ABBREVIATIONS

GENERAL STRUCTURAL NOTES AFF ABOVE FINISHED FLOOR IFW INSIDE FACE OF WALL
APPLY UNLESS NOTED OTHERWISE ALT ALTERNATE IT PRECAST INVERTED TEE BEAM
1.0 STRUCTURAL ENGINEERING GENERAL REQUIREMENTS: 1 DUTIES AND RESPONSIBILITIES OF THE SPECIAL INSPECTOR: AB ANCHOR BOLT K (KIP) 1000 POUNDS
ADD'L ADDITIONAL LB PRECAST ELL BEAM
DELEGATED STRUCTURAL ENGINEERING SUBMITTALS: A) THE SPECIAL INSPECTOR SHALL OBSERVE THE WORK ASSIGNED TO BE CERTAIN IT CONFORMS WITH THE APPROVED
ARCH ARCHITECT LBS (#) POUNDS
BUILDING CODE: DESIGN DRAWINGS AND SPECIFICATION.
ARCH'L ARCHITECTURAL LL LIVE LOAD
FOR THE PURPOSES OF THIS SECTION, DELEGATED STRUCTURAL ENGINEERING SUBMITTALS ARE DEFINED AS THOSE B) THE SPECIAL INSPECTOR SHALL FURNISH INSPECTION REPORTS TO THE BUILDING OFFICIAL, AND TO THE ENGINEER
@ AT (MEASUREMENT) LLH LONG LEG HORIZONTAL
2018 EDITION OF THE INTERNATIONAL BUILDING CODE / ASCE/SEI 7-16 WITH CITY OF THORNTON AMENDMENTS. PORTIONS OF THE DESIGN WHICH SHALL BE ENGINEERED BY THE CONTRACTOR'S SUPPLIER AND SUBMITTED AT THE TIME OR ARCHITECT OF RECORD. ALL DISCREPANCIES SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE CONTRACTOR FOR BM BEAM LLV LONG LEG VERTICAL
OF THE APPLICATION. CORRECTION, THEN, IF UNCORRECTED, TO THE DESIGN AUTHORITY AND THE BUILDING OFFICIAL. BFF BELOW FINISHED FLOOR LOC LOCATION
DESIGN CRITERIA / LOADS: C) UPON COMPLETION OF THE WORK THE SPECIAL INSPECTOR SHALL COMPLETE AND SIGN THE APPROPRIATE FORMS BOB BOTTOM OF BEAM LVL LAMINATED VENEER LUMBER
SUBMITTAL DOCUMENTS FOR DELEGATED STRUCTURAL ENGINEERING SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE CERTIFYING THAT TO THE BEST OF THEIR KNOWLEDGE THE WORK IS IN CONFORMANCE WITH THE APPROVED PLANS AND

S
BOD BOTTOM OF DECK MAS MASONRY
ALL COMPONENTS REQUIRING DESIGN BY THE CONTRACTOR AND THEIR SUBCONTRACTORS SHALL USE THE DESIGN CRITERIA DEFINED ARCHITECT OR ENGINEER OF RECORD WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING OFFICIAL WITH A SPECIFICATIONS AND THE APPLICABLE WORKMANSHIP PROVISIONS OF THE CODE. BOF BOTTOM OF FOOTING MAS CJ MASONRY CONTROL JOINT

E
NOTATION INDICATING THAT THE DELEGATED STRUCTURAL ENGINEERING SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND

210106
BELOW. ALL FORCES AND PRESSURES LISTED BELOW SHALL BE THE MINIMUM PERMISSIBLE UNLESS SUBSTANTIATING CALCULATIONS BOT (B) BOTTOM MAX MAXIMUM
USING THE DESIGN CRITERIA SHOWN ARE PROVIDED TO THE LEFFLER GROUP FOR REVIEW AND ACCEPTANCE PRIOR TO FABRICATION. THAT THEY HAVE BEEN FOUND TO BE IN GENERAL CONFORMANCE WITH THE DESIGN OF THE BUILDING. THE DELEGATED ALL TEST & INSPECTION REPORTS SHALL BE COPIED TO THE STRUCTURAL ENGINEER WITHIN 3 DAYS OF INSPECTION OR BRG BEARING MBM METAL BUILDING MANUFACTURER

INTERIOR DESIGN
580 BURBANK ST. SUITE 125, BROOMFIELD, CO 80020 PHONE: 303.465.4306 FAX: 303.465.4382 www.allredarch.com
T
STRUCTURAL ENGINEERING SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THEIR DESIGN AND SUBMITTAL DOCUMENTS TEST. CFS COLD FORMED STEEL MECH'L MECHANICAL

RISK CATEGORY = IV HAVE BEEN APPROVED BY THE BUILDING OFFICIAL. CGS CENTER OF GRAVITY STRAND MFR('S) MANUFACTURER('S)

A
CIP CAST IN PLACE MIN MINIMUM
SITE VISITS:

I
CL CENTERLINE MPII MFR PRINTED INSTALLATION INSTRUCTIONS
FLOOR: DELEGATED STRUCTURAL ENGINEERING SUBMITTAL ITEMS:
CJ CONTROL JOINT N/A NOT APPLICABLE

| JOB NO.
LIVE LOADS - SEE SHEET S0.5. THE STRUCTURAL ENGINEER OF RECORD SHALL MAKE PERIODIC VISITS TO THE SITE TO OBSERVE GENERAL COMPLIANCE WITH

C
CJP COMPLETE JOINT PENETRATION NTS NOT TO SCALE
SUPERIMPOSED DEAD LOAD = 10 PSF + MASONRY WALL HEIGHTS. STEEL STAIRS THE APPROVED STRUCTURAL PLANS, SPECIFICATIONS AND CHANGE ORDERS. THE ENGINEER SHALL SUBMIT A STATEMENT IN CTR'D CENTERED OC ON CENTER
WRITING TO THE BUILDING DEPARTMENT STATING THAT SITE VISITS HAVE BEEN MADE, AND THAT TO THE BEST OF THEIR CLB CENTERLINE OF BEAM OFW OUTSIDE FACE OF WALL

O
ROOF: GENERAL REQUIREMENTS: KNOWLEDGE, ANY DEFICIENCIES NOTED HAVE BEEN CORRECTED. THE OWNER’S TESTING AGENCY SHALL ALSO SUBMIT A FINAL CLC CENTERLINE OF COLUMN OH OPPOSITE HAND
ROOF LIVE LOAD = 20 PSF (NON-REDUCIBLE) REPORT AS REQUIRED IN SECTION 1704 OF THE 2012 IBC. CLF CENTERLINE OF FOOTING OPP OPPOSITE

S
SUPERIMPOSED DEAD LOAD ON ROOF TRUSSES = 10 PSF (FUTURE SOLAR – 25 PSF). ENTIRE CONTRACT DOCUMENTS SHALL BE USED TO BUILD BUILDING. SOME CRITICAL ITEMS REQUIRED BY OTHER CLW CENTERLINE OF WALL OPNG OPENING
NET UPLIFT ON ROOF JOISTS/TRUSSES = SEE SHEET S0.6. DISCIPLINES MAY NOT BE SHOWN ON STRUCTURAL DRAWING (i.e. WALL, FLOOR AND ROOF OPENING, ARCHITECTURAL, 2.0 FOUNDATIONS: CLR CLEAR OS OVERSIZED

S
MECHANICAL AND PLUMBING LOADS, SUPPORT PLATES ETC.). IT IS THE CONTRACTOR'S SOLE RESPONSIBILITY TO COL COLUMN OSB ORIENTED STRAND BOARD

|
PERFORM CAREFUL COORDINATION BETWEEN TRADES DURING CONSTRUCTION. GEOTECHNICAL REPORT BY KUMAR AND ASSOCIATES, INC; JOB NO.21-3-157 DATED 08/12/2021. CONC CONCRETE PAF POWDER ACTUATED FASTENER

A
SNOW:
GROUND SNOW LOAD, Pg = 30 PSF CMU CONCRETE MASONRY UNIT PC PRECAST CONCRETE

PLANNING
CONN CONNECTION PEMB PRE-ENGINEERED METAL BUILDING
ROOF SNOW LOAD, Pf = 36 PSF (NON-REDUCIBLE) WHERE DISCREPANCIES OCCUR BETWEEN PLANS, DETAILS, GENERAL STRUCTURAL NOTES AND SPECIFICATIONS, THE MORE THE FOUNDATION AND FLOOR SLAB SYSTEMS SHOWN ON THE STRUCTURAL DRAWINGS HAVE BEEN DESIGNED IN ACCORDANCE

&
CONT CONTINUOUS PFWT PREFABRICATED WOOD TRUSS
SNOW DRIFT PER ASCE-7 (Ce = 1.0, Ct = 1.1, Cs = 1.0) STRINGENT REQUIREMENTS SHALL GOVERN. SPECIFIC DETAILS ON DRAWINGS SHALL TAKE PRECEDENCE OVER TYPICAL WITH THE GEOTECHNICAL REPORT RECOMMENDATIONS. THE FOLLOWING FOUNDATION AND SLAB MOVEMENTS HAVE BEEN
d PENNY (SIZE) PJ PANEL JOINT
IMPORTANCE FACTOR, I = 1.2 DETAILS AND GENERAL STRUCTURAL NOTES. BRING ALL DISCREPANCIES TO THE ATTENTION OF THE ENGINEER ESTIMATED BY THE GEOTECHNICAL ENGINEER USING THE DESIGN CRITERIA PRESENTED IN THE SOILS REPORT:
DAS DEFORMED ANCHOR STUD PL PLATE
SNOW DRIFT = SEE SHEET S0.6. IMMEDIATELY UPON DISCOVERY. • TOTAL SETTLEMENT OF PIERS = 1”
DEG DEGREE PLF POUNDS PER LINEAR FOOT
• DIFFERENTIAL SETTLEMENT OF PIERS = 3/4” DIA DIAMETER PLWD PLYWOOD
WIND DESIGN DATA: DO NOT SCALE DRAWINGS FOR THE PURPOSE OF ESTABLISHING DIMENSIONS OF ANY KIND.

