R12-S07C01–Design & Build Start-Up Transportation

Client: Project:
Hub Project (SUTH)

Document Title: Structural Design Calculation of Substation Room

Aconex Doc. No. R12-S07C01-RCO-CAL-ST-0007

Revision No. 00

STRUCTURAL DESIGN CALCULATION


OF SUBSTATION ROOM

Revision Date Status Prepared By Reviewed By Approved By

00 06/03/2023 For Approval GAP GAP ARCCO

ORIGINATOR:
Al Raeel Engineering Construction &
Development Co. Ltd.
Project No: R12 Contract No. S07C01

R12-S07C01-RCO-CAL-ST-0007 Page 1 of 150


GAP ENGINEERING CONSULTANT

3/5/2023 START-UP
TRANSPORTATION
HUB

SUBSTATION ROOM
STRUCTURAL DESIGN
PREPARED FOR
RED SEA
DEVELOPMENT
COMPANY

PREPARED BY
GAP ENGINEERING
CONSULTANTS

GAP ENGINEERING CONSULTANTS


1

INTRODUCTION AND DESIGN CRITERIA

Page 1
1. EXECUTIVE SUMMARY:

1.1 The Red Sea Project is one of three giga-projects announced by HRH
Crown Prince Mohammad bin Salman bin Abdulaziz Al-Saud in 2017. The
Project supports the government’s strategy to diversify the Kingdom’s
tourism offering as laid in Vision 2030, the bold blueprint for the future of
Saudi Arabia.

2 STRUCTURAL DESIGN TECHNIQUE AND PHILOSOPHY:


2.1. Design was conducted according to SBC Saudi building code (301,
303, and 304).

2.2. The structural elements will be designed and


checked for serviceability and ultimate limit state,
moments, normal forces, sheer, punching and
bearing resistant under service and ultimate dead,
live, Earthquake and wind loads and for enveloping
maximum and minimum load combinations
according to SBC-301-2018.

2.3. 3-Dimensional ETABS-16&19 model will be generated for modeling the


reactions submitted from the steel building designer and applied to the
design of the pedestals taking into consideration directions of loading and
eccentricity.

2.4. 2-Dimensional SAFE-16&20 model will be generated for modeling and


designing of foundations.

Page 2
3 DESIGN CRITERIA:

3.1 Design load & combinations are according to:


- SBC - 301 -2018

3.2 Design Codes and References:


- SBC – 303 & SBC – 304-2018
- ACI 360R-10
- ACI 350M-06

3.3 Material Specifications:

Material Grade Strength

a)concrete
Foundations Fc’ = 35 Mpa
Floor slabs Fc’ = 35 Mpa
Ground beams Fc’ = 35 Mpa
Pedestals Fc’ = 35 Mpa
R.C Walls Fc’ = 35 Mpa
Plain concrete Fc’ = 20 Mpa
b)Reinforcing bars ASTM Fy = 420Mpa
A615
Table 1: Material specifications grade 60

Page 3
3.4 Concrete protection for reinforcement:
 The table below defines the minimum concrete cover measured
from outer most rebar (tie-bar) that shall be provided for
reinforcement of cast-in-place concrete structures.

Concrete cover (mm)

(a) Reinforced concrete FOUNDATIONS 75 (ALL SIDES)

(b) Reinforced concrete PEDESTALS 50

(c) Reinforced concrete GROUND BEAMS 50

(d) Reinforced concrete SLABS ON GRADE 30

Table 2: concrete cover

Page 4
3.5.0. Loading:
 Provisions of this design are based on the
assumption that the structures shall be designed to
resist all applicable loads.
 Dead, live, Wind and Seismic loads were calculated
according to SBC - 301, Rain loads were assumed
to be negligible compared to the roof live loads are
displayed below.

3.5.1 Dead loads:

Occupan L
cy
Unit weight of Reinforced Concrete 24.00 KN/m3o
Unit weight of Plain Concrete 23.00 KN/m3
Unit weight of Natural or Engineering
17.00 KN/m3
Soil / Fill
Unit weight of water 10.00 KN/m3
18.00 KN/m3
Unit weight of CMU block wall

3.5.2 Live loads

Live Load to be specified for mechanical use as per material data sheet for each
machine separately

3.5.3 Seismic loads:

 AS PER SOIL REPORT R12-I00C18-RCO-RPT-ST-0001


 SBC-301
Parameter Value
Soil type D

Ss. g% 30

Page 5
S1. g% 4
Table 4: Site Seismicity

3.5.4 Wind Loads:


3.5.1.1. Building is classified as occupancy category F1 (Industrial moderate hazard).
3.5.1.2. As per SBC -201 Group F1 building classified as risk category II
Location Wind
Ultimate wind speed
46 m / s
risk category II
Table 5: Site Wind Speed

3.6.0 Load Combinations:


 The service load combinations used for design are listed below.
1. D
2. D+L
3. D + Lr
4. D + (0.6W or 0.7E)
5. D + 0.75L + 0.75(0.6W) + 0.75Lr
6. D + 0.75L + 0.75(0.7E)
7. 0.6D + 0.6W
8. 0.6D + 0.7E
9. 1.0D + 1.0T
10. 1.0D + 0.75(L+T)
 The ultimate load combinations used for design are listed below.
1. 1.4D
2. 1.4D + 1.7L + 0.5Lr
3. 1.2D + 1.6Lr + (L or 0.5W)
4. 1.2D + 1.0W + L + 0.5Lr
5. 1.2D + 1.0E + L
6. 0.9D + 1.0W
7. 0.9D + 1.0E
8. 1.2D + 1.2T + 0.5L
9. 1.2D + 1.6L + 1.0T
 Where:
. D= Dead Load
. E= Earthquake Load.
. L= Live Load.
. Lr = Roof Live Load
. W= Wind Load.

3.7.0 Soil Parameters


With reference to soil report no R12-I00C18-RCO-RPT-ST-0001

 Total soil unit weight = 17 kn/m2

 Soil coefficient of friction between soil and concrete = 0.50

Page 6
 Active lateral Earth Pressure = 0.27

 Passive lateral Earth Pressure = 3.69

 Maximum width of footing considered as 4.00 m

 Allowable bearing capacity = 200 KPA (at 1.5 m depth)

 Settlement = 13 mm

 Subgrade reaction = 15384 kn/m3

Page 7
3.8 SLAB ON GRADE DESIGN CRITERIA:

3.8.1 SHRINKAGE AND TEMPERATURE RFT.


ACI-350M.06

3.8.2 Safety Factor


ACI-360.R.10

3.8.3 – Subgrade modulus for slab on grade

Page 8
According to the CBR value stated in the soil report (25%)
With referring to ACI 360-R-10

The relevant subgrade modulus = 290 PCI


Design will be based on 200 PCI as a conservative approach.

All this parameters to be verified by the contractor by performing plate loading test.

Page 9
GAP ENGINEERING CONSULTANT

3D MODEL INPUT

Page 10
User Report 6
Model File: TEMPLATE 21-9-2014 (A.RABIE)-STANDARD VILLA, Revision 0
05/03/2023
Structure Data 05/03/2023

1 Structure Data
This chapter provides model geometry information, including items such as story levels, point coordinates,
and element connectivity.

1.1 Story Data


Table 1.1 - Story Definitions

Height Master Similar Splice


Tower Name Color
m Story To Story
T1 ROOF 4 No None No Cyan
T1 GRADE BEAMS 2 No None No Magenta

1.2 Mass
Table 1.2 - Mass Source Definition

Include Include Source Source Source Move


Is Lump Load
Name Lateral Vertical Self Added Load Mass Multiplier
Default Mass? Pattern
Mass? Mass? Mass? Mass? Patterns? Centroid?
MsSrc1 Yes Yes No Yes No No Yes No Dead 1
MsSrc1 SDL 1
MsSrc1 WALL 1
MsSrc1 Live 0.25

Table 1.3 - Centers Of Mass And Rigidity

Cum Cum
Mass X Mass Y XCM YCM XCCM YCCM XCR YCR
Story Diaphragm Mass X Mass Y
kg kg m m m m m m
kg kg

ROOF D1 53354.06 53354.06 5.8657 8.8488 53354.06 53354.06 5.8657 8.8488 5.1796 9.2685

GRADE BEAMS D1 0 0 10.229 11.9771 53354.06 53354.06 5.8657 8.8488

Table 1.4 - Mass Summary by Diaphragm

Mass
X Mass Y Mass
Mass X Mass Y Moment
Story Diaphragm Center Center
kg kg of Inertia
m m
ton-m2

ROOF D1 53354.06 53354.06 2816.2099 5.8657 8.8488


GRADE BEAMS D1 0 0 0 10.229 11.9771

Table 1.5 - Mass Summary by Story

UX UY UZ
Story
kg kg kg
ROOF 220223.36 220223.36 0
GRADE BEAMS 101035.11 101035.11 0
Base 4845.69 4845.69 0

Page 2 of 42
Structure Data 05/03/2023

Table 1.6 - Mass Summary by Group

Self Self
Mass X Mass Y Mass Z
Group Mass Weight
kg kg kg
kg kN
All 0 1779.732 326104.17 326104.17 0
Columns 0 0 0 0 0
DXFIN2 0 0 0 0 0
DXFIN3 0 0 0 0 0
DXFIN4 0 0 0 0 0
DXFIN5 0 0 0 0 0
DXFIN6 0 0 0 0 0
DXFIN7 0 0 0 0 0
Group1 0 0 0 0 0
DXFIN1 0 0 0 0 0

1.3 Groups
Table 1.7 - Group Definitions

Steel Concrete Composite


Name Color
Design? Design? Design?
All Yellow No No No
Columns Yellow No No No
DXFIN2 Gray8Dark No No No
DXFIN3 Blue No No No
DXFIN4 Green No No No
DXFIN5 Cyan No No No
DXFIN6 Red No No No
DXFIN7 Magenta No No No
Group1 Yellow No No No
DXFIN1 Gray8Dark No No No

Page 3 of 42
Properties 05/03/2023

2 Properties

This chapter provides property information for materials, frame sections, shell sections, and links.

