LT CABLE SIZING
LT CABLE SIZING
COVER SHEET
Mcnally Bharat
THIS DOCUMENT IS MBE’S PROPERTY AND MUST NOT BE USED
EXCEPT IN CONNECTION WITH MBE’S WORK. USE OR DISCLOSURE
OF THE CONTENTS OF THIS DOCUMENT TO THIRD PARTY/IES
Engineering Company Limited WITHOUT EXPRESS/WRITTEN PERMISSION OF MBE IS STRICTLY
PROJECTS DIVISION 4, Mangoe Lane, Kolkata, India PROHIBITED.
MBE REPLY
3. Formula used to calculate percentage voltage drop = [1.732 x Full load current x (Resistance x Cosø + Reactance x Sinø ) x Length of cable in Mtr x 100] / [Supply voltage in Volt]
4. Starting current has been considered as 7.2 times of the full load current while calculating voltage drop during starting.
5. Resistance and reactance values for cables have been taken as base temperature of 20 deg. C from Approved cable manufacturer catalogue.
Actual Resistance & reactance values have been considered at 90 deg. C for XLPE cable.
6. Resistance & reactance correction due to temperature variation shall be followed by the follwing formula
Rt = R x {1+ (temp variation x resistivity of the conductor)}
Xt = R x {1+ (temp variation x resistivity of the conductor)}
7. Permissive voltage drop during starting condition, limited to 15% & during running condition, limited to 3% of the rated voltage.
( Refer CL# 3.1.6 OF SECTION: D2.03, SHT 2 0F 6 OF SPEC NO. TCE 52594A-H-570-002)
8. Cable lengths are based on layout drawing and considering the maximum length of similar type/rating
feeders estimated among the no of drives for the same equipment. During detail engineering, any changes take place in
location of equipment, & routing of cables , this shall be incorporated and revised in the cable schedule accordingly.
9. AC Current ratting in air at 40 deg C and Resistance at 20 deg. C of the XLPE cables have been taken from Table no 1,2,3 & 4
of manufacturer M/S RPG CABLES LTD
CLIENT : ESSAR POWER GUJARAT LTD. TITLE : CABLE SIZING CALCULATION FOR LT POWER CABLE FOR AHP
CONSULTANT : TCE CONSULTING ENGG. LTD. DOC NO: 2-A357-DC00-3-0007, REV-5
PROJECT : 2X600 MW THERMAL POWER PLANT AT SALAYA
LT MCC AT SWGR
1 HP Water Pump - A 195 0.95 0.865 0.502 330.141 0.6052 545.507 3C XLPE 300.0 AL 798 2 150 0.1 0.129 0.071 0.010 0.005 6.295 1.517 0.3 0.954 32.770 7.896
ROOM IN ESP AREA
LT MCC AT SWGR
2 HP Water Pump - B 195 0.95 0.865 0.502 330.141 0.6052 545.507 3C XLPE 300.0 AL 798 2 150 0.1 0.129 0.071 0.010 0.005 6.295 1.517 0.3 0.954 32.770 7.896
ROOM IN ESP AREA
LT MCC AT SWGR
3 LP Water Pump - A 15 0.905 0.86 0.510 26.813 0.6052 44.305 3C XLPE 35.0 AL 117 1 150 0.868 1.117 0.078 0.167 0.012 6.966 1.679 0.3 0.954 20.532 4.947
