Relay Test Report

11/20/2021
PAGE 1

Nameplate Data
MANUFACTURER: Siemens MODEL: 7UT63 TEST STATUS: Pass
ASSET ID: B2+RP09 SERIAL NUMBER: DATASHEET:
SUBSTATION 500kV New Lahore (South) PT RATIO: kV : V Counter Clockwise Rotation 0-360 Lead
LZOP: A JOB #: PTW # 919
PROTECTION: Differential Prot. Set I RELAY FIRMWARE:

Differential Settings Sat Nov 20 10:52:06 2021

Pickup 0.2 pu Current Tolerance 12 % Slope From X Axis


Trip Time 20 ms Trip Time Tolerance 10 % +50 ms Ibias Equation
Prefault Level 50 % Simulate Breaker NO Unrestrained Pickup 10 pu
Prefault Time 800 ms Use Reference Voltage NO Slope Ibias(pu) Gradient (%)
Off Delay 0 ms 1 0 30
Through Fault Current 100 % Ib Harmonic Tolerance 15 % 2 2.5 60
2nd Harmonic Content 15 % Harmonic Ramp Mode Ramp To Operate
Fault Duration 500 ms Nth Harmonic Content 30 % 5th
*A vertical offset is created between slopes
ICT Correction NO Nominal Current Protected Object when two equivalent restraint values are entered.
The Gradient % of the first equivalent point will be
the value of the vertical offset in per unit.

525 kV 231 kV
750 MVA
3,000 :1 A 2,400 :1 A

0 824.786 A 1,874.51 A
YY0
0.275 A 0.781 A
Single Phase Single Phase
Pickup Factor Interposing CTs 1.50 Pickup Factor
1.50

Stabilization Test Sat Nov 20 11:03:23 2021

Injected Currents Currents Observed From Relay


Phase

W1 W2 W1 W2
Ibias Idiff
I (A) ϕ (°) I (A) ϕ (°) I (A) ϕ (°) I (A) ϕ (°)
0.275 0 0.781 180
A-N 823.00 0 1,870.0 180 2.02 0
824.78 0 1,874.5 180
0.275 240 0.781 60
B-N 829.00 240 1,870.0 60 1.98 0
824.78 240 1,874.5 60
0.275 120 0.781 300
C-A 823.00 120 1,870.0 300 2.02 0.01
824.78 120 1,874.5 300

Timing Test Sat Nov 20 11:13:09 2021

TEST EQUIPMENT USED: FREJA546 (SN201906070004) TESTED BY:

COPYRIGHT © 2002-2021 POWERDB, INC. www.powerdb.com Form Schema 0


Relay Test Report
11/20/2021
PAGE 2

Phase Fault Current Expected Maximum Measured P/F


Tested (% Ib) Trip Time (s) Trip Time (s) Trip Time (s)

A-N 100.0 0.020 0.072 0.029 P

B-N 100.0 0.020 0.072 0.032 P

C-N 100.0 0.020 0.072 0.028 P

ABC 100.0 0.020 0.072 0.029 P

Pickup Test Sat Nov 20 13:16:25 2021

Winding 1 Winding 2
Phase
Pickup Pickup
Pickup Pickup Error P/F Pickup Pickup Error P/F
Setting Setting
(pu) (A) (%) (pu) (A) (%)
(pu) (pu)

A-N 0.20 0.198 0.082 -1.0 P 0.20 0.192 0.225 -4.0 P

B-N 0.20 0.196 0.081 -2.0 P 0.20 0.192 0.225 -4.0 P

C-N 0.20 0.192 0.079 -4.0 P 0.20 0.194 0.227 -3.0 P

ABC 0.20 0.198 0.054 -1.0 P 0.20 0.194 0.152 -3.0 P

Characteristic Test Sat Nov 20 12:20:24 2021

Ibias Idiff W1 W2 Error P/F


# (pu) (pu) (A) (A) (%)

1 1.30 0.39 0.23 0.36 -1.0 P

2 1.90 0.57 0.34 0.52 -0.0 P

3 2.30 0.69 0.41 0.63 0.0 P

4 3.20 0.96 0.57 0.87 -0.0 P

5 3.70 1.10 0.66 1.02 -1.0 P

6 4.20 1.26 0.75 1.15 -0.3 P

7 0.40 0.19 0.08 0.08 -5.0 P

8 6.50 2.40 1.22 1.60 -0.0 P

9 7.40 2.91 1.42 1.75 -1.0 P

Characteristic Shot Test Sat Nov 20 12:23:47 2021

COPYRIGHT © 2002-2021 POWERDB, INC. www.powerdb.com Form Schema 0


Relay Test Report
11/20/2021
PAGE 3

Ibias Idiff W1 W2 P/F


# (pu) (pu) (A) (A)

1 3.10 1.30 0.60 0.70 P ...


2 4.40 1.20 0.77 1.25 P ...
3 5.90 2.40 1.14 1.37 P ...
4 6.20 2.00 1.13 1.64 P ...
5 6.90 3.10 1.37 1.48 P ...
6 7.50 2.80 1.42 1.84 P ...
7 2.20 0.50 0.37 0.66 P ...
8 1.50 0.70 0.30 0.31 P ...
Winding 1 Winding 2
2nd Harmonic
Pickup = 0.150A , Tolerance = 15%Block Test Pickup = 0.150A , Tolerance = 15%
Sat Nov 20 12:37:23 2021
Phase

Funda- 2nd 2nd Funda- 2nd 2nd


Error P/F Error P/F
mental Harmonic Harmonic mental Harmonic Harmonic
(%) (%)
I (A) I (A) I (%) I (A) I (A) I (%)

A-N 1.00 0.132 13.250 -11.7 P 1.00 0.140 14.050 -6.3 P

B-N 1.00 0.133 13.350 -11.0 P 1.00 0.139 13.950 -7.0 P

C-N 1.00 0.133 13.350 -11.0 P 1.00 0.141 14.150 -5.7 P

ABC 1.00 0.131 13.150 -12.3 P 1.00 0.132 13.250 -11.7 P

Nth Harmonic Shot Test


Winding 1 Winding 2
Fundamental Current = 1.000A Fundamental Current = 1.000A
Phase

5th 5th 5th 5th 5th 5th 5th 5th No


No
Harmonic Harmonic Operate Harmonic Harmonic Harmonic Harmonic Operate Harmonic Harmonic Operate
I (A) I (%) I (A) I (%) Operate I (A) I (%) I (A) I (%)

A-N 0.250 25.00 P 0.350 35.00 P 0.250 25.00 P 0.350 35.00 P

B-N 0.250 25.00 P 0.350 35.00 P 0.250 25.00 P 0.350 35.00 P

C-N 0.250 25.00 P 0.350 35.00 P 0.250 25.00 P 0.350 35.00 P

ABC 0.250 25.00 P 0.350 35.00 P 0.250 25.00 P 0.350 35.00 P

Harmonic Content for No Operation: 35 % Harmonic Content for Operation: 25 %

COPYRIGHT © 2002-2021 POWERDB, INC. www.powerdb.com Form Schema 0