Professional Documents
Culture Documents
UNDP cvil design calculations final
UNDP cvil design calculations final
Hybrid-System design
(civil works)
UNDP Hodeida office Site Survey Report
Wind load calculations according to the drawings and dimensions shown above.
Input Data
• Terrain category: = 0
• the highest temperature in Hodeida= 39C.
• the highest pressure in Hodeida= 1015mb.
• Basic wind velocity at the project site : v = 10 m/s ,according to wind atlas website ,but we
will take 2 safety factor to be vb = 20 m/s
• Horizontal dimension of rectangular plan parallel to the wind direction: d = 4.12 m
• Horizontal dimension of rectangular plan perpendicular to the wind direction (crosswind
dimension): b = 11.618 m
• Height of solar panels from rooftop: h = 4.5 m
• Roof pitch angle: α = 15 °
• Degree of blockage under the canopy roof: φ = 0
• Orography factor at reference height ze: c0(ze) = 1
• Structural factor: cscd = 1
Reference height
The reference height for the wind action ze is equal to the maximum height above rooftop of the
solar panels h, as specified in EN1991-1-4table7.3(8). Therefore:
ze = h = 4.5 m
The reference area for the wind action Aref is equal to the area of sloped solar panels. It is
calculated from the plan dimensions b and d by taking into account the inclination of the area of
sloped solar panels surface with angle α. Therefore:
The basic wind velocity vb is defined in EN1991-1-4 table4.2(2)P as a function of the wind
direction and time of year at 10 m above ground of terrain category II. The value of vb includes the
effects of the directional factor cdir and the seasonal factor cseason and it is provided in the National
Annex. In the following calculations the basic wind velocity is considered as vb = 35.00 m/s.
Terrain roughness
The roughness length z0 and the minimum height zmin are specified in EN1991-1-4 Table 4.1 as a
function of the terrain category. For terrain category 0 the corresponding values are z0 = 0.003 m
and zmin = 1.0 m.
The terrain factor kr depending on the roughness length z0 = 0.003 m is calculated in accordance
with EN1991-1-4 equation (4.5):
The roughness factor cr(ze) at the reference height ze accounts for the variability of the mean wind
velocity at the site. It is calculated in accordance with EN1991-1-4 equation 4.4. For the examined
case ze ≥ zmin:
Orography factor
As we know that the Terrain category: = 0 and based on the recommended procedure in EN1994-
1-1table4.3.3 for calculation of the orography factor c0(ze) is described in EN1994-1-1tableA.3, the
orography factor is considered as c0(ze) = 1.000.
The mean wind velocity vm(ze) at reference height ze depends on the terrain roughness, terrain
orography and the basic wind velocity vb. It is determined using EN1991-1-4 equation (4.3):
Wind turbulence
The turbulence intensity Iv(ze) at reference height ze is defined as the standard deviation of the
turbulence divided by the mean wind velocity. It is calculated in accordance with EN1991-1-4
equation 4.7. For the examined case ze ≥ zmin.