2.1 Materials
Table 2.1 - Material Properties - General

Material Type SymType Grade Color Notes


A416Gr270 Tendon Uniaxial Unknown Green
A992Fy50 Steel Isotropic Unknown Magenta
DUMMY Concrete Isotropic Unknown Gray8Dark
Fc' -- 35 Concrete Isotropic Unknown Gray8Dark
Fy--420 Rebar Uniaxial Unknown Green
Fyv-280 Rebar Uniaxial Unknown Red
Fyv-420 Rebar Uniaxial Unknown Red

2.2 Frame Sections


Table 2.2 - Frame Section Property Definitions - Summary (Part 1 of 3)

Area J I33 I22 As2 As3


Name Material Shape Color
mm2 cm4 cm4 cm4 mm2 mm2
C-0.3X0.5 Fc' -- 35 Concrete Rectangular 4194432 150000 281737.1 312500 112500 125000 125000
C-0.3X0.7 Fc' -- 35 Concrete Rectangular Cyan 210000 460378.2 857500 157500 175000 175000
DB-C-(0.3X0.70) Fc' -- 35 Concrete Rectangular 16745481 210000 460378.2 857500 157500 175000 175000
GB-300X700 Fc' -- 35 Concrete Rectangular Blue 210000 460378.2 857500 157500 175000 175000

Table 2.2 - Frame Section Property Definitions - Summary (Part 2 of 3)

CG CG PNA PNA
S33Pos S33Neg S22Pos S22Neg Z33 Z22 R33 R22
Offset 3 Offset 2 Offset 3 Offset 2
cm3 cm3 cm3 cm3 cm3 cm3 mm mm
mm mm mm mm

12500 12500 7500 7500 18750 11250 144.3 86.6 0 0 0 0


24500 24500 10500 10500 36750 15750 202.1 86.6 0 0 0 0
24500 24500 10500 10500 36750 15750 202.1 86.6 0 0 0 0
24500 24500 10500 10500 36750 15750 202.1 86.6 0 0 0 0

Table 2.2 - Frame Section Property Definitions - Summary (Part 3 of 3)

As2 As3 J I33 I22 Mass Weight


Modifier Modifier Modifier Modifier Modifier Modifier Modifier
1 1 1 1 1 1 1
1 1 1 1 1 1 1
1 1 1 1 1 1 1
1 1 1 1 1 1 1

2.3 Shell Sections


Table 2.3 - Area Section Property Definitions - Summary

Total Deck
Element Deck
Name Type Material Thickness Depth
Type Material
mm mm
Deck1 Deck Membrane Fc' -- 35 162.5 A992Fy50 75
S-0.25-THIN Slab Shell-Thin Fc' -- 35 250
W-.0.50 Wall Shell-Thin Fc' -- 35 500
W-0.20 Wall Shell-Thin Fc' -- 35 200

Page 4 of 42
Properties 05/03/2023

Table 2.3 - Area Section Property Definitions - Summary (continued)

Total Deck
Element Deck
Name Type Material Thickness Depth
Type Material
mm mm
W-0.35 Wall Shell-Thin Fc' -- 35 350

2.4 Reinforcement Sizes


Table 2.4 - Reinforcing Bar Sizes

Diameter Area
Name
mm mm2
6 6 28.3
8 8 50.3
10 10 78.5
12 12 113.1
14 14 153.9
16 16 201.1
18 18 254.5
20 20 314.2
22 22 380.1
25 25 490.9
26 26 530.9
28 28 615.8
32 32 804.2
36 36 1017.9
40 40 1256.6
50 50 1963.5

Page 5 of 42
Loads 05/03/2023

3 Loads
This chapter provides loading information as applied to the model.
3.1 Load Patterns
Table 3.1 - Load Pattern Definitions

Self
Is Auto
Name Type Weight Auto Load
Load
Multiplier
Dead No Dead 1
Live No Live 0
QX No Seismic 0 ASCE 7-10
QY No Seismic 0 ASCE 7-10
SDL No Super Dead 0
WALL No Super Dead 0
WIND(0,90) No Wind 0 ASCE 7-10
WIND(180,270) No Wind 0 ASCE 7-10

3.2 Auto Wind Loading


Table 3.2 - Load Pattern Definitions - Auto Wind - ASCE 7-10 (Part 1 of 3)

Parapet
Is Auto Exposure Top Include User ASCE e1 e2
Name Bottom Story Height
Load Source Story Parapet Cp? Case Ratio Ratio
m
WIND(0,90) No Diaphragms ROOF GRADE BEAMS Yes 0.5 No Create All 0.15 0.15
WIND(0,90) No
WIND(180,270) No Diaphragms ROOF GRADE BEAMS Yes 0.5 No Create All 0.15 0.15
WIND(180,270) No

Table 3.2 - Load Pattern Definitions - Auto Wind - ASCE 7-10 (Part 2 of 3)

Wind Direction
Exposure Gust Width Width Depth
Speed kzt Kd Angle Story Diaphragm
Type Factor Type m m
mph deg
103 C 1 0.85 0.85 Auto 0 ROOF D1 14.7 10.9
GRADE BEAMS D1 0 0
103 C 1 0.85 0.85 Auto 180 ROOF D1 14.7 10.9
GRADE BEAMS D1 0 0

Table 3.2 - Load Pattern Definitions - Auto Wind - ASCE 7-10 (Part 3 of 3)

Y
m
8.8696
0
8.8696
0

Page 6 of 42
Loads 05/03/2023

ASCE 7-10 Auto Wind Load Calculation


This calculation presents the automatically generated lateral wind loads for load pattern WIND(0,90)
according to ASCE 7-10, as calculated by ETABS.

Exposure Parameters

Exposure From = Diaphragms


Exposure Category = C
Wind Direction = 0 degrees

Basic Wind Speed, V [ASCE 26.5.1] V = 103 mph


Windward Coefficient, C p,wind [ASCE
Cp,wind =Varies
27.4.1]

Leeward Coefficient, C p,lee [ASCE 27.4.1] Cp,lee =Varies

Wind Case = All Cases


Top Story = ROOF
Bottom Story = GRADE BEAMS
Include Parapet = Yes, Parapet Height = 0.5
Factors and Coefficients

Gradient Height, z g [ASCE Table 26.9-1] z g = 900

Emperical Exponent, α [ASCE Table 26.9-1] α = 9.5


2
α
Velocity Pressure Exposure Coefficient,
K z; [ASCE Table 27.3-1]
K z = 2.01 ( zz )
g
for 15ft ≤ z ≤ z g
2
α

K z = 2.01 ( 15z )
g
for z < 15ft

Topographical Factor, Kzt [ASCE 26.8.2] K zt = 1


Directionality Factor, K d [ASCE 26.6] K d = 0.85
Gust Effect Factor, G [ASCE 26.9] G = 0.85
Lateral Loading

Velocity Pressure, q z [ASCE 27.3.2 Eq.


q z = 0.00256 K z K zt K d V 2
27.3-1]
Design Wind Pressure, p [ASCE 27.4.2 Eq.
p = qG Cp,wind + q h ( G Cp,lee )
27.4-2]

Applied Story Forces

Page 7 of 42
Loads 05/03/2023

Lateral Load to Stories -C


47.7234kN Lateral Load to Stories - C
ROOF ROOF
34.1745kN

GRADE BEAMS GRADE BEAMS

Base Base
0.0 8.0 16.0 24.0 32.0 40.0 48.0 0.0 6.0 12.0 18.0 24.0 30.0 36.0
Force, kN Force, kN

Page 8 of 42
Loads 05/03/2023

Story Elevation X-Dir Y-Dir Story Elevation X-Dir Y-Dir


m kN kN m kN kN
ROOF 4.2 47.7234 0 ROOF 4.2 0 34.1745
GRADE GRADE
0.2 0 0 0.2 0 0
BEAMS BEAMS
Base -1.8 0 0 Base -1.8 0 0
Lateral Load to Stories -C
35.7926kN Lateral Load to Stories -C
35.7926kN
ROOF ROOF

GRADE BEAMS GRADE BEAMS

Base Base
0.0 6.0 12.0 18.0 24.0 30.0 36.0 0.0 6.0 12.0 18.0 24.0 30.0 36.0
Force, kN Force, kN

Story Elevation X-Dir Y-Dir Story Elevation X-Dir Y-Dir


m kN kN m kN kN
ROOF 4.2 35.7926 0 ROOF 4.2 35.7926 0
GRADE GRADE
0.2 0 0 0.2 0 0
BEAMS BEAMS
Base -1.8 0 0 Base -1.8 0 0