ALLRED
DL DEAD LOAD PREFAB PREFABRICATED
RISK CATEGORY = IV ALL RISKS ASSOCIATED WITH THESE DESIGN REQUIREMENTS HAVE BEEN FULLY EVALUATED AND ACCEPTED BY THE OWNER. DP DEEP OR DRILLED PIER PSF POUNDS PER SQUARE FOOT
ULTIMATE DESIGN WIND SPEED, Vult = 120 MPH (3 SEC. GUST) ALL PROPRIETARY ITEMS, MATERIALS AND COMPONENTS SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE

|
DN DOWN PSI POUNDS PER SQUARE INCH
EQUIVALENT NOMINAL DESIGN WIND SPEED, Vasd = 90 MPH (3 SEC. GUST, USING I = 1.15) MANUFACTURER’S INSTRUCTIONS, GUIDELINES AND/OR RECOMMENDATIONS. PERIMETER FOUNDATION DRAINS AND UNDERSLAB DRAINS ARE NON-STRUCTURAL ITEMS RELATED TO SOIL PERFORMANCE AND DTL DETAIL PT POST TENSION
EXPOSURE C WATER TRANSPORT AWAY FROM THE BUILDING. THESE ITEMS ARE NOT THE RESPONSIBILITY OF THE STRUCTURAL ENGINEER DWG(S) DRAWING(S) PTL PRESSURE TREATED LUMBER

ARCHITECTURE
MEAN ROOF HEIGHT USED FOR DESIGN, h = 25 FT ITEMS SHOWN BY OTHER DISCIPLINES WITH REFERENCE TO STRUCTURAL DRAWING BUT NOT SHOWN ON THESE STRUCTURAL AND ARE NOT DEFINED OR SHOWN IN THE STRUCTURAL DRAWINGS. REFER TO OTHER DISCIPLINES' DRAWINGS AND THE EA EACH RB PRECAST RECTANGLE BEAM

PERMIT SET
Kd = 0.85 DOCUMENTS SHALL BE CONSIDERED DESIGN BUILD ITEMS AND COSTS REQUIRED FOR THESE ITEMS SHALL BE INCLUDED IN GEOTECHNICAL REPORT FOR REQUIREMENTS. EC EPOXY COATED RE: REFERENCE

CONTRACTOR'S PRICING EXERCISES AND BID. CONTRACTOR SHALL SUBMIT DESIGN BY OTHERS FOR REVIEW. EE EACH END REINF REINFORCING
Kzt = 1.0
EL ELEVATION REQ'D REQUIRED
VELOCITY PRESSURE CONSTANT = 0.86X 0.00256 = 0.0022 (AMBIENT AIR DENSITY ADJUSTMENT) EQUIVALENT FLUID PRESSURE USED FOR WALL DESIGN = 55 PCF FOR “ACTIVE” CONDITION AND 75 PCF FOR “AT REST”
ENGR ENGINEER RS ROUGH SAWN
INTERNAL PRESSURE COEFFICIENT, GCpi = ±0.18 THE STRUCTURAL CONSTRUCTION DOCUMENTS REPRESENT THE FINISHED STRUCTURE. THEY DO NOT INDICATE THE METHOD CONDITION.
EOS EDGE OF SLAB SCHED SCHEDULE
COMPONENTS AND CLADDING DESIGN WIND PRESSURES: OF CONSTRUCTION. THE CONTRACTOR SHALL PROVIDE ALL MEASURES NECESSARY TO PROTECT THE STRUCTURE DURING EQ EQUAL SLH SHORT LEG HORIZONTAL
CONSTRUCTION. SUCH MEASURES SHALL INCLUDE, BUT NOT BE LIMITED TO, BRACING, SHORING FOR LOADS DUE TO FOR BID PURPOSES ONLY, ASSUME TOP OF BEDROCK 24FT BELOW FINISHED FLOOR (AT ELEVATION 76'-0"). SEE EQUIP EQUIPMENT SLV SHORT LEG VERTICAL
STRENGTH DESIGN: -28.8 PSF (WALL, FIELD); -35.4 PSF (WALL, CORNER); CONSTRUCTION EQUIPMENT, ETC. THE STRUCTURAL ENGINEER SHALL NOT BE RESPONSIBLE FOR THE CONTRACTOR'S SPECIFICATIONS FOR ADD OR DEDUCT PROVISIONS FROM THE BASE BID. EXACT BEARING ELEVATION SHALL BE FIELD EXIST (E) EXISTING SIM SIMILAR
-46.2 PSF (ROOF, ZONE 1); -61.0 PSF (ROOF, ZONES 2 & 3) MEANS, METHODS, TECHNIQUES, SEQUENCES FOR PROCEDURE OF CONSTRUCTION, OR THE SAFETY PRECAUTIONS AND THE VERIFIED BY SOILS ENGINEER AT THE TIME OF DRILLING. EXP ANCH EXPANSION ANCHOR SOG SLAB ON GRADE
- (BASED ON 10 SF) PROGRAMS INCIDENT THERETO, NOR SHALL OBSERVATION VISITS TO THE SITE INCLUDE INSPECTION OF THESE ITEMS. DESIGN END BEARING PRESSURE = 25,000 PSF EXP JT (EJ) EXPANSION JOINT SOV SLAB ON VOID
ALLOWABLE STRESS DESIGN: -17.3 PSF (WALL, FIELD); -21.2 PSF (WALL, CORNER); DESIGN SIDE SHEAR RESISTANCE = 2,500 PSF EW EACH WAY SQ SQUARE
-27.7 PSF (ROOF, ZONE 1); -36.6 PSF (ROOF, ZONES 2 & 3) CONSTRUCTION MATERIALS SHALL BE SPREAD OUT IF PLACED ON FRAMED CONSTRUCTION. LOAD SHALL NOT EXCEED THE MINIMUM DEAD LOAD PRESSURE = 15,000 PSF ON END BEARING AREA FDN FOUNDATION STD STANDARD
- (BASED ON 10 SF) DESIGN LIVE LOAD PER SQUARE FOOT. MINIMUM PENETRATION INTO BEDROCK = 8 FT FF FINISHED FLOOR STL STEEL
MINIMUM LENGTH = 20 FT FOM FACE OF MEMBER T&B TOP AND BOTTOM
FOW FACE OF WALL TL TOTAL LOAD
SEISMIC DESIGN DATA: WHERE REFERENCE IS MADE TO VARIOUS TEST STANDARDS FOR MATERIALS, SUCH STANDARDS SHALL BE THE LATEST
FP FIRE PROOFING TJI PLYWOOD WEB JOIST
RISK CATEGORY = IV EDITION AND/OR ADDENDA. SHEAR RINGS ARE NOT REQUIRED

CITY OF THORNTON
FTG FOOTING TOB TOP OF BEAM
SEISMIC IMPORTANCE FACTOR, Ie = 1.5
FV FIELD VERIFY TOC TOP OF CONCRETE
Ss = 0.194, S1 = 0.056 ESTABLISH AND VERIFY ALL OPENINGS AND INSERTS FOR ARCHITECTURAL, MECHANICAL, PLUMBING AND ELECTRICAL FOUNDATION SUBMITTALS:

FIRE STATION #7
GA GAGE TOD TOP OF DECK
SITE CLASS: D WITH APPROPRIATE TRADES, DRAWINGS AND SUBCONTRACTORS PRIOR TO CONSTRUCTION. SHOW PENETRATIONS AND GALV GALVANIZED TOF TOP OF FOOTING
SDS = 0.207, SD1 = 0.090 BLOCKOUT LOCATIONS ON SHOP DRAWINGS AND OTHER SUBMITTALS PRIOR TO ENGINEER’S REVIEW. THE FOLLOWING ITEMS SHALL BE SUBMITTED FOR REVIEW FOR THE LIMITED PURPOSE OF CHECKING FOR CONFORMANCE WITH GSN GENERAL STRUCTURAL NOTES TOL TOP OF LEDGER
SEISMIC DESIGN CATEGORY C INFORMATION GIVEN AND THE DESIGN CONCEPT EXPRESSED IN THE CONTRACT DOCUMENTS. REFER TO PROJECT GLB (GLULAM) GLUED-LAMINATED BEAM TOM TOP OF MASONRY
BASIC SEISMIC FORCE RESISTING SYSTEM = STEEL SYSTEMS NOT SPECIFICALLY DETAILED FOR SEISMIC RESISTANCE / INTERMEDIATE OPTIONS ARE FOR CONTRACTOR'S CONVENIENCE. IF HE CHOOSES AN OPTION, CONTRACTOR SHALL BE RESPONSIBLE FOR SPECIFICATIONS FOR ADDITIONAL REQUIRED SUBMITTALS. GT GIRDER TRUSS TOP TOP OF PLATE
REINFORCED MASONRY SHEAR WALLS. ALL NECESSARY CHANGES AND SHALL COORDINATE ALL DETAILS. HC PRECAST HOLLOW CORE PLANK TOS TOP OF STEEL
DESIGN BASE SHEAR, V=108K (ULT) MIX DESIGNS HDAS HEADED ANCHOR STUD TOW TOP OF WALL
SEISMIC RESPONSE COEFFICIENT, STRENGTH DESIGN, Cs = 0.103 NOTES AND DETAILS ON DRAWINGS SHALL TAKE PRECEDENCE OVER GENERAL STRUCTURAL NOTES AND TYPICAL DETAILS. STEEL REINFORCEMENT SHOP DRAWINGS HDG HOT-DIP GALVANIZED TYP TYPICAL

RESPONSE MODIFICATION FACTOR, R = 3 TYPICAL DETAILS MAY NOT NECESSARILY BE CUT ON PLANS, BUT APPLY UNLESS NOTED OTHERWISE. WHERE NO DETAILS WELDING CERTIFICATES HK HOOK UNO UNLESS NOTED OTHERWISE
HORIZ HORIZONTAL VERT VERTICAL
ANALYSIS PROCEDURE = EQUIVALENT LATERAL FORCE PROCEDURE ARE SHOWN, CONSTRUCTION SHALL CONFORM TO SIMILAR WORK ON THE PROJECT. MATERIAL TEST REPORTS
HT HEIGHT WP WORK POINT
MATERIAL CERTIFICATES
WWF WELDED WIRE FABRIC
DESCRIPTION OF THE LATERAL LOAD AND CONNECTING DIAPHRAGM ELEMENTS THAT PROVIDE FOR LATERAL STRENGTH AND STABILITY IN DETAILS INDICATED AS TYPICAL (i.e., TYP) APPLY TO ALL SIMILAR CONDITIONS. FIELD QUALITY CONTROL TEST AND INSPECTION REPORTS
W/ (w/) WITH
THE COMPLETED STRUCTURE: COLD-WEATHER AND HOT-WEATHER PROCEDURES W/O (w/o) WITHOUT
• STEEL BRACED FRAMES AND MASONRY SHEAR WALLS SOME DETAILS ARE DEFINED AS TYPICAL TO THE PROJECT AND NOT NECESSARILY CUT OR CALLED OUT ON PLANS. IT
• METAL ROOF DIAPHRAGM (FLEXIBLE) IS THE CONTRACTOR'S RESPONSIBILITY TO APPLY AND COORDINATE THESE DETAILS WITH CONDITIONS DEFINED 3.0 CONCRETE:
• ANCHOR RODS AND BASE PLATE GROUT THROUGHOUT THE CONTRACT DOCUMENTS AS REQUIRED.