Iv(ze) = kI / [ c0(ze) ⋅ ln(max{ze, zmin} / z0) ] = 1.000 / [ 1.000 ⋅ ln(max{4.500 m, 1.0 m} / 0.003 m) ] = 0.1367
The basic velocity pressure qb is the pressure corresponding to the wind momentum determined at
the basic wind velocity vb. The basic velocity pressure is calculated according to the fundamental
relation specified in EN1991-14table4.5(1):
qb = (1/2)×ρ × vb2 = (1/2) ×1.132779 kg/m3× (20 m/s)2 = 226.5558 N/m2 = 0.2265558 kN /m2
The peak velocity pressure qp(ze) at reference height ze includes mean and short-term velocity
fluctuations. It is determined according to EN1991-1-4 equation 4.8:
The net pressure coefficients Cp,net represent the maximum local pressure for all wind directions
and they are used in the design of local elements such as solar panels surface area. Net pressure
coefficients are given for four zones A, B, C, D as defined in the figure included in EN1991-1-4
Table 7.7 that is reproduced above. Zones B, C extend at the sides of the solar panel installation
area, Zone D extends along the ridge, and Zones A extend at the remaining area for each of the
two sloped faces of the solar panels surface area
The inclined length of the solar panels surface area parallel to the wind direction is:
Zone C corresponds to the regions parallel to the windward and leeward edges having width d'/10
= 0.427 m. Zone B corresponds to the regions parallel to the side edges having width b/10 = 1.191
m, where b is the width of the solar panels surface area transverse to the wind direction. Zone D
corresponds to the region parallel to the ridge having width d'/10 = 0.427 m at each side of the
ridge. Zone A corresponds to the remaining central region for each of the two sloped faces of the
solar panels surface area
The net pressure coefficient cp,net for each of the zones A, B, C, D are defined in EN1991-1-4
Table 7.7 as a function of the roof angle α and the blockage factor φ. For the examined case: α =
15.00 ° and φ = 0.000. Therefore, according to EN1991-1-4 Table 7.7 the following net pressure
coefficients and overall force coefficient are obtained, using linear interpolation where appropriate:
Negative values for the external pressure coefficient correspond to suction directed away from the
upper surface inducing uplift forces on the roof. Both positive and negative values should be
considered for each zone.
UNDP Hodeida office Site Survey Report
The net wind pressure on the surfaces of the structure wnet corresponds to the combined effects of
external wind pressure and internal wind pressure.
For structural surfaces consisting of only one skin the net pressure effect is determined as:
For structural surfaces consisting of more than one skin EN1991-1-4table7.2.10 is applicable.
For the different pressure zones on the solar panels surface area the following net pressures are
obtained:
(zones A is the remaining central region of the two sloped faces located more than d'/10 = 0.427 m
or b/10 = 1.191 m from the edges and the central ridge)
(zone C extends up to d'/10 = 0.427 m from the windward and leeward edges)
Negative net pressure values correspond to suction directed away from the external surface
inducing uplift forces on the solar panels surface area. Both positive and negative values should be
considered.
The overall pressure coefficients cf represents the overall wind force and it will be used in the
design of the overall load bearing structure. The overall pressure coefficient cf is defined in
EN1991-1-4 Table 7.7 as a function of the roof angle α and the blockage factor φ. For the
examined case: α = 15.00 ° and φ = 0.000. Therefore, according to EN1991-1-4 Table 7.7 the
following overall pressure coefficient is obtained, using linear interpolation where appropriate:
cf = -0.800 or 0.400
Negative values for the overall pressure coefficient correspond to suction directed away from the
upper surface inducing uplift forces on the solar panels surface area. Both positive and negative
values should be considered, as explained below.
Structural factor
The structural factor cscd takes into account the structure size effects from the non-simultaneous
occurrence of peak wind pressures on the surface and the dynamic effects of structural vibrations
due to turbulence. The structural factor cscd is determined in accordance with EN1991-1-4 Section
The wind force Fw corresponding to the overall wind effect on each sloped face of the solar panels
surface area is calculated in accordance with EN1991-1-4 equation 5.3:
Fw = cscd×cf×Aref×qp(ze)
where Aref = 49.107 m2 is the reference wind area for the sloped face of the solar panels surface
area as calculated above.
Input Data
• Density 2700kg/m3
• Tensile Strength, Ultimate :260 MPa.
• Tensile Strength, yield :240 MPa.
• Modulus of Elasticity :69GPa
• Poisson Ratio:0.33.
• Fatigue Strength: 100 GPa.
• Shear Modulus:26 GPa.
• Shear Strength:205 MPa.
UNDP Hodeida office Site Survey Report
Solar panel load PL= total solar panels weight/ length of solar panel installation area
Solar panel weight per meter=5.15045 KN/ 11.658 m = 0.441795 KN/m
As we know the solar panels are installed above 4 rails, so the solar panel load per rail
= 0.441795 KN/m /4=0.11044875 KN/m
As we know this wind load is distributed for 4 beams beneath, that means
1- the wind load acting downwards (Wkd )= 0.747 kN/m/4 =0.18675 kN/m
2- the wind load acting upwards (Wkup )=- 1.494 kN/m /m/4 =- 0.3735 kN/m
Based on the calculations above, the rail uniform distributed load is 0.313698 KN/m
Input Data
• Shear force along z-z axis (parallel to width): Vz,Ed = 0.540 kN.
