HE

DATE : JUNE 19, 2023


Specification No. : HETS-2112-033-Rev:0
DE No. : HEDE-2112-033-Rev:0

HI-ESSENCE Cable Sdn. Bhd.

Specification
For

1.) I02-300V CU/PE/OSCR/PE/SWA/PVC-FR CABLE

CONFIRMED BY CUSTOMER:

Prepared by Checked by Approved by

NURIL HAZWANI IBRAHIM TENGKU NUR ILYANIS ABDUL RAHIM JUSOH


HE
DATE : APRIL 22, 2021
Specification No. : HETS-2007-010-Rev:5
DE No. : HEDE-2007-010-Rev:5

1.) I02-300V CU/PE/OSCR/PE/SWA/PVC-FR CABLE


1. SCOPE
This specification covers 300V plain annealed circular stranded copper conductor, PE insulated,
collectively screened, PE inner covering, galvanized steel wire armoured, and PVC outer sheathed,
flame retardant cables mainly in accordance with BS EN 50288-7.

2. CONSTRUCTION
Conductor : Plain annealed circular stranded copper conductor class 2 as perIEC 60228.
Insulation : Polyethylene (PE) compound.
Twisted : Two insulated core shall be twisted together into a pairs.
Collectively screened : Laminated aluminum/Polyester tape with a tinned annealed copper drain
wire.
Inner Covering : Black colored Polyethylene (PE) compound.
Armouring : Galvanized steel wire armoured with binder tape.
Outer sheath : Flame retardant polyvinyl chloride (PVC) compound with ultra violet (UV).
Outer sheath color : Light Blue (IS)

Core identification:
Single pair : White (+), Black (-)

Cable marking: (to be embossed or printed)


EX:“ HE CABLE 300V CU/PE/OSCR/PE/SWA/PVC 1PR×1.0MMSQ I0201PR10IS1,
BS EN 50288-7, 20xx”

Length marking:
“Continuously marked at every 1m interval throughout the cable length”

3.TEST
3.1 Standard Factory Routine Tests (To be performed during FAT)
a) Construction and dimensional test
b) Conductor resistance test
c) Insulation resistance test
d) A.C. voltage test

3.2 Additional Type Tests (The Cables Compliance to this Test. If required we can perform
these Test but with additional cost impact)
a) Flame retardant test according to IEC 60332-3 Cat A. (compliance to)
b) H.C.L. emission < 17% by weight, test according to IEC 60754-1. (compliance to)
c) Oxygen index >30, test according to ASTM D 2863. (compliance to)

4. PACKING
Each drum of cable length shall be wound on reel to prevent damage during transportation and
handling
HE
DATE : APRIL 22, 2021
Specification No. : HETS-2007-010-Rev:5
DE No. : HEDE-2007-010-Rev:5

5. TABLE: 300V CU/PE/OSCR/PE/SWA/PVC-FR CABLE(I02)


No. Conductor Thickness Dimension Thickness Diameter Diameter Thickness Overall Maximum Test
Nominal Diameter of of of of of of Diameter Conductor voltage
of Inner
Cross- Insulation drain wire Inner Armour Outer
pairs Covering Resistance
Sectional Covering Wire Sheath
(minimum) (20℃)
Area (approx.) (minimum) (nominal) (approx.) (nominal) (minimum) (approx.)
mm2 mm mm mm2 mm mm mm mm mm Ω/km kV/min
1PR 1.0 1.29 0.26 0.5 0.75 7.0 0.9 0.84 12.0 18.1 1.0/1
NOTE:
1) The cable inner & overall diameter, D <20mm-----Tolerance ±10%
2) The cable inner & overall diameter, 20mm≤ D <40mm-----Tolerance ±2mm
3) The cable inner & overall diameter, D≥40mm-----Tolerance ±5%

6. OVALITY
The measurement of ovality shall be made in accordance to BS 7211 in which the difference between any 2 values of diameter shall not be more than 15% of the
upper limit (Max. spec) for the mean overall diameter.

≤ 15%

::Where OD = Overall diameter

7. MEASUREMENT OF CABLE DIAMETER


The measurements of the diameters were made in accordance to the IEC 60811-203 in which the cable diameters are measured by using the diameter tape (for
cable diameter exceed 25 mm) by taking the average readings of 2 points. While for cable diameter not exceeding 25 mm, the measurement shall be made by