TC500A Commercial Thermostat

CONNECTED DEVICE FOR COMMERCIAL BUILDINGS

PRODUCT DATA

FEATURES
• Easily customizable and intuitive user interface.
• Multiple, configurable, levels of user privilege access
for features such as Occupancy set points, Date/Time,
Schedules, Calendars of special events, remote and
local Manual Override, remote and local Occupancy
Override, Choice of language and units, and screen
lockouts to prevent unauthorized settings changes.
• Advanced commercial control algorithms such as auto
changeover, scheduled purge, power-up delay time,
freeze protection, demand limit controls, and same
reliable optimized recovery methods established over
decades of use.
• Settings to switch Fahrenheit to Celsius and vice-versa.
• Heat setpoints are limited automatically between 40°F
to 90°F and cool setpoints are limited automatically
between 50°F to 99°F
APPLICATION • Auto display goes into sleep mode when there is no
user action.
• A LED indicator to show the operational status of the
TC500A-N Thermostats is an advanced, configurable,
thermostat when the display goes to sleep mode.
connected devices for commercial buildings. It controls
• Real-Time Clock time keeping accuracy with 72 hour
and monitors Rooftop Unit, Heat Pump equipment, and
retention during power loss.
their accessories. This device communicates over Wi-Fi,
• Thermostat can be configured via HMI, the Honeywell
Bluetooth, BACnet I/P over Wi-Fi, BACnet MS/TP, and Sylk
Connect Mobile app, or BACnet.
to easily integrate with the building automation system.
• BACnet settings can be configured via HMI or the
The built-in intelligent control algorithms of the device Honeywell Connect Mobile app.
help to achieve the perfect balance between Energy
Efficiency and Comfort. The device is packaged with Equipment Control Features
numerous presets suitable for most commercial building
requirements that enable the easy and quick initial setup. • 5H/3C Heat Pump, 3H/4C Conventional, Fan coil,
modulating heat system, and modulating cool system.
The firmware of the device can be upgraded via Wi-Fi and • Constant speed Fan, 3-speed Fan, Multispeed, and
MS/TP network. The device has four universal terminals Variable Speed Fan
and a pair of Sylk terminals to connect with sensors or • Packaged Economizer Enable Output
other accessories. It also has a built-in temperature • Multiple Dehumidification and Humidification options
sensor, humidity sensor, and proximity sensor. • Service mode to manually command the outputs to test
the operation of the mechanical equipment
Users can connect to the thermostat via Wi-Fi with the • Auto mode to switch between heating and cooling
Honeywell Connect Me app. The Honeywell Connect Me according to the current space temperature
app gives authorized users access to the Honeywell TC500 • Staging control, PID Tuning, CPH, OAT Lockout, DAT
Thermostats in their commercial buildings. They can Lockout, Modulating control
remotely monitor sites, schedules, settings, and override • Demand Limit Control to save energy
controls. Users can add and configure devices, manage • System Switch Options
users, and more – all from a mobile device. • Smoke Monitor
• Purge, Delta T, Internal, External Economizer controls,
and Auto Demand Response.
• Exhaust fan configuration in the Internal Economizer
controls.
TC500A COMMERCIAL THERMOSTAT

TECHNICAL SPECIFICATIONS Table 3. IO Characteristics (Continued)

UI x 2 • Resistive Temperature Sensor


Power Characteristics Input
— NTC10K Type II, C7021 series
— NTC10K Type III (Space Tem-
Table 1. Power Characteristics
perature Sensor only), C7023
series
Power Supply Rated voltage: 24VAC — NTC20K, TR21, and C7041
50/60Hz, series
Working voltage range: • Temperature Accuracy
20-30VAC, UL listed — ±1°F(±0.5°C) at 50 to 90 °F(10
class-2 transformer or IEC to 32°C)
61558 listed transformer. — ±2°F(±1.1°C) at 30 to 122°F(-
1.1 to 50°C)
Power Consumption Max. 8.5VA @ 24VAC
• Voltage Input, SELV
(Display ON) (355mA @ 24VAC)
— 0-10V, ±5% of full scale
Min. Load 4VA (all DOs OFF, No Sylk • Digital Input
sensor) — Dry contact closure
— Open circuit (≥ 100Kohms)
Max. Load 96VA (all DOs ON) — Closed circuit (≤100ohms)

DO (G, • Relay Output


Display Y1,Y2,Y3,W1,W2
,W3)
• Rated Average Current
— 1A at 24VAC
• Rated Pulse Current
Table 2. Display — 3.5A at 24VAC

Display Type 24 BPP TFT display with DO (AUX) • Relay Dry Contact
CTP • Rated Average Current
— 1A at 24VAC/DC
Resolutions 480x480 pixel • Rated Pulse Current
— 3.5A at 24VAC/DC
Active Display Area 4” diagonally

