SSCI Advance

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 9

Advanced Screening Techniques for Sub-

Synchronous Interaction in Wind Farms


M. Sahni, Member, IEEE, D. Muthumuni, Member IEEE, B. Badrzadeh, Member IEEE
A. Gole, Fellow IEEE, A. Kulkarni, Member IEEE

1
Significant research and development activities have
Abstract— This paper aims to outline comprehensive been recently embarked upon to identify Sub Synchronous
screening guidelines associated with the Sub Synchronous Resonance (SSR) and Sub Synchronous Control Interactions
Control Interaction (SSCI) and Sub Synchronous (SSCI) in wind farms. One of key challenges facing system
Torsional Interaction (SSTI) for wind power plants.
planners and utility personnel has been the lack of a
Specific guidelines and methodologies to identify the
comprehensive screening approach for SSR/SSCI issues for
critical system conditions to be assessed for screening
analysis are presented. The application of these interconnecting Wind Generation Resources (WGRs). EMT-
techniques on a portion ERCOT grid model with series type simulation based studies to demonstrate the sub
compensated lines has been demonstrated. Current synchronous interaction phenomena are presented in [2]-[3].
injection based frequency scans on the system and turbine This reference highlights the need to perform EMT based
side are utilized. Based on these scans a guideline to simulations using detailed manufacturer provided turbine
identify the specific candidates for further investigation models to identify potential SSCI issues during the design
using Electro Magnetic Transient (EMT)-type simulation stage. In addition to SSCI, the Type 3 wind turbines can also
is proposed. The results of the screening study are further experience classical SSR phenomena referred to as Induction
corroborated by the EMT based simulation case studies.
Generator Effect (IGE) and Torsional Interaction (TI). [4]
An electrical damping analysis based screening technique
discusses the TI phenomena of Type 1 wind turbines
for the analysis of SSTI has been presented. The SSTI
screening studies have been further corroborated by demonstrating the same through EMT simulation case
means of EMT simulations. studies. Using a standard IEEE test system, the impact of the
series compensation levels on TI and the possibility of
Index Terms— Wind Generation Resources, Screening mitigating the problem with the use of Thyristor Controlled
Techniques, Sub-Synchronous Control Interaction, Sub- Series Compensation (TCSC) has been demonstrated. IGE
Synchronous Torsional Interaction, Frequency Scanning and TI phenomenon for Type 3 wind turbines are discussed in
[5]. EMT simulation results are compared with conclusions
I. INTRODUCTION
derived from a small signal analysis. A modal analysis of a

T HERE has been significant interest on the topic of Sub


Synchronous Control Interactions (SSCI) due to
wind farm comprising of Type 3 turbines connected to a
series compensated network is presented in [6]. The paper
integration of wind farms to utility transmission grids. In has highlighted the need to model the system network
particular, the control interaction at sub synchronous dynamics in order to capture the electric network resonance
frequencies between wind farms employing Type 3 turbines modes that are significantly different from the fundamental
and in close proximity to series compensated lines has gained frequency. Both EMT simulations and modal analysis have
industry attention. The only practical experience of SSCI is their merits and limitations when used to identify SSR and
related to the event of October 2009 in the Electric Reliability SSCI issues at the design stage of a large wind farm. Small
Council of Texas (ERCOT) grid [1]. signal analysis provides valuable insight into potential modes
of oscillations at a given operating point with the Eigen
M. Sahni is with PwrSolutions Inc, 2777 N Stemmons Fwy, Suite 1520, values and vectors being utilized to determine damping
Dallas, TX-75207.
D. Muthumuni is with Manitoba HVDC Research Center, 211 Commerce
factors at the dominant modes. However, modification and/or
Drive, Winnipeg, MB R3P 1A3, Canada. testing of design parameters and/or damping controls to
B. Badrzadeh is with Vestas Technology R&D, Hedeager 42, Århus, verify acceptable operation of the turbine model has still been
8200, Denmark (email:babad@vestas.com).
A. Gole is Professor of Electrical and Computer Engineering at the known to require EMT simulations.
University of Manitoba, Winnipeg, Canada. Significant research and development activities have
A. Kulkarni is Professor at the Indian Institute of Technology, Bombay
and is currently a Visiting Professor at the University of Manitoba, Canada. recently attempted to address mitigation methods for wind
farm SSR issues [7]-[10]. While detailed EMT based analysis