WALL STUD DEFLECTIONS HAVE BEEN LIMITED TO L/600 FOR MASONRY FINISH. ALL DIMENSIONS SHOWN (INCLUDING ELEVATIONS) ON STRUCTURAL DRAWINGS ARE TO ASSIST CONTRACTOR IN
ALL CONCRETE WORK SHALL CONFORM TO THE LATEST EDITION OF ACI 301, UNLESS MORE STRINGENT REQUIREMENTS ARE
DEFINED ELSEWHERE IN THE CONTRACT DOCUMENTS.
SHEET INDEX
VERIFICATION.
COORDINATION: CONCRETE DEFINED ON THE STRUCTURAL DRAWINGS SHALL HAVE THE FOLLOWING PROPERTIES: SHEET DESCRIPTION
CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION OF ALL DIMENSIONS WITH ARCHITECTURAL DRAWINGS PRIOR TO S0.1 GENERAL NOTES
START OF CONSTRUCTION – RESOLVE ANY DISCREPANCY WITH THE ARCHITECT. CONTRACTOR SHALL COORDINATE ALL USE MIN f'c, 28 DAY MAX SLUMP MAX w/c RATIO AIR CONTENT* CEMENT TYPE S0.2 GENERAL NOTES
THESE DRAWINGS ARE A SCHEMATIC REPRESENTATION OF THE STRUCTURAL SYSTEM AND REQUIREMENTS FOR THE PROJECT, AND ARE ONLY This document is not certified
A PORTION OF THE COMPLETE CONTRACT DOCUMENTS. THE STRUCTURAL SYSTEMS REQUIRE CAREFUL COORDINATION BETWEEN ALL FINISHED GRADE ELEVATIONS SHOWN IN CIVIL DRAWINGS WITH MINIMUM FOOTING DEPTHS SHOWN IN STRUCTURAL DRILLED PIERS ---------------- 3,000 PSI ------ 7” ------- 0.50 ------- NO REQUIREMENT ---- I/II S0.3 SPECIAL INSPECTIONS 10/08/2021 2:24:08 PM
STRUCTURAL COMPONENTS AND MATERIALS SHOWN IN THESE STRUCTURAL DRAWINGS, AND CAREFUL COORDINATION OF INFORMATION SHOWN DRAWINGS – NOTIFY ENGINEER OF ANY DISCREPANCY PRIOR TO START OF CONSTRUCTION. GRADE BEAMS ------------------ 3,000 PSI ------ 4” ------- 0.50 ------- NO REQUIREMENT ---- I/II A digitally signed version of this document has been
S0.4 SPECIAL INSPECTIONS provided by this office in accordance with State Law. If
ON OTHER DISCIPLINES’ DRAWINGS IN ORDER TO BE CONSTRUCTED. THE CONTRACTOR SHALL COORDINATE CONSTRUCTION OPERATIONS SLABS ON GROUND (INTERIOR) --- 4,000 PSI ------ 4” ------- 0.45 ------- NO REQUIREMENT ---- I/II the digital signature is not affixed to this document, this is
S0.5 LOAD MAPS
WITH ALL SUBCONTRACTORS AND OTHER RELATED ENTITIES TO ENSURE EFFICIENT AND ORDERLY INSTALLATION OF EACH PART OF THE ANY ENGINEERING DESIGN, PROVIDED BY OTHERS AND SUBMITTED FOR REVIEW, SHALL BEAR THE SEAL OF AN ENGINEER SLABS ON GROUND (EXTERIOR)**-- 3,750 PSI ------ 4” ------- 0.45 ----------- 5.0% ---------- I/II an uncertified copy.
WORK. EACH CONTRACTOR SHALL COORDINATE ITS OPERATIONS WITH THE OPERATIONS OF OTHER CONTRACTORS FOR PROPER REGISTERED IN THE STATE OF THE PROJECT. APPARATUS BAY SLAB ----------- 4,000 PSI ------ 4” ------- 0.45 ------- NO REQUIREMENT ---- I/II S0.6 LOAD MAPS
INSTALLATION, CONNECTION AND OPERATION. TOPPING FOR STEEL DECK ------- 3,500 PSI ------ 4” ------- 0.50 ------- NO REQUIREMENT ---- I/II S0.7 SCHEDULES
SUPPLIER OF ENGINEERED STRUCTURAL COMPONENTS (i.e. STEEL JOISTS, STAIRS, PRECAST ITEMS) SHALL BE BENCHES ---------------------- 5,000 PSI ------ 4" ------- 0.45 ----------- 5.0% ---------- I/II S0.8 SCHEDULES
EXISTING CONDITIONS: RESPONSIBLE FOR COMPLETE DESIGN AND SHALL USE ENTIRE CONTRACT DOCUMENTS TO INCLUDE ALL LOADS AND DETAIL S1.0 DRILLED PIER PLAN
REQUIREMENTS FROM ALL DISCIPLINES. SUPPLIER SHALL PROVIDE ADDITIONAL MATERIAL REQUIRED TO MEET ALL THEIR * SPECIFIED AIR CONTENT IS TOTAL CONCRETE AIR CONTENT (ENTRAPPED + ENTRAINED). S2.0 FOUNDATION PLAN
CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS PRIOR TO CONSTRUCTION. ANY VARIANCE FROM CONDITIONS SHOWN ON THESE REQUIREMENTS FOR INSTALLATION (i.e. WIDER BEARING PLATES, SHIMS, ERECTION BOLTS ETC.).
S2.1 FRAMING PLAN
DRAWINGS MUST BE BROUGHT TO THE ATTENTION OF THE ENGINEER IMMEDIATELY. ** PAVING AND EXTERIOR FLATWORK - REFER TO ARCHITECTURAL/CIVIL DRAWINGS AND SPECIFICATIONS.
STRUCTURAL STEEL SUPPLIER SHALL FURNISH BOLTS FOR OSHA CONNECTIONS. S2.2 ROOF FRAMING PLAN
SHOP DRAWINGS/SUBMITTALS: MECHANICALLY VIBRATE ALL CONCRETE WHEN PLACED, EXCEPT THAT SLABS ON GRADE NEED BE VIBRATED ONLY AROUND S3.1 CONCRETE DETAILS 10/08/2021
SPECIAL INSPECTION: UNDER-FLOOR DUCTS, ETC. IF PLASTICIZER IS USED, A HIGHER FINAL SLUMP MAY BE ALLOWED UPON STRUCTURAL S3.2 CONCRETE DETAILS
SHOP DRAWINGS SHALL BE SUBMITTED FOR ALL STRUCTURAL ITEMS IN ADDITION TO ITEMS REQUIRED BY ARCHITECTURAL 1 ENGINEER'S APPROVAL. CAST CLOSURE POUR AROUND COLUMNS AFTER COLUMN DEAD LOAD IS APPLIED. UNLESS APPROVED S3.3 FOUNDATION DETAILS
SPECIFICATIONS. THE STRUCTURAL SHOP DRAWING REVIEW IS INTENDED TO HELP THE ENGINEER VERIFY THE DESIGN CONCEPT. THE THE SPECIAL INSPECTOR SHALL BE IDENTIFIED AND THEIR CREDENTIALS PROVIDED TO THE CITY FOR REIVEW PRIOR RO OTHERWISE IN WRITING BY THE ARCHITECT, ALL CONCRETE SLABS ON GRADE SHALL BE BOUND BY CONTROL JOINTS (KEYED S3.4 FOUNDATION DETAILS
CONTRACTOR SHALL REVIEW ALL SHOP DRAWINGS PRIOR TO SUBMITTAL. ITEMS NOT IN ACCORDANCE WITH CONTRACT DOCUMENTS SHALL PERMIT ISSUANCE. OR SAW CUT), SUCH THAT THE ENCLOSED AREA DOES NOT EXCEED 144 SQUARE FEET. KEYED CONTROL JOINTS NEED ONLY REVISION NAME DATE
S4.1 MASONRY DETAILS 1
BE IDENTIFIED UPON HIS REVIEW AND REVISED PRIOR TO FORWARDING TO ARCHITECT. THE STRUCTURAL SHOP DRAWINGS WILL BE OCCUR AT EXPOSED EDGES DURING POURING, ALL OTHER JOINTS MAY BE SAW CUT. REFER TO ARCHITECTURAL DRAWINGS FOR
S4.2 MASONRY DETAILS 1 ADDENDUM #1 2021 1008
RETURNED FOR RESUBMITTAL IF A CURSORY REVIEW SHOWS MAJOR ERRORS WHICH SHOULD HAVE BEEN FOUND BY THE CONTRACTOR’S THE OWNER SHALL EMPLOY ONE OR MORE SPECIAL INSPECTORS OR AGENCIES WHO SHALL PROVIDE INSPECTIONS DURING SPECIFIC JOINT LOCATIONS.
CHECKING. CONSTRUCTION FOR THE ITEMS LISTED BELOW. THE CONTRACTOR SHALL COOPERATE WITH THE SPECIAL INSPECTOR AND S4.3 MASONRY DETAILS
SHALL FURNISH TOOLS, EQUIPMENT AND ASSISTANCE AS REQUESTED. THE CONTRACTOR SHALL NOTIFY THE INSPECTOR AT ALL SLABS SHALL BE WATER-CURED OR STEAM-CURED PER THE SPECIFICATIONS. S5.1 STEEL DETAILS
VERIFY ALL DIMENSIONS WITH ARCHITECT AND ALL FINISHED GRADE WITH CIVIL DRAWINGS. LEAST 24 HOURS PRIOR TO EXPECTED TIME FOR OPERATIONS REQUIRING TESTING OR INSPECTION SERVICES. THE S5.2 STEEL DETAILS
INSPECTOR SHALL FAMILIARIZE HIMSELF WITH ALL APPLICABLE PORTIONS OF THE CONTRACT DOCUMENTS PERTAINING TO REVIBRATE TOPS OF DRILLED PIERS 15 MINUTES AFTER PLACING CONCRETE. S5.3 STEEL DETAILS
ANY CHANGES, SUBSTITUTIONS, OR DEVIATIONS FROM CONTRACT DOCUMENTS SHALL BE CLOUDED BY MANUFACTURER OR FABRICATOR. ANY THE AREA OF INVESTIGATION PRIOR TO PERFORMING SERVICES. COMPENSATION FOR SPECIAL INSPECTION SERVICES
S5.4 STEEL DETAILS
OF THE AFOREMENTIONED WHICH ARE NOT CLOUDED OR FLAGGED BY SUBMITTING PARTIES, SHALL NOT BE CONSIDERED APPROVED AFTER SHALL BE PROVIDED BY THE OWNER. FLY ASH SHALL BE LIMITED TO 20% OF CEMENTITIOUS MATERIALS.
ENGINEER'S REVIEW, UNLESS NOTED ACCORDINGLY. S5.5 CFS DETAILS
THE LEFFLER GROUP IS NOT THE SPECIAL INSPECTOR, AND SHALL NOT PERFORM THESE SERVICES. “WET STABBING” OF ANY EMBEDDED ITEM OR BOLT IS STRICTLY PROHIBITED. S5.6 CFS DETAILS ISSUE DATE: 2021 0907
THE ENGINEER HAS THE RIGHT TO APPROVE OR DISAPPROVE ANY CHANGES TO CONTRACT DOCUMENTS AT ANY TIME BEFORE OR AFTER S5.7 CFS DETAILS
SHOP DRAWING REVIEW. INSPECTION BY THE OWNER OR OWNER'S AGENT DOES NOT RELIEVE THE CONTRACTOR OF HIS RESPONSIBILITY TO VOID FORMS:
PERFORM THE WORK IN ACCORDANCE WITH THE CONTRACT DOCUMENTS.
THE SHOP DRAWINGS DO NOT REPLACE THE CONTRACT DOCUMENTS. ITEMS OMITTED OR SHOWN INCORRECTLY AND ARE NOT FLAGGED BY VOID FORM UNITS SHALL HAVE A BIODEGRADABLE PAPER SURFACE, TREATED FOR MOISTURE RESISTANCE. STRUCTURALLY