ROOM IN ESP AREA
LT MCC AT SWGR
4 LP Water Pump - B 15 0.905 0.86 0.510 26.813 0.6052 44.305 3C XLPE 35.0 AL 117 1 150 0.868 1.117 0.078 0.167 0.012 6.966 1.679 0.3 0.954 20.532 4.947
ROOM IN ESP AREA
LT MCC AT SWGR
5 LP Water Pump - C 15 0.905 0.86 0.510 26.813 0.6052 44.305 3C XLPE 35.0 AL 117 1 150 0.868 1.117 0.078 0.167 0.012 6.966 1.679 0.3 0.954 20.532 4.947
ROOM IN ESP AREA
LT MCC AT SWGR
12 Clinker Grinder - 1A 11 0.87 0.79 0.613 22.266 0.6052 36.792 3C XLPE 25.0 AL 96 1 175 1.2 1.544 0.081 0.270 0.014 8.564 2.064 0.3 0.954 26.247 6.325
ROOM IN ESP AREA
LT MCC AT SWGR
13 Clinker Grinder - 1B 11 0.87 0.79 0.613 22.266 0.6052 36.792 3C XLPE 25.0 AL 96 1 175 1.2 1.544 0.081 0.270 0.014 8.564 2.064 0.3 0.954 26.247 6.325
ROOM IN ESP AREA
LT MCC AT SWGR
14 Clinker Grinder - 2A 11 0.87 0.79 0.613 22.266 0.6052 36.792 3C XLPE 25.0 AL 96 1 175 1.2 1.544 0.081 0.270 0.014 8.564 2.064 0.3 0.954 26.247 6.325
ROOM IN ESP AREA
LT MCC AT SWGR
15 Clinker Grinder - 2B 11 0.87 0.79 0.613 22.266 0.6052 36.792 3C XLPE 25.0 AL 96 1 175 1.2 1.544 0.081 0.270 0.014 8.564 2.064 0.3 0.954 26.247 6.325
ROOM IN ESP AREA
LT MCC AT SWGR
16 Clinker Grinder for HCSD System 11 0.87 0.79 0.613 22.266 0.6052 36.792 3C XLPE 25.0 AL 96 1 175 1.2 1.544 0.081 0.270 0.014 8.564 2.064 0.3 0.954 26.247 6.325
ROOM IN ESP AREA
Reciprocating Feeder-A (with
LT MCC AT SWGR
17 frequency controller) below 1.5 0.76 0.79 0.613 3.476 0.6052 5.743 4C XLPE 10.0 AL 50 1 170 3.08 3.962 0.084 0.674 0.014 3.256 0.785 0.3 0.954 9.348 2.253
ROOM IN ESP AREA
Dewatering Bin
Reciprocating Feeder-B (with
LT MCC AT SWGR
18 frequency controller) below 1.5 0.76 0.79 0.613 3.476 0.6052 5.743 4C XLPE 10.0 AL 50 1 170 3.08 3.962 0.084 0.674 0.014 3.256 0.785 0.3 0.954 9.348 2.253
ROOM IN ESP AREA
Dewatering Bin
Reciprocating Feeder-C (with
LT MCC AT SWGR
19 frequency controller) below 1.5 0.76 0.79 0.613 3.476 0.6052 5.743 4C XLPE 10.0 AL 50 1 170 3.08 3.962 0.084 0.674 0.014 3.256 0.785 0.3 0.954 9.348 2.253
ROOM IN ESP AREA
Dewatering Bin
LT MCC AT SWGR
20 Bin Vibrator- A for Dewatering Bin 3.5 0.83 0.82 0.572 7.155 0.6052 11.822 4C XLPE 10.0 AL 50 1 170 3.08 3.962 0.084 0.674 0.014 6.945 1.673 0.3 0.954 19.242 4.637
ROOM IN ESP AREA
LT MCC AT SWGR
21 Bin Vibrator- B for Dewatering Bin 3.5 0.83 0.82 0.572 7.155 0.6052 11.822 4C XLPE 10.0 AL 50 1 170 3.08 3.962 0.084 0.674 0.014 6.945 1.673 0.3 0.954 19.242 4.637
ROOM IN ESP AREA
1 OF 6
CLIENT : ESSAR POWER GUJARAT LTD. TITLE : CABLE SIZING CALCULATION FOR LT POWER CABLE FOR AHP
CONSULTANT : TCE CONSULTING ENGG. LTD. DOC NO: 2-A357-DC00-3-0007, REV-5