978-1-4673-1935-5/12/$31.00 ©2012 IEEE


has been presented as the predominant approach for induction generator effect will be discussed in future
mitigation techniques, the discussion presented in the publications. The adequacy of the screening techniques has
research alluded to above does not focus on identifying been validated by means of EMT simulations. The Electric
screening techniques associated with SSR/SSCI. Reliability Council of Texas (ERCOT) grid model has been
Additionally, the mitigation solutions discussed in [7]-[10] utilized as the test system. The frequency scan results
are based on application of FACTS devices. While credible, presented in this paper are based on detailed wind turbine
these are often expensive and more importantly external vendor developed EMT simulation models.
solutions to mitigate SSR/SSCI concerns. Typically these
solutions will figure lower in the hierarchical order when II. SYSTEM SIDE FREQUENCY SCANS
compared to intrinsic options based on turbine control system Current injection based frequency scanning techniques
design changes. More importantly, from a utility and/or have been utilized to perform system and turbine side scans.
regional planning authority standpoint, detailed turbine Unlike the passive impedance scan, the current injection
models typically required for EMT based simulations may based scan is an accurate method and will capture the impact
not be available during the early part of the generation of other dynamic devices (winds farms, FACTS devices,
interconnection process. While the traditional frequency generators) on the system side and well as capturing the
scanning techniques for conventional generation related SSR impact of all the complex controls and mechanical shaft
have been well documented, there is little to suggest the systems on the turbine side. However, prior to the application
presence of a comprehensive screening approach for of the current injection based scanning technique, the
quantifying the potential of SSR/SSCI concerns associated transmission grid model and the location of the wind farm
with Wind Generation Resources (WGRs). under study have been utilized to identify critical system
EMT simulations can capture all aspects of the wind conditions to be studied for screening. The ensuing sub-
farm behavior including equipment and control system non- sections in this section provide a brief description of the test
linear responses, impact of hard limiters, response to large system, discuss the guidelines utilized to identify critical
disturbances (faults) and fast control loops. However, it is conditions to be studied for screening and present the
important to note that EMT simulations are time consuming frequency scans on the system and turbine side.
due to the detailed nature of the mathematical modeling used
in such programs. As such, the ‘critical’ scenarios that must
be studied should be judiciously selected after careful A. System Description
evaluation of the system, the turbine characteristics and the As mentioned earlier, a section of the ERCOT grid,
particular phenomena being investigated (SSTI/SSCI in this pertaining to the expected interconnection of a WGR utilizing
case). To that effect, the identification of possible SSTI/SSCI Type 3 wind turbines has been utilized as the test system.
issues through a comprehensive screening process is an Figure 1 provides a one-line schematic outlining the system
important step in the integration of wind farms to grids where under study within a 2-bus radius of the Point of Common
potential for such problems cannot be ruled out. The presence Coupling (PCC) for the proposed WGR. As evident from
of such a screening technique is also intended to equip the Figure 1, the proposed WGR, sized at 200 MW & comprising
utilities and/or transmission planning authorities with a of Type 3 turbines, is connected at Bus 2. The series
guideline for performing and/or evaluating such studies as compensation is located between the following buses:
part of the Generation Interconnection procedure. • Bus 13- Bus 16
This paper presents a comprehensive approach for • Bus 15 – Bus 16
utilizing advanced screening techniques to assess the
potential for SSTI/SSCI issues associated with WGRs The other lines between Buses 13-16, 15-16 & 13-15 are
connecting to the grid in close proximity of series normally open thereby rendering the total series
compensated lines. Basic guidelines associated with compensation to be the sum of the two individual segments.
identification of critical system conditions to be utilized for The series compensation level varies between 50% and 80%
screening (especially the system side) have been presented. owing to the tapping of the original compensated line with
Current injection based frequency scanning technique [11]- additional intermediate tap stations. It is important to note
[12] has been utilized for the frequency scans on both the that while only a limited section of the grid model has been
system and the turbine side. Frequency scanning methods shown in Figure 1, a larger albeit equivalenced section of the
have been utilized to identify scenarios that are likely to transmission system was utilized for the system side
cause SSTI/SSCI issues and hence are candidates for detailed frequency scans.
EMT based investigations. Frequency scans on the system
side have been compared with scans on the turbine side as
well as with results from electrical damping torque analysis.
The sub-synchronous interaction phenomena investigated in
this paper include the control and torsional interaction. The
indicative of a resulting system topology that is
Bus 2
Bus 1 Bus 4 weaker and potentially prone to SSCI but not
anywhere close to being radial.
• None of the contingencies of CTG#1 through
Bus 3
CTG#5 result in more than three (3) line outages
Bus 6 with respect to Bus 8.
Bus 5

