Professional Documents
Culture Documents
Manual Email Version
Manual Email Version
Manual Email Version
OPERATORS MANUAL
JOHNSON MFG & SALES INC (920)244-7581
N5499 COUNTY RD E
OGDENSBURG, WI 54962 (920)244-7580-FAX
www.johnsonoutdoorwoodfurnaces.com
Table of Contents
UL Listing Information 1
Installation 5-8
Wiring Schematic 9
Purging Lines 13
Maintenance 18-23
Freeze Protection 24
Firewood Facts 25
Warranty 26
For Plenum mount and using an existing force air system, use an exchanger. For large
plenums use more than one exchanger, and step these down. Caution: DO NOT neck
down the plenum.
Air Handlers
This is a complete furnace, an all-in-one. It comes with an exchanger, blower, fan, and
filter; all mounted in an attractive box. Easy to hook up by simply connecting the two
copper lines to the feed and return lines.
Simply mount to wall (outside wall preferred). They come in 2’ increments up to 8’, but
can easily be cut to length. If using these, don’t skimp; it takes a lot of running footage to
heat a house. These will be fed from a zone tank, and again, each zone requires a 24 Volt
thermostat, a 24 Volt transformer, and a pump. DO NOT exceed 75’ of total length in
each zone. Heat radiates from the baseboard on demand. This is an excellent passive
system as no blowers are needed.
In Floor Heating
Pex-Al-Pex pipe (usually ½”) is mounted in the cement floor and/or ceiling joists.
Controls are the same as the water baseboard. This is the ultimate passive system. The
location of each zone is critical, and professional help should be requesting when
planning a system.
These are compact water to water heat exchangers which come in various sizes to meet
your heating needs. They are made of stainless steel and have a variety of uses, such as:
Hot tubs
Swimming pools
Domestic water
Pumps
There are factors used to determine the size of the pump needed:
(a) Size and length of pipe, (b) number of gallons per minute required, (c) height of water
to be pumped, (d) number of buildings to be heated, (e) usage of a manifold.
We offer Grundfos brand pumps that carry a three year warranty. The most commonly
used model is the Super Brute 15-58, but we also carry the UP26-99, and other sizes are
available for your needs. NOTE: Always mount pump in a horizontal position and
always install shutoff valves on each side of the pump. By-pass valves and lines are a
nice addition.
Three
Grundfos Speeds to
Super Brute Help you
1558 adjust the flow
Needed.
Variable Speed
INSTALLATION
Installation clearance and restrictions
Inspect monthly to insure that chimney is clear and in good condition. A continuous
air supply is mandatory.
LOCATION
When locating your Johnson, keep in mind the convenience of hauling wood to the
location and the prevailing wind direction (smoke can cause problems). You may
want to check with your insurance company to see what they recommend for distance
from the buildings, as each company varies. Additional consideration may include
any future construction that you may want to heat. NOTE: When placing furnace
downhill from a building being heated, or more then 50’ from a building being
heated; the circulating pump must be mounted on the furnace to insure proper water
flow. Pump size and capabilities need to be determined based on distance and
amount of lift.
FOUNDATION
Place on non-combustible flooring with adequate support. See diagram on page 8 for
more information.
TRENCH
The trench for your lines must be 24” deep and 10” to 12” wide. Place electrical
supply to the bottom of the trench and the water lines on top. NOTE: If lines travel
under a driveway or where heavy equipment will travel, the lines should be buried
4ft. to 5ft. deep. Use pipe insulation.
WIRING
Use electrical wire rated and approved for underground use. All installation must
follow state and local or provincial codes. See wiring schematic on page 12 for more
information.
UNDERGROUND PIPE
Use 1” Pex-Al-Pex pipe for the lines running into the house. In floor heating systems
should use ½” Pex-Al-Pex within the building. All fittings should be brass Pex
fittings. Fittings require the beveling tool for installation.
PLUMBING
Water supply lines are located at the back of the furnace. The feed line is the bottom
and the return line is the top. Your water line must be marked “Feed” and “Return”
to insure proper hook up to the furnace and exchangers.