GENERAL NOTES
www.TheLefflerGroup.com info@theLefflerGroup.com
165 S. UNION BLVD, STE 360, LAKEWOOD, CO 80228

S0.1
THE STRUCTURAL ENGINEER OR ARCHITECT ARE NOT TO BE CONSIDERED CHANGES TO CONTRACT DOCUMENTS. IT IS THE CONTRACTOR'S PER IBC SECTION 1704, SPECIAL INSPECTION IS REQUIRED FOR THE ITEMS DEFINED IN THE SPECIAL INSPECTION SUFFICIENT TO SUPPORT THE WEIGHT OF PLASTIC CONCRETE AND OTHER SUPERIMPOSED LOADS. CONTRACTOR MUST WORK
MASONRY, STEEL, AND MECHANICAL SUBCONTRACTORS NOTE:
RESPONSIBILITY TO MAKE SURE ITEMS ARE CONSTRUCTED TO CONTRACT DOCUMENTS. MATRIX FOR EACH TYPE OF CONSTRUCTION IN THESE STRUCTURAL CONSTRUCTION DOCUMENTS. CLOSELY WITH THE MANUFACTURER TO ENSURE MATERIAL SELECTED DEGRADES QUICKLY AND COMPLETELY AFTER CONCRETE IS
STRUCTURAL DRAWINGS DO NOT INDICATE ALL WALL, FLOOR, OR ROOF

P - 720.890.4095 © 2021
PLACED ABOVE. VOID FORM UNITS SHALL NOT BE WRAPPED IN PLASTIC NOR HAVE PLASTIC PLACED ABOVE OR BELOW.
PENETRATIONS FOR MECH DUCTS, DRAINS, VENTS, ETC.; DRAWINGS
THE ADEQUACY OF ENGINEERING DESIGNS AND LAYOUT PERFORMED BY OTHERS RESTS WITH THE DESIGNING OR SUBMITTING AUTHORITY.
INDICATE TYPICAL AND SPECIAL CONDITIONS FOR FRAMING AT THE
6” VOID REQUIRED AT ALL SLABS.
PENETRATIONS. GENERAL CONTRACTOR AND SUB CONTRACTORS SHALL BE
REVIEWING IS INTENDED ONLY AS AN AID TO THE CONTRACTOR IN OBTAINING CORRECT SHOP DRAWINGS. RESPONSIBILITY FOR 4” VOID REQUIRED AT ALL GRADE BEAMS.
RESPONSIBLE FOR DETERMINING AND/OR MODIFYING OPENING LOCATIONS,
CORRECTNESS SHALL REST WITH THE CONTRACTOR.
ELEVATIONS, AND DIMENSIONS FOR MECH UNLESS NOTED OTHERWISE.
COORDINATION TO BE COMPLETED PRIOR TO FABRICATION OF STRUCTURAL
REPRODUCTION OF ANY PORTION OF THE CONTRACT DOCUMENTS FOR USE IN SUBMITTALS IS NOT PERMITTED AND MAY RESULT IN
STEEL AND ROOF JOISTS.
REJECTION.
C ALLRED&ASSOCIATES 2021
GENERAL STRUCTURAL NOTES - CONTINUED
APPLY UNLESS NOTED OTHERWISE

CERTIFICATION FOR ANCHORAGE INSTALLER ALL STRUCTURAL STEEL SHALL BE ASTM A992 (Fy = 50 KSI). ALL CHANNELS, ANGLES, AND PLATES SHALL BE ASTM
REINFORCING STEEL: ANCHORAGE ICC APPROVAL A36 (Fy = 36 KSI). ALL PIPE STEEL SHALL BE ASTM A501 (Fy = 36 KSI) OR ASTM A53, TYPE E OR S, GRADE B (Fy STEEL FOR 12, 14 AND 16 GAGE STUDS, JOISTS, TRACKS AND FOR ALL DIAGONAL TENSION STRAPS SHALL HAVE A
MIX DESIGNS = 35 KSI). ALL TUBE STEEL SHALL BE ASTM A500 (Fy = 46 KSI). ALL ANCHOR RODS SHALL BE ASTM F1554, GRADE MINIMUM YIELD STRENGTH OF 50 KSI. STEEL FOR ALL 18 AND 20 GAGE STUDS, JOISTS, AND TRACKS, AND FOR ALL
ASTM A615 (Fy = 60 KSI) DEFORMED BARS FOR ALL BARS. ALL GRADE 60 REINFORCING TO BE WELDED OR FIELD BENT STEEL REINFORCEMENT SHOP DRAWINGS 36 UNLESS NOTED OTHERWISE. GAGES OF ACCESSORIES AND BRIDGING SHALL HAVE A MINIMUM YIELD STRENGTH OF 33 KSI. STEEL SHALL BE G60
SHALL BE ASTM A706. WELDED WIRE FABRIC PER ASTM A185, WIRE PER ASTM A82. NO TACK WELDING OF REINFORCING FORMWORK SHOP DRAWINGS GALVANIZED <PAINTED>. STEEL SHEET FOR ALL STRUCTURAL FRAMING SHOWN IN THESE DRAWINGS SHALL CONFORM TO
BARS ALLOWED WITHOUT PRIOR REVIEW OF PROCEDURE WITH THE STRUCTURAL ENGINEER. LATEST ACI CODE AND DETAILING WELDING CERTIFICATES ALL REFERENCE TO HEADED STUDS SHALL BE HIGH STRENGTH HEADED STUDS. ATTACHMENT OF HEADED STUDS SHALL ASTM A 1003/A 1003M, STRUCTURAL GRADE, TYPE H, METALLIC COATED.

S
MANUAL APPLY. CLEAR CONCRETE COVERAGES AS FOLLOWS: MATERIAL TEST REPORTS CONFORM TO ALL REQUIREMENTS OF THE LATEST EDITION OF THE "RECOMMENDED PRACTICES FOR STUD WELDING" AND
MATERIAL CERTIFICATES THE "STRUCTURAL WELDING CODE" PUBLISHED BY AWS. UNLESS SPECIFICALLY NOTED ELSEWHERE WITHIN THESE ENGINEERED COLD FORMED METAL FRAMING SHOP DRAWINGS, THE

210106
CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH ------------- 3" FIELD QUALITY CONTROL TEST AND INSPECTION REPORTS FOLLOWING SHALL APPLY AS A MINIMUM. ALL STUDS SHALL BE SECURELY SEATED FOR FULL END BEARING ON TOP AND

INTERIOR DESIGN
EXPOSED TO EARTH OR WEATHER COLD-WEATHER AND HOT-WEATHER PROCEDURES ALL BOLTS, ANCHOR BOLTS, EXPANSION BOLTS, ETC. SHALL BE INSTALLED WITH STEEL WASHERS AT FACE OF WOOD OR BOTTOM TRACK. UNLESS NOTED OTHERWISE, PROVIDE DOUBLE STUDS AT ALL JAMBS, CORNERS, INTERSECTIONS, BEAM

580 BURBANK ST. SUITE 125, BROOMFIELD, CO 80020 PHONE: 303.465.4306 FAX: 303.465.4382 www.allredarch.com
T
#6 OR LARGER ------------------------------------------- 2" AT SLOTTED HOLES IN STEEL SECTIONS. BEARINGS AND JOIST BEARINGS. BRIDGING SHALL BE INSTALLED PER MANUFACTURER'S RECOMMENDATION WITH THE
#5 AND SMALLER ----------------------------------------- 1 1/2" 4.0 MASONRY: FOLLOWING MINIMUM REQUIREMENTS.

A
COLUMNS (TO TIES) ----------------------------------------- 1 1/2" ALL WELDING SHALL BE PERFORMED BY WELDERS HOLDING VALID CERTIFICATES AND HAVING CURRENT EXPERIENCE IN
BEAMS (TO STIRRUPS) --------------------------------------- 1 1/2" ALL MASONRY WORK SHALL CONFORM TO THE LATEST EDITION OF ACI 530.1, UNLESS MORE STRINGENT REQUIREMENTS ARE THE TYPE OF WELD SHOWN ON THE DRAWINGS OR NOTES. CERTIFICATES SHALL BE THOSE ISSUED BY AN ACCEPTED BRIDGING SHALL BE STEEL CHANNEL MADE FROM ASTM A1003/A1003M, STRUCTURAL GRADE, TYPE H, METALLIC
I

| JOB NO.
FLAT SLAB ------------------------------------------------- 3/4" DEFINED ELSEWHERE IN THE CONTRACT DOCUMENTS. TESTING AGENCY. ALL WELDING DONE BY E70 SERIES LOW HYDROGEN RODS UNLESS NOTED OTHERWISE. FOR GRADE 60 COATED STEEL SHEET, OF SAME GRADE AND COATING DESIGNATION USED FOR FRAMING MEMBERS.

ALL OTHERS PER LATEST EDITION OF ACI 318. HOLLOW CONCRETE MASONRY UNITS SHALL BE MEDIUM WEIGHT AND SHALL CONFORM TO ASTM C90, GRADE N, TYPE 1,F'cmu =
REINFORCING BARS, USE E90 SERIES. ALL WELDING PER LATEST AMERICAN WELDING SOCIETY STANDARDS, (EXCEPT
STEEL JOISTS AND JOIST GIRDERS SHALL COMPLY WITH SJI STANDARDS). SHOP WELDS AND FIELD WELDS SHALL BE PROVIDE WALL BRIDGING AS NOTED ON THE DRAWINGS. SOLID BLOCKING SHALL BE INSTALLED IN LIEU OF
C
O
3,250 PSI, F'm = 2,500 PSI, RUNNING BOND, MORTAR TYPE S, GROUT 2,500 PSI. GROUT MIX SHALL CONFORM TO ASTM SHOWN ON THE SHOP DRAWINGS SUBMITTED FOR REVIEW. ALL FULL (COMPLETE) PENETRATION WELDS SHALL BE TESTED BRIDGING WHERE NOTED ON THE DRAWINGS.
C476. MORTAR MIX SHALL CONFORM TO ASTM C270. MECHANICALLY VIBRATE GROUT IN VERTICAL SPACES IMMEDIATELY AND CERTIFIED BY AN INDEPENDENT TESTING LABORATORY.

S
LAP SPLICES IN CONCRETE:
AFTER POURING AND AGAIN ABOUT 5 MINUTES LATER. PROVIDE CLEANOUTS IF GROUT LIFT EXCEEDS 4'-0" IN BLOCK PROVIDE SOFFIT AND JOIST BRIDGING AS NOTED ON THE DRAWINGS. SOLID BLOCKING SHALL BE INSTALLED

S
LAP SPLICES, UNLESS NOTED OTHERWISE, SHALL BE CLASS "B" TENSION LAP SPLICES PER LATEST EDITION OF ACI 318. WALLS. MAXIMUM GROUT LIFT SHALL BE 8'-0". UNLESS NOTED OTHERWISE ON THE PLANS, PLACE CONTROL JOINTS IN FILLET WELD SIZES SHOWN IN CONTRACT DOCUMENTS ARE THE FILLET WELD LEG SIZE. GROOVE WELD SIZES SHOWN IN IN LIEU OF BRIDGING WHERE NOTED ON THE DRAWINGS.

|
LAP SPLICES IN CONCRETE COLUMNS SHALL BE STANDARD COMPRESSION LAP SPLICES. STAGGER SPLICES A MINIMUM OF MASONRY WALLS SUCH THAT NO STRAIGHT RUN OF WALL EXCEEDS 24'-0". CONTROL JOINTS SHALL NOT OCCUR AT WALL CONTRACT DOCUMENTS ARE THE REQUIRED WELD SIZE “(E)”.

A
ONE LAP LENGTH. LAPS IN WELDED WIRE FABRIC SHALL BE MADE SO THAT THE OVERLAP, MEASURED BETWEEN OUTERMOST CORNERS, INTERSECTIONS, ENDS, WITHIN 24" OF CONCENTRATED POINTS OF BEARING OR JAMBS, OR OVER OPENINGS BRIDGING CLIPS TO PROVIDE ATTACHMENT TO STUD WEB AND WRAP AROUND THE BRIDGING CHANNEL. BRIDGING
CROSS WIRES OF EACH FABRIC SHEET, IS NOT LESS THAN THE SPACING OF CROSS WIRES PLUS 2 INCHES. ALL WELDED UNLESS SPECIFICALLY SHOWN ON THE STRUCTURAL DRAWINGS. SOLID GROUT 24” BELOW AND TO EACH SIDE OF POINT LOAD THE ENGINEER SHALL BE COMPENSATED FOR ANY ANALYSIS, RE-DESIGN AND/OR REVIEW OF CONNECTIONS NOT ACCESSORIES SHALL BE FORMED FROM STRUCTURAL QUALITY STEEL WITH MINIMUM YIELD STRENGTH OF 50 KSI AND HAVE

PLANNING
&
WIRE FABRIC SHALL BE CHAIRED TO ENSURE PROPER CLEARANCES. CONDITIONS ON MASONRY MINIMUM. ALL MASONRY BELOW FINISHED FLOOR OR GRADE SHALL BE GROUTED SOLID. “WET CONFORMING TO THE CONTRACT DOCUMENTS, WHETHER MADE BY THE CONTRACTOR, THEIR SUBCONTRACTOR(S), MINIMUM PROTECTIVE COATING COMPLYING WITH ASTM A1003/A1003M (OR ASTM A653/A653M).
STABBING” OF ANY EMBEDDED ITEM OR BOLT IS STRICTLY PROHIBITED. FABRICATOR, DETAILER OR ERECTOR. ALL STRUCTURAL FRAMING ACCESSORIES SHALL BE FORMED FROM STRUCTURAL QUALITY STEEL WITH MINIMUM YIELD
ALL SPLICE LOCATIONS SUBJECT TO APPROVAL BY THE STRUCTURAL ENGINEER. UNLESS NOTED, LAP TOP BARS AT MID- STRENGTH OF 50 KSI AND HAVE MINIMUM PROTECTIVE COATING EQUAL TO ASTM A1003 G-60 GALVANIZED COATING.
SPAN AND BOTTOM BARS OVER SUPPORT. PROVIDE BENT CORNER BARS TO MATCH AND LAP WITH HORIZONTAL BARS AT ALL HOLLOW BRICK MASONRY SHALL CONFORM TO ASTM C652, GRADE MW, TYPE HBS, F'm 2,300 PSI, RUNNING BOND, MORTAR CONTRACTOR SHALL NOT RECEIVE ADDITIONAL COMPENSATION FOR DETAILING, FABRICATION, ERECTION OR SCHEDULE
CORNERS AND INTERSECTIONS PER TYPICAL DETAILS. REINFORCING BAR SPACING GIVEN ARE MAXIMUM ON CENTERS. ALL TYPE S, 1,800 PSI. GROUT 3,000 PSI. MECHANICALLY VIBRATE GROUT IN VERTICAL SPACES IMMEDIATELY AFTER POURING IMPACTS AS A RESULT OF INCORRECT DETAILING IN THE SHOP DRAWINGS. WHEN REQUIRED, DEFLECTION CONNECTIONS SHALL ALLOW FOR POSITIVE ATTACHMENT TO STRUCTURE AND STUD WEB AND

ALLRED
BARS PER CRSI SPECIFICATIONS AND HANDBOOK. DOWEL ALL VERTICAL REINFORCING TO FOUNDATION WITH STANDARD 90- AND AGAIN ABOUT 5 MINUTES LATER. PROVIDE CLEANOUTS IF GROUT LIFT EXCEEDS 4'-0" IN BLOCK WALLS. MAXIMUM SHALL PROVIDE FRICTIONLESS, VERTICAL MOVEMENT. CONNECTION PRODUCTS ARE REQUIRED TO HAVE A VALID ICC ES
DEGREE HOOKS UNLESS NOTED OTHERWISE. SECURELY TIE ALL BARS IN LOCATION BEFORE PLACING CONCRETE. CONCRETE GROUT LIFT SHALL BE 8'-0". UNLESS NOTED OTHERWISE ON THE PLANS, PLACE CONTROL JOINTS IN MASONRY WALLS SUCH HIGH STRENGTH BOLTS: REPORT OR EQUIVALENT COMPLYING WITH ICC ACCEPTANCE CRITERIA AC261. ALL STRUCTURAL FRAMING ACCESSORIES

|
COLUMN DOWEL EMBEDMENT SHALL BE A STANDARD COMPRESSION DOWEL WITH EMBEDMENT LENGTH ACCORDING TO THE LATEST THAT NO STRAIGHT RUN OF WALL EXCEEDS 24'-0". CONTROL JOINTS SHALL NOT OCCUR AT WALL CORNERS, INTERSECTIONS, SHALL BE FORMED FROM STRUCTURAL QUALITY STEEL WITH MINIMUM YIELD STRENGTH OF 50 KSI AND HAVE MINIMUM
EDITION OF THE ACI 318. ENDS, WITHIN 24" OF CONCENTRATED POINTS OF BEARING OR JAMBS, OR OVER OPENINGS UNLESS SPECIFICALLY SHOWN ON ALL HIGH STRENGTH BOLTS SHALL BE ASTM 7/8” DIAMETER A325 AND SHALL BE INSTALLED AS BEARING-TYPE PROTECTIVE COATING COMPLYING WITH ASTM 1003/A1003M (OR ASTM A653/A653M).

ARCHITECTURE
THE STRUCTURAL DRAWINGS. SOLID GROUT 24” BELOW AND TO EACH SIDE OF POINT LOAD CONDITIONS ON MASONRY CONNECTIONS WITH THREADS INCLUDED IN SHEAR PLANE (I.E. A TYPE "N" CONNECTION) UNLESS NOTED

PERMIT SET
CONCRETE INSERTS: MINIMUM. ALL MASONRY BELOW FINISHED FLOOR OR GRADE SHALL BE GROUTED SOLID. “WET STABBING” OF ANY EMBEDDED OTHERWISE. UNLESS SPECIFICALLY NOTED OTHERWISE IN THESE STRUCTURAL DRAWINGS, ALL A325 HIGH STRENGTH RIGID CONNECTIONS FOR ATTACHMENT OF METAL FRAMING TO METAL FRAMING AND TO THE PRIMARY STRUCTURE SHALL BE
ITEM OR BOLT IS STRICTLY PROHIBITED. BOLTS SHALL BE TENSIONED TO THE VALUES SHOWN IN TABLE J3.1 OF THE AISC SPECIFICATION FOR STEEL FORMED FROM STRUCTURAL QUALITY STEEL WITH MINIMUM YIELD STRENGTH OF 50 KSI AND HAVE MINIMUM PROTECTIVE
THIN SLAB TYPE INSERTS SHALL BE GALVANIZED AND HAVE THE FOLLOWING MINIMUM WORKING LOADS(A 4:1 RATIO OF BUILDINGS, USING ANY AISC APPROVED METHOD. ALL HIGH STRENGTH BOLTING SHALL BE INSPECTED BY AN COATING EQUAL TO COMPLYING WITH ASTM 1003/A1003M (OR ASTM A653/A653M).
ULTIMATE TO WORKING VALUES IS ASSUMED): VERTICAL REINFORCING LAP SPLICES SHALL BE 48 BAR DIAMETERS. LAP SPLICES SHALL BE 1.3 X LAP LENGTH WHEN INDEPENDENT TESTING LABORATORY.
ADJACENT SPLICES ARE SEPARATED BY 3" OR LESS. ALL MEMBERS TO BE MANUFACTURED BY A MEMBER OF “STEEL STUD MANUFACTURERS ASSOCIATION” (SSMA), OR APPROVED
BOLT DIAMETER SHEAR TENSION STEEL DECKING: EQUAL.
1/2" 1,000 LBS. 650 LBS. HORIZONTAL REINFORCING LAP SPLICES SHALL BE 48 BAR DIAMETERS. STAGGER SPLICES A MINIMUM OF 40 BAR
5/8” 1,250 LBS. 700 LBS. DIAMETERS. DO NOT SPLICE WITHIN 8'-0" OF CONTROL JOINTS. PROVIDE BENT BARS PER TYPICAL DETAILS, TO MATCH ALL STEEL DECK SHALL BE DESIGNED, FABRICATED, WELDED AND ERECTED IN ACCORDANCE WITH THE LATEST EDITION POWDER ACTUATED FASTENERS (PAF'S) SHALL BE HILTI X-U 0.157” DIA. OR APPROVED EQUAL. RE: DETAILS FOR
3/4" 1,600 LBS. 850 LBS. HORIZONTAL BOND BEAM REINFORCING, AT CORNERS AND WALL INTERSECTION TO MAINTAIN BOND BEAM CONTINUITY. OF THE "STANDARD SPECIFICATIONS" OF THE STEEL DECK INSTITUTE. EMBED INTO CONCRETE; RE: MFR FOR REQ'D EMBED. IN STEEL.

MASONRY LINTELS: ALL WELDING SHALL BE PERFORMED BY WELDERS EXPERIENCED IN LIGHT GAGE STEEL DECK WORK. DECK WELDING MAY BE ALL SCREWS TO BE #10 U.N.O., SCREWS ATTACHED PER MFR. INSTRUCTIONS AND SHALL PENETRATE 3 THREAD MINIMUM
COIL LOOP INSERTS SHALL BE GALVANIZED AND HAVE THE FOLLOWING MINIMUM WORKING LOADS(A 3:1 RATIO OF ULTIMATE ACHIEVED WITH E60 SERIES LOW HYDROGEN RODS. BEYOND THE ATTACHED MATERIAL.
TO WORKING VALUES IS ASSUMED): UNLESS NOTED OTHERWISE OR SHOWN, PROVIDE LINTELS IN MASONRY WALLS, PER STEEL OR MASONRY LINTEL SCHEDULES.
USE THESE LINTELS FOR OPENINGS REQUIRED BY OTHER DISCIPLINES (MECHANICAL, ELECTRICAL, PLUMBING, ETC.). STEEL GRATING: ALL WELDING SHALL BE PERFORMED BY WELDERS EXPERIENCED IN LIGHT GAGE STRUCTURAL STEEL FRAMING WORK.
BOLT DIAMETER SHEAR TENSION PROVIDE MINIMUM 5" BEARING OF ANGLES ON JAMBS. UNLESS SPECIFICALLY INDICATED, CONTRACTOR MAY USE EITHER
1/2" 2,200 LBS. 2,820 LBS. STEEL OR MASONRY LINTELS. UNLESS NOTED OTHERWISE IN ARCHITECTURAL SPECIFICATIONS, USE GALVANIZED STEEL GRATING WITH 2-1/2" X 3/16" DO NOT NOTCH FLANGES OF JOISTS OR STUDS.

CITY OF THORNTON
5/8" 3,000 LBS. 3,620 LBS. BEARING BARS AT 1 3/16" O.C. AND CROSS BARS AT 4" O.C. GRATING SHALL BE ERECTED AND ATTACHED PER

FIRE STATION #7
3/4” 3,100 LBS. 3,660 LBS. THESE LINTELS, OR THE OPENING THEY SPAN, SHALL NOT BE PLACED SO AS TO INTERFERE WITH THE REQUIREMENTS OF MANUFACTURER'S RECOMMENDATIONS. HEADERS, JAMBS, STUDS, JOISTS, RAFTERS, KICKERS AND GIRTS SHALL BE INSTALLED IN ONE-PIECE LENGTHS WITH
OTHER STRUCTURAL ELEMENTS (I.E. BOND BEAMS, LINTELS, CONTROL JOINTS, CONCENTRATED POINTS OF BEARING, ETC.) 1 NO SPLICES PERMITTED UNLESS SPECIFICALLY NOTED OTHERWISE IN THESE DRAWINGS.
THREADED COIL RODS, COIL NUTS, ETC., USED IN CONJUNCTION WITH CONCRETE INSERTS, SHALL HAVE A WORKING LOAD WITHOUT THE PRIOR APPROVAL OF THE STRUCTURAL ENGINEER. STEEL JOISTS AND JOIST GIRDERS:
EQUAL TO OR GREATER THAN THE CORRESPONDING CONCRETE INSERT. CONTRACTOR SHALL SUBMIT MANUFACTURER'S SIZE PERFORMANCE SPECIFICATION FOR ALTERNATIVE STAIRS DESIGN:
AND STRENGTH DATA PRIOR TO CONSTRUCTION TO THE STRUCTURAL ENGINEER THRU THE ARCHITECT. SOLID GROUT SHALL BE PROVIDED BETWEEN WEBS AND MASONRY FACE SHELLS FOR FULL LENGTH OF ALL STEEL LINTELS. ALL JOISTS AND JOIST GIRDERS SHALL BE DESIGNED, FABRICATED, WELDED AND ERECTED IN ACCORDANCE WITH THE
MORTAR MAY BE USED FOR GROUT FOR THIS PURPOSE ONLY. FACE UNITS, SOAPS, ROMANS, ETC., SHALL BE LAID WITH LATEST EDITION OF THE "STANDARD SPECIFICATIONS" OF THE STEEL JOIST INSTITUTE. STAIRS SHALL BE DESIGNED FOR SELF WEIGHT PLUS A LIVE LOAD EQUAL TO 100 PSF. CONTRACTOR SHALL SUBMIT SHOP
POST INSTALLED ANCHORS TO CONCRETE: FULL HEAD AND BED JOINTS. FOR ADDITIONAL INFORMATION AT OPENINGS IN MASONRY WALLS, SEE TYPICAL DETAILS. DRAWINGS WITH DESIGN CALCULATIONS SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN THE GOVERNING
JOIST SIZES INDICATED ON PLANS HAVE BEEN DESIGNED BY THE LEFFLER GROUP IN ACCORDANCE WITH SJI JURISDICTION OF THE PROJECT, SUBMITTED FOR REVIEW PRIOR TO MANUFACTURE.
THE INSTALLATION OF POST INTALLED ANCHORS SHALL BE INSPECTED IN ACCORDANCE WITH SECTION 1.3 OF ACI 318, AND MASONRY VENEER WITH CMU BACKING (ADJUSTABLE WIRE): REQUIREMENTS.
THE GOVERNING BUILDING CODE. ANCHORS SHALL BE INSTALLED BY QUALIFIED PERSONNEL IN ACCORDANCE WITH THE METALS SUBMITTALS:
CONTRACT DOCUMENTS AND THE MANUFACTURER'S PRINTED INSTALLATION INSTRUCTIONS (MPII). THE FOLLOWING VENEER TIES SHALL BE OF 3/16” DIA. WIRE RECTANGULAR TYPE AND SHALL CONFORM TO ASTM A82. TIES SHALL BE OF ALL JOISTS AND JOIST GIRDERS SHALL BE CAMBERED FOR THE DESIGN DEAD LOAD. MANUFACTURER SHALL ADD
INSTALLATION CONDITIONS ARE REQUIRED: SUFFICIENT LENGTH SUCH THAT MINIMUM EMBEDMENT INTO CMU WALL AND MASONRY VENEER SHALL BE AT LEAST 1/2 THE ADDITIONAL WEB MEMBERS AS REQUIRED AND ADJUST CHORD AND WEB SIZES ACCORDINGLY, BUT SHALL NOT ALTER DEPTH THE FOLLOWING ITEMS SHALL BE SUBMITTED FOR REVIEW FOR THE LIMITED PURPOSE OF CHECKING FOR CONFORMANCE
BLOCK WIDTH. VENEER TIES SHALL BE HOT DIPPED GALVANIZED AND SHALL CONFORM TO ASTM A153. VENEER TIES SHALL OF JOISTS AND JOIST GIRDERS. WITH INFORMATION GIVEN AND THE DESIGN CONCEPT EXPRESSED IN THE CONTRACT DOCUMENTS. REFER TO PROJECT
NORMAL WEIGHT CONCRETE WITH A MIN f'c = 2500 PSI AND MAX f'c = 8000 PSI. BE PLACED 16” O.C. MAXIMUM VERTICAL SPACING AND 24” O.C. MAXIMUM HORIZONTAL SPACING. SPECIFICATIONS FOR ADDITIONAL REQUIRED SUBMITTALS.
CONCRETE AT TIME OF ANCHOR INSTALLATION SHALL HAVE A MINIMUM COMPRESSION STRENGTH OF 2500 PSI. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS FOR REVIEW PRIOR TO MANUFACTURE. SHOP DRAWINGS SHALL INCLUDE
MASONRY VENEER WITH STEEL STUD BACKING: DETAILS OF ANY OPTIONAL FIELD SPLICES, AND IF HIGH STRENGTH BOLTS OR FULL PENETRATION WELDS ARE COLD-FORMED METAL FRAMING (CFS) SHOP DRAWINGS: SUBMIT SHOP DRAWINGS FOR INSTALLATION OF COLD FORMED
ADHESIVE ANCHORS: UTILIZED, CONTRACTOR SHALL RETAIN AN INDEPENDENT TESTING LABORATORY TO CERTIFY COMPLIANCE WITH AISC AND STEEL SYSTEMS. PROVIDE 1/4” = 1'-0” SCALE ELEVATIONS OF ALL ROOFS, FLOORS, SOFFITS, WALLS AND OTHER
VENEER TIES SHALL BE OF 3/16” DIA. WIRE LOOP TIES AND SHOULD EMBED IN VENEER JOINT A MINIMUM OF 1/2 THE AWS SPECIFICATIONS RESPECTIVELY. WORK. SHOW ALL OPENINGS IN VERTICAL WORK; ALL BEAMS AND POSTS; SECTIONS THROUGH COLD FORMED
THE INSTALLATION OF ADHESIVE ANCHORS HORIZONTALLY OR UPWARDLY INCLINED TO SUPPORT SUSTAINED TENSION LOADS WIDTH OF THE VENEER. WIRE SHOULD BE COLD DRAWN STEEL CONFORMING TO ASTM A82. WIRE LOOP TIES SHALL BE CONSTRUCTION; AND FRAMING COORDINATED WITH THE BUILDING STRUCTURE AND OTHER TRADES. ALL SHOP DRAWINGS
SHALL ONLY BE PERFORMED BY PERSONNEL CERTIFIED BY THE ACI/CRSI ADHESIVE ANCHOR INSTALLER CERTIFICATION ATTACHED TO STEEL STUD BACKING AT 16” O.C. MAXIMUM VERTICAL SPACING. WIRE LOOP TIES SHALL BE ATTACHED TO ALL STEEL JOISTS/GIRDERS OR BEAMS SHALL BEAR AT A PANEL POINT. JOISTS OR BEAMS TO BE EQUALLY SPACED SHALL BE REVIEWED BY THE CONTRACTOR PRIOR TO SUBMITTING DRAWINGS FOR REVIEW. NO ENGINEERED DRAWINGS OR
PROGRAM. REFER TO THE SPECIAL INSPECTIONS MATRIX FOR ADDITIONAL TESTING AND INSPECTION REQUIREMENTS. THE STEEL STUDS USING 12 GAGE x 3/4” WIRE ANCHOR STRAP. ATTACH ANCHOR STRAP TO STUD USING 1 1/4” x #10 ZINC BETWEEN COLUMN LINES - TYPICAL U.N.O. PROVIDE BRIDGING AS REQUIRED, PER SJI SPECIFICATIONS. WHERE BOTTOM CALCULATIONS PERMITTED.
FOLLOWING INSTALLATION CONDITIONS ARE REQUIRED: COATED SCREWS. WIRE LOOP AND ANCHOR STRAPS SHALL BE HOT DIPPED GALVANIZED AND SHALL CONFORM TO ASTM A153. CHORD WELDING IS INDICATED, DO NOT WELD BOTTOM CHORD TO SUPPORT UNTIL FULL DEAD LOAD IS IN PLACE.
PRODUCT DATA
ANCHORS SHALL MEET THE REQUIREMENTS OF ACI 355.4 PROVIDE CONTINUOUS STEEL ANGLE 4” x 4” x 5/16” FOR SUPPORT OF ALL VENEER MORE THAN 25’ ABOVE ITS SUPPORT ON WHERE CROSS BRIDGING INTERFERES WITH MECHANICAL INSTALLATIONS, REMOVE THIS CROSS BRIDGING AFTER TOTAL SHOP DRAWINGS
ANCHORS SHALL BE INSTALLED IN HOLES DRILLED WITH A ROTARY IMPACT DRILL OR ROCK DRILL. CORE DRILLING IS NOT A FOUNDATION WALL OR WALL LEDGE. SEE TYPICAL DETAIL FOR ADDITIONAL INFORMATION. DEAD LOAD IS APPLIED AND REPLACE WITH HORIZONTAL ANGLES L2 X 2 X 3/16 AT TOP AND BOTTOM CHORDS. STRUCTURAL STEEL
PERMITTED. STEEL JOIST FRAMING
CONCRETE AT TIME OF ANCHOR INSTALLATION SHALL HAVE A MINIMUM AGE OF 21 DAYS. MASONRY SUBMITTALS: MANUFACTURER SHALL DESIGN JOIST SHOES WHERE BEARING LENGTH IS LESS THAN 4" AT LH SERIES JOIST AND LESS STEEL DECKING
CONCRETE TEMPERATURE AT TIME OF ANCHOR INSTALLATION SHALL BE AT LEAST 50 DEGREES F. THAN 3" AT K SERIES JOIST. COLD-FORMED METAL FRAMING (PLANS, DETAILS, ELEVATIONS) – NO ENGINEERING PERMITTED
DRY USE CONDITION – UNSATURATED CONCRETE, INSTALLATION HOLE CONTAINS NO WATER. THE FOLLOWING ITEMS SHALL BE SUBMITTED FOR REVIEW FOR THE LIMITED PURPOSE OF CHECKING FOR CONFORMANCE WITH METAL STAIRS
INFORMATION GIVEN AND THE DESIGN CONCEPT EXPRESSED IN THE CONTRACT DOCUMENTS. REFER TO PROJECT JOIST SEAT DEPTH OF 2 1/2” FOR K SERIES, 5” FOR LH SERIES, AND 7 1/2” FOR JOIST GIRDERS HAS BEEN WELDING PROCEDURE SPECIFICATIONS AND PROCEDURE QUALIFICATION RECORDS
ACCEPTABLE ADHESIVES: SPECIFICATIONS FOR ADDITIONAL REQUIRED SUBMITTALS. ASSUMED, UNLESS NOTED OTHERWISE. STEEL JOIST SUPPLIER TO NOTIFY THE ENGINEER IF LOADING CONDITIONS QUALIFICATION DATA FOR QUALIFIED INSTALLER, FABRICATOR, PROFESSIONAL ENGINEER, TESTING AGENCY
HILTI HIT-HY 200 MAX ADHESIVE REQUIRE DIFFERENT DEPTHS. WELDING CERTIFICATES
SIMPSON SET-XP ADHESIVE SHOP DRAWINGS: SUBMIT SHOP DRAWINGS FOR FABRICATION, BENDING AND PLACEMENT OF REINFORCEMENT STEEL. COMPLY MILL TEST REPORTS
DEWALT AC200+ ADHESIVE WITH ACI 530, AND PROVIDE 1/4” = 1'-0” SCALE ELEVATIONS OF ALL WALLS, COLUMNS AND STEM WALLS AND OTHER DRYPACK: PRODUCT TEST REPORTS 10/08/2021
DEWALT/POWERS PURE110+ ADHESIVE VERTICAL WORK. SHOW ALL OPENINGS IN VERTICAL WORK, AND BEAMS; ALL POCKETS IN BEAMS AND WALLS; TOP AND SOURCE QUALITY CONTROL REPORTS
BOTTOM ELEVATIONS OF MEMBERS, SECTIONS THROUGH COLUMNS, PILASTERS AND BEAMS; PLAN VIEW OF ALL WALLS; DRYPACK SHALL BE 5,000 PSI NON-SHRINK GROUT, FIVE STAR OR EQUIVALENT. INSTALL DRYPACK UNDER BEARING
TORQUE-CONTROLLED EXPANSION ANCHORS: PLACING SEQUENCE FOR MULTIPLE LAYERS OF REINFORCING STEEL; LOCATIONS OF ALL CONTROL JOINTS. ALL OPENINGS PLATES BEFORE FRAMING MEMBER IS INSTALLED. AT COLUMNS, INSTALL DRYPACK UNDER BASE PLATES AFTER COLUMN
SHALL BE REVIEWED BY THE CONTRACTOR PRIOR TO SUBMITTING DRAWINGS FOR REVIEW. SHOW SPECIAL REINFORCEMENT AT HAS BEEN PLUMBED BUT PRIOR TO FLOOR OR ROOF INSTALLATION. NOTES
REFER TO SPECIAL INSPECTION MATRIX FOR TESTING AND INSPECTION REQUIREMENTS. OPENINGS. REVISION NAME DATE