Page 9 of 42
Loads 05/03/2023

Lateral Load to Stories - C Lateral Load to Stories - C


ROOF ROOF
25.6309kN 25.6309kN

GRADE BEAMS GRADE BEAMS

Base Base
0.0 5.0 10.0 15.0 20.0 25.0 30.0 0.0 5.0 10.0 15.0 20.0 25.0 30.0
Force, kN Force, kN

Story Elevation X-Dir Y-Dir Story Elevation X-Dir Y-Dir


m kN kN m kN kN
ROOF 4.2 0 25.6309 ROOF 4.2 0 25.6309
GRADE GRADE
0.2 0 0 0.2 0 0
BEAMS BEAMS
Base -1.8 0 0 Base -1.8 0 0

Page 10 of 42
Loads 05/03/2023

Lateral Load to Stories35.7926kN


-C Lateral Load to Stories -C
34.5664kN
ROOF ROOF
-26.5401kN 25.6309kN

GRADE BEAMS GRADE BEAMS

Base Base
-36.0-24.0-12.0 0.0 12.0 24.0 36.0 0.0 6.0 12.0 18.0 24.0 30.0 36.0
Force, kN Force, kN

Story Elevation X-Dir Y-Dir Story Elevation X-Dir Y-Dir


m kN kN m kN kN
ROOF 4.2 35.7926 -26.5401 ROOF 4.2 34.5664 25.6309
GRADE GRADE
0.2 0 0 0.2 0 0
BEAMS BEAMS
Base -1.8 0 0 Base -1.8 0 0

Page 11 of 42
Loads 05/03/2023

Lateral Load to 26.8683kN


Stories - C Lateral Load to 26.8683kN
Stories - C
ROOF ROOF
-19.9228kN -19.9228kN

GRADE BEAMS GRADE BEAMS

Base Base
-20.0-10.0 0.0 10.0 20.0 30.0 40.0 -20.0-10.0 0.0 10.0 20.0 30.0 40.0
Force, kN Force, kN

Story Elevation X-Dir Y-Dir Story Elevation X-Dir Y-Dir


m kN kN m kN kN
ROOF 4.2 26.8683 -19.9228 ROOF 4.2 26.8683 -19.9228
GRADE GRADE
0.2 0 0 0.2 0 0
BEAMS BEAMS
Base -1.8 0 0 Base -1.8 0 0

Page 12 of 42
Loads 05/03/2023

Lateral Load to Stories -C


25.9478kN Lateral Load to Stories -C
25.9478kN
ROOF ROOF
19.2402kN 19.2402kN

GRADE BEAMS GRADE BEAMS

Base Base
0.0 5.0 10.0 15.0 20.0 25.0 30.0 0.0 5.0 10.0 15.0 20.0 25.0 30.0
Force, kN Force, kN

Story Elevation X-Dir Y-Dir Story Elevation X-Dir Y-Dir


m kN kN m kN kN
ROOF 4.2 25.9478 19.2402 ROOF 4.2 25.9478 19.2402
GRADE GRADE
0.2 0 0 0.2 0 0
BEAMS BEAMS
Base -1.8 0 0 Base -1.8 0 0

Page 13 of 42
Loads 05/03/2023

ASCE 7-10 Auto Wind Load Calculation


This calculation presents the automatically generated lateral wind loads for load pattern WIND(180,270)
according to ASCE 7-10, as calculated by ETABS.

Exposure Parameters

Exposure From = Diaphragms


Exposure Category = C
Wind Direction = 180 degrees

Basic Wind Speed, V [ASCE 26.5.1] V = 103 mph


Windward Coefficient, C p,wind [ASCE
Cp,wind =Varies
27.4.1]
Leeward Coefficient, C p,lee [ASCE
Cp,lee =Varies
27.4.1]
Wind Case = All Cases
Top Story = ROOF
Bottom Story = GRADE BEAMS
Include Parapet = Yes, Parapet Height = 0.5
Factors and Coefficients

Gradient Height, z g [ASCE Table 26.9-1] z g = 900


Emperical Exponent, α [ASCE Table
α = 9.5
26.9-1]
2
α
Velocity Pressure Exposure Coefficient,
K z; [ASCE Table 27.3-1]
K z = 2.01 ( zz )
g
for 15ft ≤ z ≤ z g
2
α

K z = 2.01 ( 15z )
g
for z < 15ft

Topographical Factor, Kzt [ASCE 26.8.2] K zt = 1


Directionality Factor, K d [ASCE 26.6] K d = 0.85
Gust Effect Factor, G [ASCE 26.9] G = 0.85
Lateral Loading

Velocity Pressure, q z [ASCE 27.3.2 Eq.


q z = 0.00256 K z K zt K d V 2
27.3-1]
Design Wind Pressure, p [ASCE 27.4.2
p = qG Cp,wind + q h ( G Cp,lee )
Eq. 27.4-2]

Applied Story Forces

Page 14 of 42
Loads 05/03/2023

Lateral Load to Stories - C


-47.7234kN Lateral Load to Stories - C
ROOF ROOF
-34.1745kN

GRADE BEAMS GRADE BEAMS

Base Base
-48.0-40.0-32.0-24.0-16.0 -8.0 0.0 -36.0-30.0-24.0-18.0-12.0 -6.0 0.0
Force, kN Force, kN

Page 15 of 42
Loads 05/03/2023

Story Elevation X-Dir Y-Dir Story Elevation X-Dir Y-Dir


m kN kN m kN kN
ROOF 4.2 -47.7234 0 ROOF 4.2 0 -34.1745
GRADE GRADE
0.2 0 0 0.2 0 0
BEAMS BEAMS
Base -1.8 0 0 Base -1.8 0 0
Lateral Load to Stories - C
-35.7926kN Lateral Load to Stories - C
-35.7926kN
ROOF ROOF

GRADE BEAMS GRADE BEAMS

Base Base
-36.0-30.0-24.0-18.0-12.0 -6.0 0.0 -36.0-30.0-24.0-18.0-12.0 -6.0 0.0
Force, kN Force, kN

Story Elevation X-Dir Y-Dir Story Elevation X-Dir Y-Dir


m kN kN m kN kN
ROOF 4.2 -35.7926 0 ROOF 4.2 -35.7926 0
GRADE GRADE
0.2 0 0 0.2 0 0
BEAMS BEAMS
Base -1.8 0 0 Base -1.8 0 0

Page 16 of 42
Loads 05/03/2023

Lateral Load to Stories - C Lateral Load to Stories - C


ROOF ROOF
-25.6309kN -25.6309kN

GRADE BEAMS GRADE BEAMS

Base Base
-30.0-25.0-20.0-15.0-10.0 -5.0 0.0 -30.0-25.0-20.0-15.0-10.0 -5.0 0.0
Force, kN Force, kN

Story Elevation X-Dir Y-Dir Story Elevation X-Dir Y-Dir


m kN kN m kN kN
ROOF 4.2 0 -25.6309 ROOF 4.2 0 -25.6309
GRADE GRADE
0.2 0 0 0.2 0 0
BEAMS BEAMS
Base -1.8 0 0 Base -1.8 0 0

Page 17 of 42
Loads 05/03/2023

Lateral Load to Stories - C


-35.7926kN Lateral Load to Stories - C
-34.5664kN
ROOF ROOF
26.5401kN -25.6309kN

GRADE BEAMS GRADE BEAMS

Base Base
-36.0-24.0-12.0 0.0 12.0 24.0 36.0 -36.0-30.0-24.0-18.0-12.0 -6.0 0.0
Force, kN Force, kN

Story Elevation X-Dir Y-Dir Story Elevation X-Dir Y-Dir


m kN kN m kN kN
ROOF 4.2 -35.7926 26.5401 ROOF 4.2 -34.5664 -25.6309
GRADE GRADE
0.2 0 0 0.2 0 0
BEAMS BEAMS
Base -1.8 0 0 Base -1.8 0 0

Page 18 of 42
Loads 05/03/2023

Lateral Load to Stories - C


-26.8683kN Lateral Load to Stories - C
-26.8683kN
ROOF ROOF
19.9228kN 19.9228kN

GRADE BEAMS GRADE BEAMS

Base Base
-30.0-20.0-10.0 0.0 10.0 20.0 30.0 -30.0-20.0-10.0 0.0 10.0 20.0 30.0
Force, kN Force, kN

Story Elevation X-Dir Y-Dir Story Elevation X-Dir Y-Dir


m kN kN m kN kN
ROOF 4.2 -26.8683 19.9228 ROOF 4.2 -26.8683 19.9228
GRADE GRADE
0.2 0 0 0.2 0 0
BEAMS BEAMS
Base -1.8 0 0 Base -1.8 0 0

Page 19 of 42
Loads 05/03/2023

Lateral Load to Stories - C


-25.9478kN Lateral Load to Stories - C
-25.9478kN
ROOF ROOF
-19.2402kN -19.2402kN

GRADE BEAMS GRADE BEAMS

Base Base
-30.0-25.0-20.0-15.0-10.0 -5.0 0.0 -30.0-25.0-20.0-15.0-10.0 -5.0 0.0
Force, kN Force, kN

Story Elevation X-Dir Y-Dir Story Elevation X-Dir Y-Dir


m kN kN m kN kN
ROOF 4.2 -25.9478 -19.2402 ROOF 4.2 -25.9478 -19.2402
GRADE GRADE
0.2 0 0 0.2 0 0
BEAMS BEAMS
Base -1.8 0 0 Base -1.8 0 0

