Professional Documents
Culture Documents
m4-Conductor and Support Selections
m4-Conductor and Support Selections
• AAAC is superior in terms of tensile strength, low sag, can be operated at higher temperature.
• AAAC (All Aluminum Alloyed Conductor) is preferred choice than ACSR (Aluminum Conductor Steel
Reinforced) for transmission line because of its high tensile strength.
• ACSR has problem of corrosion so AAAC is preferred in areas of pollution and moisture, coastal areas
• However, ACSR is preferred than AAAC because it is cheaper
• Stranded conductor:
– One or more layers wrapped helically over
central wire.
• Advantages:
– Increased flexibility
– Increased mechanical strength
– Skin effect decreases
Goat 185 316.5 0.08989 680 630 30 7 3.7 3.71 25.97 1492 896 596 13780 0.787 18.99 773 1
Shee
p
225 366.1 0.07771 745 690 30 7 4 3.99 27.93 1726 1036 690 15190 0.787 " 667 1
• It is often seen as a bluish (or other color) glow in the air adjacent to
pointed metal conductors carrying high voltages, and emits light by
the same property as a gas discharge lamp.
• A corona will occur when the strength of the electric field (potential
gradient) around a conductor is high enough to form a conductive
region, but not high enough to cause electrical breakdown or arcing
to nearby objects
𝑞
By Gauss's law, this must be , where 𝑞 is the net charge
𝜖0
enclosed by the Gaussian surface. so that
Therefore,
1/8/2023 MK/ TnD 17
Corona
Since,
𝑷 𝟐𝟕𝟑+𝟐𝟓°𝑪
𝜹= ×
𝟐𝟕𝟑+𝒕 𝟕𝟔𝟎
𝑷
= 𝟎. 𝟑𝟗𝟐𝟏 ×
𝟐𝟕𝟑+𝒕
• Also, the corona discharge is dependent on conductor surface i.e. roughness factor (m)
m = 1 for smooth surface
= 0.93 - 0.98 for rough solid conductor
= 0.8 to 0.87 for stranded conductor
𝑮𝑴𝑫
Or, 𝑽𝒓𝒎𝒔 > 𝟐𝟏. 𝟐𝟏 × 𝒓 × 𝒍𝒏 𝒌𝑽 × 𝒎 × 𝜹
𝒓
• Corona Inception Voltage is a voltage level beyond which corona starts to occur.
𝑮𝑴𝑫
i.e. 𝑉𝑐𝑖 = 𝟑 × 𝟐𝟏. 𝟐𝟏 × 𝒓 × 𝒎 × 𝜹 × 𝒍𝒏 𝒌𝑽
𝒓
The corona occurs if 𝑽system(max) > 𝑽𝒄𝒊 at any instant.
• To avoid corona, “r” should be increased so that 𝑉𝑠𝑦𝑠𝑡𝑒𝑚(𝑚𝑎𝑥) decreases sufficiently below 𝑉𝑐𝑖 .
• Effective “r” is more in bundled conductor, hence corona is lower in bundled conductors.
• Step -2: See Table A-2.2 Determine nearest current carrying capacity conductor
higher than given line current at 40⁰C
Computation of Resistance
Computing the resistance per unit length at maximum possible ambient temperature. If
R is given at ambient temperature i.e. 20 0C.
𝜂 > 94%
The change in the terminal voltage when the load is changed from
no load to full load expressed in terms of full load voltage. i.e.
because of R & X of the line.
−𝟕
𝑮𝑴𝑫
𝑳 = 𝟐 × 𝟏𝟎 𝐥𝐧 𝑯/𝒎
𝑮𝑴𝑹
𝟐𝝅𝝐𝟎
𝑪= 𝑮𝑴𝑫 μF/km
𝒍𝒏
𝑮𝑴𝑹
Where,
DAB = (Dab . Dab' . Da'b . Da'b')1/4
GMRa = √(Daa' . r)
GMRb = √(Dbb' . r)
GMRc = √(Dcc' . r)
Putting the values of GMD and GMRL, inductance per meter per phase is obtained;
L = 2 * 10 -7 ln ( GMD/GMRL )
Putting the value of GMRC, capacitance per meter per phase is obtained;
Note: Daa' Dbb' and Dcc' are not used in GMD calculation but used in GMRLcalculation.