• Bending moment about minor axis z-z: Mz,Ed = 0.288 kNm
• Buckling length factor for flexural buckling about minor axis z-z: Lcr,z/L = 1
• Shape of Mz bending moment inside the effective length Lcr,z: = Uniform (no internal
loading)
• Ratio of end moment with smallest absolute value to end moment with largest absolute
value, taking into account signs, inside the effective length Lcr,z: ψz = 1
• Steel partial material safety factor for cross-section resistance: γM0 = 1
• Steel partial material safety factor for member instability resistance: γM1 = 1
• Factor η for shear buckling verification: η = 1.2
• Calculation method for the interaction factors kyy, kyz, kzy, kzz: = Both methods
The following design properties are obtained for the examined cross-section:
axis
Wv- Minimum section modulus about V- 0.000005776 m3
axis
Wpl,u Plastic section modulus about U-axis 0.000017704 m3
Wpl,v Plastic section modulus about V-axis 0.00000942 m3
Iu Maximum moment of inertia 0.000000622 m4
Iv Minimum moment of inertia 0.00000016 m4
iu Maximum radius of gyration 0.031580743 m
iv Minimum radius of gyration 0.016012203 m
au+ Core size along positive Y(U)-axis 0.009377383 m
au- Core size along negative Y(U)-axis 0.009265053 m
av+ Core size along positive Z(V)-axis 0.022402964 m
av- Core size along negative Z(V)-axis 0.021840969 m
ym Y-coordinate of the center of mass 0.02748937 m
zm Z-coordinate of the center of mass 0.044418137 m
Yb Y-coordinate of the shear center 0.027454641 m
Zb Z-coordinate of the shear center 0.034338953 m
P Perimeter 0.574870911 m
Pi Internal perimeter 0.215392396 m
Pe External perimeter 0.359478516 m
Ip Polar moment of inertia 0.000000782 m4
ip Polar radius of gyration 0.035408106 m
Wp Polar section modulus 0.000014959 m3
The classification of the cross-section parts (height and width) is specified in EN1993-1-1
Table 5.2. In this calculation cross-section classification is carried out for the case of
predominant axial force NEd and bending moment My,Ed about the major axis y-y. For this
case the height is classified for the combination of bending and compression and the
compressive width is classified for pure compression. The class of the compression part
depends on its width c to thickness t ratio, adjusted by the factor ε = 0.990. The
UNDP Hodeida office Site Survey Report
classification of the total cross-section is determined by the class of its most unfavorable
compression part, height or width.
Width classification
height classification
For constant axial force N = 0.0 kN (compression negative) and increasing value of bending
moment My the fully plastic profile of the cross-section corresponds to plastic neutral axis
at normalized height α = 0.500 (where α > 0.5 when the axial force is compressive, α = 0
for height fully in tension, and α = 1 for height fully in compression).
The class of the total cross-section corresponds to the most adverse of the width class
(Class 1) and the height class (Class 1). Therefore, the cross-section is classified as Class 1.
The shear buckling resistance of the height and width is verified in accordance with
EN1993-1-1 table6.2.6(6).