Page 20 of 42
Loads 05/03/2023

3.3 Auto Seismic Loading


Table 3.5 - Load Pattern Definitions - Auto Seismic - ASCE 7-10 (Part 1 of 3)

X Dir X Dir Y Dir Y Dir


Is Auto Ecc Top
Name X Dir? Plus Minus Y Dir? Plus Minus Bottom Story
Load Ratio Story
Ecc? Ecc? Ecc? Ecc?
QX No No Yes Yes No No No 0.05 ROOF GRADE BEAMS
QY No No No No No Yes Yes 0.05 ROOF GRADE BEAMS

Table 3.5 - Load Pattern Definitions - Auto Seismic - ASCE 7-10 (Part 2 of 3)

Ss And S1 TL Site
Period Type Ct and X Ss S1 Fa Fv SDS SD1
From sec Class
Program Calculated 0.016; 0.9 User Defined 0.3 0.04 8 D 1.56 2.4 0.312 0.064
Program Calculated 0.016; 0.9 User Defined 0.3 0.04 8 D 1.56 2.4 0.312 0.064

Table 3.5 - Load Pattern Definitions - Auto Seismic - ASCE 7-10 (Part 3 of 3)

Period Weight Base


Coeff
Omega Cd I Used Used Shear
Used
sec kN kN
3 2.5 1
3 2.5 1

Page 21 of 42
Loads 05/03/2023

ASCE 7-10 Auto Seismic Load Calculation


This calculation presents the automatically generated lateral seismic loads for load pattern QX according to
ASCE 7-10, as calculated by ETABS.

Direction and Eccentricity

Direction = Multiple
Eccentricity Ratio = 5% for all diaphragms
Structural Period

Period Calculation Method = Program Calculated

Coefficient, C t [ASCE Table 12.8-2] Ct = 0.016ft


Coefficient, x [ASCE Table 12.8-2] x = 0.9
Structure Height Above Base, h n h n = 13.12 ft
Long-Period Transition Period, T L [ASCE
T L = 8 sec
11.4.5]
Factors and Coefficients

Response Modification Factor, R [ASCE


R = 2.5
Table 12.2-1]
System Overstrength Factor, Ω 0 [ASCE
Ω0 = 3
Table 12.2-1]
Deflection Amplification Factor, C d [ASCE
Cd = 2.5
Table 12.2-1]
Importance Factor, I [ASCE Table 11.5-1] I=1
Ss and S1 Source = User Specified
Mapped MCE Spectral Response
S s = 0.3g
Acceleration, S s [ASCE 11.4.1]
Mapped MCE Spectral Response
S 1 = 0.04g
Acceleration, S 1 [ASCE 11.4.1]
Site Class [ASCE Table 20.3-1] = D - Stiff
Soil
Site Coefficient, F a [ASCE Table 11.4-1] F a = 1.56
Site Coefficient, F v [ASCE Table 11.4-2] F v = 2.4
Seismic Response

MCE Spectral Response Acceleration,


S MS = F a S S S MS = 0.468g
S MS [ASCE 11.4.3, Eq. 11.4-1]
MCE Spectral Response Acceleration,
S M1 = F v S 1 S M1 =0.096g
S M1 [ASCE 11.4.3, Eq. 11.4-2]
Design Spectral Response Acceleration, 2
S DS = S S DS = 0.312g
S DS [ASCE 11.4.4, Eq. 11.4-3] 3 MS
Design Spectral Response Acceleration, 2
S D1 = S S D1 =0.064g
S D1 [ASCE 11.4.4, Eq. 11.4-4] 3 M1

Page 22 of 42
Loads 05/03/2023

Equivalent Lateral Forces

S DS
Seismic Response Coefficient, C S [ASCE
CS = R
12.8.1.1, Eq. 12.8-2] ( )
I

S D1
[ASCE 12.8.1.1, Eq. 12.8-3] CS,max = R
T( )
I

[ASCE 12.8.1.1, Eq. 12.8-5] CS,min = max ( 0.044 S DS I,0.01 ) = 0.013728


S1
[ASCE 12.8.1.1, Eq. 12.8-6] CS,min = 0.5 R for S 1 = 0.6g
( )
I

CS,min ≤ Cs ≤ CS,max
Calculated Base Shear
Period Used W V
Direction Cs
(sec) (kN) (kN)
X + Ecc. Y 0.276 0.092775 2159.6535 200.3617
X - Ecc. Y 0.276 0.092775 2159.6535 200.3617

Applied Story Forces

Page 23 of 42
Loads 05/03/2023

Lateral Load to Stories -X


200.3617kN
ROOF

GRADE BEAMS

Base
0 40 80 120 160 200 240
Force, kN

Story Elevation X-Dir Y-Dir


m kN kN
ROOF 4.2 200.3617 0
GRADE
0.2 0 0
BEAMS
Base -1.8 0 0

Page 24 of 42
Loads 05/03/2023

ASCE 7-10 Auto Seismic Load Calculation


This calculation presents the automatically generated lateral seismic loads for load pattern QY according to
ASCE 7-10, as calculated by ETABS.

Direction and Eccentricity

Direction = Multiple
Eccentricity Ratio = 5% for all diaphragms
Structural Period

Period Calculation Method = Program Calculated

Coefficient, C t [ASCE Table 12.8-2] Ct = 0.016ft


Coefficient, x [ASCE Table 12.8-2] x = 0.9
Structure Height Above Base, h n h n = 13.12 ft
Long-Period Transition Period, T L [ASCE
T L = 8 sec
11.4.5]
Factors and Coefficients

Response Modification Factor, R [ASCE


R = 2.5
Table 12.2-1]
System Overstrength Factor, Ω 0 [ASCE
Ω0 = 3
Table 12.2-1]
Deflection Amplification Factor, C d
Cd = 2.5
[ASCE Table 12.2-1]
Importance Factor, I [ASCE Table 11.5-1] I=1
Ss and S1 Source = User Specified
Mapped MCE Spectral Response
S s = 0.3g
Acceleration, S s [ASCE 11.4.1]
Mapped MCE Spectral Response
S 1 = 0.04g
Acceleration, S 1 [ASCE 11.4.1]
Site Class [ASCE Table 20.3-1] = D - Stiff
Soil
Site Coefficient, F a [ASCE Table 11.4-1] F a = 1.56
Site Coefficient, F v [ASCE Table 11.4-2] F v = 2.4
Seismic Response

MCE Spectral Response Acceleration,


S MS = F a S S S MS = 0.468g
S MS [ASCE 11.4.3, Eq. 11.4-1]
MCE Spectral Response Acceleration,
S M1 = F v S 1 S M1 =0.096g
S M1 [ASCE 11.4.3, Eq. 11.4-2]
Design Spectral Response Acceleration, 2
S DS = S S DS = 0.312g
S DS [ASCE 11.4.4, Eq. 11.4-3] 3 MS
Design Spectral Response Acceleration, 2
S D1 = S S D1 =0.064g
S D1 [ASCE 11.4.4, Eq. 11.4-4] 3 M1

Page 25 of 42
Loads 05/03/2023

Equivalent Lateral Forces

S DS
Seismic Response Coefficient, C S
CS = R
[ASCE 12.8.1.1, Eq. 12.8-2] ( )
I

S D1
[ASCE 12.8.1.1, Eq. 12.8-3] CS,max = R
T( )
I

[ASCE 12.8.1.1, Eq. 12.8-5] CS,min = max ( 0.044 S DS I,0.01 ) = 0.013728


S1
[ASCE 12.8.1.1, Eq. 12.8-6] CS,min = 0.5 R for S 1 = 0.6g
( )
I

CS,min ≤ Cs ≤ CS,max
Calculated Base Shear
Period Used W V
Direction Cs
(sec) (kN) (kN)
Y + Ecc. X 0.276 0.092775 2159.6535 200.3617
Y - Ecc. X 0.276 0.092775 2159.6535 200.3617

Applied Story Forces

Page 26 of 42
Loads 05/03/2023

Lateral Load to Stories - Y


ROOF
200.3617kN

GRADE BEAMS

Base
0 40 80 120 160 200 240
Force, kN

Story Elevation X-Dir Y-Dir


m kN kN
ROOF 4.2 0 200.3617
GRADE
0.2 0 0
BEAMS
Base -1.8 0 0

Page 27 of 42
Loads 05/03/2023

3.4 Load Cases


Table 3.8 - Load Case Definitions - Summary

Name Type
Modal1 Modal - Ritz
Dead Linear Static
Live Linear Static
Wall Linear Static
SDL Linear Static
QX Linear Static
QY Linear Static
SPEC-X Response Spectrum
SPEC-Y Response Spectrum
WIND(0,90) Linear Static
WIND(180,270) Linear Static
1.2DL+0.5LL+1.6LR-SEQ-NL Nonlinear Static

Table 3.9 - Load Case Definitions - Linear Static

Exclude Mass Stiffness Load Load


Name Load Name Design Type Notes
Group Source Type Type SF
Dead None MsSrc1 P-Delta Load Dead 1 Program Determined
Live None MsSrc1 P-Delta Load Live 1 Program Determined
QX None MsSrc1 P-Delta Load QX 1 Program Determined
QY None MsSrc1 P-Delta Load QY 1 Program Determined
SDL None MsSrc1 P-Delta Load SDL 1 Program Determined
Wall None MsSrc1 P-Delta Load WALL 1 Program Determined
WIND(0,90) None MsSrc1 P-Delta Load WIND(0,90) 1 Program Determined
WIND(180,270) None MsSrc1 P-Delta Load WIND(180,270) 1 Program Determined

