NO.CNEEC-NEPRI-REPORT-BOILER-01-04 Date: 13 - Oct – 2011
Subsystem: Auxiliary boiler system Start Time: 09 - Oct – 2011 8:30 Finish Time: 09 - Oct – 2011 16:30 Work Item: Interlock and protection test NO. Check Items Check Results Ⅰ Boiler fan 1 Permissible conditions for start ⑴ Change over to remote location Yes □ No □ ⑵ No boiler fire off signal Yes □ No □ ⑶ No blower electrical fault signal Yes □ No □ 2 Start/stop control operation A Start remote Yes □ No □ B Stop remote Yes □ No □ 3 Signal alarm and interlocking alarm ⑴ Boiler fire off action, delay 600S interlock blower trip Yes □ No □ ⑵ Local emergency button test Yes □ No □ II Feed water pump of boiler 1 Permissible conditions for start ⑴ Change over to remote location Yes □ No □ ⑵ No blower electrical fault signal Yes □ No □ 2 Start/stop control operation A Start Yes □ No □ B Stop Yes □ No □ 3 Signal alarm and interlocking alarm Yes □ No □ ⑴ Local emergency button test Yes □ No □ III Oil supply pump of boiler 1 Permissible conditions for start ⑴ No daily oil tank level low signal Yes □ No □ ⑵ No pump electrical fault signal Yes □ No □ 2 Start/stop control operation A Start remote Yes □ No □ B Stop remote Yes □ No □ 3 Signal alarm and interlocking alarm ⑴ Daily oil tank level extreme low, interlock pump trip Yes □ No □ ⑵ Local emergency button test Yes □ No □ IV Main protection test of start-up boiler Yes □ No □ 1 Boiler ignition fail, boiler trip Yes □ No □ 2 Motor overload protection, boiler trip Yes □ No □ 3 Air duct pressure low, boiler trip Yes □ No □ 4 Boiler drum level extreme low, boiler trip Yes □ No □ 5 Main steam pressure extreme high, boiler trip Yes □ No □ 6 Both two feed water pump trip, boiler trip Yes □ No □ 7 Oil incoming pressure low, boiler trip Yes □ No □ 8 Back oil pressure high, boiler trip Yes □ No □ 9 Boiler furnace pressure high, boiler trip Yes □ No □ 10 Boiler outlet gas temperature high alarm Yes □ No □