, f’c = 3000 psi
With 4.5” ED (6 dia), Pt = 2250#, Vt = 3560#
With 7.5” ED (10 dia), Pt = 2950#, Vt = 4300#
1” bolts, min. 7” embed., 12” spacing, f’c = 3000 psi, 6” ED
(6 dia, the only choice), Pt = 3250#, Vt = 4500#
1 ¼” bolts (max.), min. 9” embed., 15” spacing, f’c = 2500 –
4000 psi, 7 ½ ” ED (the only choice),
Pt = 4000#, Vt = 5800#
6
Relevant Provisions of IBC
Anchorage to Concrete per IBC-12, Cont’d
Section 1909, Strength Design
Design headed bolts, headed studs, J- or L-bolts and post-
installed expansion and undercut anchors per ACI 318
App. D, with mod’s by IBC Sec. 1905.1.9 & 1905.1.10
(discussed below)
Applies to strength design and EQ load
Strength design of anchors not within the scope of App. D
“shall be in accordance with an approved procedure.”
13
14
7
Relevant Provisions of IBC
But Why Not to Simply Use the Latest ACI 318?
You should not mix and match building code and referenced
standards, which are often one step ahead of IBC
IBC takes exceptions to some of their provisions
E.g., see IBC Sec. 1905 for changes to ACI 318 anchoring
provisions
Paragraph numbering changes from edition to edition makes
it challenging for referencing
We’ll discuss ACI 318-19
And occasionally, some changes from previous editions
15
8
ACI 318
What ACI 318-14, -11 Did Not Cover
Through-bolts, specialty inserts
Multiple anchors connected to a single steel plate at
embedded end [but covered plates at the top]
Grouted anchors
“Direct” anchors, such as powder-actuated
Anchors used mostly for hi-cycle fatigue or impact loading
Grout
17
ACI 318
ACI 318-19 Chapter 17: What Changed?
Relocated anchor inspection requirements from Chapter 17
Chapter is reformatted
Now covers:
Screw anchors
Shear lugs
18
9
ACI 318
General Methodology
Based on Concrete Capacity Design (CCD) method
Provisions changed in every edition of ACI 318 since ’02
Design approach depends on: N
ACI 318
Tension on Anchor Groups, Cont’d
Eccentric T or M: distribution by elastic analysis…
…but plastic analysis OK if the req’d anchor ductility exists.
Then, equal distribution among tension anchors M
For both cases, the exact location of C cannot
be found by RC formulas.
Without web stiffeners, may be assumed at
the leading edge of column
With web stiffeners, may be at edge of
C T
the base plate*
10
ACI 318
Anchors with EQ Loads in SDC C – F
A major change in 2011
Previous approach: “Ductile anchors” req’d (ductile yielding
of bolt controls over concrete capacity)
ACI 318-08 App. D required that strength be governed by a
ductile steel element, not embedment, unless reduced:
The attachment is designed to yield at a force < 0.75ΦNn or
0.75ΦVn governed by concrete failure modes, or
Take design strength of non-ductile anchors =
(0.4)(0.75)ΦNn or (0.4)(0.75)ΦVn …
…Or for stud bearing walls, (0.5)(0.75)ΦNn or (0.5)(0.75)ΦVn
21 (because of redundancy)
ACI 318
EQ Loads in SDC C – F in ACI 318-11 – 19
Revision of “ductile anchor” requirements for tension,
elimination of them for shear
Added 20% threshold value for N or V for triggering EQ req’s
When EQ component of total Nu or Vu on anchor or group is
< 20%, can design without special EQ provisions
Otherwise, special EQ provisions apply:
Follow ACI 318-19 Sec. 17.10.5 for N; ACI 318-19 Sec.
17.10.6 for V
For “non-ductile anchors,” alternate forms of protection
against anchor failure can be provided
22
11
ACI 318
Options for Ductile Anchors N per Sec. 17.10.5.3*
a) “Ductile anchor” req’d over 20% threshold for single anchor.
See below for various provisions for a group (details next)
b) Design anchor(s) for max. transmitted tension based on
development of ductile yield mechanism in the attachment**
c) Design anchor(s) for max. tension transmitted by a non-
yielding attachment** (e.g., crushing of wood sill plate)
d) Design anchor(s) for max. tension from design load comb.’s
that include E, with E increased by overstrength factor Ωo***
ACI 318
More on 17.10.5.3 Opt. (a)
For a group of anchors, to comply with option (a),
“the ratio of the tensile load on the most highly stressed
anchor to the steel strength of that anchor shall be” > “ratio
of the tensile load on tension-loaded anchors to the concrete-
governed strength of those anchors.”
