PRESSURE TEST AND FLUSING TEST CERTIFICATE

CLIENT NAME : AL MAJED

P.O. BOX : 583

PHONE : 4447 8888 FAX : 4447 7700

PROJECT LOCATION : HUBLOT @ LAGOONA MALL JOB CARD NO: AFSQ 394

SYSTEM : SPRINKLER SYSTEM Date: 24/07/2016

Operation Electric Hydraulics Pneumatic

DELUGE AND
Piping supervised YES NO Detecting Media Supervised YES NO
PRE ACTION
Does valve operate from the manual trip remote or both control stations YES NO
VALVES
Is there any accessible facility in each circuit for testing If no please explain

YES NO

MAKE MODEL Does each circuit operate Does each circuit operate Maximum time to operate release
supervision loss alarm? valve release

YES NO YES NO YES NO

PRESSURE Location and Make and Setting Static Pressure Residual Pressure Flow Rate
REDUCING floor model
VALVE TEST
Inlet psi Outlet psi Inlet psi Outlet psi Flow gpm

Backflow device Indicate means used for forward flow test of backward flow
forward flow test
When means to test device was opened was system flow demand created YES NO

Hydrostatic: Hydrostatic test shall be made at not less than 200 psi ( 13.6 bars ) fro 2 hours or 50 psi ( 3.4 bar ) above static
pressure in excess of 150 psi ( 10.2 bar) for 2 hours. Differential dry pipe valve clappers shall be left open during the test to
prevent damage. All aboveground piping leakage shall be stopped.
Test
Description Pneumatic: Establish 40 psi ( 2.7 bar) air pressure and measure drop, which shall not exceed 1 ½ psi (0.1 bar) in 24 hours. Test
pressure tanks at normal water level and air pressure and measure air pressure drop which shall not exceed 1 ½ psi in 24 hrs.

All piping hydrostatically tested at 174 psi 12 .bar for 12 Hours

Dry piping pneumatically tested YES NO

Equipment operates properly YES NO

Pressure test/ AFSQ/ 3-14


Do you certify as the sprinkler contractor that additives and corrosive chemicals, sodium silicate or derivatives of sodium silicate,
brine or other corrosive chemicals were not used for testing systems or stopping leaks

TEST YES  NO

`Drain Test Reading of gauge located near water supply Residual pressure with valve in test connection open wide
test connection ……………..psi ( …………bar ) ………..psi (………bar )

Verified by copy of the Contractors Material and Test YES NO OTHER EXPLAIN

Certificate for Underground piping

Flushed by installer of underground sprinkler piping YES NO

If powder driven fasteners are used in concrete has representative sample If No explain

test been satisfactorily completed YES NO

New Fire Fighting Pioes were flushed according to NFPA standards

YES  NO

How Flushing was obtained Through what type of opening


FLUSHING
TEST Public water Tank or Reservoir Hydrant Butt Open Pipe 

Fire Pump 

Do you certify as the sprinkler contractor that welding procedures used complied with minimum requirements of
AWS B2 1.2.1. ASME Section IX Welding and brassing, qualifications, or other applicable qualifications standard as
required by AHJ . YES NO

Do you certify that all welding was performed by welders or welding operators qualified in accordance with a
minimum requirement of AWS B2 ASME Section IX welding and brassing qualifications or other applicable
qualification standard as required by AHJ . YES NO
WELDING
Do you certify that the welding was conducted in compliance with a documented quality control procedure to
ensure that :

1. All discs are retrieved 2. That opening in the pipe are smooth, the slag and other welding residue are
removed 3. The internal diameters of piping are not penetrated 4. Completed welds are free from cracks,
incomplete fusion, surface porosity greater porosity greater than 1/32 inch dia undercut deeper than the
lesser of 25% of the wall thickness or 1/32 inch and 5. Completed circumferential butt weld
reinforcement does not exceed 3/32 inch YES NO

Do you certify that you have a control feature to ensure that all cut outs ( discs) are retrieved. YES NO
CUTOUTS( DISCS )

Hydraulic Data Nameplate provided If no explain :

nameplate YES NO

Pressure test/ AFSQ/ 3-14


Sprinkler contractor removed caps and all straps YES  NO
CAPS

Date left in service with all control valves open : 21/07/2016


REMARKS
NAME OF SPRINKLER CONTRACTOR : ALPHA FIRE SERVICES WLL

Client/ Client Representative Title …………………………………………………………………………………………………………………..


SIGNATURES

Name …………………………………………………………………………………………………………………

Signature ……………………………………………………………………………………………………………

Date …………………………………………………………………………………………………………………….

Title : ALPHA FIRE SERVICES WLL


SPRINKLER
CONTRACTOR
Name MANESH.K

Signature ……………………………………………………………………………………………………………….

Lic No ; 8080 Date; 24/07/2016

ADDITIONAL
EXPLANATIONS AND
REMARKS IF ANY

Pressure test/ AFSQ/ 3-14