1 MHP Switchgear, protection and measurement (4 hours) • Isolators, fuses, main switches, Moulded case circuit breakers(MCCB), Oil and air CB, earth leakage CB, contactors • Under voltage trips, Over voltage trips, Over current trips, temperature trips • Lightening protection, Earthing system • Metering equipment, voltmeter, ammeter‐AC and DC, Energy meter, speed meter, pressure gauge, frequency meter • Appropriate choice of switchgear, protection and measurement.
Switchgear and Protection equipments for
2 MHP Single Line Diagram of MHP
Switchgear and Protection equipments for
3 MHP Single Line Diagram of MHP
Switchgear and Protection equipments for
4 MHP Isolator • Manually operated switches which have the basic function of isolating the load from the supply. • These are very cheap but they are not used very often because they do not offer any form of protection to the power supply. • All consumer circuits shall have isolation switches and fuses or MCBs fitted at entry point and these must be clearly labelled in the local language. • A well-illustrated electrical safety booklet shall be provided for each household. • If the number of consumers is large, isolation switches shall be provided to clusters of consumers. • This will allow a speedier location of earth faults.
Switchgear and Protection equipments for
5 MHP Overcurrent Protection Devices • Basically, there are two types of overcurrent's to be distinguished: • Firstly, the overcurrent of high intensity, i.e., a short-circuit current, where the protection device must open the circuit very rapidly to avoid damage, and • Secondly, the overcurrent which exceeds the nominal current by only a small amount which is basically an overload situation. • Overload of short duration is not dangerous (may occur at motor starts etc.) but if it persists for a long time, conductors and installations will be heated up gradually. The overload protection device must therefore cut the circuit only after a certain time delay.
Switchgear and Protection equipments for
6 MHP Fuse • Fuses act as both a protective and a disconnecting device and were the earliest such devices used on electrical systems. • They basically consist of a metallic element which melts and becomes discontinuous at a relatively high current, thus preventing the further passage of the current. • The disadvantage of fuses is that, having melted upon a transient overcurrent, they require replacement before the protected circuit can carry load again. • Dependent on the intensity of the fault current, the operating time of a fuse can take from a few tenths of seconds to hours.
Switchgear and Protection equipments for
7 MHP Fuse • Due to the fact that fuses need replacement after a single tripping operation (stock of fuses), they are generally used at the highest protection level, i.e they trip only if all other protection devices fail(back-up protection). Switchgear and Protection equipments for 8 MHP Main Switch • These are again manually operated switches which are similar to the isolator but with an addition of a fuse on the phase conductor. • The addition of a fuse allows this switch to be used where current limiting is required.
Switchgear and Protection equipments for
9 MHP Switch fuses and main fuse
Switchgear and Protection equipments for
10 MHP (Miniature Circuit Breaker)MCB • An overload condition on the (synchronous) generator may occur if too many appliances are connected to the network or if a short at a customer at the end of the line has occurred without producing a current high enough to trip the fuse at the generator. • When the current exceeds a pre-set value, the overcurrent relay will initiate (after a time delay determined by its characteristics) the opening of the circuit (if the relay is mounted directly on the line) or, in larger power systems, to initiate tripping of the associated circuit breaker. • There are basically three different types of relays available: i. the electromagnetic version with a solenoid which trips instantaneously when sufficient current passes through the coil ii. the thermal relay with a bimetal strip which trips after a time delay inversely dependent on the overcurrent; the characteristics of the thermal relay iii. these two features may be combined in one relay: for an overload situation, the relay trips after a certain time delay; for a short-circuit current of several times nominal current (typically 5 to 10 Id the relay trips almost instantaneously) Switchgear and Protection equipments for 11 MHP MCB • Appropriate MCBs (0.5 A for 100W and 1A for 200W) are recommended to be installed at the load points. • 1𝑚𝑚2 size PVC insulated cables are recommended for house wiring if the maximum load used by the house is less than 200 W.
Switchgear and Protection equipments for
12 MHP Moulded Case Circuit Breaker(MCCB)
Switchgear and Protection equipments for
13 MHP Moulded Case Circuit Breaker(MCCB) • They are very much similar to MCB but it has higher rupturing capacity with comparison to MCB and its physical size is larger than MCB. • MCCB has various categories as per breaking capacity, such as: 5kA, 10kA, 25kA, 30kA, 35kA, 40kA, 50kA, 80kA, etc. • MCCB are very suitable to protect main cable in the distribution system. • The standard ratings of MCCB are- 5A,10A, 15A, 20A, 30A, 40A, 50A, 60A, 75A, 100A, 125A, 150A, 160A, 175A, 200A, 125A, 250A, 300A, 400A, 500A, 600A, 700A, 800A, 1000A, 1200A, 1600A. • Trip characteristics is adjustable. Switchgear and Protection equipments for 14 MHP MCB VS MCCB
Switchgear and Protection equipments for
15 MHP Air Circuit and Oil Circuit Breaker • Oil circuit breakers are being replaced by the MCCB. They are very costly and offer the same facilities as the MCCB. • ACBs were used at currents of over 600 amps and are also being replaced by the MCCB.