PROJECT : 2X600 MW THERMAL POWER PLANT AT SALAYA
LT MCC AT SWGR
22 Bin Vibrator- C for Dewatering Bin 3.5 0.83 0.82 0.572 7.155 0.6052 11.822 4C XLPE 10.0 AL 50 1 170 3.08 3.962 0.084 0.674 0.014 6.945 1.673 0.3 0.954 19.242 4.637
ROOM IN ESP AREA
LT MCC AT SWGR
23 Bin Vibrator- D for Dewatering Bin 3.5 0.83 0.82 0.572 7.155 0.6052 11.822 4C XLPE 10.0 AL 50 1 170 3.08 3.962 0.084 0.674 0.014 6.945 1.673 0.3 0.954 19.242 4.637
ROOM IN ESP AREA
LT MCC AT SWGR
24 Bin Vibrator- E for Dewatering Bin 3.5 0.83 0.82 0.572 7.155 0.6052 11.822 4C XLPE 10.0 AL 50 1 170 3.08 3.962 0.084 0.674 0.014 6.945 1.673 0.3 0.954 19.242 4.637
ROOM IN ESP AREA
LT MCC AT SWGR
25 Bin Vibrator- F for Dewatering Bin 3.5 0.83 0.82 0.572 7.155 0.6052 11.822 4C XLPE 10.0 AL 50 1 170 3.08 3.962 0.084 0.674 0.014 6.945 1.673 0.3 0.954 19.242 4.637
ROOM IN ESP AREA
LT MCC AT SWGR
26 Bin Vibrator- G for Dewatering Bin 3.5 0.83 0.82 0.572 7.155 0.6052 11.822 4C XLPE 10.0 AL 50 1 170 3.08 3.962 0.084 0.674 0.014 6.945 1.673 0.3 0.954 19.242 4.637
ROOM IN ESP AREA
LT MCC AT SWGR
27 Bin Vibrator- H for Dewatering Bin 3.5 0.83 0.82 0.572 7.155 0.6052 11.822 4C XLPE 10.0 AL 50 1 170 3.08 3.962 0.084 0.674 0.014 6.945 1.673 0.3 0.954 19.242 4.637
ROOM IN ESP AREA
LT MCC AT SWGR
28 Bin Vibrator- I for Dewatering Bin 3.5 0.83 0.82 0.572 7.155 0.6052 11.822 4C XLPE 10.0 AL 50 1 170 3.08 3.962 0.084 0.674 0.014 6.945 1.673 0.3 0.954 19.242 4.637
ROOM IN ESP AREA
LT MCC AT SWGR
29 Belt Conveyor 7.5 0.86 0.83 0.558 14.618 0.6052 24.154 3C XLPE 16.0 AL 64 1 180 1.91 2.457 0.080 0.442 0.014 9.496 2.288 0.3 0.954 26.682 6.429
ROOM IN ESP AREA
LT MCC AT SWGR
36 Conveying Air Compressor - A 195 0.95 0.865 0.502 330.141 0.6052 545.507 3C XLPE 300.0 AL 798 2 225 0.1 0.129 0.071 0.014 0.008 9.443 2.275 0.3 0.954 49.154 11.844
ROOM IN ESP AREA
LT MCC AT SWGR
37 Conveying Air Compressor - B 195 0.95 0.865 0.502 330.141 0.6052 545.507 3C XLPE 300.0 AL 798 2 220 0.1 0.129 0.071 0.014 0.008 9.233 2.225 0.3 0.954 48.062 11.581
ROOM IN ESP AREA
LT MCC AT SWGR
38 Conveying Air Compressor - C 195 0.95 0.865 0.502 330.141 0.6052 545.507 3C XLPE 300.0 AL 798 2 215 0.1 0.129 0.071 0.014 0.008 9.023 2.174 0.3 0.954 46.970 11.318
ROOM IN ESP AREA
LT MCC AT SWGR
39 Conveying Air Compressor - D 195 0.95 0.865 0.502 330.141 0.6052 545.507 3C XLPE 300.0 AL 798 2 210 0.1 0.129 0.071 0.014 0.007 8.813 2.124 0.3 0.954 45.877 11.055
ROOM IN ESP AREA
LT MCC AT SWGR
40 Conveying Air Compressor - E 195 0.95 0.865 0.502 330.141 0.6052 545.507 3C XLPE 300.0 AL 798 2 205 0.1 0.129 0.071 0.013 0.007 8.603 2.073 0.3 0.954 44.785 10.792
ROOM IN ESP AREA