Entering the home, cement foundations can be drilled with a large hammer drill and a
1 ½” bit or routed up over the cement foundation and then entered through the sill
plate area. When routing water lines over cement they must be properly insulated and
protected. Once in the home, continue using 1” or ¾” diameter line to finish
plumbing the inside components. NOTE: If entering cold crawl spaces (such as
under a mobile home), water lines must be insulated as well as underground. Water
lines that are not insulated resting on cold surfaces results in extreme heat loss and a
large consumption of wood. Follow the plumbing diagrams in the following pages to
complete hook up in the home.
INSTALLATION
DO NOT connect to an existing heating system unless you are using water to water or
water to air exchanger system. For sample installation, refer to How to Choose the
Correct Components. We recommend that a qualified installer complete the
installation. For further information, contact us or your local dealer.
CONTROLS
An Aquastat is used as a safety limit on the system. It is located on the back of the
furnace, and is set 10°F higher then the fan control Aquastat on the furnace. If the
secondary aquastat reaches the setting it will over ride the room thermostat and turn
on the pump or fan, of the existing furnace to get rid of excess heat.
INSULATION
We sell an all in one insulation product, featuring low-E wrap insulation with an “R”
rating of 11 for a single wrap. We recommend the five wrap (R value of 55). It
comes ready to lay encased in 5” flexible tile. It is available in many options from
two lines to four lines, in both Pex and Pex-Al and can be order in many lengths.
With its “R” Rating and correct installation you will save on wood consumption.
The furnace can either be filled at the furnace through the overflow tube on the roof,
or inside the home via an additional water connection. For simple inside house
connection, splice a ¾” boiler drain valve into the incoming feed line. When water is
needed attach a garden hose from your domestic water to the valve and fill as
required. On the initial filling, air will have to be removed from the lines. To do this,
open valves until water runs out and then close the valves. Air in the lines may cause
pump damage. Watch for plumbing leaks. DO NOT start the pump until the furnace
is full of water. NOTE: Only soft water (not hard) should be used to fill your
furnace. If you do not have soft water, a soft water kit may be purchased from us or
your dealer.
Setting your Johnson Stove
When pouring a slab to set your Johnson Outdoor Furnace, you should have
a notch formed in the back of the slab for the supply and return lines at the
back of the unit.
The slab should be poured according to the size of the unit being installed.
The leg spacing can be found below, measuring from outside of each foot
on the unit.
The notch at the back measures 2 Ft. X 1 Ft. Slab thickness is 4”.
1’
2’
You may pour your slab a few inches wider and/or longer if desired.
Hook Up For Existing Forced Air Furnace
Bleeder valves
Cold Supply
Hot Supply
From Stove
Existing
water heater
Filter by-pass
Heat
Side Arm Spiral Exchanger
Shut off flanges
Existing
Pump* furnace
Wye Strainer*
Direct Connection
From open wood furnace system to gas boiler without heat exchanger
Supply to
house Supply from wood
system furnace
Valve
Return s
Strap-on
aquastat
Return
Gas boiler
To aquastat
on boiler
110V
Transformer
R
R Brown C
Y
Red G W
W
G Black R Outdoor Air
Conditioning
Thermostat (Wood)
PURGING LINES ON YOUR SYSTEM
Valve Boiler Drain Valve or fill stove Valve
You may place valves and a drain valve on either the supply or return line in order to purge
(remove) air in your lines. To do this, attach water supply to the drain valve, and shut off the left
valve first. Turn on the water, and allow to run for five minutes or so. After air has been purged
from that side, open the left valve and close the right. Turn on the water again, and again allow
the water to run to remove the air. This boiler drain valve can also be used to fill the furnace
from the inside of the house.