Table 3.10 - Load Case Definitions - Nonlinear Static (Part 1 of 3)

Load
Mass Initial Load Load Load Geometric Monitor
Name App
Source Condition Type Name SF Nonlinearity Type
Type
1.2DL+0.5LL+1.6LR-SEQ-NL Previous Unstressed Load Live 0.5 P-Delta Full DOF/Joint
1.2DL+0.5LL+1.6LR-SEQ-NL Load SDL 1.2

Table 3.10 - Load Case Definitions - Nonlinear Static (Part 2 of 3)

Max Max
Results Event Event Max Max CS
DOF Story PointBay Total Null Iteration?
Type Stepping? Tolerance Events Iterations
Steps Steps
U1 ROOF 1 Final State 200 50 Yes 0.01 24 Yes 10

Table 3.10 - Load Case Definitions - Nonlinear Static (Part 3 of 3)

Iteration Line
Design Type Notes
Tolerance Search?
0.0001 No Program Determined

Page 28 of 42
Loads 05/03/2023

Table 3.11 - Modal Case Definitions - Ritz

Target
Exclude Mass Stiffness Load Load Max Max Min
Name Ratio Design Type Notes
Group Source Type Type Name Cycles Modes Modes
%
Accel
Modal1 None MsSrc1 P-Delta Accel 0 90 15 1 Program Determined
UX
Accel
Modal1 Accel 0 90
UY

Modal1 Accel Accel UZ 0 90

Table 3.12 - Load Case Definitions - Response Spectrum (Part 1 of 2)

Trans Modal
Load Coordinate Angle Modal Rigid
Name Mass Source Function Accel SF Combo
Name System deg Case Response?
mm/sec2 Method

SPEC-X Previous (MsSrc1) U1 QATIF 9806.65 Global 0 Modal1 CQC No


SPEC-Y Previous (MsSrc1) U2 QATIF 9806.65 Global 0 Modal1 CQC No

Table 3.12 - Load Case Definitions - Response Spectrum (Part 2 of 2)

Directional
Eccentricity
Combo Design Type Notes
Ratio
Type
SRSS 0.05 Program Determined
SRSS 0.05 Program Determined

3.5 Load Combinations


Table 3.13 - Load Combination Definitions (Part 1 of 2)

Name Type Is Auto Load Name SF


0.9DL-1QX Linear Add No Dead 0.84
0.9DL-1QX Wall 0.84
0.9DL-1QX SDL 0.84
0.9DL-1QX QX -1
0.9DL+1QX Linear Add No Dead 0.84
0.9DL+1QX Wall 0.84
0.9DL+1QX SDL 0.84
0.9DL+1QX QX 1
0.9DL+1QY Linear Add No Dead 0.84
0.9DL+1QY Wall 0.84
0.9DL+1QY SDL 0.84
0.9DL+1QY QY 1
0.9DL+1W(0,90) Linear Add No Dead 0.9
0.9DL+1W(0,90) Wall 0.9
0.9DL+1W(0,90) SDL 0.9
0.9DL+1W(0,90) WIND(0,90) 1
0.9DL+1W(180,270) Linear Add No Dead 0.9
0.9DL+1W(180,270) Wall 0.9
0.9DL+1W(180,270) SDL 0.9
0.9DL+1W(180,270) WIND(180,270) 1
0.9DL-QY Linear Add No Dead 0.84
0.9DL-QY Wall 0.84
0.9DL-QY SDL 0.84

Page 29 of 42
Loads 05/03/2023

Table 3.13 - Load Combination Definitions (Part 1 of 2, continued)

Name Type Is Auto Load Name SF


0.9DL-QY QY -1
1.2DL+0.5LL+1.6LR Linear Add No Live 0.5
1.2DL+0.5LL+1.6LR SDL 1.2
1.2DL+0.5LL+1.6LR Dead 1.2
1.2DL+0.5LL+1.6LR Wall 1.2
1.2DL+1LL-1QX Linear Add No Dead 1.26
1.2DL+1LL-1QX Live 1
1.2DL+1LL-1QX Wall 1.26
1.2DL+1LL-1QX SDL 1.26
1.2DL+1LL-1QX QX -1
1.2DL+1LL-1QY Linear Add No Dead 1.26
1.2DL+1LL-1QY Live 1
1.2DL+1LL-1QY Wall 1.26
1.2DL+1LL-1QY SDL 1.26
1.2DL+1LL-1QY QY -1
1.2DL+1LL+1QX Linear Add No Dead 1.26
1.2DL+1LL+1QX Live 1
1.2DL+1LL+1QX Wall 1.26
1.2DL+1LL+1QX SDL 1.26
1.2DL+1LL+1QX QX 1
1.2DL+1LL+1QY Linear Add No Dead 1.26
1.2DL+1LL+1QY Live 1
1.2DL+1LL+1QY Wall 1.26
1.2DL+1LL+1QY SDL 1.26
1.2DL+1LL+1QY QY 1
1.2DL+1LL+1W(0,90) Linear Add No Dead 1.2
1.2DL+1LL+1W(0,90) Live 1
1.2DL+1LL+1W(0,90) Wall 1.2
1.2DL+1LL+1W(0,90) SDL 1.2
1.2DL+1LL+1W(0,90) WIND(0,90) 1
1.2DL+1LL+1W(180,270) Linear Add No Dead 1.2
1.2DL+1LL+1W(180,270) Live 0.5
1.2DL+1LL+1W(180,270) Wall 1.2
1.2DL+1LL+1W(180,270) SDL 1.2
1.2DL+1LL+1W(180,270) WIND(180,270) 1
1.4DL Linear Add No Dead 1.4
1.4DL Wall 1.4
1.4DL SDL 1.4
1.4DL+1.7LL Linear Add No Live 1.7
1.4DL+1.7LL SDL 1.4
1.4DL+1.7LL Dead 1.4
1.4DL+1.7LL Wall 1.4
DEAD+WALL Linear Add No Dead 1
DEAD+WALL Wall 1
DSlbU1 Linear Add Yes AutoSeq 1.4
DSlbU1 Wall 1.4
DSlbU1 SDL 1.4
DSlbU1 AutoSeq 1.4
DSlbU2 Linear Add Yes AutoSeq 1.2
DSlbU2 Live 1.6

Page 30 of 42
Loads 05/03/2023

Table 3.13 - Load Combination Definitions (Part 1 of 2, continued)

Name Type Is Auto Load Name SF


DSlbU2 Wall 1.2
DSlbU2 SDL 1.2
DSlbU2 AutoSeq 1.2
DSlbU3 Linear Add Yes AutoSeq 1.2
DSlbU3 Live 1
DSlbU3 Wall 1.2
DSlbU3 SDL 1.2
DSlbU3 AutoSeq 1.2
DSlbU3 WIND(0,90) 1
DSlbU4 Linear Add Yes AutoSeq 1.2
DSlbU4 Live 1
DSlbU4 Wall 1.2
DSlbU4 SDL 1.2
DSlbU4 AutoSeq 1.2
DSlbU4 WIND(0,90) -1
DSlbU5 Linear Add Yes AutoSeq 1.2
DSlbU5 Live 1
DSlbU5 Wall 1.2
DSlbU5 SDL 1.2
DSlbU5 AutoSeq 1.2
DSlbU5 WIND(180,270) 1
DSlbU6 Linear Add Yes AutoSeq 1.2
DSlbU6 Live 1
DSlbU6 Wall 1.2
DSlbU6 SDL 1.2
DSlbU6 AutoSeq 1.2
DSlbU6 WIND(180,270) -1
DSlbU7 Linear Add Yes AutoSeq 0.9
DSlbU7 AutoSeq 0.9
DSlbU7 WIND(0,90) 1
DSlbU8 Linear Add Yes AutoSeq 0.9
DSlbU8 AutoSeq 0.9
DSlbU8 WIND(0,90) -1
DSlbU9 Linear Add Yes AutoSeq 0.9
DSlbU9 AutoSeq 0.9
DSlbU9 WIND(180,270) 1
DSlbU10 Linear Add Yes AutoSeq 0.9
DSlbU10 AutoSeq 0.9
DSlbU10 WIND(180,270) -1
DSlbU11 Linear Add Yes AutoSeq 1.2
DSlbU11 Live 1
DSlbU11 Wall 1.2
DSlbU11 SDL 1.2
DSlbU11 AutoSeq 1.2
DSlbU11 QX 1
DSlbU12 Linear Add Yes AutoSeq 1.2
DSlbU12 Live 1
DSlbU12 Wall 1.2
DSlbU12 SDL 1.2
DSlbU12 AutoSeq 1.2

Page 31 of 42
Loads 05/03/2023

Table 3.13 - Load Combination Definitions (Part 1 of 2, continued)