LT MCC AT SWGR
41 Conveying Air Compressor - F 195 0.95 0.865 0.502 330.141 0.6052 545.507 3C XLPE 300.0 AL 798 2 200 0.1 0.129 0.071 0.013 0.007 8.394 2.023 0.3 0.954 43.693 10.528
ROOM IN ESP AREA
2 OF 6
CLIENT : ESSAR POWER GUJARAT LTD. TITLE : CABLE SIZING CALCULATION FOR LT POWER CABLE FOR AHP
CONSULTANT : TCE CONSULTING ENGG. LTD. DOC NO: 2-A357-DC00-3-0007, REV-5
PROJECT : 2X600 MW THERMAL POWER PLANT AT SALAYA
LT MCC AT SILO
48 Silo Aeration Blower-A 37 0.925 0.86 0.510 64.709 0.6052 106.922 3C XLPE 50.0 AL 142 1 60 0.641 0.825 0.075 0.049 0.005 5.026 1.211 0.3 0.954 15.449 3.723
AREA
LT MCC AT SILO
49 Silo Aeration Blower-B 37 0.925 0.86 0.510 64.709 0.6052 106.922 3C XLPE 50.0 AL 142 1 60 0.641 0.825 0.075 0.049 0.005 5.026 1.211 0.3 0.954 15.449 3.723
AREA
LT MCC AT SILO
50 Silo Aeration Blower-C 37 0.925 0.86 0.510 64.709 0.6052 106.922 3C XLPE 50.0 AL 142 1 60 0.641 0.825 0.075 0.049 0.005 5.026 1.211 0.3 0.954 15.449 3.723
AREA
LT MCC AT SILO
51 Heater -A for silo areation blower 27 0.91 0.87 0.493 47.447 0.6052 78.399 4C XLPE 25.0 AL 96 1 60 1.2 1.544 0.081 0.093 0.005 6.818 1.643 0.3 0.954 19.176 4.621
AREA
LT MCC AT SILO
52 Heater -B for silo areation blower 27 0.91 0.87 0.493 47.447 0.6052 78.399 4C XLPE 25.0 AL 96 1 60 1.2 1.544 0.081 0.093 0.005 6.818 1.643 0.3 0.954 19.176 4.621
AREA
LT MCC AT SILO
53 Heater -C for silo areation blower 27 0.91 0.87 0.493 47.447 0.6052 78.399 4C XLPE 25.0 AL 96 1 60 1.2 1.544 0.081 0.093 0.005 6.818 1.643 0.3 0.954 19.176 4.621
AREA
LT MCC AT SWGR Sludge Pump- A below Settling
54 9.3 0.86 0.83 0.558 18.126 0.6052 29.951 3C XLPE 16.0 AL 64 1 165 1.91 2.457 0.080 0.405 0.013 10.794 2.601 0.3 0.954 30.329 7.308
ROOM IN ESP AREA Tank
LT MCC AT SILO
58 Drain Sump Pump- A (Silo Area) 5.5 0.85 0.83 0.558 10.846 0.6052 17.921 3C XLPE 16.0 AL 64 1 60 1.91 2.457 0.080 0.147 0.005 2.349 0.566 0.3 0.954 6.599 1.590
AREA
LT MCC AT SILO
59 Drain Sump Pump- B (Silo Area) 5.5 0.85 0.83 0.558 10.846 0.6052 17.921 3C XLPE 16.0 AL 64 1 60 1.91 2.457 0.080 0.147 0.005 2.349 0.566 0.3 0.954 6.599 1.590
AREA
LT MCC AT SILO
60 Dust Conditioner-A (Rotary Type) 11 0.885 0.86 0.510 20.107 0.6052 33.224 3C XLPE 16.0 AL 64 1 75 1.91 2.457 0.080 0.184 0.006 5.625 1.355 0.3 0.954 15.293 3.685
AREA
LT MCC AT SILO
61 Dust Conditioner-B (Rotary Type) 11 0.885 0.86 0.510 20.107 0.6052 33.224 3C XLPE 16.0 AL 64 1 75 1.91 2.457 0.080 0.184 0.006 5.625 1.355 0.3 0.954 15.293 3.685
AREA
3 OF 6
CLIENT : ESSAR POWER GUJARAT LTD. TITLE : CABLE SIZING CALCULATION FOR LT POWER CABLE FOR AHP
CONSULTANT : TCE CONSULTING ENGG. LTD. DOC NO: 2-A357-DC00-3-0007, REV-5