hw/tw ≤ 72 ⋅ ε / η
The critical cross-section is verified for tensile axial force in accordance with EN1993-1-1
table6.2.3:
Where NEd = 0.0 kN is the design tensile axial force. The tension resistance Nt,Rd is
estimated as the plastic tension resistance Npl,Rd on the basis of the gross cross-section area
A and the steel yield stress fy:
The critical cross-section is verified for compressive axial force in accordance with EN1993-
1-1 table6.2.4:
Where NEd = -0.0 kN is the design compressive axial force. For the case of class 1, 2, or 3
cross-section the compression resistance Nc,Rd is estimated as:
The critical cross-section is verified for bending moment in accordance with EN1993-1-1
table6.2.5:
For class 1 or 2 cross-sections the design resistance Mc,Rd for bending about one principal
axis is estimated as the corresponding plastic bending resistance Mpl,Rd on the basis of the
corresponding plastic section modulus Wpl:
The critical cross-section is verified for shear force in accordance with EN1993-1-1
table6.2.6:
For class 1 or 2 cross-sections the design shear resistance for shear force along one principal
axis is estimated as the plastic shear resistance Vpl,Rd on the basis of the corresponding shear
area Av:
= 48.967 kN
Therefore, the utilization for the shear resistance verification is equal to:
Input Data
Defined Parameters
• Density 2700kg/m3
• Tensile Strength, Ultimate :260 MPa=260000 N/m2
• Tensile Strength, yield :240 MPa=240000K N/m2
• Modulus of Elasticity :69GPa
• Poisson Ratio:0.33.
• Fatigue Strength: 100 GPa.
• Shear Modulus:26 GPa.
• Shear Strength:205 MPa.
factor ε according to EN1993-1-1 §6.3.1.3(1): ε = (235 MPa / fy)0.5 = (235 MPa / 240
MPa)0.5 = 0.990
The following design properties are obtained for the examined cross-section:
UNDP Hodeida office Site Survey Report
The class of the compression part depends on its width c to thickness t ratio, adjusted by
the factor ε = 0.990. The classification of the total cross-section is determined by the class
of its most unfavorable compression part, height or width.
Width classification
height classification
For constant axial force N = 0.0 kN (compression negative) and increasing value of bending
moment My the fully plastic profile of the cross-section corresponds to plastic neutral axis
at normalized height α = 0.500 (where α > 0.5 when the axial force is compressive, α = 0
for height fully in tension, and α = 1 for height fully in compression).
The class of the total cross-section corresponds to the most adverse of the width class
(Class 1) and the height class (Class 1). Therefore, the cross-section is classified as Class 1.
The shear buckling resistance of the height and width is verified in accordance with
EN1993-1-1 table6.2.6(6).
hw/tw ≤ 72 ⋅ ε / η
The critical cross-section is verified for tensile axial force in accordance with EN1993-1-1
table6.2.3:
Where NEd =1.043 KN is the design tensile axial force. The tension resistance Nt,Rd is
estimated as the plastic tension resistance Npl,Rd on the basis of the gross cross-section area
A and the steel yield stress fy:
The critical cross-section is verified for compressive axial force in accordance with EN1993-
1-1 table6.2.4:
Where NEd = 1.043 KN kN is the design compressive axial force. For the case of class 1, 2,
or 3 cross-section the compression resistance Nc,Rd is estimated as:
The critical cross-section is verified for bending moment in accordance with EN1993-1-1
table6.2.5:
For class 1 or 2 cross-sections the design resistance Mc,Rd for bending about one principal
axis is estimated as the corresponding plastic bending resistance Mpl,Rd on the basis of the
corresponding plastic section modulus Wpl:
The critical cross-section is verified for shear force in accordance with EN1993-1-1
table6.2.6:
For class 1 or 2 cross-sections the design shear resistance for shear force along one principal
axis is estimated as the plastic shear resistance Vpl,Rd on the basis of the corresponding shear
area Av:
= 24.9479 kN
Therefore, the utilization for the shear resistance verification is equal to:
Columns buckling check can be analyzed with the Euler column formula
Fcr = (n ×π2 ×E ×I )/ L2
where:
Fcr = (0.25×3.142×69000000000×0.000000199)/3.22
Allowable stress
Limiting slenderness
column slenderness
308.4459≥53.241212
ze = z = 3.200 m
For terrain category 0 the corresponding values are z0 = 0.003 m and zmin = 1.0 m.
Wind turbulence
The basic velocity pressure is calculated according to the fundamental relation specified in
EN1991-14 table 4.5(1):
The peak velocity pressure qp(ze) at reference height ze includes mean and short-term
velocity fluctuations. It is determined according to EN1991-1-4 equation 4.8:
The wind force on the structure Fw for the overall wind effect is estimated according to the
force coefficient method as specified in EN1991-1-4 §5.3.