Name Type Is Auto Load Name SF


DSlbU12 QX -1
DSlbU13 Linear Add Yes AutoSeq 1.2
DSlbU13 Live 1
DSlbU13 Wall 1.2
DSlbU13 SDL 1.2
DSlbU13 AutoSeq 1.2
DSlbU13 QY 1
DSlbU14 Linear Add Yes AutoSeq 1.2
DSlbU14 Live 1
DSlbU14 Wall 1.2
DSlbU14 SDL 1.2
DSlbU14 AutoSeq 1.2
DSlbU14 QY -1
DSlbU15 Linear Add Yes AutoSeq 1.2
DSlbU15 Live 1
DSlbU15 Wall 1.2
DSlbU15 SDL 1.2
DSlbU15 AutoSeq 1.2
DSlbU15 SPEC-X 1
DSlbU16 Linear Add Yes AutoSeq 1.2
DSlbU16 Live 1
DSlbU16 Wall 1.2
DSlbU16 SDL 1.2
DSlbU16 AutoSeq 1.2
DSlbU16 SPEC-X -1
DSlbU17 Linear Add Yes AutoSeq 1.2
DSlbU17 Live 1
DSlbU17 Wall 1.2
DSlbU17 SDL 1.2
DSlbU17 AutoSeq 1.2
DSlbU17 SPEC-Y 1
DSlbU18 Linear Add Yes AutoSeq 1.2
DSlbU18 Live 1
DSlbU18 Wall 1.2
DSlbU18 SDL 1.2
DSlbU18 AutoSeq 1.2
DSlbU18 SPEC-Y -1
DSlbU19 Linear Add Yes AutoSeq 0.9
DSlbU19 AutoSeq 0.9
DSlbU19 QX 1
DSlbU20 Linear Add Yes AutoSeq 0.9
DSlbU20 AutoSeq 0.9
DSlbU20 QX -1
DSlbU21 Linear Add Yes AutoSeq 0.9
DSlbU21 AutoSeq 0.9
DSlbU21 QY 1
DSlbU22 Linear Add Yes AutoSeq 0.9
DSlbU22 AutoSeq 0.9
DSlbU22 QY -1
DSlbU23 Linear Add Yes AutoSeq 0.9

Page 32 of 42
Loads 05/03/2023

Table 3.13 - Load Combination Definitions (Part 1 of 2, continued)

Name Type Is Auto Load Name SF


DSlbU23 AutoSeq 0.9
DSlbU23 SPEC-X 1
DSlbU24 Linear Add Yes AutoSeq 0.9
DSlbU24 AutoSeq 0.9
DSlbU24 SPEC-X -1
DSlbU25 Linear Add Yes AutoSeq 0.9
DSlbU25 AutoSeq 0.9
DSlbU25 SPEC-Y 1
DSlbU26 Linear Add Yes AutoSeq 0.9
DSlbU26 AutoSeq 0.9
DSlbU26 SPEC-Y -1
L.T.D. Linear Add No Dead 2.5
L.T.D. SDL 2.5
L.T.D. Wall 2.5
S(0.6DL-0.7QX) Linear Add No Dead 0.6
S(0.6DL-0.7QX) Wall 0.6
S(0.6DL-0.7QX) SDL 0.6
S(0.6DL-0.7QX) QX -0.7
S(0.6DL-0.7QY) Linear Add No Dead 0.6
S(0.6DL-0.7QY) Wall 0.6
S(0.6DL-0.7QY) SDL 0.6
S(0.6DL-0.7QY) QY -0.7
S(0.6DL+0.6(180,270)) Linear Add No Dead 0.6
S(0.6DL+0.6(180,270)) Wall 0.6
S(0.6DL+0.6(180,270)) SDL 0.6
S(0.6DL+0.6(180,270)) WIND(180,270) 0.6
S(0.6DL+0.6W(0,90)) Linear Add No Dead 0.6
S(0.6DL+0.6W(0,90)) Wall 0.6
S(0.6DL+0.6W(0,90)) SDL 0.6
S(0.6DL+0.6W(0,90)) WIND(0,90) 0.6
S(0.6DL+0.7QX) Linear Add No Dead 0.6
S(0.6DL+0.7QX) Wall 0.6
S(0.6DL+0.7QX) SDL 0.6
S(0.6DL+0.7QX) QX 0.7
S(0.6DL+0.7QY) Linear Add No Dead 0.6
S(0.6DL+0.7QY) Wall 0.6
S(0.6DL+0.7QY) SDL 0.6
S(0.6DL+0.7QY) QY 0.7
S(DL-0.7QX) Linear Add No Dead 1
S(DL-0.7QX) Wall 1
S(DL-0.7QX) SDL 1
S(DL-0.7QX) QX -0.7
S(DL-0.7QY) Linear Add No Dead 1
S(DL-0.7QY) Wall 1
S(DL-0.7QY) SDL 1
S(DL-0.7QY) QY -0.7
S(DL+0.6(W180,270)) Linear Add No Dead 1
S(DL+0.6(W180,270)) Wall 1
S(DL+0.6(W180,270)) SDL 1
S(DL+0.6(W180,270)) WIND(180,270) 0.6

Page 33 of 42
Loads 05/03/2023

Table 3.13 - Load Combination Definitions (Part 1 of 2, continued)

Name Type Is Auto Load Name SF


S(DL+0.6W(0,90)) Linear Add No Dead 1
S(DL+0.6W(0,90)) Wall 1
S(DL+0.6W(0,90)) SDL 1
S(DL+0.6W(0,90)) WIND(0,90) 0.6
S(DL+0.7QX) Linear Add No Dead 1
S(DL+0.7QX) Wall 1
S(DL+0.7QX) SDL 1
S(DL+0.7QX) QX 0.7
S(DL+0.7QY) Linear Add No Dead 1
S(DL+0.7QY) Wall 1
S(DL+0.7QY) SDL 1
S(DL+0.7QY) QY 0.7
S(DL+0.75LL-0.75*0.7QX) Linear Add No Dead 1
S(DL+0.75LL-0.75*0.7QX) Wall 1
S(DL+0.75LL-0.75*0.7QX) SDL 1
S(DL+0.75LL-0.75*0.7QX) Live 0.75
S(DL+0.75LL-0.75*0.7QX) QX -0.525
S(DL+0.75LL-0.75*0.7QY) Linear Add No Dead 1
S(DL+0.75LL-0.75*0.7QY) Wall 1
S(DL+0.75LL-0.75*0.7QY) SDL 1
S(DL+0.75LL-0.75*0.7QY) Live 0.75
S(DL+0.75LL-0.75*0.7QY) QY -0.525
S(DL+0.75LL+0.75*0.6W(0,90)) Linear Add No Dead 1
S(DL+0.75LL+0.75*0.6W(0,90)) Wall 1
S(DL+0.75LL+0.75*0.6W(0,90)) SDL 1
S(DL+0.75LL+0.75*0.6W(0,90)) Live 0.75
S(DL+0.75LL+0.75*0.6W(0,90)) WIND(0,90) 0.45
S(DL+0.75LL+0.75*0.6W(180,270)) Linear Add No Dead 1
S(DL+0.75LL+0.75*0.6W(180,270)) Wall 1
S(DL+0.75LL+0.75*0.6W(180,270)) SDL 1
S(DL+0.75LL+0.75*0.6W(180,270)) Live 0.75
S(DL+0.75LL+0.75*0.6W(180,270)) WIND(180,270) 0.45
S(DL+0.75LL+0.75*0.7QX) Linear Add No Dead 1
S(DL+0.75LL+0.75*0.7QX) Wall 1
S(DL+0.75LL+0.75*0.7QX) SDL 1
S(DL+0.75LL+0.75*0.7QX) Live 0.75
S(DL+0.75LL+0.75*0.7QX) QX 0.525
S(DL+0.75LL+0.75*0.7QY) Linear Add No Dead 1
S(DL+0.75LL+0.75*0.7QY) Wall 1
S(DL+0.75LL+0.75*0.7QY) SDL 1
S(DL+0.75LL+0.75*0.7QY) Live 0.75
S(DL+0.75LL+0.75*0.7QY) QY 0.525
S(DL+0.75LL+0.75LR) Linear Add No Dead 1
S(DL+0.75LL+0.75LR) Wall 1
S(DL+0.75LL+0.75LR) SDL 1
S(DL+0.75LL+0.75LR) Live 0.75
S(DL+LL) Linear Add No Dead 1
S(DL+LL) Wall 1
S(DL+LL) SDL 1
S(DL+LL) Live 1

Page 34 of 42
Loads 05/03/2023

Table 3.13 - Load Combination Definitions (Part 1 of 2, continued)

Name Type Is Auto Load Name SF


SERVICE Envelope No S(DL+LL) 1
SERVICE S(DL+0.6W(0,90)) 1
SERVICE S(DL+0.6(W180,270)) 1
SERVICE S(DL+0.7QX) 1
SERVICE S(DL-0.7QX) 1
SERVICE S(DL+0.7QY) 1
SERVICE S(0.6DL-0.7QY) 1
SERVICE S(0.6DL+0.6W(0,90)) 1
SERVICE S(0.6DL+0.6(180,270)) 1
SERVICE S(0.6DL+0.7QX) 1
SERVICE S(0.6DL-0.7QX) 1
SERVICE S(0.6DL+0.7QY) 1
SERVICE S(0.6DL-0.7QY) 1
SERVICE S(DL+0.75LL+0.75*0.6W(180,270)) 1
SERVICE S(DL+0.75LL+0.75*0.6W(180,270)) 1
SERVICE S(DL+0.75LL+0.75*0.7QX) 1
SERVICE S(DL+0.75LL-0.75*0.7QX) 1
SERVICE S(DL+0.75LL+0.75*0.7QY) 1
SERVICE S(DL+0.75LL-0.75*0.7QY) 1
SERVICE S(DL+0.75LL+0.75LR) 1
TDL Linear Add No Dead 1
TDL Wall 1
TDL SDL 1
Ultimate Envelope No 1.4DL 1
Ultimate 1.4DL+1.7LL 1
Ultimate 1.2DL+1LL+1W(0,90) 1
Ultimate 1.2DL+1LL+1W(180,270) 1
Ultimate 0.9DL+1W(0,90) 1
Ultimate 0.9DL+1W(180,270) 1
Ultimate 1.2DL+1LL+1QX 1
Ultimate 1.2DL+1LL-1QX 1
Ultimate 1.2DL+1LL+1QY 1
Ultimate 1.2DL+1LL-1QY 1
Ultimate 0.9DL+1QX 1
Ultimate 0.9DL-1QX 1
Ultimate 0.9DL+1QY 1
Ultimate 0.9DL-QY 1
ULTIMATE-GRAVITY Envelope No 1.4DL 1
ULTIMATE-GRAVITY 1.4DL+1.7LL 1
ULTIMATE-GRAVITY 1.2DL+0.5LL+1.6LR 1

