Factory Acceptance Tests on Disconnector 1HYD900710-402

PGHV-DC (In Loose Conditions- On Transportable Units as per IEC) Revions: H


Released Date :07/03/2022

Following Routine Tests/checks to be carried out on the disconnector type SDF, eDB, eDBL & TnT with Motor Operating
Mechanism type MD50/ MD50G/MD100/MD120 & Hand Operating Mechanism drive of HD80.
For Hand drive HD80 the Mechanical operations tests 2.a, 2.b, & 2.c are not applicable

Sr. No. Test Description Outcomes References


1 Visual Checks
Paint Shade of Drive Box Found OK/Not found OK Approved Drawings
Rating Plate engraving details Found OK/Not found OK Approved Drawings
Dimensional checks Values Approved Drawings
2 Mechanical operations test on Disconnector
a. 5 Operations at 100 % of rated Motor Measure operations time, Time should be less than
and/or control Voltage No Load current 12 sec
b. 5 Operations at 85 % of rated Motor and/or Measure operations time, No load current for MD50
No Load current with supply voltage up to
control Voltage
Measure operations time, 250 V shall be less than
c. 5 Operations at 110 % of rated Motor No Load current, 1A
and/or control Voltage Satisfactory / Not satisfactory
d. 5 Manual Operations
3 Function of Auxiliary Switch Should be as per functional Approved Drawings
Verification of NO, NC, MBB contacts diagram
4 Functioning of Blocking Magnet Satisfactory/ Not satisfactory
5 Operations at 85 % of Rated Voltage
5 Function of miscellaneous accessories
Heater Circuit For supply upto 250 V
Measure the Resistance of heater kΩ = _____________ should be 2.5k Ω
And for supply up
Illumination Lamp(As per approved ON/OFF Operation of Lamp to125V should be 0.55k
schematic drawing) Ω
3 Pin plug sockets (As per approved Check the output when switched
schematic drawing) on
Earthing connections Check for the proper earthing

6 Dielectric Tests on Auxiliary and Control Withstood/Failed


Circuits
Test to be carried out at 1kV for 1 sec.
(Motor and Hub magnet, Contactors Coils
shall be disconnected during the test)
7 Measurement of resistance of Value of resistance in μΩ
Main circuit Or in terms of mV.
Current shall be injected through the current
path and resistance shall be measured; the
current shall be 50Adc/100Adc/200Adc

Prepared By Mayank Bariya Sheet 1 of 1