PROJECT : 2X600 MW THERMAL POWER PLANT AT SALAYA
LT MCC AT SILO
65 Silo vent fan - A 9.3 0.86 0.83 0.558 18.126 0.6052 29.951 3C XLPE 16.0 AL 64 1 120 1.91 2.457 0.080 0.295 0.010 7.850 1.892 0.3 0.954 22.057 5.315
AREA
LT MCC AT SILO
66 Silo vent fan - B 9.3 0.86 0.83 0.558 18.126 0.6052 29.951 3C XLPE 16.0 AL 64 1 130 1.91 2.457 0.080 0.319 0.010 8.504 2.049 0.3 0.954 23.896 5.758
AREA
LT MCC AT SWGR
67 Vent Fan for intermediate silo 11 0.885 0.86 0.510 20.107 0.6052 33.224 3C XLPE 25.0 AL 96 1 180 1.2 1.544 0.081 0.278 0.015 8.580 2.067 0.3 0.954 24.379 5.875
ROOM IN ESP AREA
LT MCC AT SILO
68 Rotary Feeder- A 2.2 0.8 0.82 0.572 4.666 0.6052 7.709 3C XLPE 2.5 CU 43 1 115 7.41 9.448 0.099 1.087 0.011 7.253 1.748 0.3 0.954 19.598 4.722
AREA
LT MCC AT SILO
69 Rotary Feeder- B 2.2 0.8 0.82 0.572 4.666 0.6052 7.709 3C XLPE 2.5 CU 43 1 125 7.41 9.448 0.099 1.181 0.012 7.884 1.900 0.3 0.954 21.303 5.133
AREA
LT MCC AT SWGR Rotary Feeder- C below
70 2.2 0.8 0.82 0.572 4.666 0.6052 7.709 3C XLPE 2.5 CU 43 1 165 7.41 9.448 0.099 1.559 0.016 10.406 2.508 0.3 0.954 28.119 6.776
ROOM IN ESP AREA intermediate silo
LT MCC AT SWGR
71 Measuring Loop Pump 2.2 0.8 0.82 0.572 4.666 0.6052 7.709 3C XLPE 2.5 CU 43 1 155 7.41 9.448 0.099 1.465 0.015 9.776 2.356 0.3 0.954 26.415 6.365
ROOM IN ESP AREA
LT MCC AT SWGR
72 Paddle Mixer for HCSD System 37 0.925 0.86 0.510 64.709 0.6052 106.922 3C XLPE 95.0 AL 221 1 165 0.32 0.412 0.073 0.068 0.012 7.230 1.742 0.3 0.954 25.650 6.181
ROOM IN ESP AREA
LT MCC AT SWGR
73 Agitator for Mixing Tank 75 0.93 0.87 0.493 128.962 0.6052 213.091 3C XLPE 120.0 AL 257 1 165 0.253 0.325 0.071 0.054 0.012 11.730 2.827 0.3 0.954 43.955 10.592
ROOM IN ESP AREA
LT MCC AT SWGR Electricaly operated Under Slung
74 15.5 0.75 0.75 0.661 38.337 0.6052 63.345 4C XLPE 35.0 AL 117 1 200 0.868 1.117 0.078 0.223 0.016 11.806 2.845 0.3 0.954 39.150 9.434
ROOM IN ESP AREA Crane in Compressor House
LT MCC AT SWGR
77 Electric Hoist over Mixing Tank 4.6 0.75 0.75 0.661 11.377 0.6052 18.799 4C XLPE 16.0 AL 64 1 170 1.91 2.457 0.080 0.418 0.014 6.349 1.530 0.3 0.954 19.613 4.726
ROOM IN ESP AREA
LT MCC AT SWGR Supply for pressurized ventilation
78 37 0.925 0.86 0.510 64.709 0.6052 106.922 3C XLPE 50.0 AL 142 1 100 0.641 0.825 0.075 0.082 0.008 8.377 2.019 0.3 0.954 25.749 6.205
ROOM IN ESP AREA system
4 OF 6
CLIENT : ESSAR POWER GUJARAT LTD. TITLE : CABLE SIZING CALCULATION FOR LT POWER CABLE FOR AHP
CONSULTANT : TCE CONSULTING ENGG. LTD. DOC NO: 2-A357-DC00-3-0007, REV-5
PROJECT : 2X600 MW THERMAL POWER PLANT AT SALAYA
LT MCC AT SWGR
96 ACDB 15 0.75 0.75 0.661 37.100 0.6052 61.302 4C XLPE 35.0 AL 117 1 50 0.868 1.117 0.078 0.056 0.004 2.856 0.688 0.3 0.954 9.472 2.282
ROOM IN ESP AREA
LT MCC AT SWGR
97 BYPASS SUPPLY FOR UPS 17.64706 0.885 0.85 0.527 32.637 0.6052 53.928 3C XLPE 16.0 AL 64 1 60 1.91 2.457 0.080 0.147 0.005 7.225 1.741
ROOM IN ESP AREA
LT MCC AT SWGR
100 SILO MCC SUPPLY # 1 237.0653 0.97 0.85 0.527 400.020 0.6052 660.971 1C XLPE 630.0 AL 1628 11 550 0.0778 0.100 0.070 0.005 0.004 4.228 1.01874276
ROOM IN ESP AREA
LT MCC AT SWGR
101 SILO MCC SUPPLY # 2 237.0653 0.97 0.85 0.527 400.020 0.6052 660.971 1C XLPE 630.0 AL 1628 11 550 0.0778 0.100 0.070 0.005 0.004 4.228 1.01874276
ROOM IN ESP AREA
LT MCC AT SILO
104 Electric Hoist in silo area 4.6 0.75 0.75 0.661 11.377 0.6052 18.799 4C XLPE 16.0 AL 64 1 120 1.91 2.457 0.080 0.295 0.010 4.482 1.080 0.3 0.954 13.845 3.336
AREA
5 OF 6
CLIENT : ESSAR POWER GUJARAT LTD. TITLE : CABLE SIZING CALCULATION FOR LT POWER CABLE FOR AHP
CONSULTANT : TCE CONSULTING ENGG. LTD. DOC NO: 2-A357-DC00-3-0007, REV-5
PROJECT : 2X600 MW THERMAL POWER PLANT AT SALAYA
6 OF 6
CLIENT : ESSAR POWER GUJARAT LTD. TITLE : CABLE SIZING CALCULATION FOR LT POWER CABLE FOR AHP
CONSULTANT : TCE CONSULTING ENGG. LTD. DOC NO: 2-A357-DC00-3-0007, REV-5
PROJECT : 2X600 MW THERMAL POWER PLANT AT SALAYA
A) SAMPLE CALCULATION OF LT CABLE FOR 195KW HP WATER PUMP / CONVEYING AIR COMPRESSOR
Minimum Cross - sectional area of cable `A` to withstand short circuit current = I sh . SQRT(t) / k
Where, t = Fault clearing time = 0.16 sec (As per TCE specification : 5259A-H-570-002,
SEC: D2.03, CL NO# 3.1.2, SHT 2 OF 6)
2. DERATING FACTOR
Group rating factors considered for three core cables laid on cable trays exposed to air.
For 50 deg.C ambient temperature, derating factor (K1) for XLPE Cable = 0.89 (Ref # Table # 14 of RPG CABLES enclosed).
Group derating factor (K2) for 3no trays & 9 no cables in 1 tray = 0.68 (Ref # Table # 20 of RPG CABLES enclosed).
voltage= 415 V
pf= 0.86
efficiency= 0.93
Current Rating of 3C-300 sq mm (Al) cable (XLPE), 1100 V Grade in air = 455 A (Refer table#3 of RPG CABLE enclosed)
No of runs = 1.2318
No of runs selected = 2
Voltage = 415 V
Resistance per Km of the selected cable at 20 DEG c (Ohms/km) = 0.1 ohms/km (Refer table#24 of RPG CABLE enclosed)
The voltage drop for a given cable length under steady state condition is given by the formula :
Since this voltage drop is less than the permissible limit of 3% ( Refer CL# 3.1.6 OF SECTION: D2.03, SHT 2 OF 6 OF SPEC NO. TCE-5259A-H-570-002)
Hence cable size of 2x 3C X 300sqmm selected on the basis of Full load current is adequate.