Table 3.13 - Load Combination Definitions (Part 2 of 2)

Notes
Dead (min) - Static Earthquake [Strength]

Dead (min) + Static Earthquake [Strength]

Page 35 of 42
Loads 05/03/2023

Table 3.13 - Load Combination Definitions (Part 2 of 2, continued)

Notes

Dead (min) + Static Earthquake [Strength]

Dead (min) + Wind [Strength]

Dead (min) + Wind [Strength]

Dead (min) - Static Earthquake [Strength]

Dead + Live [Strength]

Dead + Live - Static Earthquake [Strength]

Dead + Live - Static Earthquake [Strength]

Dead + Live + Static Earthquake [Strength]

Dead + Live + Static Earthquake [Strength]

Dead + Live + Wind + Snow [Strength]

Dead + Live + Wind + Snow [Strength]

Page 36 of 42
Loads 05/03/2023

Table 3.13 - Load Combination Definitions (Part 2 of 2, continued)

Notes

Dead [Strength]

Dead + Live [Strength]

Page 37 of 42
Loads 05/03/2023

Table 3.13 - Load Combination Definitions (Part 2 of 2, continued)

Notes

Page 38 of 42
Loads 05/03/2023

Table 3.13 - Load Combination Definitions (Part 2 of 2, continued)

Notes

Page 39 of 42
Loads 05/03/2023

Table 3.13 - Load Combination Definitions (Part 2 of 2, continued)

Notes

Page 40 of 42
Loads 05/03/2023

Table 3.13 - Load Combination Definitions (Part 2 of 2, continued)

Notes

Page 41 of 42
Loads 05/03/2023

Table 3.13 - Load Combination Definitions (Part 2 of 2, continued)

Notes

Page 42 of 42
WALL LOAD
live load= 3.00 kn/m2
Roof is in accessible
SDL=3.00 kn/m2
10 cm sloped light weight Concrete = 0.075 x 15 = 1.125
kn/m2
2 layers of membrane = 2 x 0.05 = 0.1 kn/m2
insulation board = 100 mm = 0.003x100 = 0.3 kn/m2
5 cm sand = 0.05 x 16 =0.8 kn/m2
2 cm mortar = 0.02x20 = 0.4 kn/m2
1 cm tiles = 0.01 x25 =0.25
Page 66
Page 67
Page 68
Page 69
GAP ENGINEERING CONSULTANT

DEISGN OUTPUT

Page 70
GAP ENGINEERING CONSULTANT

SLAB DESIGN

Page 71
LONGTERM
DEFLECTION = 16
MM < 5800/240 =
24 MM
CAPACITY OF MESH
T12@150 = 6.66X154 = 754 MM2/M

ADDITIONAL TOP
T12@150
MAIN MESH COVERS ALL RFT. NEEDED
MAIN MESH COVERS ALL RFT. NEEDED
MAIN MESH COVERS ALL RFT. NEEDED
GAP ENGINEERING CONSULTANT

ROOF BEAMS DESIGN

Page 79
LONGITUDINAL BARS
4T16 = 4X201 = 804 MM2 COVERS
THE REQUIRED AS.

LONGITUDINAL BARS
6T16 = 6X201 = 1206 MM2
COVERS THE REQUIRED AS.
LONGITUDINAL BARS
2T10@150 = 1046 MM2/M'
COVERS THE REQUIRED AS.
GAP ENGINEERING CONSULTANT

GROUND BEAMS DESIGN

Page 82
LONGITUDINAL BARS
4T16 = 4X201 = 804 MM2 COVERS
THE REQUIRED AS.
LONGITUDINAL BARS
2T10@150 = 1046 MM2/M'
COVERS THE REQUIRED AS.
GAP ENGINEERING CONSULTANT

COLUMNS DESIGN

Page 85
ETABS 18.1.1 License #*1JPZP5TDMTGY7F2

ETABS Concrete Frame Design


ACI 318-14 Column Section Design

Column Element Details (Summary)

Level Element Unique Name Section ID Combo ID Station Loc Length (mm) LLRF Type
ROOF C19 16 C-0.3X0.7 1.4DL+1.7LL 3750 4000 0.853 Sway Ordinary

Section Properties

b (mm) h (mm) dc (mm) Cover (Torsion) (mm)


300 700 58 27.3

Material Properties

E c (MPa) f' c (MPa) Lt.Wt Factor (Unitless) f y (MPa) f ys (MPa)


26168.49 35 1 420 280

Design Code Parameters

ϕT ϕ CTied ϕ CSpiral ϕ Vns ϕ Vs ϕ Vjoint Ω0


0.9 0.65 0.75 0.75 0.6 0.85 2.5

Axial Force and Biaxial Moment Design For P u , M u2 , M u3

Design P u Design M u2 Design M u3 Minimum M 2 Minimum M 3 Rebar % Capacity Ratio


kN kN-m kN-m kN-m kN-m % Unitless
319.8817 -88.5735 -83.7 7.7539 11.5925 1.34 0.59

Axial Force and Biaxial Moment Factors

C m Factor δ ns Factor δ s Factor K Factor Effective Length


Unitless Unitless Unitless Unitless mm
Major Bend(M3) 0.343624 1 1 1 3750
Minor Bend(M2) 0.8 1 1 0.9 5750

Shear Design for V u2 , V u3

Shear V u Shear ϕV c Shear ϕV s Shear ϕV p Rebar Av /s


kN kN kN kN mm²/m
Major, V u2 36.5917 157.5966 0 0 0
Minor, V u3 25.7625 138.6136 0 0 0

Substation.EDB Page 1 of 2 05/03/2023


ETABS 18.1.1 License #*1JPZP5TDMTGY7F2

Joint Shear Check/Design

Joint Shear Shear Shear Shear Joint Shear


Force V u,Top V u,Tot ϕV c Area Ratio
kN kN kN kN mm² Unitless
Major Shear, V u2 N/A N/A N/A N/A N/A N/A
Minor Shear, V u3 N/A N/A N/A N/A N/A N/A

(6/5) Beam/Column Capacity Ratio

Major Ratio Minor Ratio


N/A N/A

Notes:

N/A: Not Applicable

N/C: Not Calculated

N/N: Not Needed

Substation.EDB Page 2 of 2 05/03/2023


ETABS 18.1.1 License #*1JPZP5TDMTGY7F2

ETABS Concrete Frame Design


ACI 318-14 Column Section Design

Column Element Details (Summary)

Level Element Unique Name Section ID Combo ID Station Loc Length (mm) LLRF Type
ROOF C14 15 C-0.3X0.5 1.2DL+1LL-1QX 3750 4000 1 Sway Ordinary

Section Properties

b (mm) h (mm) dc (mm) Cover (Torsion) (mm)


300 500 58 27.3

Material Properties

E c (MPa) f' c (MPa) Lt.Wt Factor (Unitless) f y (MPa) f ys (MPa)


26168.49 35 1 420 280

Design Code Parameters

ϕT ϕ CTied ϕ CSpiral ϕ Vns ϕ Vs ϕ Vjoint Ω0


0.9 0.65 0.75 0.75 0.6 0.85 2.5

Axial Force and Biaxial Moment Design For P u , M u2 , M u3

Design P u Design M u2 Design M u3 Minimum M 2 Minimum M 3 Rebar % Capacity Ratio


kN kN-m kN-m kN-m kN-m % Unitless
163.1153 -57.9807 67.6044 3.9539 4.9326 1.34 0.659

Axial Force and Biaxial Moment Factors

C m Factor δ ns Factor δ s Factor K Factor Effective Length


Unitless Unitless Unitless Unitless mm
Major Bend(M3) 0.376945 1 1 1 3750
Minor Bend(M2) 0.8 1 1 0.9 3750

Shear Design for V u2 , V u3

Shear V u Shear ϕV c Shear ϕV s Shear ϕV p Rebar Av /s


kN kN kN kN mm²/m
Major, V u2 28.6318 105.413 0 0 0
Minor, V u3 28.4704 96.1919 0 0 0

Substation.EDB Page 1 of 2 05/03/2023


ETABS 18.1.1 License #*1JPZP5TDMTGY7F2

Joint Shear Check/Design

Joint Shear Shear Shear Shear Joint Shear


Force V u,Top V u,Tot ϕV c Area Ratio
kN kN kN kN mm² Unitless
Major Shear, V u2 N/A N/A N/A N/A N/A N/A
Minor Shear, V u3 N/A N/A N/A N/A N/A N/A