Backlight LCD (Dimmable) Operating Environment


Table 4. Operating Environment
IO Characteristics
Ambient 32 to 122 °F (0 to 50°C)
Table 3. IO Characteristics Operating
Temperature
UIO x 2 • Resistive Temperature Sensor
Input Ambient 10 to 90% relative humidity (non-
— NTC10K Type II, C7021 series Operating condensing)
— NTC10K Type III (Space Tem- Humidity
perature Sensor only), C7023
series Storage -40 to 150 °F(-40 to 65.5°C)
— NTC20K, TR21, and C7041 Temperature
series
• Temperature Accuracy Protection IP20
— ±1°F(±0.5°C) at 50 to 90 °F(10 Class
to 32°C)
— ±2°F(±1.1°C) at 30 to 122°F(-
1.1 to 50°C) Onboard Sensors
• Voltage Input, SELV
— 0-10V, ±5% of full scale Table 5. Onboard Sensors
• Digital Input
— Dry contact closure Temperature Heat: 40 to 90°F (4.5 to 32°C)
— Open circuit (≥ 100Kohms) Cool: 50 to 99°F (10 to 37°C)
— Closed circuit (≤100ohms) Resolution: 1 °F (0.5°C)
• Voltage Output Control Accuracy: ±1.5°F (0.8°C) at
— 0-10V, ±3% of full scale @2K Room Temperature
ohms
Humidity Range: 20~90% RH
Resolution: 1%RH
Control Accuracy: ±5%RH at Room
Temperature and 20~90%RH

31-00398M-06 | Rev. 02-23 2


TC500A COMMERCIAL THERMOSTAT

Compliances Table 9. Supported Sensors and Functions

Sensors Options Part Numbers


Table 6. Compliances
Dirty Filter Direct DPS200, DPS400,
Certificates CE, FCC, ICES, UL/cUL, RoHs, REACH, Sensor (Normally Open) DPS1000
California Title 24, BTL, and Prop65. Reverse (Dry contact
(Normally differential
Standards EN 60730-1, EN 60730-2-9, EN Closed) pressure switch)
301489-1, EN 301489-17, EN
300328, EN 301893, EN 62479, Proof Of Air Direct DPS200, DPS400,
UL60730-1, UL60730-2-9, Title 47 Flow Sensor (Normally Open) DPS1000
part 15 subpart B, Title 47 part 15 Reverse (Dry contact
subpart C, RSS 210, ICES-003 (Normally airflow switch)
Closed)
Communication Technologies Shutdown Direct Dry contact
Sensor (Normally Open) shutdown switch
Table 7. Communication Technologies Reverse
(Normally
BACnet IP Over Wi-Fi Closed)

Wi-Fi 802.11 b/g/n Mixed Air NTC 20K C7250A, C7041


Supported security levels Temperature NTC 10K Type II C7021
OPEN, Sensor NTC 10K Type III C7023
WPA, Sylk C7400S
WPA2,
WPA3_WPA2_AES
Outdoor Air NTC 20K C7250A, C7041
Bluetooth BLE 4.2 with 1 Mbps Temperature NTC 10K Type II C7021
Classic Bluetooth with Sensor NTC 10K Type III C7023
max. 3 Mbps Sylk C7400S

SylkTM Honeywell SylkTM Return Air NTC 20K C7250A, C7041


Temperature NTC 10K Type II C7021
BACnet MS/TP Over RS485 Sensor NTC 10K Type III C7023
(9.6, 19.2, 38.4, 76.8, Sylk C7400S
115.2 Kbps)
Discharge Air NTC 20K C7250A, C7041
Temperature NTC 10K Type II C7021
Electrical Characteristics Sensor NTC 10K Type III
Sylk
C7023
C7400S
Table 8. Electrical Characteristics Space NTC 20K TR21, C7041,
Temperature NTC 10K Type II C7772A, C7021,
Rated Impulse Voltage 500 V Sensors NTC 10K Type III C7772F, C7023,
Sylk C7772G
Construction of Control Independently Mounted TR40, TR40-H,
Control TR40-CO2, TR40-
H-CO2
Operation Method Type 1 Action TR120 (max 1)
Pollution Degree 2 CO2 sensor 0-10 / 2-10 VDC C7233, C7263,
Sylk C7232
Purpose of Control Operating Control TR40-CO2
TR40-H-CO2
Supported Sensors and Functions Proof of Digital Input Dry contact
waterflow waterflow switch
Table 9. Supported Sensors and Functions
Window Open Direct Dry contact
Sensors Options Part Numbers Sensor (Normally Open) window open
Reverse sensor
Occupancy Direct Dry contact (Normally
Sensor (Normally Open) occupancy sensor Closed
Reverse
(Normally
Closed)