Return to Stove Supply from Stove
IN-FLOOR
HEATING Pump
FLOW
DIAGRAM Tee Tee
1” Tempering Valve
- +
Return
Supply
Installation Guide For Pex-AL Pipe & Fittings
Tools Required: The fitting will 5. If it is necessary to
To install Pex-Al Pipe then slip easily remove the fitting,
you will need the into the pipe release the nut,
following: without damaging remove the split
Beveling tool
the O-ring. ring and pull the
Plastic Pipe Cutter fitting off of the
Adjustable end- pipe. Before
wrench(s) reassembling the
joint, inspect the
Cutting & Joining Pex- split ring and O-
AL: rings and replace
1. Cut the pipe them if necessary.
square. Only a
plastic pipe cutter Bending Pex-Al Pipe
Pex-Al pipe is easy to
should be used. 4. Push the fitting
bend and unlike plastic
Ensure that the fully home in the pipes, retains the shape
cutting blade is in pipe. If necessary, of the bend.
good condition at this point the
and sharp. A fitting can be Crossovers
hacksaw is not rotated in the pipe Pex-Al flexibility allows
recommended. to facilitate you to form crossovers
2. Remove the nut threading onto a by hand without the
need for fittings.
and split ring from valve, tee, etc.
the fitting. Tighten the nut by
hand, plus one full
turn with a
wrench,
3.
Push the nut and
split ring onto the
pipe. Bevel the
inside of the pipe.
FIRING THE FURNACE
Start with a small fire and add to it as needed. The fire will continue to burn until
operating temperature has been reached. During the initial burn, the water jacket will
sweat for up to two days. This is normal, and this moisture does not indicate a leak.
Establish a routine for the storage of fuel, care of the furnace, and firing techniques.
Do not overfill the furnace with fuel. Make sure you match the amount of wood to
the outside temperature. Only add enough wood to meet the time between fills.
Filling the furnace to the maximum may cause excessive creosote, and this will result
in greater wood consumption. It is better to add small amounts of wood twice a day
than larger amounts once per day. A small intense fire is preferable to a large
smoldering fire to reduce the amount of creosote deposition. When loading, do not
bang wood against furnace end wall or damage may result.
Remove ashes through ash door with shovel as needed. Ash removed should be
stored for five days in a tightly sealed metal container before disposing of.
***CAUTION*** DO NOT leave doors open for long periods when adding wood or
removing ash. This can cause your furnace to overheat.
Daily Maintenance:
Check water level and add water as needed. Check door gasket for a proper seal.
Check for creosote buildup and clean as needed.
Weekly Maintenance:
Remove ashes as required. Check bypass and chimney for excess creosote and
remove.
Annual Maintenance:
Perform Spring Clean and Check as outlined on page 23. Clean blowers and
solenoids as outlined on page 24. Test water to make sure there is a proper
amount of oxygen scavenger chemical. If using Antifreeze check to make sure it
is still good.
Additional Maintenance:
If you DO NOT have antifreeze in your system it must be flushed and drained
every two to three years.
Maintenance Record
Notes:
JOHNSON MFG & SALES INC.
If you have questions, please do not hesitate to consult your owner’s manual, the
above number, or your local dealer.
Johnson Mfg & Sales
N5499 County Rd E
Ogdensburg, WI 54962
(920)244-7581
Water Treatment Program for Johnson Outdoor Furnaces
The treatment program consists of two chemicals:
Prep Solution 102
And
Water Treatment 101
*Note: Prep 102 should always be used on new furnaces, and is strongly
recommended each time you clean and flush your system. Prep 102 is a cleaner and
metal conditioner, and will clean and condition the interior water jacket to prolong the
life of your furnace. IF YOU HAVE ANTIFREEZE IN YOUR SYSTEM YOU DO
NOT NEED TO DRAIN & FLUSH EVERY TWO YEARS, BUT YOU MUST
TEST THE ANTIFREEZE EVERY YEAR TO MAKE SURE IT IS STILL IN
GOOD CONDITION!
The following instructions should be used for Prep 102:
1. Drain furnace completely by removing the drain plug/boiler drain valve.
2. Place a garden hose at vent/fill tube located on top of furnace. Run water until
clear.
3. Replace drain plug/boiler drain valve, and start running water into the system.
After system has filled half way, add the Prep 102 at the fill tube in the following
amounts: for a new furnace 1 bottle, for used or dirty furnace 2 bottles; then
continue filling the furnace to normal working range.
4. Start the circulating pump, and then do either of the following:
Hot Process: Start a small fire in the furnace and bring the water
temperature up to 100° or to normal working range. Once the
temperature has been reached, allow the fire to go out and continue to
circulate the water for 4 to 7 hours.
Cold Process: Let the system circulate for no more than 12 hours.
*Hot Process recommended, but is not mandatory.
5. After using either the hot or cold process, turn off the circulating pump, drain the
furnace completely, open the boiler drain valve, and place the garden hose in the
fill vent on top of the stove and flush the system until the water runs clear. Make
sure that when you finish and replace the drain plug/boiler valve that you use
pipe compound or Teflon tape on the threads.
Then complete the following steps for the Water Treatment 101:
1. Fill stove with soft water. If not available at your tap, Johnson Mfg & Sales sells
a Softener Solution Kit.
2. Add approximately 1 bottle of Treatment 101 for a Little John or 2 bottles of
Treatment 101 for a Big John. This may vary based on the size of your total
system, and the type of water that you have available to you; you may need more
then this amount.
3. Start the circulating pump and let circulate for a minimum of 2 hours.
4. After one week, take a water sample by pulling the sight tube off and filling the
sample bottle with about a ¼ cup of water (2 ounces or so,) and send the sample
to Johnson Mfg & Sales for testing to determine if you water meets the proper
specifications to reduce corrosion damage to your furnace.
If you do not have antifreeze in your system, you must drain the water and flush the
system every 2-3 years. It must then be refilled with soft water and new treatment
added. If you have antifreeze in your system you must check it every year to make
sure the antifreeze is still good. To check the antifreeze you will need to use the
appropriate tester (one for propylene glycol); we can test this for you. You also will
want to look at the antifreeze to make sure that it is not black or discolored as this is
a sign that your antifreeze has gone bad. Systems that have been overheated will
need to replace their antifreeze, and drain and flush the system, as overheating
causes damage to the antifreeze.
Water must be tested at least annually by sending a water sample to Johnson Mfg &
Sales Inc. You may also purchase a water test kit from us or your local dealer to
test your own water. Many dealers also offer water testing.
Propylene Glycol has the ability to lower the freezing point of water, therefore
protecting the system in sub-zero climates. These fluids can be added to the water in
a Kitec heating system if freezing is a concern.
Ethylene Glycol has better physical properties than Propylene Glycol, especially at
lower temperatures. However, Propylene Glycol is less toxic and is recommended for
applications involving possible human contact. When using Glycol with potable
water systems some form of isolation should be provided to avoid contamination of
potable water sources (heat exchanger).
Ethylene Glycol solutions should not be used directly in a boiler because of the
danger of chemical corrosion caused by ethylene glycol breakdown on the heating
surface.
If a 50/50 glycol- water mixture is used, the head loss in the pipe should be increased
by 50% for the same flow rate.
The use of auto antifreeze is not permitted. This will cause fouling of metal
components, pump, seal wear, fluid gelation, and reduced heat transfer because of the
silicate present in automobile antifreeze.
If using antifreeze in your system you must check it annually to make sure that your
ratio is adequate. If your antifreeze has been scalded by overheating, or is black or
gelled, your system must be drained, and flushed, and the antifreeze must be replaced.
If not using antifreeze, you must drain the water and flush the system every 2-3 years,
and refill with soft water and new water treatment.
Diameter of tree
Measured at chest height Deciduous Coniferous
7 15 20
8 11 13
9 8 10
10 5 8
12 4 6
14 3 3.7
16 2 2.5
18 1.5 1.9
When burning wood it is essential to have the wood as dry as possible in order to produce
more heat per pound of fuel, thereby obtaining a higher heat value. Air dried wood
contains approximately 20% moisture and will yield about 5,800 BTU’s per pound.
Green wood containing approximately 60% moisture will yield only about 4,100 BTU’s
per pound. The heavier the weight of dry wood, the more BTU’s per cord.
DUPLICATE
OWNERS
MANUAL
THIS
SPACE
INTENTIONALLY
LEFT
BLANK