Walkdown comments of 14BAY01(Protection Panel For GT-14)
RFI No. 19K9-SCT-RFI-E10-0201 4/18/2024
Package. 14BAY01(Protection Panel For GT-14) Desc. Location GT-14 Electrical Building S. No. Comment Description Category Remarks Spare control cables heat shrinkable sleeves to be provided inside the Protection /Marshalling 1 panel. C 2 Cable dressing inside the Trunks to be provided. C 3 13BBA01-0222C Cables ferrules to be changed ( as written site modification required ) after C confirmation from Engineering team. 4 GT-14 Marshalling panel permanent KKS to be provided. C 5 GT-14 Marshalling panel missing panel bolts to be provided. C 6 14BAY01-0001C cable to be terminated as per latest Rev-3 interconnection schdule. C 7 General cleaning inside the Marshalling Panel work to be completed . C 8 Marshalling panel touch up paint . C 9 Spare conduit in the GCB side to be extended upto the the GCB with outdoor rated sealant. C 10 Inside the Mrashalling Panel general cable dressing work to be completed . C 11 Inside the Generator protection panel FOC Patch cords cables tags to be provided . C 12 Inside the Marshalling Panel/Protection panels some of the control cables ferrules are C oversized ,need to be replaced as per cable size. 13 Cable route of the tray numbering is not matching with the schdule (actual ) on the site. C Missing RFI to be attached of the system boundary and need to be confirmed cables are B 14 terminated as per latest interconnection drawing .