TABLE I
CRITICAL SYSTEM CONDITIONS TO BE STUDIED FOR SCREENING

Bus 9
Bus 7 CTG
Contingency Definition
Label
OPEN Line from Bus 8 TO Bus 5 CKT 1
Bus 8 CTG#1 OPEN Line from Bus 8 TO Bus 4 CKT 1
Open Transformer Bus 8 to Bus 10 to Bus 13 CKT 1
OPEN Line from Bus 8 TO Bus 5 CKT 1
Bus 11
Bus 10 CTG#2 OPEN Line from Bus 8 TO Bus 4 CKT 1
OPEN Line from Bus 9 TO Bus 8 CKT 1
OPEN Line from Bus 8 TO Bus 5 CKT 1
Bus 13
OPEN Line from Bus 8 TO Bus 4 CKT 1
CTG#3 OPEN Line from Bus 8 TO Bus 6 CKT 1
Bus 12
Bus 14
OPEN Line from Bus 6 TO other buses downstream
OPEN other lines
Bus 15 OPEN Line from Bus 8 TO Bus 5 CKT 1
Bus 16
OPEN Line from Bus 8 TO Bus 4 CKT 1
CTG#4
OPEN Line from Bus 4 TO other buses downstream
Fig 1: One-line Schematic, Test System OPEN other lines
OPEN Line from Bus 8 TO Bus 5 CKT 1
B. Identification of critical system conditions OPEN Line from Bus 8 TO Bus 4 CKT 1
The following aspects were taken into account when CTG#5 OPEN LINE from Bus 5 to other buses downstream
identifying the critical system conditions to be studied for OPEN Line from Bus 4 TO other buses downstream
screening via system side frequency scans: OPEN other lines
• Location of WGR vis-à-vis series compensated OPEN Line from Bus 8 TO Bus 6 CKT 1
segments OPEN Line from Bus 8 TO Bus 5 CKT 1
• System topology CTG#6 OPEN Line from Bus 8 TO Bus 4 CKT 1
• Credible system outage conditions based on OPEN Line from Bus 9 TO Bus 8 CKT 1
planning contingencies OPEN Line from Bus 8 TO Bus 7 CKT 1
• System conditions resulting in WGR being near OPEN all lines outlined in CTG#6
radial or completely radial to series compensated
CTG#7 OPEN Line from Bus 13 TO Bus 12 CKT 1
segment
OPEN Line from Bus 13 TO Bus 14 CKT 1
Based on a combination of the above, eight (8) distinct
OPEN all lines outlined in CTG#7
contingencies (combination of line outages) were identified CTG#8
as critical conditions to be studied for screening. Table I OPEN Line from Bus 3 TO Bus 1 CKT 1
depicts the list of contingencies identified as critical for the
screening study. CTG#1 through CTG#5 were based on To that effect, CTG#6 was created to comprise of outages
planning contingencies studied for bus section and/or breaker of all lines connecting into Bus 8 barring the transformers &
failure outages associated with Bus 8. However, a closer look line connecting the WGR. Additionally, CTG#7 was created
at the line segments being opened in CTG#1 through CTG#5 incrementally from CTG#6 to comprise of the outage of the
provides the following observations with respect to 345kV lines Bus 13-12 & Bus 13-14. Note that while CTG#7
conditions for potential SSCI concerns: makes the proposed WGR near radial to the series
compensated lines, the presence of the line from Bus 3 to Bus
• Each of the contingencies from CTG#1 through 1 prevents it from being completely radial. To that effect,
CTG#5 result in varying number of line outages CTG#8 was incrementally created from CTG#7 to comprise
associated with Bus 8. These conditions are of the outage of the aforementioned line. These
contingencies, identified as critical system conditions, were Frequency Scan - CTG001
then subjected to the system side frequency scans to gain
2.5
insight into the potential resonant frequencies.
2

|Z1| (ohms)
1.5
C. System Side Frequency Scans CTG001_current_injection
CTG001_Harm_Imp_Scan