SHEET1
CLIENT : ESSAR POWER GUJARAT LTD. TITLE : CABLE SIZING CALCULATION FOR LT POWER CABLE FOR AHP
CONSULTANT : TCE CONSULTING ENGG. LTD. DOC NO: 2-A357-DC00-3-0007, REV-5
PROJECT : 2X600 MW THERMAL POWER PLANT AT SALAYA
B) SAMPLE CALCULATION OF LT CABLE FOR SILO MCC INCOMER (630A ACB INCOMER)
1. DERATING FACTOR
Group rating factors considered for three core cables laid on cable trays exposed to air.
For 50 deg.C ambient temperature, derating factor (K1) for XLPE Cable = 0.89 (Ref # Table # 14 of RPG CABLES enclosed).
Group derating factor (K2) for 3no trays & 9 no cables in 1 tray = 0.68 (Ref # Table # 20 of RPG CABLES enclosed).
Current Rating of 1C-630 sq mm (Al) cable (XLPE), 1100 V Grade in air = 814 A (Refer table#3 of RPG CABLE enclosed)
No of runs = 0.812004
No of runs selected = 1
Hence cable size selected based on load current = 1X1C-630 sq. mm / Phase & 1 run for neutral.
Voltage = 415 V
Resistance per Km of the selected cable (Ohms/km) = 0.0469 ohms/km (Refer table#24 of RPG CABLE
Resistance per Km of the selected cable (Ohms/km) AT 90 DEG. = 0.060 ohms/km enclosed)
COS α = 0.85
SIN α = 0.526783
The voltage drop for a given cable length under steady state condition is given by the formula :
Since this voltage drop is less than the permissible limit of 3% ( Refer CL# 3.1.6 OF SECTION: D2.03, SHT 2 OF 6 OF SPEC NO. TCE-5259A-H-570-002)
Hence cable size of 3x 1C X 630sqmm / Phase & 2X1C-630 for Neutral selected on the basis of Full load current is adequate.
SHEET2
CLIENT: ESSAR POWER GUJARAT LTD. TITLE: CABLE SIZING CALCULATION FOR LT POWER CABLE
CONSULTANT: TCE CONSULTING ENGG. LTD. DOC NO: 2-A357-DC00-3-0002, REV-5
PROJECT: 2X600 MW THERMAL POWER PLANT AT SALAYA
ANNEXURE-1
SL NO DESCRIPTION NO OF NO OF MOTOR TRANSMISSION MOTOR DUTY POWER AT TOTAL POWER POWER TOTAL KVA
RUNNING STANDBY RATING EFFICIENCY EFFICIENCY FACTOR MOTOR INPUT REQUIREMENT FACTOR
EQUIPMENT EQUIPMENT (KW) TERMINAL (KW)
(KW)
1 SILO AREATION BLOWER 2 1 37 0.95 0.92 0.9 38.1006865 76.201373 0.86 88.6062477
HEATER FOR SILO AREATION
2
BLOWER 2 1 27 1 0.91 0.9 26.7032967 53.40659341 0.86 62.10069
3 DRAIN SUMP PUMP (SILO AREA) 1 1 5.5 1 0.86 0.4 2.558139535 2.558139535 0.86 2.97458085
4 DUST CONDITIONER (ROTARY TYPE) 2 0 11 0.95 0.91 0.9 11.45170619 22.90341238 0.87 26.3257614
5 TELESCOPIC CHUTE FOR FA SILO 2 0 2.2 1 0.8 0.9 2.475 4.95 0.82 6.03658537
6 SILO VENT FAN 2 0 7.5 1 0.83 0.9 8.13253012 16.26506024 0.85 19.135365
7 ROTARY FEEDER BELOW FA SILO 2 0 2.2 0.95 0.8 0.9 2.605263158 5.210526316 0.82 6.35430039
8 HOIST IN SILO UTILITY BUILDING 1 0 4.6 0.4 0.85 0.4 5.411764706 5.411764706 0.85 6.36678201
9 WELDING RECEPTACLE 16
10 LIGHTING LOAD 25
11 ACDB 10
12 CONTROL & AUXILIARY 10
TOTAL KVA REQUIRED = 278.900313 KVA
CONSIDERING 10% MARGIN = 306.790344 KVA
In duct at 30
AC current rating of Cu
degC (A)
In air at 40 degC
(A)
In duct at 30
degC (A)
AC current rating of AL
cable (in trefoil)
In ground at 30
degC (A)
In air at 40 degC
(A)
Aprox. weight -
Cu conductor
(Kg.)
