Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

GENERAL NOTES :

POWER LAYOUT

WF WF WF

SCHEDULE OF LOADS AND COMPUTATIONS :


DISTRIBUTION PANELBOARD " DP " WF WF WF

CKT. VA PER BRANCH CKT. BREAKER SIZE OF HOMERUN


LOAD DESCRIPTION VOLTS ( WIRES IN CONDUIT )
NO. CKT. AF P AT

1 LIGHT OUTLETS 689 230 50 2 15 2 - 3.5mm² TW + 1 - 3.5mm² TW (G) in 15mmØ C

2 LIGHT OUTLETS 1128 230 50 2 15 2 - 3.5mm² TW + 1 - 3.5mm² TW (G) in 15mmØ C LIGHTING LAYOUT
3 CONVENIENCE OUTLETS 1080 230 50 2 20 2 - 3.5mm² TW + 1 - 3.5mm² TW (G) in 15mmØ C

4 CONVENIENCE OUTLETS 1080 230 50 2 20 2 - 3.5mm² TW + 1 - 3.5mm² TW (G) in 15mmØ C


ELECTRICAL SYMBOLS :
5 CEILING FANS 540 230 50 2 20 2 - 3.5mm² TW + 1 - 3.5mm² TW (G) in 15mmØ C OVERHEAD SERVICE ENTRANCE: 230
V, 1Ø, 2W, 60Hz., A.C. WITH 20mmØ 2
2-36 WATTS, 230 VOLTS, 60Hz, FLUORESCENT LIGHTING FIXTURE,
TOTAL 4517 MACB : 50AF, 2P, 240V, 40AT, 18kAIC TYPE "F" CONDULET, WEATHERHEAD BOX TYPE

1 18 WATTS COMPACT FLUORESCENT LAMP WITH MEDIUM BASE,


2 - 5.5mm² THWN + 1-5.5mm²
4517 1.00 = 19.64 AMPERES KEYLESS TYPE PORCELAIN RECEPTACLE OUTLET
I@ "DP" TW (G) in 20mmØ RSC
L 100% D.F. = 230 USE : 2 - 8.0mm² THHN + 1 - 5.5mm² TW (G) in 20mm Ø RSC WALL FAN, 65 WATTS, 230V, 60Hz
WF

S FC WALL FAN CONTROL SWITCH


M 5.5mm² TW GROUND WIRE
in 15mmØ C - CLAMPED TO S SINGLE POLE WALL SWITCH
COPPER-CLAD GROUNDING
S² 2 SINGLE POLE WALL SWITCHES IN ONE SWITCH PLATE
ROD

3100 mm (MIN.)
ELECTRICAL RISER

1800 mm
DUPLEX CONVENIENCE OUTLET, GROUNDING TYPE, 20A, 250VOLTS
SCHEDULE OF LIGHTING FIXTURES AND LAMPS : GROUND FLOOR LEVEL
"WP" DENOTES WEATHERPROOF OUTLET
1800 mm

BUILDING LINE
INSTALLATION/ CONCEALED OR EMBEDDED CONDUIT RUN
SYMBOLS DESCRIPTION FINISHED GRADE LEVEL
MOUNTING
UNDERGROUND OR UNDERFLOOR CONDUIT RUN
GROUNDING SYSTEM
ONE (1)-18W, 230V, 60Hz AC,COMPACT FLUORESCENT LIGHTING FIXTURE WITH MEDIUM SURFACED CEILING 16mmØ X 2400mm LENGTH
1 CIRCUIT HOMERUN
BASE KEYLESS TYPE PORCELAIN RECEPTACLE MOUNTED COPPERCLAD GROUNDING
ROD DISTRIBUTION PANELBOARD
SURFACED CEILING
2 TWO (2)-36W, 230V, 60Hz AC, FLUORESCENT LIGHTING FIXTURE , BOX TYPE
MOUNTED M ELECTRIC SERVICE METER
NOTE: ALL FLUORESCENT LIGHTING FIXTURES SHALL BE EQUIPPED WITH A HIGH POWER FACTOR, PRE-HEAT ELECTRIC SERVICE ENTRANCE
WITH STARTER AND THERMALLY PROTECTED BALLAST, COMPLETE WITH ALL NECESSARY ACCESSORIES,
WIRED AND READY FOR USE.
ELECTRICAL RISER DIAGRAM PULL BOX / JUNCTION BOX WITH COVER PLATE

GROUNDING SYSTEM

VARIOUS DPWH
(SEE COVER SHEET) (SEE COVER SHEET) (SEE COVER SHEET) PROPOSED PROJECTS ELECTRICAL SYMBOLS, GENERAL NOTES, BOD
SCHEDULE OF LIGHTING FIXTURES AND LAMPS, 1
NOTE : STANDARD ONE-STOREY SCHEDULE OF LOADS AND COMPUTATION, EE-2
GILBERTO S. REYES RAUL C. ASIS ROGELIO L. SINGSON 1-2
SCHOOL BUILDING ELECTRICAL RISER DIAGRAM
OIC, BUILDING DIVISION DIRECTOR IV, BOD UNDERSECRETARY SECRETARY