3 31-00398M-06 | Rev. 02-23


TC500A COMMERCIAL THERMOSTAT

Table 9. Supported Sensors and Functions Table 10. Terminal Identification

Sensors Options Part Numbers Terminal Label Connection

Drain Pan / Direct Dry contact BACnet Communications


+
Leak Detector (Normally Open) float switch or (BACnet MS/TP A)
Reverse water sensor RS485
(Normally BACnet Communications
_
Closed (BACnet MS/TP B)

Jumper between R and RC for


R-RC
Terminal Identification single transformer system

24VAC power from cooling


RC
transformer

G Fan

Relay output, Compressor


Y1
contactor (stage1)

Relay output, Compressor


Y2
contactor (stage2)
24VAC
Relay output, Compressor
Y3 contactor (stage3)/Configurable
Output

W1 Relay output, Heat (stage1)

W2 Relay output, Heat (stage2)


Fig. 1. Terminals Relay output, heat
W3
(stage3)/Configurable Output
Table 10. Terminal Identification
Relay dry contact, Aux-1
Terminal Label Connection
Aux
24VAC power from heating Relay dry contact, Aux-2
R
transformer

24VAC 24VAC common (Neutral). For 2


C
transformer systems, use Thermostat Variants
common wire from cooling
transformer Table 11. Thermostat Part Numbers

1 Universal input/output TC500A-N Thermostat with North


UIO1 American Wi-Fi
COM Common conformance
2 Universal input/output
UIO2
COM Common Accessories
1 Universal input Table 12. Accessories Part Numbers
UI1
COM Common Decoplate-N TC500 deco plate for NA
junction boxes
2 Universal input
UI2 3011-7144-001 Replacement Backplate
COM Common for TC500A-N
Sylk bus, master, power output
Sylk
(S-BUS) Sylk bus, master, power output

31-00398M-06 | Rev. 02-23 4


TC500A COMMERCIAL THERMOSTAT

Terminal Assignments
Table 13. Terminal Assignments

Terminal Assignments
(Default & Optional Assignments)
Type Terminal Label
DEFAULT INPUTS OUTPUTS

DO1 G Supply Fan Fan Command High


Speed Fan

DO2 W1 Heat Stage 1 Heating Floating Open

DO3 W2 Heat Stage 2 Heating Floating


Closed

DO4 W3 / Aux NA Heat Stage 3,


Cool/Compressor
Stage 4,
Reversing Valve OB,
Low Speed Fan,
Medium Speed Fan,
Occupancy,
Dehumidification,
Humidification,
Purge Output,
Exhaust Fan 1,
Exhaust Fan 2.

DO5 Y1 Cool/Compressor Cooling Floating Open


Stage 1
Digital DO6 Y2 Cool/Compressor NA Cooling Floating
Outputs Stage 2 Closed

DO7 Y3 / Aux NA Cool/Compressor


Stage 3,
External Economizer,
Low Speed Fan,
Medium Speed Fan,
Occupancy,
Dehumidification,
Humidification,
Purge Output,
Exhaust Fan 1,
Exhaust Fan 2.

DO8 Aux Cool/Compressor


(Dry Contact, Stage 4,
2 terminals) External Economizer,
Low Speed Fan,
Medium Speed Fan,
Occupancy,
Dehumidification,
Humidification,
Purge Output,
Exhaust Fan 1,
Exhaust Fan 2.

5 31-00398M-06 | Rev. 02-23


TC500A COMMERCIAL THERMOSTAT

Table 13. Terminal Assignments

Terminal Assignments
(Default & Optional Assignments)
Type Terminal Label
DEFAULT INPUTS OUTPUTS

UI1 UI1 NA CO2 Sensor Input,


(2 terminals) Dirty Filter,
Universal
Discharge Air Sensor,
Inputs UI2 UI2 NA Drain Pan Sensor,
(2 terminals) External Economizer Fault,
Mixed Air Sensor,
UIO1 UIO1 NA Occupancy Sensor, CO2 Output,
(2 terminals) Outdoor Air Sensor, Fan Speed Control,
Proof of Airflow, Modulating Cool,
Universal UIO2 UIO2 NA Modulating Heat,
Inputs/ Proof of Waterflow,
(2 terminals) Return Air Sensor, Purge Output.
Outputs
Shutdown,
Space Temperature Sensor,
Window Open Sensor.

R R 24v Power

Power C C Common

RC RC 24v Power / Cooling

1 Selectable type pre-


Sylk Bus S-Bus Sylk connection defined by Sylk address
2 number

31-00398M-06 | Rev. 02-23 6


TC500A COMMERCIAL THERMOSTAT

DIMENSIONS
Thermostat
4 x 11/32”
3 -19/32 ” (91.2 mm) (9mm) 4 x 3/16”
(4.5mm)

4 - 15/32” 2 - 3/8” 3 - 1/4”


(113.7 mm) (60.3mm) (82.75mm)

Decoplate-N

7 - 2/25 ” (180 mm) 2/5” (10.2 mm)

5 - 9/10”
(150 mm)

7 31-00398M-06 | Rev. 02-23


TC500A COMMERCIAL THERMOSTAT

GENERAL SAFETY applicables aux appareils radio exempts de licence.


L’exploitation est autorisée aux deux conditions
INFORMATION suivantes:
1. L’appareil ne doit pas produire de brouillage;
• When performing any work (installation, mounting, 2. L’appareil doit accepter tout brouillage radioélec-
start-up), all manufacturer instructions and in trique subi, même si le brouillage est susceptible
particular the mounting Instructions guide (31- d’en compromettre le fonctionnement.
00399M) and the user guide (31-00400M) are to be • This equipment has been tested and found to comply
observed. with the limits for a Class B digital device, pursuant to
• TC500A-N Thermostat may be installed and mounted part 15 of the FCC Rules. These limits are designed to
only by authorized and trained personnel. provide reasonable protection against harmful
• Rules regarding electrostatic discharge should be interference in a residential installation. This
followed. equipment generates uses and can radiate radio
• If TC500A-N Thermostat is modified in any way, except frequency energy and, if not installed and used in
by the manufacturer, all warranties concerning accordance with the instructions, may cause harmful
operation and safety are invalidated. interference to radio communications. However, there
• Make sure that the local standards and regulations are is no guarantee that interference will not occur in a
observed at all times. particular installation. If this equipment does cause
• Use only accessory equipment which comes from or harmful interference to radio or television reception,
has been approved by Honeywell. which can be determined by turning the equipment off
• It is recommended that devices be kept at room and on, the user is encouraged to try to correct the
temperature for at least 24 hours before applying interference by one or more of the following measures:
power. This is to allow any condensation resulting from — Reorient or relocate the receiving antenna.
low shipping/storage temperatures to evaporate. — Increase the separation between the equipment
• Investigated according to United States Standard UL- and receiver.
60730-1, and UL60730-2-9. — Connect the equipment into an outlet on a circuit
• Investigated according to Canadian National different from that to which the receiver is con-
Standard(s) C22.2, No. 205-M1983 (CNL-listed). nected.
• Do not open TC500A-N Thermostat, as it contains no — Consult the dealer or an experienced radio/TV
user-serviceable parts inside! technician for help.
• CE declarations according to LVD Directive • To satisfy FCC&IC RF exposure requirements, a
2014/35/EU and EMC Directive 2014/30/EU. separation distance of 20 cm or more should be
• Product standards are EN 60730-1 and EN 60730-2-9. maintained between the antenna of this device and
• TC500A-N Thermostat is Class B digital apparatus and persons during device operation. To ensure
complies with Canadian ICES-003. compliance, operations at closer than this distance is
• This device complies with part 15 of the FCC Rules. not recommended.
Operation is subject to the following two conditions: (1) • Les antennes installées doivent être situées de facon à
This device may not cause harmful interference, and (2) ce que la population ne puisse y être exposée à une
this device must accept any interference received, distance de moin de 20 cm. Installer les antennes de
including interference that may cause undesired facon à ce que le personnel ne puisse approcher à 20
operation. cm ou moins de la position centrale de l’ antenne.
• Caution: Changes or modifications to this unit not Region Selection (for Wi-Fi 2.4G device)
expressly approved by the party responsible for • Limited by local law regulations, version for North
compliance could void the user's authority to operate America does not have region selection option.
the equipment.
• This device contains licence-exempt Safety Information as per EN60730-1
transmitter(s)/receiver(s) that comply with Innovation, TC500A-N Thermostat is intended for residential,
Science and Economic Development Canada’s licence- commercial environments.
exempt RSS(s). Operation is subject to the following
two conditions: TC500A-N Thermostat is an independently mounted
1. This device may not cause interference. electronic control system with fixed wiring.
2. This device must accept any interference, including
interference that may cause undesired operation of TC500A-N Thermostat is used for the purpose of building
the device. HVAC control and is suitable for use only in non-safety
• L’émetteur/récepteur exempt de licence contenu dans controls for installation on or in appliances.
le présent appareil est conforme aux CNR d’Innovation,
Sciences et Développement économique Canada Note
All images used in this document are for illustrative purposes
only and may not match the actual product.

Honeywell Building Technologies


Honeywell
715 Peachtree Street NE
Atlanta, GA 30308
® U.S. Registered Trademark
customer.honeywell.com © 2023 Honeywell International Inc.
31-00398M-06 | Rev. 02-23
buildingcontrols.honeywell.com