SITE TEST REPORT

Customer: NGSA-WOA

Name of Substation: MADINAH EAST 110KV/33KV SUBSTAION Contract No. : 4400008122

ENERGY METER REPORT Page 1 of 4


Panel Name: AMI-2 Equip. No.: ENERGY METER Dwg. Ref.:

1. GENERAL INFORMATION:
METER No. RM3 Feeder Name AH48
Manufacturer Landis +Gyr Serial No. 51386221
Type E850 Class 0.2
Meter constant 100000 Rated Auxiliary Supply 100 – 240V AC/DC
CT Ratio 2000/1A VT Ratio 33000/120V

2. MECHANICAL CHECK AND VISUAL INSPECTION:

S.N Item Description Remarks


1. Inspect for any physical damage or defects. Ok
2 Tightness off all connection Ok
3 Digits & decimal checked Ok

3. ELECTRICAL TESTS:

3.1 FUNCTION TEST


S.N Description Remarks
1 Case Earthing checked. Ok
2 Indications/ Indications label checked. Ok
4 Test switch / plug checked for correct function. Ok
5 Test switch CT shorting Checked. Ok

3.2 CREEP TEST (5 min)

Injected voltage Injected current MWh-Imp MWh-Exp MVARh-Imp MVARh-Exp

83.16 V 0 0 0 0 0
Note: The meter must not deliver more than one pulse during the creep test.

Date :
Testing Engineer NGSA CSD Engineer
SEC ID : MAS-050
Signature: ________________ Signature: ________________
Name : ATTIQ UR REHMAN Name :
SITE TEST REPORT

Customer: NGSA-WOA

Name of Substation: MADINAH EAST 110KV/33KV SUBSTAION Contract No. : 4400008122

ENERGY METER REPORT Page 2 of 4


Panel Name: AMI-2 Equip. No.: ENERGY METER Dwg. Ref.:
3.3 MEASUREMENT TEST

3.3.1 Voltage test Limits: ± 0.2 %


PHASE Injected voltage V Expected (KV) Displayed (KV) Error %
R-N 69.28 19.05 19.06 0.05
Y-N 69.28 19.05 19.04 -0.05

B-N 69.28 19.05 19.04 -0.05

3.3.2 Current test Limits: ± 0.2


PHASE Injected current A Expected (A) Displayed (A) Error %
R-N 1 2000 1999 0.05
Y-N 1 2000 2000 0
B-N 1 2000 1999 0.05

Error % = ((Measured value - Expected value) *100) / Expected value

3.3.3 Active and Reactive power test


Limits: ± 0.2 %
Expected Expected
Injected Injected Measured Measured
Angle power ERROR power ERROR
voltage V current A MW MVAR
MW % MVAR %
69.3 0.25 0 28.57 28.5 0.24 0 0.01 0.01
69.3 0.25 45 20.20 20.0 0.99 20.20 20.3 0.49
69.3 0.5 90 0 0.01 0.01 57.17 57.1 -0.12
69.3 0.75 135 -60.62 -60.7 0.13 60.62 60.5 -0.19
69.3 1 180 -114.31 114.3 0.008 0 0 0
69.3 1 270 0 0.1 0.1 -114.31 -114.2 -0.09

For (- Minus) sign in some fields this means we have Received power instead of delivered.

MW= √3 *VL*I*COSƟ

MVAR= √3 *V*I*SINƟ

Error % = ((Measured value - Expected value ) *100) / Expected value

Date :
Testing Engineer NGSA CSD Engineer
SEC ID : MAS-050
Signature: ________________ Signature: ________________
Name : ATTIQ UR REHMAN Name :
SITE TEST REPORT

Customer: NGSA-WOA

Name of Substation: MADINAH EAST 110KV/33KV SUBSTAION Contract No. : 4400008122

ENERGY METER REPORT Page 3 of 4


Panel Name: AMI-2 Equip. No.: ENERGY METER Dwg. Ref.:
3.4 ENERGY TEST

Full load test (69.3 V – 1 A) (5 min) Limits: ± 0.2 %

MWH = √3 *V*I*COSƟ *(5/60) MVARH = √3 *V*I*SINƟ*(5/60)

Expected Energy
Angle
MWh-import MWh-export KVARh- import KVARh- export
30 8.2 --- 4.7 ---
150 --- -8.2 4.7 ---
210 --- -8.2 --- -4.7
-30 8.2 --- --- -4.7

Measured Energy
Angle
MWh- import MWh- export Expected Error %
30 8.2 --- 8.2 0
150 --- -8.2 -8.2 0
210 --- -8.2 -8.2 0
-30 8.2 --- 8.2 0

Measured Energy
Angle
MVARh- import MVARh- export Expected Error %
30 4.7 --- 4.7 0

150 4.7 --- 4.7 0

210 --- -4.7 -4.7 0

-30 --- -4.7 -4.7 0

Date :
Testing Engineer NGSA CSD Engineer
SEC ID : MAS-050
Signature: ________________ Signature: ________________
Name : ATTIQ UR REHMAN Name :
SITE TEST REPORT

Customer: NGSA-WOA

Name of Substation: MADINAH EAST 110KV/33KV SUBSTAION Contract No. : 4400008122

ENERGY METER REPORT Page 4 of 4


Panel Name: AMI-2 Equip. No.: ENERGY METER Dwg. Ref.:

3.5 MAXIMUM DEMAND TEST (69.28 V – 1 A) (5 min) Limits: ± 0.2 %

MAX. MW= √3 *V*I*COSƟ


Angle Expected Demand MW Measured Demand MW Error %

0 114.31 114.3 0.008

3.6 ACCURACY TEST

LED (I/Wh) pulse test (69.28 V – 1 A) for 1min Limits: ± 0.2 %

Angle 0°
Error % 0.08

LED (I/Varh) pulse test (69.28 V – 1 A) for 1min Limits: ± 0.2 %

Angle 90°
Error % 0.08

Error % = ((Measured value - Expected value) *100) / Expected value

4. TESTING EQUIPMENT USED

Item Test Equipment Serial Number Calibration due date


1 FREJA 300 1402724 10-April-2020
2 ZERA 050024548 27-OCT-2019
;;

Date :
Testing Engineer NGSA CSD Engineer
SEC ID : MAS-050
Signature: ________________ Signature: ________________
Name : ATTIQ UR REHMAN Name :