C T
24
12
ACI 318
ACI 318-19 Sec. 17.10.5.3 Option (a), Cont’d
In any case (for an anchor or a group):
1. Steel strength = 1.2Nsa (nom. steel strength of anchor)
2. Concrete-governed strength = least of nominal strengths for
applicable limit states for N
3. Anchors transmit N via ductile steel element with a stretch length > 8
anchor dia. (see below)
4. Where load can reverse, protect anchor from buckling
5. For partly threaded ductile bolts futa : fya > 1.3 unless upset ends are
used
6. For deformed bars used as ductile elements, comply w/Sec. 20.2.2*
(e.g., except in special seismic systems use A615, A706, A955, A996,
otherwise use A706; max yield = 80 ksi).
25
ACI 318
Stretch Length in Option (a)
For load reversal, restrain buckling by a chair or tube
But these should not share in resisting tension
Anchor chair
Stretch length
> 8 dia.
13
ACI 318
Stretch Length, Another Version
Stretch length
> 8 dia.
Sleeve
ACI 318
More on Option (d), Using Ωo
IBC Chap. 19 adds an exception that wall anchors designed
for out-of-plane designed per ASCE-16 Eq’s 12.11-1 and
12.14-10 (wall anchorage forces) are complying with Option
(d) – see a later discussion for stud wall anchors
28
14
ACI 318
ACI 318-19 Req’ts for Shear in SDC C – F
ACI 318-19 Sec. 17.10.6
When EQ component of total Vu on anchor or group is < 20%,
can design without special EQ provisions
Otherwise, special EQ provisions apply.
Follow ACI 318-19 Sec. 17.10.6.3, which lists 3 design
options (next)
If anchor reinf. used, no further capacity reduction req’d
But no req’ts for “ductile anchor” behavior V
ACI 318
3 Options for Shear per Sec. 17.10.6.3
a) Design anchor(s) for max. transmitted shear based on
development of ductile yield mechanism in the attachment
b) Design anchor(s) for max. shear transmitted by a non-
yielding attachment
c) Design anchor(s) for max. shear from design load comb.’s
that include E increased by overstrength factor Ωo*
30
15
ACI 318
Strength of Anchors – General, Sec. 17.5
Based on calc’s or testing for the following limit states:
Steel strength of anchor in tension and in shear
31
ACI 318
How to Determine Strength of Anchors
Sec. 17.5.1.2: Can be based on calc’s using models of Sec.
17.5.1.2 . . .
. . . or test results using 5% fractile for the used limit states
See Sec. 2.3 for definitions: 90% confidence that there is
95% probability of the actual strength exceeding nominal
This is why some adhesive anchor mfr’s tables contain
values that exceed those computed for cast-in anchors!
5% Tested
strength
32
16
ACI 318
Cracked Concrete Assumption
ACI 318: Assume concrete is cracked for anchor design
unless can be shown otherwise
Why?
Reduced holding capacity if crack passes through anchor
33
ACI 318
34
17
ACI 318
Design for Tension: Some Practical Data
Finding Ase,N (same as Ase,V), also Abrg of ‘heavy hex’ head or
nut (used in shear calc’s)
¾” dia. Ase,N = 0.334 Abrg = 0.911
7/8” dia. Ase,N = 0.462 Abrg = 1.188
1” dia. Ase,N = 0.606 Abrg = 1.501
1 1/8” dia. Ase,N = 0.763 Abrg = 1.851
1 ¼” dia. Ase,N = 0.969 Abrg = 2.237 (in2)
ACI 318
Design for Tension: Some Practical Data, Cont’d
Finding futa : For ASTM F1554 Gr. 36 futa = 58 ksi
Strength reduction factors Φ for tension for load comb’s of
ACI 318-19 Table 17.5.3(a)
0.75 if governed by ductile steel element
36
18
ACI 318
More on Φ Factors for Tension and Shear: Table
17.5.3(b)
For cast-in anchors governed by concrete breakout, side-face
blowout, bond
0.75 if supplementary reinforcement (discussed later) is
present,
0.70 if not
For concrete pullout and pryout: 0.70
See Table 17.5.3(b) for Φ factors for post-installed anchors
37
ACI 318
Concrete Breakout Strength in Tension
Develop ‘breakout prism’ f.k.a. ‘concrete cone failure’
ACI 318-19 Sec. 17.3.2: Provisions for concrete breakout
strength apply for anchors w/ dia. < 4”*
4” is max. dia. covered in ASTM F1554
The angle (~ 35 deg.) is different from 45 deg. used before
hef = embedment length N
TOP OF CONCRETE
1.5
1
h ef
*ACI 318-02 thru -08 Sec. D.4.2.2
limited these to anchors w/ dia. < 2”,
embedment length < 25”
38 Lines start at centerline of anchor
19
ACI 318
Concrete Breakout Strength in Tension, Cont’d
Should we use a plate at bottom to increase the prism area?