Based on the guidelines outlined in the previous sub- 1

section, the current injection technique based frequency scans 0.5

have been implemented on the eight (8) contingency 0


conditions depicted in Table I. It is important to note that the 0 10 20 30 40 50 60
Frequency (Hz)
WGR under study has to be disconnected when performing
the frequency scan into the system for the following key Frequency Scan - CTG007

reasons: 2.5

• The presence of the WGR model will 2

require the use of precise turbine model.

|Z1| (ohms)
1.5
CTG007-Current_injection
• In the absence of the same, any 1
CTG007-Harmonic_Scan

representative turbine impedances utilized have been 0.5


tested to skew the results of the system side 0
frequency scan. 0 10 20 30 40 50 60
Frequency (Hz)
• Another notable aspect is the prevention of
the use of “turbine short circuit model” based Frequency Scan - CTG008

impedances. This is so since the turbine source 4.5


4
impedances provided for the commercial short 3.5

circuit software are representative values to capture |Z1| (ohms) 3


2.5 CTG008-current_injection

to short circuit contribution of the turbines. These 2


1.5
CTG008-Harmonic_Scan

values are provided due to the inability of 1

commercial short circuit software to capture the


0.5
0

effect of the control & protection aspects of the 0 10 20 30 40


Frequency (Hz)
50 60

turbine that actually limit the short circuit current.


Fig 2: System Side Frequency Scans, CTG#1, CTG#7 & CTG#8
Figure 2 depicts an illustrative frequency scan for CTG#1,
CTG#7 and CTG#8 looking into the system from behind the
Similar frequency scans were performed for varying series
station transformer of the WGR under study. The system side
compensation levels thereby resulting in shifting of the
frequency scans for CTG#2 through CTG#6 were very
system resonant frequency which is well documented. The
similar to those for CTG#1. As evident from Figure 2, for
key conclusions associated with critical system conditions for
system conditions represented by CTG#1 through CTG#5,
further investigation remained unchanged by virtue of the
the system impedance across sub-synchronous frequency
series compensation levels.
range of interest is not indicative of any distinct resonant
Results associated with the system side frequency scans
frequency. However, CTG#7, which represents the “near
are indicative of the following, albeit pending turbine side
radial” scenario shows a distinct resonant frequency (depicted
scans:
by the impedance dip) at around 20-22 Hz. On similar lines,
CTG#8, the completely radial scenario is indicative of a • Conditions represented via CTG#1 through
frequency scan depicting a classic SSR situation. The CTG#6 do not seem to pose any SSCI concerns
frequency scan plot for CTG#8 is indicative of a clear system • Conditions represented via CTG#7 and
resonant frequency at around 20 Hz. Note that the system CTG#8 require further investigation by means of
side scans for CTG#1, CTG#7 & CTG#8 were also turbine side scans and finally EMT based
performed using the traditional scanning technique. In the simulations
absence of any near-by power electronic devices, the
frequency scans from the traditional and current injection III. TURBINE SIDE FREQUENCY SCANS

techniques compare well. While the system side frequency scans provide valuable
insight into the potential system conditions that could pose
SSCI concerns, those conditions don’t necessarily have to
imply SSCI concerns. This paper intends to underline the
benefits of assessing the system side scans in conjunction
with turbine side scans to make conclusive inferences on
candidates posing SSCI concerns. Additionally, the turbine side scan results depicted in Figures 3-5:
side scans also underline the importance of using the current • Interestingly, the apparent resistance of the turbine
injection technique as outlined in [11]-[12]. model is negative across the entire range of sub-
Note that the magnitude of the sub-synchronous currents synchronous frequencies tested. Additionally, the
injected into the turbine model should still result in above observation is true for each of the scenarios
acceptable steady state operation of the model in order to tested irrespective of the active power dispatch level.
obtain meaningful measurements using this technique. • Regarding the reactance of the turbine model, there
Turbine side scans were performed on the Type 3 wind are no significant dips across the sub-synchronous
turbine model for varying active power dispatch levels. The frequency range although the reactance does tend to
active power dispatch levels tested were 100%, 55.5% and cross-over at around 40Hz. However, the turbine
30%. More importantly, instead of plotting the positive model utilized for this assessment is inclusive of the
sequence impedance as obtained from the current injection pad-mount transformer. That combined with the
technique, the resistive and reactive components of the relatively smaller magnitude of the reactance at sub-
turbine apparent impedance were plotted. Figures 3 through 5 synchronous frequencies seems to indicate turbine R
depict the plots of the turbine apparent resistance and to be the dominant indicator. The frequency scan
reactance for the three active power dispatch levels as investigation associated with the turbine model sans
obtained from the frequency scans. the pad-mount transformer has been identified as
one of the future works resulting from this research.
Turbine Side Scans, R & X, 100% Dispatch • Effectively, the following key aspects can serve as
6
guidelines for utilizing the turbine side scans in
4
conjunction with the system side scans:
o Any potential resonant points on the
2
apparent reactance of the turbine in close
Ohms

Resistance
0
0 10 20 30 40 50 60
Reactance coincidence with the system resonant
-2
frequency (if any) are indicative of a
-4
condition requiring detailed investigation
-6 o The negative apparent resistance across the
Frequency (Hz)
entire sub-synchronous frequency range is
Fig 3: Turbine Side Frequency Scans, 100% Dispatch indicative of negative damping at those
frequencies. In other words, in case of
Turbine Side Scans, R&X, 56% Dispatch potential SSCI conditions, the negative
resistance is indicative of inadequate
4
damping or growing sub-synchronous
2
oscillations.
0
o In the absence of any significant/obvious
Ohms

Resistance
0 10 20 30 40 50 60
-2 Reactance
resonant points on the apparent reactance of
-4

-6
the turbine, the negative turbine resistance
-8
should be used to draw conclusions
Frequency (Hz) regarding the screening study. In the
presence of network resonant conditions,
Fig 4: Turbine Side Frequency Scans, 55.56% Dispatch
the negative resistance should be utilized as
an indicator of conditions needing further
Turbine Side Scans, R & X, 30% Dispatch investigation.
15 To further corroborate the significance of the negative
10 apparent resistance associated with the turbine model,
5 frequency scans of the turbine were repeated for frequencies
above the synchronous frequency. Figure 6 depicts an
Ohms

Resistance
0
Reactance
-5
0 10 20 30 40 50 60 illustrative example of the turbine model frequency scan for
-10 frequency above the synchronous range. As evident from
-15 Figure 6, the resistance of the turbine model is positive across
Frequency (Hz) the frequency range tested above the synchronous frequency.
Finally, the system and turbine side scans, in conjunction
Fig 5: Turbine Side Frequency Scans, 30% Dispatch
with the abovementioned guidelines indicate CTG#7 and
CTG#8 as potential candidates for further investigation.
The following key insights are obtained from the turbine
Turbine Side Scans, R, 100% Dispatch

40
35
30
25
Ohms

20 Resistance
15
10
5
0
60 70 80 90 100
Frequency (Hz)

Fig 6: Turbine Side Frequency Scans for frequency range above


synchronous, 100% Dispatch

The ensuing section discusses the results of EMT based


simulations to corroborate the findings of the screening study.
Fig 8: Turbine Response, EMT Simulation, Scenario CTG#8
IV. EMT SIMULATIONS
EMT simulations were performed for the conditions
identified as candidates for further investigation based on the
screening techniques outlined above. EMT simulations
performed spanned variations across turbine active power
dispatch level, system condition (CTG#), turbine power
factor and whether the contingency was simulated as a
faultless outage or preceded by a fault. The variation around
the faultless/fault based outage was done to assess the impact
of disturbance in terms of triggering SSCI concerns that
maybe poorly damped due to the negative turbine resistance
at sub-synchronous frequencies.
Figures 7 through 9 depict the turbine response during
Fig 9: Turbine Response, EMT Simulation, Scenario CTG#7
EMT simulations for scenarios associated with CTG#1,
CTG#8 & CTG#7 respectively.
As evident from the results of the EMT simulations
depicted in Figures 7-9, scenarios associated with CTG#1 and
CTG#7 exhibit stable responses. Additionally the scenario
corresponding to a fault based outage of CTG#7 exhibits
stable response thereby indicating that the disturbance does
not seem to trigger any SSCI concerns for the “near radial”
condition. However, the results associated with CTG#8 are
indicative of potential SSCI issues with the turbine model
issuing a trip signal soon after the outage is effected thereby
placing the WGR radial to the series compensated segment.
Figure 10 further demonstrates the sub-synchronous
oscillations manifesting itself in the voltage and current on
the medium voltage side for CTG#8 conditions. However, it
is important to note the number of transmission line outage
Fig 7: Turbine Response, EMT Simulation, Scenario CTG#1 conditions that result in the completely radial condition.
Additionally, it is imperative to ensure that the
aforementioned condition does not result in other system
reliability concerns especially from a transient stability
standpoint. In other words, conditions resulting in the SSCI
issue being the first incremental reliability concern have been
used as guideline for assessing the “N-x” conditions to be
studied from an SSCI standpoint.
The results of the EMT simulations presented in this by-passed to gauge the results of the screening approach.
section corroborate the findings obtained from the screening Figures 12 and 13 depict the results of the EMT simulation
approach outlined above. with the generic turbine model for the completely radial case.
Figure 12 corresponds to the series compensation in place
while Figure 13 corresponds to the series compensation by-
passed. As evident from Figure 13, the torque on shaft from
mass 1-2 keeps oscillating after event is cleared & the
position of mass 1 w.r.t generator keeps oscillating thereby
implying that the twist is not constant and the shaft is being
subjected to fatigue.
Main : Graphs
T1_2
25.0

y
-20.0
DW1
0.50

Fig 10: WGR Medium Voltage Voltage & Current, CTG#8

y
-3.50
DW2
0.50

V. SSTI SCREENING

y
Having discussed the screening techniques for SSCI -3.50

phenomena, this section briefly discusses the methodology 3.125


WM

for SSTI screening analysis for WGRs. Electrical damping


analysis is utilized to identify potential sub-synchronous y 2.900

frequencies indicative of SSTI concerns. The same has been 2.50


P1

accomplished by injecting/creating a SS variation in the


y

turbine speed by adding a small amplitude sinusoidal -1.50

modulation signal with the frequency of the signal equaling 0.0 5.0 10.0 15.0 20.0 25.0

the SS frequency of interest. The damping factor is then


calculated from the complex electrical torque signal. The Fig 12: EMT Simulations, SSTI Assessment, With Series Compensation
damping torque coefficient (De) calculated is plotted as a Main : Graphs
function of the modulation frequency. Figure 11 depicts the 0.70
T1_2
0.60
plot associated with the damping factor for a modified 0.50
0.40
0.30
generic DFIG turbine model over the sub-synchronous
y