Fw,u = Fw γF γf3
The critical cross-section is verified for shear force in accordance with EN1993-1-1
table6.2.6:
For class 1 or 2 cross-sections the design shear resistance for shear force along one principal
axis is estimated as the plastic shear resistance Vpl,Rd on the basis of the corresponding shear
area Av:
= 23.6426 kN
Therefore, the utilization for the shear resistance verification is equal to:
Columns buckling check can be analyzed with the Euler column formula
Fcr = n π2 E I / L2
where:
Fcr = (0.25×3.142×69000000000×0.000000316)/42
Allowable stress
Limiting slenderness
column slenderness
299.4238 ≥53.241212 ⇒ ok
The column cross-section is verified for compressive axial force in accordance with EN1993-1-1
table 6.2.4:
UNDP Hodeida office Site Survey Report
the column cross-section is verified for shear force in accordance with EN1993-1-1 table
6.2.6:
As mentioned in the calculations above that the axial force from the column at the column
base is NEd = 1.447 KN
We try to select foundatio with deminsions L=0.5m ,W=0.5m,T=0.5m
Overturning Check
Overturning moment, Mover = Design load ×lever arm to the foundation base
Mover = Fw,d ×(h + 0.5)
3KN+1.447 KN =4.447 KN
Oil density=700kg/m3
M3=1000L .
Oil volume = 8 L
Based on these given data, we can calculate the required foundation to install the diesel
genset as follows:
Where:
= Dry weight of gen set +weight of fuel + weight of oil + Weight of Coolant
L =2.4+0.4=2.8m.
B =1+0.4l=1.4m.
Foundation depth = W/(DxBxL)
=17.97cm
Length=280cm
Width =140cm.
The total concrete volume is 0.90161m3 and its concrete mixture ratio of 1:2:3 (cement:
sand: aggregate)
UNDP Hodeida office Site Survey Report
• Terrain category: = 0
• Basic wind velocity: vb = 20 m/s
• Diameter of the cylindrical element: b = 0.0842 m
• Length of the cylindrical element: l = 6 m
• Maximum height above ground of the cylindrical element: z = 6 m
• Orientation of the cylindrical element: = Vertical
• Surface type: = galvanized steel
• Orography factor at reference height ze: c0(ze) = 1
• Structural factor: cscd = 1
• Air density: ρ = 1.132779 kg/m3
The reference height for the wind action ze is equal to the maximum height above ground
of the section being considered, as specified in EN1991-1-4 table7.9.2(5). The reference
area for the wind action Aref is the projected area of the cylinder, as specified in EN1991-1-4
table7.9.2(4). Therefore:
ze = z = 6.000 m
The basic wind velocity vb is defined in EN1991-1-4 table4.2(2)P as a function of the wind
direction and time of year at 10 m above ground of terrain category 0. The value of vb
includes the effects of the directional factor cdir and the seasonal factor cseason and it is
provided in the National Annex. In the following calculations the basic wind velocity is
considered as
vb = 20 m/s.
UNDP Hodeida office Site Survey Report
Terrain roughness
The roughness length z0 and the minimum height zmin are specified in EN1991-1-4 Table
4.1 as a function of the terrain category. For terrain category 0 the corresponding values are
The roughness factor cr(ze) at the reference height ze accounts for the variability of the
mean wind velocity at the site. It is calculated in accordance with EN1991-1-4 equation
4.4. For the examined case ze ≥ zmin:
Orography factor
It is not applicable in this case because the terrain category is 0,so in the following
calculations the orography factor is considered as c0(ze) = 1.000.
The mean wind velocity vm(ze) at reference height ze depends on the terrain roughness,
terrain orography and the basic wind velocity vb. It is determined using EN1991-1-4
equation (4.3):
Wind turbulence
The turbulence intensity Iv(ze) at reference height ze is defined as the standard deviation of
the turbulence divided by the mean wind velocity. It is calculated in accordance with
EN1991-1-4 equation 4.7. For the examined case ze ≥ zmin.