ACI 318-19 Sec. 17.6.2.1.3 allows calculating projected area
from the effective perimeter of the plate or washer
Added width of eff. perimeter < plate thickness each side
Probably not worth the effort
N
TOP OF CONCRETE
1.5
1
h ef
tpl tpl
ACI 318
Concrete Breakout Strength in Tension, Cont’d
20
ACI 318
Concrete Breakout Strength in Tension, Cont’d
Projected area of a group (ANc) with 4 anchors close to edge
ca1 = min. edge distance
ANc 1.5hef
s2
ca2
ACI 318
Concrete Breakout Strength in Tension, Cont’d
Nb = basic concrete breakout strength for a single anchor
located away from other anchors and edges, in cracked conc.
Nb = kcλa(f’c)1/2hef1.5 Eq. 17.6.2.2.1
where kc = 24 for cast-in anchors
kc = 17 for post-installed anchors
λa = mod. for LW conc. per 17.2.4 (= 1.0λ for cast-in)
Alternatively, for cast-in headed bolts and studs with
11” < hef < 25”
Nb = 16λa (f’c)1/2hef 5/3 Eq. 17.6.2.2.3
When anchors are located < 1.5hef from 3 or more edges, remember
42 to modify hef by the effects of Sec. 17.6.2.1.2
21
ACI 318
Concrete Breakout Strength in Tension, Cont’d
Sec. 17.6.2.1.2: Modify hef for computing ANc in accordance
with Sec. 17.6.2.1.1 when anchors are located < 1.5 hef from 3
or more edges:
Use h’ef the greater of ca, max /1.5 or smax /3
The value of h’ef applies to ACI Eq’s 17.6.2.1 – 17.6.2.4
Ca2,1
s2
h’ef is instructor’s term, not in ACI
ANc = projected area of a group Ca2,2
ca1 s1 1.5hef
43
ACI 318
Concrete Breakout Strength in Tension, Cont’d
Example: Find h’ef and ANc for four anchors shown
Solution:
ca, max = 12”
ca, max /1.5 = 8”
smax / 3 = 4”/ 3 = 1.33”
ca2,1 = 12”
Use h’ef = 8” and 1.5 h’ef = 12”
s2 = 4”
ANc = (8 + 4 + 12)(6 + 4 + 12) =
Ca2,2 = 8”
= 528 in2
ca1 s1 1.5h’ef
44
6” 4”
22
ACI 318
Concrete Breakout Strength in Tension, Cont’d
ACI 318
Concrete Breakout Strength in Tension, Cont’d
Breakout splitting factor ψcp,N (modifies tensile strength of
post-installed anchors in uncracked concrete w/o suppl. reinf.)