From conductor Table: Conductor LYNX is nearest one to satisfy thermal limit/
continuous current carrying capacity.
𝟐𝝅𝝐𝟎
𝑪= 𝑮𝑴𝑫 μF/km
𝒍𝒏 𝑮𝑴𝑹
• Therefore, it is important to find the most economical size of the conductor. Kelvin's law helps in finding
this
– Annual transmission line cost (𝐶1 ) = (𝑘0 + 𝑘1𝐴)ϑ
– Where , (𝟏+𝒊)𝒏 ×𝒊
𝑘0 = Conductor size independent cost (insulator, tower cost) Annuity Factor (ϑ) =
[ 𝟏+𝒊 𝒏 −𝟏]
𝑘1 = Conductor size dependent cost
𝜗 = Annuity factor n = 20 to 25 years
• Total annual cost (C) = Annual transmission line cost + Annual energy loss cost
Where , 𝒌𝟏 𝒌𝟐
𝑘0 = Conductor size independent cost
𝑘1 = Conductor size dependent cost
𝜗 = Annuity factor 𝒌𝟏 𝒌𝟐 𝒌𝟏 𝒌𝟐
𝒌𝟏 𝒌 𝟐
• For transmission lines, increasing the size of conductor varies the size of tower, Kelvin’s law
doesn’t apply but the fundamental principle Annual transmission line cost (𝐶1 ) = (𝑘0 + 𝑘1𝐴)𝜗
still applies.
• Above 132kV → Pole height ↑ If Span length fixed
Cndtr =Conductor
TLC = Transmission line cost
𝜗𝑇𝐿𝐶 = Annual transmission line cost
• The various types of line support are Wooden Poles, Tubular Steel Poles, RCC
Poles and latticed steel towers.
Wooden Up to LV Distribution Easy to install and cheap Tendency to rot at Used at places with ample
Poles 60m System the ground level supplies of good quality of wood
available. Life is 25-30 years.
Tubular From 50 Up to 33kV light weight, long life, and Costlier than All steel supports should be well-
Steel Poles to 80 m greater strength than wooden and RCC galvanized & should have a life
wooden poles. poles. of at least 30 yrs.
Concrete From 80 Up to 33kV stronger and more durable, Bulky & Heavy, Rectangular in shape at the
Poles to 200 m low maintenance Difficult to bottom and square at the top.
transport Have Long Life.
Latticed 300m and 66 kV and Robust Construction, Costly They are mechanically very
steel above above Withstand Severe weather, strong and have a long life.
towers Suitable for double circuit
• Temperature:
– If there is a change in temperature, there is a change in the length of the conductor.
– Therefore, the length of the conductor increases with the rising temperature between the fixed supports.
– The sag too will, therefore, increase with an increase in temperature.
– It is measured in (°C).
Let,
L = length of the span, i.e. AB,
W is the weight per unit length of the conductor,
T is the tension in the conductor.
We have chosen any point on conductor, say point P.
The distance of point P from Lowest point O is x.
y is the height from point O to point P.
We get,
Suppose AOB is the conductor that has point O as the lowest point.
𝑑𝑠 ′ 2
𝑑𝑦
2
𝑑𝑠 ′ = (1 + 2𝑎2 𝑥 2 )𝑑𝑥
=1+
𝑑𝑥 𝑑𝑥
𝑑𝑠 ′ = (1 + 2a2 𝑥 2 )dx
Let,
Let,
Then,
Stringing chart:
Stress (f) =
• The weight per unit length of the conductor is changed when wind blows at a certain force on the
conductor and ice accumulate around the conductor.
• Wind force acts on the conductor to change the conductor self weight per unit length
horizontally in the direction of the air flow.
• Ice loading acts on the conductor to change the conductor self weight per unit length vertically
downward.
• Considering wind force and ice loading both at a time, the conductor will have a resultant
weight per unit length.
• The resultant weight will create an angle with the ice loading in downward direction.