0.20
0.10
0.00
frequency range. 0.0010
DW1
y

Damping Factor Analysis


-0.0013
DW2
0.1 0.0013

0.05
y

-0.0013
0 WM
excel 3.125
0 10 20 30 40 50 60 70
De

dfscan
-0.05
y

-0.1 2.900
P1
0.0200
-0.15
Freq (Hz)
y

-0.0025
0.0 5.0 10.0 15.0 20.0 25.0

Fig 11: Frequency Sweep, Damping Factor, SSTI Screening

Fig 13: EMT Simulations, SSTI Assessment, Series Compensation By-


As obvious from Figure 11, the modified generic DFIG
passed
model exhibits negative damping to sub-synchronous
variations in the speed signal at about 45-47 Hz. Note that the No such phenomenon is observed for the scenario wherein
series compensation level was tuned to result in network the series compensation is by-passed.
resonant frequency being close to 15-16Hz. EMT simulations
were performed with the series compensation in place and
VI. CONCLUSIONS 12. X. Jiang and A. M. Gole, “A frequency scanning method for the
identification of harmonic instabilities in HVDC systems,” IEEE Trans.
This paper has provided comprehensive screening PowerDelivery, vol. 10, pp. 1875–1881, Oct. 1995.
guidelines associated with SSCI and SSTI phenomena for
Wind Generation Resources. Specific guidelines and IX. BIOGRAPHIES
methodologies for identify critical system conditions to be
assessed for screening are presented. The application of these Mandhir Sahni received his B.S. degree from
guidelines and methodologies on a practical ERCOT grid Bangalore University, India and his M.S. and PhD
model has been demonstrated. Current injection based degrees from University of Texas Arlington. Dr. Sahni
frequency scans on the system and the turbine side are has over ten years of experience in power market
analysis, generation & transmission planning in
utilized. Based on these scans a guideline is proposed which deregulated energy markets in the U.S, power quality,
identifies the specific candidates for further investigation stability and protection co-ordination analysis with an
using EMT simulation. The results of the screening study are extensive background in power system analysis. He
further corroborated by the EMT based simulation case has served as the technical lead on the Electrical Reliability Council of Texas
(ERCOT) Voltage Ride-Through (VRT) study effort. He is currently leading
studies. An electrical damping analysis based screening all transmission planning activities associated with numerous CREZ utilities
technique for the analysis of SSTI has been presented. For in ERCOT. Dr. Sahni has also served as expert witness on behalf of the staff
SSTI the results of the screening studies have been further of West Virginia Public Service Commission for the hearing associated with
corroborated by means of detailed EMT simulations. the 765kV Potomac Appalachian Transmission Highway (PATH) project in
Mid-Atlantic PJM. He has also executed and/or supervised power quality,
traditional system planning/expansion studies (load flow, short circuit,
VII. FUTURE WORK stability, protection co-ordination, insulation co-ordination) and reliability
impact studies for medium and large size power systems (Taiwan Power,
Future work associated with this research includes National Electric Power Company (NEPCO), Jordan, Saudi Arabia, Georgia,
Indonesia). He has vast experience in industrial application of power systems
assessment of collection system impact on system side scans, including development of novel pattern recognition/data acquisition based
turbine side scans sans pad-mount transformer to assess algorithms for low/medium voltage switchgear arc detection an initiative
turbine reactance & IGE screening techniques. funded by the US Air Force. Dr. Sahni’s research interets include power
system planning, integration of renewbale generation into power system
VIII. REFERENCES grids, power quality and power system reliability. Dr. Sahni’s research has
been in published in numerous referred journals, IEEE P&E magazine and
1. P. Belkin, “Event of 10-22-09”, CREZ Technical Conference, January conference proceedings.
26, 2010, Electric Reliability Council of Texas
2. A. K. Jindal, G. D. Irwin and D. A. Woodford, "Sub-Synchronous
Interactions with Wind Farms connected near series compensated AC
lines", in proc. 9th Int. Workshop on Large scale integration of wind, Dharshana Muthumuni received his M.Sc. and
Quebec City, Canada, pp. 559-564, Oct 18-19, 201. Ph.D. degrees from the University of Manitoba
3. G. D. Irwin, A. K. Jindal, and D. A. Woodford, " Sub-Synchronous (Winnipeg, Canada), all in Electrical Engineering He
Control Interactions between Type 3 Wind Turbines and Series joined the HVDC Centre in June 2001 and is the
Compensated AC Transmission Systems", in proc. IEEE PES General machines and transformer simulation specialist and
Meeting, Detroit, USA, July 2011. head of PSCAD Technical Sales department.
4. Tang Y, Yu R, “Impacts of Large-Scale Wind Power Integration on Dharshana has been involved in numerous
Subsynchronous Resonance”, Power and Energy Engineering engineering studies using a variety of simulation
Conference (APPEEC), 2011 Asia-Pacific, 25-28 March 2011 products during his career including PSCAD and
5. L. Fan, R. Kavasseri, Z. L. Miao, and C. Zhu, “Modeling of dfig-based PSS/E. Showing leadership in simulation excellence,
wind farms for ssr analysis,” IEEE Trans. Power Del., vol. 25, no. Dharshana’s technical knowledge on power system behaviour, model
4,pp. 2073–2082, Oct. 2010. development and simulation studies is highly advanced and is regularly
6. L Fan, C Zhu, Z Miao, M Hu, “Modal Analysis of a DFIG-Based Wind sought out by clients around the world for his expertise.
Farm Interfaced With a Series Compensated Network”, IEEE
TRANSACTIONS ON ENERGY CONVERSION
7. R. K. Varma, S. Auddy, and Y. Semsedini, “Mitigation of Babak Badrzadeh (S’03, M’07) received his BSc
subsynchronous resonance in a series-compensated wind farm using and MSc from Iran University of Science and
FACTS controllers,” IEEE Trans. Power Del., vol. 23, no. 3, pp. 1645– Technology in 1999 and 2002, and PhD from the
1654, Jul. 2008. Robert Gordon University, UK in 2007 all in area
8. S.Golshannavaz, M.Mokhtari, D.Nazarpour, “SSR Suppression via of electrical power engineering. After spending a
STATCOM in Series Compensated Wind Farm Integrations”, 19th short period as an assistant professor at Technical
Iranian Conference on Electrical Engineering (ICEE), 17-19 May 2011 University of Denmark, he joined Mott MacDonald,
9. M. S. El-Moursi, B Bak-Jense, and M H. Abdel-Rahman, “Novel Transmission and Distribution Division, UK as a
STATCOM Controller for Mitigating SSR and Damping Power System system analysis and network planning engineer.
Oscillations in a SeriesCompensated Wind Park”, IEEE Transactions on Since March 2010 he has been with Power Plant
Power Electronics, Vol. 25, No. 2, February 2010 Solutions, Vestas Technology R&D, Aarhus, Denmark where he acts as a
10. X Zheng, Z Xu, J Zhang, “A Supplementary Damping Controller of lead engineer in the area of advanced wind power plant simulation and
TCSC for Mitigating SSR”, Power & Energy Society General Meeting, analysis. Babak has published several articles and presented tutorials in IEEE
2009. PES '09. IEEE , 26-30 July 2009 organized conference on different areas of power systems and power
11. M. Mohaddes, A. M. Gole, and S. Elez, “Steady state frequency electronics. He has prepared two two-part educational courses for IEEE
response of STATCOM,” IEEE Trans. Power Delivery, vol. 16, pp. elearning library on high power variable speed drives, and HVDC
18–23, Jan. 2001. transmission systems. Babak acts as a guest editor for the special issue of
IEEE Industry Application Magazine on high power variable speed drives.
He is an active member of IEC TC 88 WG 27, WECC REMTF, and Danish
A11 standard all in the area of electrical simulation models for wind power
generation. His area of interest includes power system electromechanical and
electromagnetic transients, application of power electronics in power
systems, wind power plants, and modeling and simulation.

