If TOA < Tset-point open the fresh air damper the maximum position
Then, if Tindoor air < Tset-point start closing the cooling coil valve
If cooling coil valve is closed and T indoor air < Tset-point start closing the damper
till you get T indoor air = T set-point
fresh
damper filter cooling heating filter
air coil coil
fan
mixing
T & RH sensors
Heat gains
Humidity generation
We should supply air with lower humidity ratio (w) and lower temperature
We either measure Dew Point directly or T & RH sensors substitute dew point sensor
Relative humidity control by cooling coil
Cooling Coil
Mixture
Room
Supply
if TDP measured > TDP set-point → send the signal to open more the CC valve
if TDP measured < TDP set-point → send the signal to close more the CC valve
• Heating coil is controlled by Tair set-point
if Tair < Tair set-point → send the signal to open more the heating coil valve
if Tair > Tair set-point → send the signal to close more the heating coil valve
Control valves
Fresh air
mixing
cooling heating
coil coil