Professional Documents
Culture Documents
Micom P642 Test Results
Micom P642 Test Results
11/20/2021
PAGE 1
Nameplate Data
MANUFACTURER: Alstom MODEL: P642 TEST STATUS: Pass
ASSET ID: B2+RP10 SERIAL NUMBER: DATASHEET:
SUBSTATION 500kV New Lahore (South) PT RATIO: kV : V Counter Clockwise Rotation 0-360 Lead
LZOP: A JOB #: PTW # 919
PROTECTION: Differential Prot. Set II RELAY FIRMWARE:
525 kV 231 kV
750 MVA
1,500 :1 A 2,400 :1 A
824.786 A 1,874.51 A
YY0
0.55 A 0.781 A
Single Phase Single Phase
Pickup Factor Interposing CTs 1.50 Pickup Factor
1.50
Stabilization Test
Injected Currents Currents Observed From Relay
Phase
W1 W2 W1 W2
Ibias Idiff
I (A) ϕ (°) I (A) ϕ (°) I (A) ϕ (°) I (A) ϕ (°)
0.550 0 0.781 180
A-N 827.10 0 1,889.0 179.9 1.006 0.00563
824.78 0 1,874.5 180
0.550 240 0.781 60
B-N 826.60 240.2 1,887.0 59.79 1.002 0.00229
824.78 240 1,874.5 60
0.550 120 0.781 300
C-A 826.30 120.1 1,883.0 300.05 1.005 0.0074
824.78 120 1,874.5 300
Winding 1 Winding 2
Phase
Pickup Pickup
Pickup Pickup Error P/F Pickup Pickup Error P/F
Setting Setting
(pu) (A) (%) (pu) (A) (%)
(pu) (pu)
Winding 1 Winding 2
Pickup = 0.150A , Tolerance = 15% Pickup = 0.150A , Tolerance = 15%
Phase