Aniruddha Gole received his B.Tech. degree from


the Indian Institute of Technology (Bombay), and
M.Sc. and Ph.D. degrees from the University of
Manitoba (Winnipeg, Canada), all in Electrical
Engineering. Dr. Gole is a Professor of Electrical
and Computer Engineering at the University of
Manitoba, Winnipeg, Canada. Since 2004, he is
also the NSERC Industrial Research Chair in
Power Systems Simulation. He is an internationally
recognized expert in the field of power systems simulation. Gole’s research
interests include the utility applications of power electronics and power
systems transient simulation. As an original member of the design team, he
has made important contributions to the PSCAD/EMTDC simulation
program. Gole is active on several working groups of CIGRE and IEEE and
is a Registered Professional Engineer in the Province of Manitoba. In 2007,
the IEEE Power Engineering Society awarded Gole the prestigious Nari
Hingorani FACTS Award "..for Contributions to the Education in the Field
of Power Systems and Embedded Power Electronics Apparatus
Simulation".[2] He was elected a Fellow of IEEE in 2010 "for contributions
to the modeling of power electronics apparatus.

A.M.Kulkarni(M'07) received his B.E. degree in


electrical engineering from the University of Roorkee,
India in 1992. He obtained his M.E. degree in electrical
engineering in 1994 and his PhD in 1998 from the
Indian Institute of Science, Bangalore. He is a Professor
at the Indian Institute of Technology, Bombay and is
currently a Visiting Professor at the University of
Manitoba, Canada. His research interests include Power
system dynamics, HVDC and FACTS.

You might also like