1. FOR MATERIAL STRENGTHS, SEE GENERAL STRUCTURAL NOTES. 1


COLD FORMED STRUCTURAL STEEL FRAMING: 1 ADDENDUM #1 2021 1008
ACCEPTABLE TORQUE-CONTROLLED EXPANSION ANCHORS: PRODUCT DATA 2. VERIFY ALL DIMENSIONS WITH ARCHITECTURAL DRAWINGS PRIOR TO START OF
HILTI KWIK BOLT-TZ STEEL REINFORCEMENT SHOP DRAWINGS ALL COLD-FORMED STEEL FRAMING SHALL BE FABRICATED AND ERECTED IN ACCORDANCE WITH MANUFACTURER'S CONSTRUCTION - RESOLVE ANY DISCREPANCIES WITH ARCHITECT.
SIMPSON STRONG-BOLT 2 QUALIFICATION DATA FOR TESTING AGENCY RECOMMENDATIONS AND IN ACCORDANCE WITH THE LATEST EDITION OF "SPECIFICATIONS FOR THE DESIGN OF COLD- 3. FOR CLARITY, ALL EXTERIOR SLABS AND SIDEWALKS MAY NOT BE SHOWN. FOR EXACT
DEWALT/POWERS POWER-STUD+SD2 MATERIAL CERTIFICATES FORMED STEEL STRUCTURAL MEMBERS" BY THE AMERICAN IRON AND STEEL INSTITUTE. DIMENSIONS, LOCATIONS, JOINT AND SCORE LINES, SEE ARCHITECTURAL DRAWINGS.
MIX DESIGNS (MORTAR AND GROUT) 4. FOR CLARITY, ALL OPENINGS MAY NOT BE SHOWN ON FRAMING PLANS. FOR EXACT SIZE,
CONCRETE SUBMITTALS: STATEMENT OF COMPRESSIVE STRENGTH OF MASONRY ALL PROPRIETARY ITEMS, MATERIALS AND COMPONENTS SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE NUMBER, AND LOCATION OF OPENINGS, SEE ARCHITECTURAL, MECHANICAL, ELECTRICAL
COLD-WEATHER AND HOT-WEATHER PROCEDURES MANUFACTURER’S INSTRUCTIONS, GUIDELINES AND/OR RECOMMENDATIONS. AND PLUMBING DRAWINGS. FOR FRAMING AT OPENINGS, SEE TYPICAL STRUCTURAL
THE FOLLOWING ITEMS SHALL BE SUBMITTED FOR REVIEW FOR THE LIMITED PURPOSE OF CHECKING FOR CONFORMANCE WITH FIELD QUALITY CONTROL TEST AND INSPECTION REPORTS DETAILS. VERIFY ALL SIZES, WEIGHTS AND LOCATIONS OF MECHANICAL EQUIPMENT WITH
INFORMATION GIVEN AND THE DESIGN CONCEPT EXPRESSED IN THE CONTRACT DOCUMENTS. REFER TO PROJECT MECHANICAL ENGINEER AND MECHANICAL CONTRACTOR THROUGH ARCHITECT. ISSUE DATE: 2021 0907
SPECIFICATIONS FOR ADDITIONAL REQUIRED SUBMITTALS. 5.0 METALS: 5. DETAILS MARKED "TYPICAL" MAY NOT BE CUT ON PLANS.
6. CONC C.J. - SHALL BE EITHER KEYED OR SAW CUT CONTROL JOINT IN SLAB ON GRADE AT
SHOP DRAWINGS: SUBMIT SHOP DRAWINGS FOR FABRICATION, BENDING AND PLACEMENT OF REINFORCEMENT STEEL. COMPLY STRUCTURAL STEEL: CONTRACTOR'S OPTION, SEE GENERAL STRUCTURAL NOTES AND PLANS.
WITH ACI DETAILING MANUAL, SP-66, AND PROVIDE 1/4” = 1'-0” SCALE ELEVATIONS OF ALL WALLS, BEAMS, GRADE 7. MAS C.J. - PROVIDE MASONRY CONTROL JOINT IN MASONRY WALL PER G.S.N. AND

GENERAL NOTES
www.TheLefflerGroup.com info@theLefflerGroup.com
165 S. UNION BLVD, STE 360, LAKEWOOD, CO 80228

S0.2
BEAMS, STEM WALLS, TIE BEAMS, CORE WALLS AND OTHER VERTICAL WORK. SHOW ALL OPENINGS IN VERTICAL WORK, SLABS ALL WORK SHALL CONFORM TO THE LATEST EDITION OF AISC MANUAL OF STEEL CONSTRUCTION, AND LATEST EDITION OF TYPICAL DETAIL.
AND BEAMS; ALL POCKETS IN BEAMS AND WALLS; TOP AND BOTTOM ELEVATIONS OF MEMBERS, SECTIONS THROUGH COLUMNS, AWS D1.1, UNLESS MORE STRINGENT REQUIREMENTS ARE DEFINED ELSEWHERE IN THE CONTRACT DOCUMENTS. THE LEFFLER 8. FOR CLARITY, DETAILS MAY SHOW ONLY ONE SIDE OF FRAMING CONDITION.

P - 720.890.4095 © 2021
PILASTERS AND BEAMS; PLAN VIEW OF ALL WALLS AND BEAM/JOIST INTERSECTIONS; PLACING SEQUENCE FOR MULTIPLE GROUP CONSULTING STRUCTURAL ENGINEERS IS THE ENGINEER OF RECORD. UNLESS AN ACTIVITY OR DUTY IS SPECIFICALLY 9. CONTRACTOR TO VERIFY, AND BE RESPONSIBLE FOR VARIATIONS IN CONCRETE QUANTITY
LAYERS OF REINFORCING STEEL; LOCATIONS OF ALL CONSTRUCTION JOINTS. ALL OPENINGS SHALL BE REVIEWED BY THE IDENTIFIED AS BEING PERFORMED BY THE PROJECT STRUCTURAL ENGINEER OF RECORD IN OSHA SUBPART R, IT WILL NOT DUE TO CAMBER, CONSTRUCTION DEAD LOAD DEFLECTIONS AND/OR TOLERANCES OF
CONTRACTOR PRIOR TO SUBMITTING DRAWINGS FOR REVIEW. SHOW SPECIAL REINFORCEMENT AT OPENINGS. BE PERFORMED BY THE ENGINEER. IT IS TO BE PERFORMED BY OTHERS. STRUCTURAL STEEL ELEMENTS (i.e. BEAMS, STEEL DECK, ETC.) AND PRECAST CONCRETE
ELEMENTS.
10. ALL SCHEDULE MARK DESIGNATIONS MAY NOT NECESSARILY BE FOUND ON THE PLANS WHERE
THE SCHEDULES OCCUR. SCHEDULES ARE TYPICAL TO THE PROJECT.

C ALLRED&ASSOCIATES 2021
SPECIAL STRUCTURAL INSPECTIONS SPECIAL STRUCTURAL INSPECTIONS SPECIAL STRUCTURAL INSPECTIONS

VERIFICATION AND VERIFICATION AND REFERENCED STANDARD VERIFICATION AND


FREQUENCY REFERENCED FREQUENCY IBC FREQUENCY REFERENCED
MATERIAL INSPECTION IBC REFERENCE MATERIAL INSPECTION ACI ACI 530.1 MATERIAL INSPECTION IBC REFERENCE
STANDARD REFERENCE STANDARD
TASK TASK 530/ASCE / ASCE 6/ TASK
CONTINUOUS PERIODIC CONTINUOUS PERIODIC 5/TMS 402 TMS 602 CONTINUOUS PERIODIC
1. VERIFY MATERIALS BELOW FOOTINGS 1. VERIFY COMPLIANCE WITH THE 1. MATERIAL VERIFICATION:
--- X --- X --- ART. 1.5 ---

S
ARE ADEQUATE TO ACHIEVE THE DESIGN APPROVAED SUBMITTALS. A) MEMBER SIZE AND THICKNESS
BEARING CAPACITY. TO MATCH CONTRACT DOCUMENTS

210106
2. VERIFY EXCAVATIONS ARE 2. AS MASONRY CONSTRUCTION X
INCLUDING TRACKS, STUDS,

INTERIOR DESIGN
EXTENDED TO PROPER DEPTH AND --- X BEGINS, THE FOLLOWING SHALL BE

580 BURBANK ST. SUITE 125, BROOMFIELD, CO 80020 PHONE: 303.465.4306 FAX: 303.465.4382 www.allredarch.com
ASSEMBLIES, CONNECTORS.