Switchgear and Protection equipments for
16 MHP Earth Leakage Circuit Breaker-ELCB • In order to protect people from electric shock at any location throughout the distribution system and in the powerhouse, an earth leakage circuit breaker (ELCB) shall be fitted on feeder as close to the generator terminals as possible. • The standard sensitivity for human protection of 30mA should be used except for larger schemes where the number of consumers is so great that cumulative earth leaks due to normal insulation resistance leakage and stray capacitance currents would cause spurious tripping. • It is usually not cost-effective to fit ELCBs to individual consumer points, but where the number of consumers is large and spurious triggering of a single 30mA ELCB in the power house poses a problem, it is recommended that clusters (typically of around 15 houses or 1.5kW) are protected by 30mA ELCBs.
Switchgear and Protection equipments for
17 MHP ELCB • These can be located inside the powerhouse or outside in weatherproof housing: If located outside, it is recommended that the powerhouse be also fitted with an ELCB the sensitivity and response time of which is reduced. • Location of earth faults without undue delay is required. This may be done through ELCB. If the powerhouse ELCB trips the first step is to isolate the powerhouse and then restart the generator. If the ELCB stays untripped the fault is in the distribution system, and the next step is to isolate clusters of consumers or all individual consumers. Progressive switching in of consumers will reveal the location of the fault. • It is recommended to install a single 150 mA or less ELCB at the powerhouse to protect each circuit drawn from the powerhouse. A single 30 mA ELCB may be installed at the load points, which use loads more than 1kW.
Switchgear and Protection equipments for
18 MHP ELCB
Switchgear and Protection equipments for
19 MHP ELCB Working Principle
Switchgear and Protection equipments for
20 MHP (Earth Leakage Circuit Breaker)ELCB
Switchgear and Protection equipments for
21 MHP Contractor • These are generally used in control circuits as in motor starters etc. • However they could be used as circuit breakers along with the relevant trips. • This makes them very expensive.
Switchgear and Protection equipments for
22 MHP Contractor
Switchgear and Protection equipments for
23 MHP Earthing • Earthing will be carried out in accordance National Electrical Code. • Pipe electrode method is preferred. • Separate earths are provided for generator neutral, lightning arrestor and ELC. • Where consumer loads are simple appliances such as lights and double insulated non - metal items like radios, no earthing is required other than the powerhouse earth. • Where consumer loads may include metal appliances such as irons, water heaters, an earth connection must be installed for each consumer likely to use such loads. Switchgear and Protection equipments for 24 MHP Earthing
Switchgear and Protection equipments for
25 MHP Direct Earthing
Switchgear and Protection equipments for
26 MHP Direct Earthing • The individual protective earthing of appliances has the disadvantage that the resistance of the earth is seldom sufficiently low to provoke a short-circuit in the line with the fault and a subsequent tripping of the fuse. • In supply systems with protective earthing it is possible that dangerous fault currents may persist for an unlimited time. • People close to the earth electrodes can be endangered due to the voltage drop between their two feet (step voltage). • The protective earthing of individual appliances is, despite its simplicity, not a very safe and effective system unless the required earth resistance can be guaranteed (the resistance of the earth may vary with time and has to be checked in accordance with regulations).
Switchgear and Protection equipments for
27 MHP Types of Earthing • The use of a conductor as a return path for a fault current (instead of the earth) is a widely applied system; this can either be accomplished by a separate conductor or the neutral wire. • The coding's used correspond to international standards: • T = earthing (Terre) • N = Neutral point of the power system (generator or transformer star point/neutral) • S = Separate conductors for earthing and neutral • C = Combined conductors for earthing and neutral, the so- called PEN conductor • PE = Protective Earthing
Switchgear and Protection equipments for
28 MHP System Earthing Types
Switchgear and Protection equipments for
29 MHP TN-C system • The metallic frames of appliances are connected to the neutral wire which is therefore used in two ways: during normal operation as a life wire (return path for single phase appliances or for unbalanced 3 -phase systems) and in case of fault condition as a protective conductor (return path for the fault current to trip the fuse). • Note that the neutral itself must never be fused since a broken fuse would interrupt not only the supply but also the protective system; and even worse, it would put all metallic frames beyond the broken PEN conductor under voltage even without a fault condition. Switchgear and Protection equipments for 30 MHP TN-C-S system • The neutral is earthed at a number of points. • This ensures that in case of a broken neutral wire, the section beyond the broken PEN conductor will still have an earthing path.