See ACI Eq’s 17.6.2.6.1a and 17.6.2.6.1b
46
0.5hef
23
ACI 318
Concrete Breakout Strength in Tension, Cont’d
Example of using anchor reinforcement to resist tension in a
large footing N
See next for pedestals
Surface reinforcement
extends beyond
breakout prism
> Ld
Anchor reinforcement
(a symm. pair) to enclose
surface reinforcement, if any < 0.5hef on centers
47
ACI 318
Resisting Tension in Column Pedestals
Using pedestal’s vertical bars
Not illustrated in ACI 318
48
24
ACI 318
Resisting Tension in Column Pedestals, Cont’d
Using anchor reinforcement (2” shown, must be < 0.5hef)
Per ACI 318-19, hook coverage is best
set at 2.5” (see a discussion later
about
hook concrete coverage)
Anchor
See a discussion later about
Anchor vs Supplementary reinforcement
49
ACI 318
Pullout Strength in Tension of Single Anchor
For a cast-in, expansion, screw or undercut anchor
Npn (nominal pullout strength) = ψc,PNp (Eq. 17.6.3.1)
ψc,P = 1.4 for uncracked concrete (by analysis); 1.0 cracked
Np = 8Abrgf’c for headed bolt or stud (Eq. 17.6.3.2.2a)
N
Abrg = net bearing area of the head, in2
See Eq. 17.6.3.2.2b for J- and L-bolts
Pullout strength is a function of concrete
crushing under head, does not depend on
embedment
50
25
ACI 318
Pullout Strength in Tension, Cont’d
Probably used L anchors…
Source: OSHA, “Investigation of the July 27, 2011 Systems-engineered Metal Building Collapse in San Marcos,
51
TX,” January 2012 https://www.osha.gov/doc/engineering/2012/2012_r_04.pdf#page=42
ACI 318
Concrete Side-Face Blowout Strength of a
Single Headed Anchor in Tension Close to Edge
Applies when hef > 2.5ca1
Max. nominal side-face blowout strength
Nsb = 160ca1(Abrg)1/2λa (f’c)1/2 Eq. 17.6.4.1
for tension, ca1 = minimum edge distance N
52
26
ACI 318
Concrete Side-Face Blowout Strength for Group
of Headed Anchors in Tension Close to Edge
When hef > 2.5ca1 and spacing s < 6ca1 nominal side-face
blowout strength for those anchors where hef > 2.5ca1
Nsbg = [1 + s/(6ca1)]Nsb Eq. 17.6.4.2
where s = distance between
N
outer anchors along the edge
Nsb from ACI 17.6.4.1 w/o mod. for
perp. edge distance (see prev. slide).
Compare Nsbg to proportion of N applied to
those anchors
53
ACI 318
Design for Shear per ACI 318 Sec. 17.7
Nominal steel strength of a headed stud anchor in shear
Vsa = Ase,Vfuta Eq. 17.7.1.2a
Ase,V = effective area of anchor in shear, in2 (see above)
futa same as for tension (see above)
For cast-in headed and hooked bolt anchors
(and some post-installed anchors)
Vsa = 0.6Ase,Vfuta Eq. 17.7.1.2b V
27
ACI 318
Concrete Breakout Strength in Shear
Nominal concrete breakout strength: Vcb and Vcbg
Shear perpendicular to edge (often controls for anchors close
to edge):
Single Vcb = (AVc/AVco)ψed,Vψc,V ψh,VVb Eq. 17.7.2.1a
Group Vcbg = (AVc/AVco)ψec,V ψed,V ψc,V ψh,V Vb Eq. 17.7.2.1b
Shear parallel to edge: Can take 2x values above, with shear
assumed to act perp. to edge and ψed,V = 1
For corner anchors, use smaller Vcb or Vcbg for both directions
Vb = basic concrete breakout strength (below)
55
ACI 318
Concrete Breakout Strength in Shear, Cont’d
AVco is projected area for one anchor in deep member