Aprox. weight -
AL conductor
(Kg.)
Aprox. overall
diameter (mm)
Armoured
Nominal
thickness of
insulation (mm)
Aprox. weight -
Cu conductor
(Kg.)
Aprox. weight -
Unarmoured
AL conductor
(Kg.)
Aprox. overall
diameter (mm)
Nominal
thickness of
insulation (mm)
Area of
conductor (mm2)
Number of cores
In duct at 30
degC (A)
AC current rating of Cu
cable (in trefoil)
In ground at 30
degC (A)
In air at 40 degC
(A)
In duct at 30
degC (A)
AC current rating of AL
cable (in trefoil)
In ground at 30
degC (A)
In air at 40 degC
(A)
Aprox. weight -
Cu conductor
(Kg.)
Aprox. weight -
AL conductor
(Kg.)
Aprox. overall
diameter (mm)
Armoured
Nominal
thickness of
insulation (mm)
Aprox. weight -
Cu conductor
(Kg.)
Aprox. weight -
AL conductor
Unarmoured
(Kg.)
Aprox. overall
diameter (mm)
Nominal
thickness of
insulation (mm)
Area of
conductor (mm2)
Number of cores
In duct at 30
AC current rating of Cu
degC (A)
In air at 40 degC
(A)
In duct at 30
degC (A)
AC current rating of AL
cable (in trefoil)
In ground at 30
degC (A)
In air at 40 degC
(A)
Aprox. weight -
Cu conductor
(Kg.)
Aprox. weight -
AL conductor
(Kg.)
Aprox. overall
diameter (mm)
Armoured
Nominal
thickness of
insulation (mm)
Aprox. weight -
Cu conductor
(Kg.)
Aprox. weight -
Unarmoured
AL conductor
(Kg.)
Aprox. overall
diameter (mm)
Nominal
thickness of
insulation (mm)
Area of
conductor (mm2)
Number of cores
In duct at 30
AC current rating of Cu
degC (A)
In air at 40 degC
(A)
In duct at 30
degC (A)
AC current rating of AL
cable (in trefoil)
In ground at 30
degC (A)
In air at 40 degC
(A)
Aprox. weight -
Cu conductor
(Kg.)
Aprox. weight -
AL conductor
(Kg.)
Aprox. overall
diameter (mm)
Armoured
Nominal
thickness of
insulation (mm)
Aprox. weight -
Cu conductor
(Kg.)
Aprox. weight -
Unarmoured
AL conductor
(Kg.)
Aprox. overall
diameter (mm)
Nominal
thickness of
insulation (mm)
Area of
conductor (mm2)
Number of cores
Electrostatic
capacitance
(uF / Km)
Voltage Drop
- Cu (V/A/
Km)
Voltage Drop
- AL (V/A/Km)
Impedance -
Cu (Ohm/Km)
Impedance -
AL (Ohm/
Km)
Reactance -
(Ohm/Km)
AC
resistance -
Cu (Ohm/
Km)
AC
resistance -
AL (Ohm/
Km)
Max. DC
resistance -
Cu (Ohm/
Km)
Max. DC
resistance -
AL (Ohm/
Km)
NMinimum
no of wires -
Class-2 (Cu)
Minimum no
of wires -
Class-2 (AL)
Nominal size
of conductor
(mm2)
Electrostatic
capacitance
(uF / Km)
Voltage Drop
- Cu (V/A/
Km)
Voltage Drop
- AL (V/A/Km)
Impedance -
Cu (Ohm/Km)
Impedance -
AL (Ohm/
Km)
Reactance -
(Ohm/Km)
AC
resistance -
Cu (Ohm/
Km)
AC
resistance -
AL (Ohm/
Km)
Max. DC
resistance -
Cu (Ohm/
Km)
Max. DC
resistance -
AL (Ohm/
Km)
NMinimum
no of wires -
Class-2 (Cu)
Minimum no
of wires -
Class-2 (AL)
Nominal size
of conductor
(mm2)