Switchgear and Protection equipments for
31 MHP TT arrangement • The drawback of the protective earthing arrangement (individual earthing of customer's appliances) can be avoided if a suitable device, a so-called residual-current circuit breaker (RCCB or fault current relay) is installed at the entrance to the customer's premises. • When a fault condition occurs, this device senses the current difference (leakage current) between the two life wires and opens the circuit. • RCCBs are also available for three-phase systems. • In Micro hydro in Srilanka, TT arrangement was used.
Switchgear and Protection equipments for
32 MHP TN-S arrangement • The protective earth conductor PE is separated from the neutral wire. • Though this arrangement requires the largest amount of conductor material, it is a relatively safe system and accidents are rare.
Switchgear and Protection equipments for
33 MHP Internal Earthing Connection in Microhydro
Switchgear and Protection equipments for
34 MHP Lighting Arrestor • Lightning arrestors shall be fitted to protect the powerhouse and consumers. • They shall be provided on each phase as follows: • One arrestor on the first pole outside the power house, • One arrestor per kilometer of distribution and additional arrestors to ensure that no consumer is more than 500 meters from an arrestor. • Arrestors shall be installed and earthed according to the manufacturers instructions by • Separate earths and as per IS: 2309 (1989). • They shall comprise horizontal/vertical air terminations, down conductors, test links and earth connections to the station earth. • The conductors shall be of 25x6 mm size and shall be mild steel (galvanized).
Switchgear and Protection equipments for
35 MHP Trips • Trips are required to protect consumer loads from unacceptable voltage and frequency conditions. • Overvoltage trips should be fitted on all schemes • Undervoltage trips shall be fitted on all schemes where motors are used by consumers and they are fitted on all schemes above 5kW. • Over and underfrequency trips shall be provided required on all schemes where motors are used by consumers and are mandatory on all schemes above 25kW.
Switchgear and Protection equipments for
36 MHP Trips
• Under Voltage trip(-15%)
Causes: defective AVR, overloaded machine, poor pf, poor transmission line regulation • Over Voltage trip Causes: defective AVR, overspeed, leading pf, poor transmission line regulation • Over current trip • Causes: short circuit, excess load, faulty equipment, lagging pf, incorrect frequency
Switchgear and Protection equipments for
37 MHP Trips • A fuse will have range of protection upto 1.6 times its rating. • MCCB will have range 1.2 times its rating against over current- protection. • Frequency trips Under frequency: overloading of machine, insufficient water, defective governor, belt slip Over frequency: excess water, defective governor, defective AVR
Switchgear and Protection equipments for
38 MHP Trips • Temperature trips causes of windings temperature rise: overloading, incorrect frequency, low pf, harmonics, defective bearings, high ambient temperature • Lighting Protection Earth wire, lighting arrestors • Earthing System Transformer and Generator neutral is grounded
Switchgear and Protection equipments for
39 MHP • Earth Fault Protection Earth fault relay and ELCB are used. Protection schemes for MH
Switchgear and Protection equipments for
40 MHP Switchgear and protection Components for MH
Switchgear and Protection equipments for
41 MHP Switchgear and Protection equipments for 42 MHP Instrumentation • All instrumentation, except kWh meters, may be included on the control panel. • Instrumentation should be at eye level or 1.5 meters from floor level. Instrumentation and measurement Devices in MHP 1. Ballast meter (indicating power dissipated in ballast): In 3-phase ELC systems 3 ballast meters, one for each phase shall be provided. Changes in the reading(s) may indicate failure of one or more ballast elements or variations in the power output of the turbine-generator. (The ballast meter gives percent of power to ballast and should be additionally labeled with power to consumer markings. It can be used to show any difference in actual power and commissioned power at any stage of the life of the scheme). 2. Ammeter and Voltmeter 3. Frequency Meter 4. Energy Meter 5. Pressure Gauge 6. Speed Meter
Switchgear and Protection equipments for
43 MHP Appropriate choice of switchgear, protection and measurement
• A number of switchgear combinations are studied and
compared with each other against relevant criteria, with the aim of achieving: • Satisfactory performance • Compatibility among the individual items; from the rated current 𝐼𝑛 to the fault-level rating 𝐼𝐶𝑈 Compatibility with upstream switchgear or taking into account its contribution • Conformity with all regulations and specifications concerning safe and reliable circuit performance • Overall Cost ( initial + maintenance + protection saving) Switchgear and Protection equipments for 44 MHP