METHOD STATEMENT

Method statement for Maintenance of Sprinkler System and Fire Extinguishers

DOCUMENT TITLE:

METHOD STATEMENT FOR MAINTENANCE OF SPRINKLER SYSTEM AND


FIRE EXTINGUISHERS

Rev. Issue Purpose/Description Prepared Reviewed Approved Company


of Revision
00 19/06/2016 Issued to Site Saurav. R Manesh.K Mithun.P AFS

TABLE OF CONTENTS

1. Health, Safety and Environment..............................................................................................................................3


2. Permit to work....................................................................................................................................................3

1
METHOD STATEMENT

Method statement for Maintenance of Sprinkler System and Fire Extinguishers

3. Methodology for Maintenance of Sprinkler System ...............................................................................................4


4. Methodology for Maintenance of ZCV Assembly ................................................................................................7
5. Methodology for Maintenance of Fire Hose Reel ........................................................................8
6. Methodology for Maintenance of Fire Extinguishers..............................................................................................9
7. Check List for Maintenance of Sprinkler System and Fire Extinguishers .........................................................11

1. HEALTH , SAFETY AND ENVIRONMENT

1) The work area must be cleaned before the starting of the procedures.
2
METHOD STATEMENT

Method statement for Maintenance of Sprinkler System and Fire Extinguishers

2) All personnel will be equipped with the necessary Personal Protective Equipment (PPE) (Safety
Helmet, Safety Shoes, Safety Gloves, Cover-all, etc…).
3) Ensure service shaft opening are provided with barricade, tape and safety nets.
4) The joint cooperation of personnel and management shall provide clean working conditions and
environmentally hazard-free work place.
5) Ensure adequate lighting is provided in the working area at all time.
6) Ensure safe installation, location and use of every scaffolding and ladders.
7) Provide good ventilation when working in rooms without any air circulation.
8) This procedure covers maintenance of Sprinkler System and Fire Extinguishers

2. PERMIT TO WORK

All work that is to be performed on site should be accompanied by the permit to work issued by the
Client.

3. METHODOLOGY FOR MAINTENANCE OF SPRINKLER SYSTEM

1. Check the total quantity of Sprinklers.

2. Check the sprinkler condition

3
METHOD STATEMENT

Method statement for Maintenance of Sprinkler System and Fire Extinguishers

a. Is the sprinkler head dusty ?

If so clean the sprinkler with brush or cloth.

b. Is the sprinkler painted ?

If so clean the sprinkler with thinner and cloth. If still could not be rectified write in
job card , and mention the total quantity of sprinklers painted. Take photos of painted
sprinklers.

4
METHOD STATEMENT

Method statement for Maintenance of Sprinkler System and Fire Extinguishers

c. Is the sprinkler rusted ?

If so write in job card to replace the sprinklers, and mention the total quantity o sprinklers rusted. Take
photos of rusted sprinklers.

d. Is the sprinkler cover missing ?

If so write in job card to provide new sprinkler cover, and mention the total quantity. Take photos .

e. Is the sprinkler deflector obstructed/ deflector inside the ceiling ?

5
METHOD STATEMENT

Method statement for Maintenance of Sprinkler System and Fire Extinguishers

This is extremely dangerous situation as in case of fire emergency the sprinkler would not spray
water properly.

If so bring it to right level by adjusting the support. If not possible write in report with photos.

3. If there are rooms, cabins or store which has no sprinklers recommend for the same
in the job card.

4. Check if there is a drain line in the end of sprinkler line for flushing the system.
Recommend if not available.

6
METHOD STATEMENT

Method statement for Maintenance of Sprinkler System and Fire Extinguishers

4. METHODOLOGY FOR MAINTENANCE OF ZONE CONTROL VALVE


ASSEMBLY

1. Check if the location is labelled in the false ceiling.If not write in report so it can be done next
time.

2. Check if all components of ZCV assembly are present (Butterfly valve, Suitable pressure
gauge, Flow Switch, Test & Drain Valve).

Butterfly valve has to be first component.

Pressure gauge can be anywhere after the butterfly valve.

Flow switch should be before the test and drain line.

Recommend if any of this is not satisfied or if any of the components are missing.

3. Close butterfly valve and make sure supervisory signal is shown in panel.

4. Coordinate with the maintenance team and check if flow switch is connected to the system
and is giving alarm.

5. Note the pressure of the system from the pressure gauge of ZCV assembly and write in job
card with appropriate unit (PSI /Bar).

If the system has only sprinklers, pressure should not exceed 12 bar / 175PSI. If the pressure
exceeds the limit recommend Pressure reducing valve after the ZCV.

7
METHOD STATEMENT

Method statement for Maintenance of Sprinkler System and Fire Extinguishers

If the system has hose reels check if it is from the same delivery line as sprinklers, if so recommend a
PRV near each hose reel , If it is separate line for hose reels and sprinkler recommend one PRV for the
hose reel system.

5. METHODOLOGY FOR MAINTENANCE OF FIRE HOSE REEL

1. Clean the hose reel cabinet and hose reel if required.

2. If the hose reel or hose reel cabinet is damaged, mention in the job card with photos.

3. Make sure the gate valve is open for all the hose reels.

4. Open and check the flow and pressure of the hose reels.

5. Make sure all the hose reels are in easily accessible area and is not obstructed.

6. Check if the hose reels require a 1” PRV and recommend if the system requires the same.

8
METHOD STATEMENT

Method statement for Maintenance of Sprinkler System and Fire Extinguishers

6. METHODOLOGY FOR MAINTENANCE OF FIRE EXTINGUISHERS

1.Dry Powder Fire Extinguisher.

a. Check the pressure on the cylinder.


If the needle is below the green area the cylinder has low pressure and if the needle is
beyond the green area the cylinder is over pressurized, in both the cases it has to be
serviced. Write in job card the weight and type of the cylinders with the total quantity for
the same.

b. Check the chemical inside the cylinder.


Hold the cylinder by the nozzle and the bottom and turn upside down and upright again,
during which the chemical has to move freely inside the cylinder. If it is not then the
chemical inside the cylinder has dried up, try tapping the cylinder gently with a hammer
and see if the chemical can be loosened. Even after that if you are not able to feel the
chemical while turning the cylinder upside down and upright, write in job card the type
and weight of the cylinder with the total quantity for the same.

c. The date on the cylinder has to be checked if the date of last service is beyond one year,
write in job card the type and weight of the cylinder with the total quantity for the same.

d. The cylinder head requires a nozzle, pin, and the seal on the head; if not available on the
cylinder then write in job card the quantity of the cylinder with the same.

e. Make sure that the extinguisher is mounted on the wall and is in easily accessible areas at
appropriate distance. Mention in job card if any fire extinguishers require mounting
brackets.

2. Carbon dioxide (CO2) Fire Extinguisher

9
METHOD STATEMENT

Method statement for Maintenance of Sprinkler System and Fire Extinguishers

a. Check the top of the cylinder if it has a nozzle, seal and pin. If any of this is missing
write the same in the job card with the total quantity of the same.

b. If the cylinder has passed 5 years from the manufacturing date recommended for hydro
testing. This has to be done every 5 years. Write in job card with the quantity of the
same so the same with the total quantity.

c. Check the weight of the cylinder using a weighing scale and see it matches with what
is written on the cylinder, if not write in job card with the total quantity.