(distance from edges > 1.5ca1 in direction perp. to shear force)
AVco = 4.5(ca1)2 Eq. 17.7.2.1.3
Note: ca1 changes to c’a1 when “narrow
section” applies per 17.7.2.1.2 Inverted ½ pyramid
ca1
Avco is
V projected 1.5ca1
surface of V
this area
1.5ca1 on the
side of 1.5ca1
concrete
ca1
56
28
ACI 318
Concrete Breakout Strength in Shear, Cont’d
AVc is total projected area of failure surface on the side of
concrete: AVc < nAVco or n4.5(ca1)2
57
ACI 318
Concrete Breakout Strength in Shear, Cont’d
Sec. 17.7.2.1.2: Mod. of ca1 for anchors in “narrow sections of
limited thickness” (both ha and ca2,max < 1.5ca1)
c’a1 < the largest of: ca2, max /1.5; ha /1.5; or s/3
for Eq’s 17.7.2.1 – 17.7.2.6 (see below) and for AVc (above)
ca1
c’a1 ca2,1
Assumed
V failure
surface V
s
Actual
ha anchor ca2,2
c’a1
58 ca1
29
ACI 318
Concrete Breakout Strength in Shear, Cont’d
Example: Find Avc for ca1 = 11”, ca2,1 = 6”, ca2,2 = 5”, s = 4”, ha =
12”
Solution: Since ha and both ca2,1 and ca2,2 < 1.5ca1 = 16.5”,
c’a1 is the larger of 6/1.5 = 4”, or 12/1.5 = 8”, or 4/3 = 1.33”
Use c’a1 = 8”
Avc = (6 + 4 + 5)(1.5x8) = 180 in2 Actual failure surface
ca1 = 11”
c’a1 Ca2,1 = 6”
Assumed
V failure V
surface s = 4”
Actual
ha anchor Ca2,2 = 5”
12”
c’a1
59 ca1 = 11”
ACI 318
Concrete Breakout Strength in Shear, Cont’d
Determination of ψ factors in
Single anchor Vcb = (AVc/AVco)ψed,Vψc,V ψh,VVb
V
Remember to modify ca1 by the effects of
60
Sec. 17.7.2.1.2 (narrow section) if applicable
30
ACI 318
Concrete Breakout Strength in Shear, Cont’d
Edge effect factor ψed,V
If ca2 > 1.5ca1 ψed,V = 1.0 Eq. 17.7.2.4.1a
If ca2 < 1.5ca1 ψed,V = 0.7 + 0.3(ca2 )/(1.5ca1 )
Eq. 17.7.2.4.1b
ca1
ca2
Remember to modify ca1 by the effects of
61
Sec. 17.7.2.1.2 (narrow section) if applicable
ACI 318
62
31
ACI 318
Concrete Breakout Strength in Shear, Cont’d
Shallow concrete factor ψh,V when ha < 1.5ca1
ψh,V = (1.5ca1/ ha )1/2
but > 1.0
ca1 Avc is 1.5ca1
projected
V
surface
of this V
area s1
ca2
ha
ca1
This is separate from Sec. 17.5.2.4 [D.6.2.4]
provisions, but still need to modify ca1 by the
63 effects of Sec. 17.5.2.4 if applicable.
ACI 318
Concrete Breakout Strength in Shear, Cont’d
Breakout thickness factor ψh,V when ha < 1.5ca1
ψh,V = (1.5ca1/ ha )1/2
but > 1.0
ca1 Avc is 1.5ca1
surface
V
of this
projected V
area s1
ha
ca2
ca1
This is separate from Sec. 17.7.2.1.2 (narrow
section) provisions, but still need to modify ca1
64 here
32
ACI 318
ca1
V Avc is
surface 1.5ca1
of this
1.5ca1 V
projected
area
ca2
ca1
65
ACI 318
Concrete Breakout Strength in Shear, Cont’d
Vb = basic concrete breakout strength in shear for 1 anchor in
cracked concrete; taken as the smaller of a) and b):
a) Vb = 7(Le /da)0.2 (da)1/2 λa(f’c)1/2 (ca1)1.5 Eq. 17.7.2.2.1a
Or . . .
Remember to modify ca1 by the effects of
66
Sec. 17.7.2.1.2 (narrow section) if applicable
33
ACI 318
Concrete Breakout Strength in Shear, Cont’d
b) Vb = 9λa(f’c)1/2 (ca1)1.5
Eq. 17.7.2.2.1b (Independent of hef)
For cast-in headed anchors, headed studs or hooked bolts
“continuously welded to steel attachments” [e.g., plate],
Vb is the lesser of this equation and . . .
