Relay Test Report

11/20/2021
PAGE 1

Nameplate Data
MANUFACTURER: Alstom MODEL: P642 TEST STATUS: Pass
ASSET ID: B2+RP10 SERIAL NUMBER: DATASHEET:
SUBSTATION 500kV New Lahore (South) PT RATIO: kV : V Counter Clockwise Rotation 0-360 Lead
LZOP: A JOB #: PTW # 919
PROTECTION: Differential Prot. Set II RELAY FIRMWARE:

Differential Settings Sat Nov 20 14:52:18 2021

Pickup 0.2 pu Current Tolerance 12 % Slope Through Origin


Trip Time 20 ms Trip Time Tolerance 10 % +50 ms Ibias Equation
Prefault Level 50 % Simulate Breaker NO Unrestrained Pickup 10 pu
Prefault Time 800 ms Use Reference Voltage NO Slope Ibias(pu) Gradient (%)
Off Delay 0 ms 1 0.667 30
Through Fault Current 100 % Ib Harmonic Tolerance 15 % 2 2 60
2nd Harmonic Content 15 % Harmonic Ramp Mode Ramp To Operate
Fault Duration 500 ms Nth Harmonic Content 35 % 5th
*A vertical offset is created between slopes
ICT Correction NO Nominal Current Protected Object when two equivalent restraint values are entered.
The Gradient % of the first equivalent point will be
the value of the vertical offset in per unit.

525 kV 231 kV
750 MVA
1,500 :1 A 2,400 :1 A

824.786 A 1,874.51 A
YY0
0.55 A 0.781 A
Single Phase Single Phase
Pickup Factor Interposing CTs 1.50 Pickup Factor
1.50

Stabilization Test
Injected Currents Currents Observed From Relay
Phase

W1 W2 W1 W2
Ibias Idiff
I (A) ϕ (°) I (A) ϕ (°) I (A) ϕ (°) I (A) ϕ (°)
0.550 0 0.781 180
A-N 827.10 0 1,889.0 179.9 1.006 0.00563
824.78 0 1,874.5 180
0.550 240 0.781 60
B-N 826.60 240.2 1,887.0 59.79 1.002 0.00229
824.78 240 1,874.5 60
0.550 120 0.781 300
C-A 826.30 120.1 1,883.0 300.05 1.005 0.0074
824.78 120 1,874.5 300

Timing Test Sat Nov 20 15:02:13 2021

TEST EQUIPMENT USED: FREJA546 (SN201906070004) TESTED BY:

COPYRIGHT © 2002-2021 POWERDB, INC. www.powerdb.com Form Schema 0, REVISED 1/29/2019


Relay Test Report
11/20/2021
PAGE 2

Phase Fault Current Expected Maximum Measured P/F


Tested (% Ib) Trip Time (s) Trip Time (s) Trip Time (s)

A-N 100.0 0.020 0.072 0.027 P

B-N 100.0 0.020 0.072 0.030 P

C-N 100.0 0.020 0.072 0.030 P

ABC 100.0 0.020 0.072 0.030 P

Pickup Test Sat Nov 20 15:03:29 2021

Winding 1 Winding 2
Phase
Pickup Pickup
Pickup Pickup Error P/F Pickup Pickup Error P/F
Setting Setting
(pu) (A) (%) (pu) (A) (%)
(pu) (pu)

A-N 0.20 0.200 0.165 0.0 P 0.20 0.192 0.225 -4.0 P

B-N 0.20 0.198 0.163 -1.0 P 0.20 0.192 0.225 -4.0 P

C-N 0.20 0.198 0.163 -1.0 P 0.20 0.194 0.227 -3.0 P

ABC 0.20 0.196 0.108 -2.0 P 0.20 0.194 0.152 -3.0 P

Characteristic Test Sat Nov 20 16:33:24 2021

Ibias Idiff W1 W2 Error P/F


# (pu) (pu) (A) (A) (%)

1 0.40 0.20 0.27 0.23 0.0 P

2 1.10 0.33 0.69 0.73 -1.0 P

3 1.40 0.42 0.89 0.93 0.0 P

4 3.40 1.44 2.27 2.09 0.0 P

5 5.90 2.94 4.05 3.46 0.0 P

2nd Harmonic Block Test Sat Nov 20 16:48:42 2021

COPYRIGHT © 2002-2021 POWERDB, INC. www.powerdb.com Form Schema 0, REVISED 1/29/2019


Relay Test Report
11/20/2021
PAGE 3

Winding 1 Winding 2
Pickup = 0.150A , Tolerance = 15% Pickup = 0.150A , Tolerance = 15%
Phase

Funda- 2nd 2nd Funda- 2nd 2nd


Error P/F Error P/F
mental Harmonic Harmonic mental Harmonic Harmonic
(%) (%)
I (A) I (A) I (%) I (A) I (A) I (%)

A-N 1.00 0.146 14.650 -2.3 P 1.00 0.147 14.750 -1.7 P

B-N 1.00 0.145 14.550 -3.0 P 1.00 0.148 14.850 -1.0 P

C-N 1.00 0.145 14.550 -3.0 P 1.00 0.149 14.950 -0.3 P

ABC 1.00 0.144 14.450 -3.7 P 1.00 0.145 14.550 -3.0 P

Nth Harmonic Shot Test


Winding 1 Winding 2
Fundamental Current = 1.000A Fundamental Current = 1.000A
Phase

5th 5th 5th 5th 5th 5th 5th 5th No


No
Harmonic Harmonic Operate Harmonic Harmonic Harmonic Harmonic Operate Harmonic Harmonic Operate
I (A) I (%) I (A) I (%) Operate I (A) I (%) I (A) I (%)

A-N 0.300 30.00 P 0.400 40.00 P 0.300 30.00 P 0.400 40.00 P

B-N 0.300 30.00 P 0.400 40.00 P 0.300 30.00 P 0.400 40.00 P

C-N 0.300 30.00 P 0.400 40.00 P 0.300 30.00 P 0.400 40.00 P

ABC 0.300 30.00 P 0.400 40.00 P 0.300 30.00 P 0.400 40.00 P

Harmonic Content for No Operation: 40 % Harmonic Content for Operation: 30 %

Characteristic Shot Test Sat Nov 20 16:37:04 2021

Ibias Idiff W1 W2 P/F


# (pu) (pu) (A) (A)

1 1.30 0.30 0.80 0.90 P ...


2 1.20 0.60 0.82 0.70 P ...
3 1.80 0.50 1.13 1.21 P ...
4 1.70 0.70 1.13 1.05 P ...
5 2.70 0.90 1.73 1.76 P ...
6 2.60 1.20 1.76 1.56 P ...
7 3.50 1.40 2.31 2.19 P ...
8 3.30 1.70 2.28 1.91 P ...
9 4.50 2.00 3.02 2.73 P ...
10 4.20 2.30 2.94 2.38 P ...

COPYRIGHT © 2002-2021 POWERDB, INC. www.powerdb.com Form Schema 0, REVISED 1/29/2019