UNDP Hodeida office Site Survey Report
The basic velocity pressure qb is the pressure corresponding to the wind momentum
determined at the basic wind velocity vb. The basic velocity pressure is calculated according
to the fundamental relation specified in EN1991-14 table4.5(1):
qb = (1/2) ⋅ ρ ⋅ vb2 = (1/2) ×1.132779 kg/m3 ×(20.00 m/s)2 = 226.5558 N/m2 = 0.226 kN/m2
The peak velocity pressure qp(ze) at reference height ze includes mean and short-term
velocity fluctuations. It is determined according to EN1991-1-4 equation 4.8:
The wind force on the structure Fw for the overall wind effect is estimated according to the
force coefficient method as specified in EN1991-1-4 table5.3.
Structural factor
The structural factor cscd takes into account the structure size effects from the non-
simultaneous occurrence of peak wind pressures on the surface and the dynamic effects of
structural vibrations due to turbulence. The structural factor cscd is determined in
accordance with EN1991-1-4 Section 6. A value of cscd = 1.0 is generally conservative for
small structures not-susceptible to wind turbulence effects such as buildings with height
UNDP Hodeida office Site Survey Report
less than 15 m or chimneys with circular cross-sections whose height is less than 60 m and
6.5 times the diameter.
Reynolds number
Reynolds number characterizes the air flow around the object. For air flow around
cylindrical objects Reynolds number is calculated according to EN1991-1-4 table7.9.1(1):
where the kinematic viscosity of the air is considered as ν = 15.0 ×10-6 m2/s in accordance
with EN1991-1-4 table7.9.1(1).
Effective slenderness
The effective slenderness λ depends on the aspect ratio and the position of the structure
and it is given in EN1991-1-4 table7.13(2).
For circular cylinders with length l ≤ 15 m the effective slenderness λ is equal to:
The end effect factor ψλ takes into account the reduced resistance of the structure due to
the wind flow around the end (end-effect). The value of ψλ is calculated in accordance with
EN1991-1-4 table7.13. For solid structures (i.e. solidity ratio φ = 1.000) the value of the
end effect factor ψλ is determined from EN1991-1-4 Figure 7.36 as a function of the
slenderness λ.
The equivalent surface roughness k depends on the surface type and it is given in EN1991-
1-4 table7.9.2(2). According to EN1991-1-4 Table 7.13 for surface type "galvanized steel"
the corresponding equivalent surface roughness is k = 0.2000 mm.
For circular cylinders the force coefficient without free-end flow cf,0 depends on the
Reynolds number Re and the normalized equivalent surface roughness k/b. The force
coefficient without free-end flow cf,0 is specified in EN1991-1-4 table7.9.2. The value cf,0 is
determined according to EN1991-1-4 Figure 7.28 for the values of Re = 0.3230 ×106, k =
0.2000 mm, b = 0.084 m, k/b = 0.002375.
The estimated value for the force coefficient without free-end flow is cf,0 = 0.836
Force coefficient
The force coefficient cf for finite cylinders is given in EN1991-1-4 table7.9.2(1) as:
cf = cf,0 ⋅ ψλ
where cf,0 is the force coefficient without free-end flow, and ψλ the end effect factor, as
calculated above. Therefore:
Fw,d = Fw γF γf3
The wind velocity for calculating the temporary deflection (SLS) criterion is 75% of the
reference wind velocity, as it is based upon a 1 year mean return period. The 0.96 factor
below reverses the cprob conversion from 50 to 25-year return period used above (in 1.2.3).
Ultimate design shear per post, Vd, = Wind force / number of posts
Vd = Fw,d (ULS) = 0.2353 kN
Support Properties
Circular Hollow Section, CHS 88.9 4.0 (S355 steel) is to be tried.
Characteristic member capacities
Mc,Rd = 5.95 kNm
Vc,Rd = 96.47 kN
UNDP Hodeida office Site Survey Report
Overturning Check
Overturning moment, Mover = Design load ×lever arm to the foundation base