ca1
ACI 318
Concrete Breakout Strength in Shear, Cont’d
34
ACI 318
Groups of Anchors: Summary of Provisions
for Breakout Strength in Shear
Consider Cases 1, 2 and 3 (next), depending on s vs. ca1,1
Case 1: Shear divided equally between anchors
ACI 318
Breakout Strength in Shear: AVc for Group
Case 1: Shear divided equally between closest and farthest
anchors from the edge. The closest anchor controls: ca1= ca1,1
Avc = 2(1.5ca1,1)1.5ca1 for deep members (ha > 1.5ca1)
Otherwise, Avc = 2(1.5ca1)ha
Consider only when s > ca1,1 Inverted ½ pyramid
ca1,1
½V ½V
1.5ca1,1
Avc is ½V ½V
surface of
1.5ca1,1
this
ha s projected 1.5ca1,1
area
ca1,1
70 ca1,2
35
ACI 318
AVc for Group, Cont’d
Case 2: All shear taken by the farthest anchor, neglect
closest anchor. Take ca1 = ca1,2
ca1
1.5ca1
Avc is V
V
surface
of this
1.5ca1 area ca1,1 1.5ca1
ha s
71
ca1,2
ACI 318
AVc for Group, Case 2, Cont’d
Consider Case 2 when:
For anchors welded to a common plate (for any s), only this
case needs checking ca1,1 s
Similar to PCI Design Handbook approach V
72
36
ACI 318
AVc for Group, Case 3 (Added in 2011)
Shear taken by the closest bolt to edge. Take ca1= ca1,1
Avc = 2(1.5ca1)1.5ca1 for deep members (ha > 1.5ca1)
Otherwise, Avc = 2(1.5ca1)ha
Consider only when s < ca1,1
Does not apply to anchors Inverted ½ pyramid
welded to common plate
1.5ca1,1
V Avc is V
surface
ca1
of this
1.5ca1 area 1.5ca1,1
ha
ca1,1 s
ca1,1
73 ca1,2
ACI 318
Case 3: A New “Penalty” for MBS and Other
Edge of concrete
74
37
ACI 318
Concrete Breakout Strength in Shear, Cont’d
Exterior edge
V2
V1
75
ACI 318
Anchor Reinforcement vs. Supplementary
Reinforcement for Concrete Breakout
Two different elements, though might be detailed the same
Anchor reinforcement is designed to supersede concrete
capacity in breakout.
Designed in accordance with ACI 318-19 Sec. 17.5.2.1: For V,
either developed per Chap. 25 on both sides of breakout
surface, or it “encloses and contacts the anchor and is
developed beyond the breakout surface.”
“For practical reasons, anchor reinforcement is only used for
cast-in anchor applications.” (ACI 318-19 Comm. R17.5.2.1)
76
38
ACI 318
Anchor Reinforcement vs. Supplementary, Cont’d
77
ACI 318
Concrete Breakout Strength in Shear, Cont’d
Using anchor reinforcement per Sec. 17.5.2.1
Must be developed (extend > Ld or Ldh) past both sides of
breakout surface…
…Or must enclose and contact the anchor and developed
beyond the breakout surface
Can use its strength instead of concrete breakout
strength to find ΦVcb (use Φ = 0.75 for N and V)
Should be in contact with anchor (Comm. R17.5.2.9) and
be near concrete surface
Commentary recommends No. 6 bar max.
78
39
ACI 318
Anchor Reinforcement for Shear
Two types
Stirrups or hairpins
79
ACI 318
Anchor Reinforcement for Shear: Hairpins
Straight, enclosing the anchor (As = total area of hairpin)
Design: ΦVn = 0.75(As)60,000 psi
For #3 hairpin As = 0.22 in2; ΦVn = 0.75(0.22)60,000 = 9,900#
ca1
V Per ACI 318-19, hook coverage is best
2.5” set at 2.5” (see next)
> Ld
1.5ca1
V
80
40
ACI 318
Anchor Reinforcement for Shear: Hairpins
Straight, enclosing the anchor (As = total area of hairpin)
Design: ΦVn = 0.75(As)60,000 psi
For #3 hairpin As = 0.22 in2; ΦVn = 0.75(0.22)60,000 = 9,900#
ca1
V Per ACI 318-19, hook coverage is best
2.5” set at 2.5” (see next)
> Ld
1.5ca1
V
81
ACI 318
Ld of Bars and Hooks per ACI 318-08—14:
41
ACI 318
Ldh for Hairpin and Hooked Bars in ACI 318-19
See Sec. 25.4 for new formulas and tables.
New concrete strength factor ψc is introduced.
For f’c < 6000 psi, ψc = f’c /15,000 + 0.6
For f’c = 4000 psi ψc = 0.867
For f’c = 3000 psi ψc = 0.8
New confining reinforcement factor ψr is introduced
ψr = 1 for “widely spaced bars” with s > 6db
Otherwise, ψr = 1.6, unless hook confinement ties or
stirrups provided (next)
For #3 bars 6db = 2.25”
For #4 bars 6db = 3” use for min. hooked bar spacing
83
ACI 318
Ldh in ACI 318-19, Cont’d
Unless side and top cover > 2.5”, need confining ties or
stirrups. So for practical designs, try to use 2.5” cover.
b) 8db
c) 6”
Comm. R25.4.3.2: Using the new factors Ldh is “as much as 50
percent longer than required by Codes prior to ACI 318-19.”