(6/5) Beam/Column Capacity Ratio

Major Ratio Minor Ratio


N/A N/A

Notes:

N/A: Not Applicable

N/C: Not Calculated

N/N: Not Needed

Substation.EDB Page 2 of 2 05/03/2023


GAP ENGINEERING CONSULTANT

FOOTINGS DESIGN

Page 95
MAXIMUM STRESS =189 KN/M2
<220 KN/M2 SAFE
PUUNCHING
SAFE
5T16 = 1005 MM2
COVERS THE
REQUIRED AS.
2T10@150 = 1046
MM2/M' COVERS
THE REQUIRED
STIRRUPSE
T14@150/M' = 1026 COVERS
ALL REQUIRED BOTTOM RFT.
T14@150/M' = 1026 COVERS
ALL REQUIRED BOTTOM RFT.
T12@150/M' = 752 COVERS
ALL REQUIRED TOP RFT.
T12@150/M' = 752 COVERS
ALL REQUIRED TOPRFT.
GAP ENGINEERING CONSULTANT

SLAB ON GRADE
SLAB 200 MM DESIGN FOR UNIFORM
LOAD 15 KN/M2
MAXIMUM SERVICE MOMENT = 2.5 KN.M/M'
Slab design as Uncracked
fr = 0.33 (35)^0.5 = 1.952 N/mm2
I gross = 1000 x 200 x 200 x 200 /12 = 666.66x10^6
mm4
Mcr = fr x Igross / 0.5H
Mcr = 13.01 kn.m
F.O.S.=2
M11=2.5 < Mcr/2 = 6.5
Slab thickness is sufficient without RFT.
MINIMUMSHRINKAGE RFT = 1000X200X0.003/2=300
MM2/M'
USE = 5T10/M' = 392.5 MM2/M'
MAXIMUM SERVICE MOMENT = 2.5 KN.M/M'
Slab design as Uncracked
fr = 0.33 (35)^0.5 = 1.952 N/mm2
I gross = 1000 x 200 x 200 x 200 /12 = 666.66x10^6
mm4
Mcr = fr x Igross / 0.5H
Mcr = 13.01 kn.m
F.O.S.=2
M22=2.7 < Mcr/2 = 6.5
Slab thickness is sufficient without RFT.
MINIMUMSHRINKAGE RFT = 1000X200X0.003/2=300
MM2/M'
USE = 5T10/M' = 392.5 MM2/M'
GAP ENGINEERING CONSULTANT

TRANSFORMER FOOTING
AS PER SUPPLIER DATA
TRANSFORMER WEIGHT = 6300 KG
WIDTH=2.00M
LENGTH=2.85M
HEIGHT=3.00 M

MINIMUM FIXATION
POINTS LOAD
INCLUDING IMPACT
FACTOR
=63X1.5/4 = 23.6 KN
MAXIMUM BEARING STRESS 22 KN/M2
PUNCHING CHECK
MINIMUM ON BASE PLATE 100X100 MM
PUNCHING IS SAFE
FLEXURAL CAPACITY FOR MESH 6.66T12/M'
SPACING 150 MM = 107 KN.M./M'
MAXIMUM M22 < FLEXURAL CAPACITY

MINIMUM SHRINKAGE RFT.ADDED TO THE FOOTING =


0.0018X1000X400 =720 MM2/M'
USE 6.66T12/M' SPACING 150 MM = 6.66X1113 =752 MM2/M'
MAXIMUM M11 < FLEXURAL CAPACITY

MINIMUM SHRINKAGE RFT.ADDED TO THE FOOTING =


0.0018X1000X400 =720 MM2/M'
USE 6.66T12/M' SPACING 150 MM = 6.66X1113 =752 MM2/M'
GAP ENGINEERING CONSULTANT

GENERATOR FOOTING
FROM DATA PROVIDED FROM SUPPLIER
GENERATOR WEIGHT = 1300 KG
W=1.00 M
L=1.90 M
H=1.50 M
EQUIPMENT LOAD INCLUDING
IMPACT LOAD = 13X1.5/4 =5
BEARING STRESS UNDER FOOTING = 17
KN/M2 < 100 SAFE
PUNCHING IS SAFE
MINIMUM BASE PLATE THICKNESS =
100X100MM
MOMENTS IS VERY SMALL
MINIMUM SHRINKAGE WILL BE ADOPTED 0.0018X1000X500=900 MM2/M'
USE 6.66T14 /M' = 1026 MM2/M' SPACING = 150 MM
MOMENTS IS VERY SMALL
MINIMUM SHRINKAGE WILL BE ADOPTED 0.0018X1000X500=900 MM2/M'
USE 6.66T14 /M' = 1026 MM2/M' SPACING = 150 MM
GAP ENGINEERING CONSULTANT

TRENCH DESIGN
MAXIMUM ELECTRICAL
EQUIPMENT LOAD FROM
= 4450 KG
ALONG LENGHT = 1.50 M
W=44.5/1.5/2
maximum stress on
soil = 50 kn/m2 <
100 kn/m2 safe
MAXIMUM ULTIMATE MOMENT= 8 KN.M/M
FLEXURAL CAPACITY OF WALL 150 MM
T10@ 150 = 14 KN.M. > 8KN.M SAFE

T10@150 = 523
MM2/M'
FLEXURAL CAPACITY OF FOOTING 200 MM
T10@ 150 = 24 KN.M. > 8 KN.M SAFE
LONGITUDINAL DIRECTION
MOEMENT IS VERY SMALL AMOUNT
MINIMUM SHRINKAGE RFT. WILL BE
ADDED
=1000X200X0.0018=360 MM2
USE 5T10/M' T&B = 392MM2
SUFFICEIENT
Reference Drawings
NOTE :

REFERENCE DRAWINGS :

DWG. NO. TITLE

- -

LEGENDS:

Correct the
Submit Grade beam Layout information
sheet

LICENSE #:2005 TEL.#: 8334733 FAX #: 8335877 P.O.BOX:5322, AL-DAMMAM 31422

OWNER:

Contractor shall confirm PROJECT :

the location and


dimension of genset DRAWING TITLE:

pad foundation with


respect to electrical SCALE: REVISION NO: DATE:

requirement
PROJECT NO: DRAWING NO: SHEET NO:
NOTE :

NOTE :

REFERENCE DRAWINGS :

DWG. NO. TITLE

- -

LEGENDS:

Correct the
information
sheet

LICENSE #:2005 TEL.#: 8334733 FAX #: 8335877 P.O.BOX:5322, AL-DAMMAM 31422

OWNER:

PROJECT :

DRAWING TITLE:

SCALE: REVISION NO: DATE:

PROJECT NO: DRAWING NO: SHEET NO:


NOTE :

REFERENCE DRAWINGS :

DWG. NO. TITLE

Correct the section with proper LEGENDS:


- -

dimesions of cable trench and include


footing section

The Section shall


be with footings

NOTE: FOR SOIL UNDER SLAB & FOUNDATION, FDT SHALL


NOTE: FOR SOIL UNDER SLAB & FOUNDATION, FDT SHALL BE CONDUCTED WITH MINIMUM OF 95% MDD &
BE CONDUCTED WITH MINIMUM OF 95% MDD & ANTI-TERMITE APPLICATION SHALL BE MADE
ANTI-TERMITE APPLICATION SHALL BE MADE IMMEDIATELY AFTER DRYING THE SURFACE, 1000 GAUGE
IMMEDIATELY AFTER DRYING THE SURFACE, 1000 GAUGE (250 MICRONS) POLYETHYLENE SHEET SHOULD BE
NOTE: FOR SOIL UNDER SLAB & FOUNDATION, FDT SHALL (250 MICRONS) POLYETHYLENE SHEET SHOULD BE
BE CONDUCTED WITH MINIMUM OF 95% MDD & INSTALLED PRIOR TO POURING THE LEAN CONCRETE.
INSTALLED PRIOR TO POURING THE LEAN CONCRETE.
ANTI-TERMITE APPLICATION SHALL BE MADE
IMMEDIATELY AFTER DRYING THE SURFACE, 1000 GAUGE
(250 MICRONS) POLYETHYLENE SHEET SHOULD BE
INSTALLED PRIOR TO POURING THE LEAN CONCRETE.
Correct the
information
sheet

LICENSE #:2005 TEL.#: 8334733 FAX #: 8335877 P.O.BOX:5322, AL-DAMMAM 31422


NOTE: FOR SOIL UNDER SLAB & FOUNDATION, FDT SHALL
BE CONDUCTED WITH MINIMUM OF 95% MDD & OWNER:
ANTI-TERMITE APPLICATION SHALL BE MADE
NOTE: FOR SOIL UNDER SLAB & FOUNDATION, FDT SHALL
IMMEDIATELY AFTER DRYING THE SURFACE, 1000 GAUGE
BE CONDUCTED WITH MINIMUM OF 95% MDD &
(250 MICRONS) POLYETHYLENE SHEET SHOULD BE
ANTI-TERMITE APPLICATION SHALL BE MADE
INSTALLED PRIOR TO POURING THE LEAN CONCRETE.
IMMEDIATELY AFTER DRYING THE SURFACE, 1000 GAUGE
(250 MICRONS) POLYETHYLENE SHEET SHOULD BE
INSTALLED PRIOR TO POURING THE LEAN CONCRETE.

PROJECT :

DRAWING TITLE:

SCALE: REVISION NO: DATE:

PROJECT NO: DRAWING NO: SHEET NO: