Professional Documents
Culture Documents
Evonik cal July 2022
Evonik cal July 2022
AS FOUND AS LEFT
Description Std. Flow Measured Instrument Instrument Error Std. Flow Measured Instrument Instrument Error Due
Date of work performed. Notes CuFt/Sec Height Flow Height CuFt/Sec CuFt/Sec Height Flow Height CuFt/Sec Date
7/28/2022 Calibration TTL=895326 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Unit in excellent shape -No adjustment
0.494 6.250 0.450 6.300 -0.044 0.494 6.250 0.450 6.100 -0.044
necessary Jul-2023
The equation recommended by the Bureau of Reclamation in their Water Measurement Manual,for use with a fully contracted, 90 o, v notch, sharp crested weir with free flow conditions and 0.2 ft < H < 1.25 ft, is:
Q = 2.49 x h2.48
AS FOUND AS LEFT
Description Std. Flow Measured Instrument Instrument Error Std. Flow Measured Instrument InstrumenError Due
Date of work performed. Notes CuFt/Sec Height Flow Height CuFt/Sec CuFt/Sec Height Flow Height CuFt/Sec Date
7/28/2022 Calibration TTL=55267882 No flow at time of calibration. 0.000 0.000 0.007 0.150 0.007 0.000 0.000 0.001 0.050 0.001
2.350 6.000 2.390 6.130 0.040 2.350 6.000 2.353 6.030 0.003
Jul-2023
Small -.1 adjustment necessary / Paper was out at calibration
The equation recommended by the Bureau of Reclamation in their Water Measurement Manual,for use with a fully suppressed rectangular weir with free flow conditions is:
Q = 3.33 x L x h3/2
NOTES:
Calibration performed by confirming levels with indicated levels using standard measurement equipment.
Levels also simulated using steel plates with known distance to reference bottom.