84
42
ACI 318
Ldh in ACI 318-19, Cont’d
Using fy = 60,000 psi, NW concrete f’c = 4000 psi, plain #4 bars
spaced 3” o.c., side cover 2.5” (so “location factor” ψ0 = 1):
a) Ldh = (60,000x1x1x1x0.867)0.51.5/[55(4000)1/2] = 5.29”
b) Ldh = 8 x 0.5 = 4”
c) Ldh = 6” gov.
Same for #3 bars, 6” controls
For f’c = 3000 psi, #4 bars
Ldh = (60,000x1x1x1x0.8)0.51.5/[55(3000)1/2] = 5.63” < 6”
ACI 318
Ldh in ACI 318-19, Cont’d
Try #5 bars, same conditions (needed later as a last resort)
a) Ldh = (60,000x1x1x1x0.867)0.6251.5/[55(4000)1/2] = 7.4”
b) Ldh = 8 x 0.625 = 5”
c) Ldh = 6”
Can use Ldh = 7.4”
86
43
ACI 318
Hairpin Anchor Reinforcement for Shear, Cont’d
Flared, enclosing the anchor
> Ld
ca1
V 2.5”
V
1.5ca1
87
ACI 318
Anchor Reinforcement for Shear, Cont’d
A combination of edge and anchor reinforcement
Edge reinforcement
Anchor reinforcement
(one or more pairs) > Ldh > Ld
ca1 1.5ca1
V 2.5”
V
s1
1.5ca1
44
ACI 318
Anchor Reinforcement for Shear, Cont’d
Remember the bend radii for anchor reinforcement
Cannot hook over pedestal ties, need separate edge bars
ACI 318
Concrete Pryout Strength in Shear, Vcp
ACI 318-19 Sec. 17.7.3
Single anchor Vcp = kcpNcp where Ncp = Ncb
Group Vcpg = kcpNcpg where Ncpg = Ncbg
Ncb and Ncbg determined as for concrete breakout strength
for tension
kcp = 2.0 for hef > 2.5” <= typ. in practical designs
V
kcp = 1.0 for hef < 2.5” hef
90
45
ACI 318 N
Combined V and T
Determine by tests or…
When Vua > 0.2ΦVn and Nua > 0.2ΦNn:
Nua / ΦNn + Vua / ΦVn < 1.2
May neglect interaction if either:
Vua < 0.2ΦVn or
91
ACI 318
Minimum Anchor Edge Distances, Spacing
To prevent splitting failure, unless suppl. reinf. provided
(smaller distances OK if tested), comply with Sec. 17.9.2
Spacing s: 4da for untorqued cast-in anchors and 6da for
torqued cast-in (& most post-installed anchors)
So, common 4” c-c untorqued A.B. spacing in MBS works
for only for da < 1” (need suppl. reinf. for larger anchors)
Min. edge distance for untorqued cast-in anchors are same as
cover for rebars; 6da for torqued cast-in anchors
ACI 318: Use 2” for concrete exposed to earth in forms
(ex. as gov’d by fire or corrosion protection req’ts)
92
46
ACI 318
Comprehensive Design Example
Problem: Design four headed anchors welded to plate to
support Nu = 12,000# and Vu = 6,000# at the base of MBS
frame in SDC B. Concrete f’c = 3000 psi NW. Foundation pier
is 30” deep, 24” x 24” in plan, reinforced as shown. A.B.’s are
4” o.c. #4 @10” tie sets Vertical
Also act as pier bars
corner bars (6) #7
hef 10”
N
30”
V 4”
10”
10” 4” 10”
93
ACI 318
Comprehensive Design Example
Solution:
Try (4) ¾” dia. ASTM F1554 Gr. 36 anchors 18” embedment.
hef = 18”
ca1 = 10”, ca2 = 10”
s = 4”, ha = 30”
- Design for tension
- Design for shear Ca2,1 = 10”
- Tension and shear interaction N
s2 = 4”
V
Ca2,2 = 10”
47
ACI 318
First, Design without Either Anchor or
Supplementary Reinforcement
But can rely on corner reinforcement by pier ties, if needed
95
ACI 318
Design for Tension, Cont’d
Concrete breakout strength for group (Φ = 0.70, no suppl. reinf.)
