SECCIONADORES RH-BR-16.5-200

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

1 2 3 4 5 6 7 8

1384±30
509±15
A 600±15 600±15 A

B B
1264±15

667
1180
C C

10000
D D

Technical Specification
1. Rated voltage:16.5kV
E 2. Rated current:200A E
3. Rated frequency:50Hz
4. Maximum breaking current:200A
5. Rated short time withstand current:25kA
6. 1min.PF withstand voltage(wet) Scale --- ---
-To earth 50kV Designed Feiru CHEN 2024/06/24
-Across the isolating distance 60kV Checked Disconnector
7. Lightning impulse withstand voltage Approved Xiaoguang LI 2024/06/24
F F
-To earth 125kV Project:
--- RH-BR-16.5/200
-Across the isolating distance 145kV
8. Minimum creepage distance:450mm Zhejiang Haivo Electrical Co.,Ltd 1RH.204.1501
1 2 3 6 7 8