CHECK LIST FOR MAINTENANCE OF SPRINKLERS & FIRE EXTINGUISHERS

Sprinkler System

1. Total number of sprinklers : _____ nos


2. Total number of painted sprinkles to be replaced : _____ nos
3. Total number of rusted sprinkler to be replaced : _____ nos

10
METHOD STATEMENT

Method statement for Maintenance of Sprinkler System and Fire Extinguishers

4. Total number of sprinkler caps to be provided : _____ nos


5. Total number of sprinklers to be brought to the ceiling level : _____ nos

Notes:

______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________

Hose reel System

1. Total number of hose reels : _____ nos


2. Total number of damaged cabinets : _____ nos
3. Total number of damaged hose : _____ nos
4. Total number of hose reels which are obstructed : _____ nos
5. Make and type of the Hose reel : _______________

Notes:

_____________________________________________________________________

_____________________________________________________________________

_____________________________________________________________________

_____________________________________________________________________

_____________________________________________________________________

_____________________________________________________________________

Zone Control Valve:

1. Butterfly valve is interfaced with fire alarm panel : ______


2. Pressure in the system with unit : ______

Notes:

_____________________________________________________________________

_____________________________________________________________________

11
METHOD STATEMENT

Method statement for Maintenance of Sprinkler System and Fire Extinguishers

_____________________________________________________________________

_____________________________________________________________________

_____________________________________________________________________

_____________________________________________________________________

Extinguisher

1. Dry powder Fire Extinguisher

a. Total number of ___kg dry powder cylinders :


______ nos

No of cylinders with undesirable pressure : ______ nos

No of cylinders with dried chemical : ______ nos

No of cylinders with missing pins : ______ nos

12
METHOD STATEMENT

Method statement for Maintenance of Sprinkler System and Fire Extinguishers

No of cylinders with missing seal : ______ nos

No of cylinder which require nozzle : ______ nos

No of cylinders with expired dates : ______ nos

No of brackets required to mount the extinguishers : ______ nos

b. Total number of ___kg dry powder cylinders : ______ nos

No of cylinders with undesirable pressure : ______ nos

No of cylinders with dried chemical : ______ nos

No of cylinders with missing pins : ______ nos

No of cylinders with missing seal : ______ nos

No of cylinder which require nozzle : ______ nos

No of cylinders with expired dates : ______ nos

No of brackets required to mount the extinguishers : ______ nos

c. Total number of ___kg dry powder cylinders : ______ nos

No of cylinders with undesirable pressure : ______ nos

No of cylinders with dried chemical : ______ nos

No of cylinders with missing pins : ______ nos

No of cylinders with missing seal : ______ nos

No of cylinder which require nozzle : ______ nos

No of cylinders with expired dates : ______ nos

No of brackets required to mount the extinguishers : ______ nos

2. CO2 Fire Extinguisher

a. Total number of ___ kg CO2 cylinders : ______ nos

No of cylinders with weight difference : ______ nos

No of cylinders with missing pins : ______ nos

No of cylinders with missing seal : ______ nos

No of cylinder which require nozzle : ______ nos

No of cylinders with expired dates : ______ nos

13
METHOD STATEMENT

Method statement for Maintenance of Sprinkler System and Fire Extinguishers

No of brackets required to mount the extinguishers : ______ nos

No of cylinders which require hydro testing (5years after MFD):______ nos

b. Total number of ___ kg CO2 cylinders : ______ nos

No of cylinders with weight difference : ______ nos

No of cylinders with missing pins : ______ nos

No of cylinders with missing seal : ______ nos

No of cylinder which require nozzle : ______ nos

No of cylinders with expired dates : ______ nos

No of brackets required to mount the extinguishers : ______ nos

No of cylinders which require hydro testing(5years afterMFD):______ nos

c. Total number of ___ kg CO2 cylinders : ______ nos

No of cylinders with weight difference : ______ nos

No of cylinders with missing pins : ______ nos

No of cylinders with missing seal : ______ nos

No of cylinder which require nozzle : ______ nos

No of cylinders with expired dates : ______ nos

No of brackets required to mount the extinguishers : ______ nos

No of cylinders which require hydro testing(5years afterMFD):______ nos