Since camax = 10” < 1.5hef = 27”, ANc = 24” x 24” = 576 in2
48
ACI 318
Comprehensive Design Example, Cont’d
Find ψec,N = 1.0 (no ecc’ty)
Find ψed,N (edge distance).
Since ca, max < 1.5 hef ψed,N = 0.7 + 0.3(ca, min) / (1.5 h’ef)
ψed,N = 0.7 + 0.3(10)/(1.5 x 6.67) = 1.0
Find ψc,N (cracking)
ψc,N = 1.25 for cast-in anchors in uncracked pier
ψcp,N = 1.0 for cast-in anchors
Find Nb (basic concrete breakout strength for a single anchor
located away from other anchors and edges)
Nb = kcλa (f’c)1/2h'ef1.5 where kc = 24 for cast-in anchors
97 Nb = 24 x 1 x (3000)1/26.671.5 = 22,644#
ACI 318
Comprehensive Design Example, Cont’d
ΦNcbg = 0.7[(576)/(400)](1)(1)(1.25)(1)22,644 = 28,531#
Pullout strength
ΦNpn = Φ ψc,PNp
Φ = 0.7 for pullout; ψc,P = 1.4 for uncracked concrete pier
98
49
ACI 318
Comprehensive Design Example, Cont’d
Concrete side-face blowout strength
Applies when hef > 2.5ca1
hef = 18” < 2.5 x 10 = 25” side-face blowout not applicable
99
ACI 318
Comprehensive Design Example, Cont’d
Design for Shear
Steel strength (Φ = 0.65)
ΦVsa = Φn0.6Ase,Vfuta
Ase,V = 0.334 (in2); futa = 58,000 psi s1 = 4”
ΦVsa = 0.65(4)(0.6)(0.334)58,000
= 30,220# ca2 = 10”
50
ACI 318
Comprehensive Design Example 1, Cont’d
ACI 318
Comprehensive Design Example, Cont’d
To find Avc and Avco use projected area bounded by 1.5ca1 =
1.5(14) = 21” deep and 24” wide (since ca2 < 1.5ca1)
AVc = (24)(1.5 x 14) = 504 in2
Vcbg = (AVc/AVco)ψec,V ψed,V ψc,V ψh,V Vb
Φ = 0.7 (no suppl. reinf.) Ca1 = 14”
ψec,V = 1.0 (no ecc’ty)
ψc,V = 1.4 (no cracking in pier by analysis) V
102
51
ACI 318
Comprehensive Design Example, Cont’d
AVco = 4.5(ca1)2 = 4.5(14)2 = 882 in2
103
ACI 318
Comprehensive Design Example, Cont’d
Le = hef for headed studs, but not more than 8da = 6”
⟹ Use Le = 6”
Vb = 8(Le /da)0.2 (da)1/2 λ (f’c)1/2 (ca1)1.5
Vb = 8(6 /0.75)0.2 (0.75)1/2 (1.0)(3000)1/2 (14)1.5 = 30,129 #
= 0.7(504/882)(1)(0.84)(1.4)(1)(30,129) = 14,173#
104
52
ACI 318
105
ACI 318
Comprehensive Design Example, Cont’d
Summary of shear capacities
106
53
ACI 318
Comprehensive Design Example, Cont’d
Tension and Shear Interaction
Applied loads: Nua = 12,000# and Vua = 6,000#
Capacities: ΦNn = 28,531# and ΦVn = 14,173#
By observation, neither Vua < 0.2ΦVn nor Nua < 0.2ΦNn
apply, so must use interaction equation
Nua / ΦNn + Vua / ΦVn < 1.2
12,000 / 28,531 + 6,000 / 14,173# = 0.84 < 1.2 O.K.
107
ACI 318
Comprehensive Design Example, Cont’d
54
ACI 318
Anchor and Pier Layout…and a Note of Caution
The design loads were very light.
Relatively heavy pier good for only minor A.B. loads!
But how can anchor bolts be welded to a common base
plate? OSHA still wants A.B.s!
Vertical pier bars (6) #7
10”
#4 @10”
tie sets 4”
(also act
as corner
10”
reinforcement)
109
10” 4” 10”
ACI 318
The Answer– the Newman Anchor*!
Anchors are attached to a common plate…
…but also protrude above the plate for column erection
One issue: Adjustability
110
Weld where shown to reduce fixity
55
Q&A
111
56