• Span length ↑
𝑊𝑜𝑟𝑘𝑖𝑛𝑔 𝑇𝑒𝑛𝑠𝑖𝑙𝑒 𝑆𝑡𝑟𝑒𝑛𝑔𝑡ℎ 𝑜𝑓 𝑎 𝑐𝑜𝑛𝑑𝑢𝑐𝑡𝑜𝑟
– Advantages → No. of tower ↓
𝐶𝑟𝑜𝑠𝑠 𝑆𝑒𝑐𝑡𝑖𝑜𝑛𝑎𝑙 𝐴𝑟𝑒𝑎 – Disadvantages → Maximum sag ↑
= 𝑆𝑡𝑟𝑒𝑠𝑠 × • Height of conductor above ground ↑
𝐹𝑎𝑐𝑡𝑜𝑟 𝑜𝑓 𝑆𝑎𝑓𝑡𝑒𝑦
• Height of tower ↑
• Required tower strength ↑
• Cost of tower ↑
• With short spans and low towers, the total number of towers and
associated fittings will be large to cover a tower will be necessary.
• If long spans are used, then the conductor sag between tower points
becomes greater and fewer stronger, higher towers and fittings, but
with correspondingly more steel, are necessary to ensure correct
clearances.
• Basic Span
– The basic span is the horizontal distance between centers of adjacent supports on level ground.
– Most Economical Span
– Line is designed over level ground.
• Average Span
– Mean span length between dead ends
– It is assumed that the conductor is freely suspended such that each individual span reacts to
change in tension as a single average span.
𝐿1 + 𝐿2 + 𝐿3 + 𝐿4 + ⋯ + 𝐿𝑛
∴ 𝐿𝑎𝑣𝑔 =
𝑛
• If all spans in a section of line are of the same length then the tension on individual span will be equal.
• Keeping the span lengths the same is possible on lines constructed on open terrains. However, for construction along highways and residential areas, the span
lengths can never be equal. Ruling Span is defined as the assumed uniform span that most closely resembles the variety of spans that are in any particular section of the line.
1/8/2023 MK/ TnD 110
Conductor Spacing
• The spacing of conductors is decided not only by the electrical consideration of the working voltage, but also by
mechanical factors such as length of span, weight of conductors, prevalent wind direction, etc.
• With the increase of sag, the magnitude of the swing also increases and proper care is to be taken to maintain
clearance under unfavorable condition.
• For HT or EHV lines, with a voltage level of 66 kV or above the conductor spacing depends upon the
configuration of the conductors.
S = Sag
𝑽𝒌𝑽 𝒎𝒂𝒙 − 𝟑𝟑
𝑯𝒈 = + 17 ft (1 m = 3.28 ft)
𝟑𝟑
hg H1 H2 H3 Ht
𝒍 = span length
T = tension in conductor
w = weight per unit length of conductor
T sin ∝
1/8/2023 MK/ TnD 115
Moments/ Forces acting on tower and tower strength computation
Moment because of
turning of conductor
Moment because of
wind force on conductor
3.
4.
1/8/2023 MK/ TnD 117
Moments acting on tower and tower strength computation
Assumption:
80% of tower is class A .
15% of tower is class B.
5% of tower is class C.
Moment due to
Moment due to wind
turning of conductor
force on conductor
Where 𝒉𝟏, 𝒉𝟐 𝒂𝒏𝒅 𝒉𝟑 heights of lower, middle and top are power conductor from ground and 𝑯𝒕
is the total height of the tower. The power conductor has maximum working tension of 6000kg and
diameter of 4cm. The earth wire has maximum working tension of 2000kg and diameter of 2 cm.
Assume maximum conductor deviation of 5⁰ is permissible for all towers and wind force is
𝟏𝟎𝟎𝒌𝒈/𝒎𝟐 . Compute most economical span.
• A transmission line has a span of 150 m between level supports. The line conductor has a cross-
sectional area of 1.25 cm and it weighs 120 kg per 100 m. If the breaking stress of the copper
conductor is 4220 kg/cm . Calculate the maximum sag for a safety factor of 4. Assume a maximum
wind pressure of 90 kg/m of projected surface.
• An overhead line has a span of 160 m of copper conductor between level supports. The conductor
diameter is 1.2 cm and has a breaking stress of 35 kg/mm . Calculate (a) the deflecting sag (b) the
vertical sag. The line is subject to a wind pressure of 40 kg/m of projected area and radial ice
coating of 9.53 mm thickness. The weight of ice is 913.5 kg/m . Allow a factor of safety of 2 and
take the density of copper as 8.9 g/cm .