T
HAVE REACHED PROPER MATERIAL. VERIFIED TO ENSURE COMPLIANCE: B) FASTENER MATERIAL AND
3. PERFORM CLASSIFICATION AND X

A
SOILS A. PROPORTIONS OF COMPONENTS.
--- X

I
TESTING OF CONTROLLED FILL SITE-PREPARED MORTAR. --- X --- ART. 2.6A --- COLD-
(RE: IBC 2. INSPECTION OF INSTALLATION:
MATERIALS. FORMED
TABLE

| JOB NO.
A) INSPECT MEMBER LAYOUT, 1705.10.2

C
1705.6) 4. VERIFY USE OF PROPER MATERIALS, B. CONSTRUCTION OF MORTAR STEEL X
DENSITIES AND LIFT THICKNESSES FRAMING CONNECTION, ORIENTATION.
X --- JOINTS. --- X --- ART 3.3B ---

O
DURING PLACEMENT AND COMPACTION B) SPECIAL INSPECTION REQUIRED
C. GRADE AND SIZE OR X
OF CONTROLLED FILL. ART. FOR FASTENERS PER MANUFACTURER.

S
5. PRIOR TO PLACEMENT OF PRESTRESSING TENDONS C) INSPECTION PRIOR TO
--- X 2.4B, ---
CONTROLLED FILL, OBSERVE AND ANCHORAGES. SHEATHING:VERIFY FLANGES ARE
--- X 2.4H

S
SUBGRADE AND VERIFY THAT SITE X
INTACT, STUDS ARE NOT CUT OR

|
HAS BEEN PREPARED PROPERLY. SPLICED.

A
1. INSPECTION OF REINFORCING D. LOCATION OF REINFORCEMENT, 3. INSPECTION OF WELDING. X

PLANNING
STEEL, INCLUDING PRESTRESSING --- X ACI318: 3.5,7.1-7.7 1910.4 CONNECTORS, PRESTRESSING TENDONS AND ART.
1. EPOXY ANCHORS

&
TENDONS, AND PLACEMENT. ANCHORAGES. --- X --- 3.4, ---
2. INSPECTION OF REINFORCING AWS D1.4 3.6A A) ALL EPOXY BOLTS TO HAVE I.C.C.
STEEL WELDING IN ACCORDANCE --- --- ACI318:3,5. RATING FOR MATERIAL INTO WHICH
WITH TABLE 1704.3, ITEM 5B. 2 E. PRESTRESSING TECHNIQUE. INSTALLATION TAKES PLACE. ALL EPOXY
--- X --- ART. 3.6B --- BOLTS ARE SUBJECT TO THE FOLLOWING
3. INSPECTION OF ANCHORS CAST

ALLRED
SPECIAL INSPECTION AND TESTING.
IN CONCRETE WHERE ALLOWABLE LOADS 3. PRIOR TO GROUTING, VERIFY THAT THE
X --- --- 1908.5, 1909.1

|
HAVE BEEN INCREASED. OR WHERE FOLLOWING ARE IN COMPLIANCE:
B) VERIFY ANCHOR TYPE, DIMENSIONS,
STRENGTH DESIGN IS USED. A. GROUT SPACE. BASE MATERIAL TYPE & STRENGTH, HOLE

ARCHITECTURE
--- X --- TABLE 7 --- DIMENSIONS, HOLE CLEANING PROCEDURES,

PERMIT SET
4. INSPECTION OF ANCHORS POST- X
--- X ACI318:3.8.6, 1909.1 ANCHOR SPACING, EDGE DISTANCES, BASE
INSTALLED IN HARDENED CONCRETE
CONCRETE 8.1.3, 21.2.8 MATERIAL THICKNESS, ANCHOR EMBEDMENT,
MEMBERS. B. GRADE, TYPE, AND SIZE OF
(RE: IBC AND TIGHTENING TORQUE.
TABLE 5. VERIFYING USE OF REQUIRED DESIGN REINFORCEMENT AND ANCHOR
--- X ACI318: CH. 1904.2, 1910.2, BOLTS, AND PRESTRESSING --- X SEC. 1.13 --- ---
1705.3) MIX. C) LOAD TEST THE FIRST 10% OF EACH
4,5.2-5.4 1910.3 TENDONS, AND ANCHORAGES. TYPE OF BOLT TO 150% RECOMMENDED
6. AT THE TIME FRESH CONCRETE IS ALLOWABLE WORKING LOAD IN TENSION. IF
ASTM C 172 C. PLACEMENT OF REINFORCEMENT, SEC. AT ANYTIME THE NUMBER OF REJECTED
SAMPLED TO FABRICATE ART.
ASTM C 31 CONNECTORS, AND PRESTRESSING TENDONS 2.1.10.7.2 BOLTS EXCEEDS 10%, TEST 100% OF
SPECIMENS FOR STRENGTH TEST, --- X 2.4, --- POST
X --- 1910.10 AND ANCHORAGES. , REMAINING BOLTS UNTIL NOT MORE THAN X
PERFORM SLUMP AND AIR CONTENT ACI318: 3.4 INSTALLED
5.6,5.8 MASONRY 3.3.3.4(b) 10% FAIL LOAD TEST. COSTS FOR
TESTS, AND DETERMINE THE ANCHORS
LEVEL B D. PROPORTIONS OF SITE-PREPARED GROUT SEC. ADDITIONAL TESTING BEYOND THE FIRST
TEMPERATURE OF THE CONCRETE.
(TMS) AND PRESTRESSING GROUT FOR BONDED 2.1.10.7.2 10% OF ANY BOLT TYPE SHALL BE BORNE BY
7. INSPECTION OF CONCRETE AND X --- --- ---
1910.6, 1910.7, TENDONS. , THE CONTRACTOR.
SHOTCRETE PLACEMENT FOR X --- ACI318: 5.9,5.10
1910.8 3.3.3.4(b)
PROPER APPLICATION TECHNIQUES.
2. EXPANSION ANCHORS

CITY OF THORNTON
8. INSPECTION FOR MAINTENANCE OF E. CONSTRUCTION OF MORTAR
SPECIFIED CURING TEMPERATURE --- X ACI318: 5.11-5.13 1910.9 JOINTS. A) ALL EXPANSION BOLTS TO HAVE I.C.C.

FIRE STATION #7
--- X --- ART. 3.5 ---
AND TECHNIQUES. RATING FOR MATERIAL INTO WHICH
INSTALLATION TAKES PLACE. ALL
EXPANSION BOLTS ARE SUBJECT TO THE
F. APPLICATION AND MEASUREMENT FOLLOWING SPECIAL INSPECTION AND
--- X --- ART. 3.6B ---
OF PRESTRESSING FORCE. TESTING.
SPECIAL STRUCTURAL INSPECTIONS 4. VERIFY DURING CONSTRUCTION: ---
B) VERIFY ANCHOR TYPE, ANCHOR
DIMENSIONS, HOLE CLEANLINESS,
A. SIZE AND LOCATION OF EMBEDMENT DEPTH, BASE MATERIAL TYPE &
STRUCTURAL ELEMENTS. STRENGTH, DRILL BIT DIAMETER, HOLE X
VERIFICATION AND FREQUENCY --- X --- ART. 3.4D ---
DEPTH, EDGE DISTANCES, ANCHOR
MATERIAL INSPECTION REFERENCED STANDARD IBC REFERENCE
B. TYPE, SIZE, AND LOCATION OF SPACING, BASE MATERIAL THICKNESS, AND
TASK
ANCHORS, INCLUDING OTHER DETAILS OF --- X SEC. 1.13 ART. 3.4 --- TIGHTENING TORQUE.
CONTINUOUS PERIODIC
ANCHORAGE OF MASONRY TO STRUCTURAL
1. INSPECT DRILLING OPERATIONS AND MEMBERS, FRAMES, OR OTHER NOTE: THIS TABLE IS NOT COMPREHENSIVE. ALL TESTING AND INSPECTION REQUIREMENTS DEFINED ELSEWHERE IN THE
MAINTAIN COMPLETE AND ACCURATE X --- CONSTRUCTION. DRAWINGS AND SPECIFICATIONS ARE REQUIRED. CONTRACTOR SHALL COORDINATE ALL REQUIREMENTS AND BRING ANY
RECORDS FOR EACH ELEMENT. DISCREPANCIES TO THE ENGINEER'S ATTENTION PRIOR TO BEGINNING THE WORK.
2. VERIFY PLACEMENT LOCATIONS AND C. WELDING OF REINFORCMENT. X --- --- --- ---
CAST-IN-
PLACE DEEP PLUMBNESS, CONFIRM ELEMENT D. PREPARATION, CONSTRUCTION,
FOUNDATION DIAMETERS, BELL DIAMETER (IF AND PROTECTION OF MASONRY DURING
ELEMENTS APPLICABLE), LENGTHS, EMBEDMENT X --- COLD WEATHER (TEMPERATURE BELOW
(RE: IBC INTO BEDROCK (IF APPLICABLE) AND 40 DEG. F OR HOT WEATHER X --- --- ART. 1.8C-D ---
TABLE ADEQUATE END-BEARING STRATA (TEMPERATURE ABOVE 90 DEG. F).
1705.8) CAPACITY. RECORD CONCRETE OR
GROUT VOLUMES. E. GROUTING OF PRESTRESSING
X --- --- ART. 3.6C ---
BONDED TENDONS.
3. FOR CONCRETE ELEMENTS, PERFORM
-- F. PLACEMENT OF GROUT AND PRESTRESSING SEC.
ADDITIONAL INSPECTIONS IN ---
- GROUT FOR BONDED TENDONS IS IN X --- --- ART. 3.5 2105.2.2,
ACCORDANCE WITH SECTION 1705.3.
COMPLIANCE. 2105.3
INSTALLATION OF OPEN WEB STEEL
5. OBSERVE PREPARATION OF GROUT
JOISTS AND JOIST GIRDERS.
SPECIMENS, MORTAR SPECIMENS, AND/OR --- X --- ART. 2.1,2.6 ---
PRISMS.

10/08/2021

REVISION NAME DATE

1 ADDENDUM #1 2021 1008

ISSUE DATE: 2021 0907

SPECIAL INSPECTIONS
www.TheLefflerGroup.com info@theLefflerGroup.com
165 S. UNION BLVD, STE 360, LAKEWOOD, CO 80228

S0.3
P - 720.890.4095 © 2021
C ALLRED&ASSOCIATES 2021
STRUCTURAL STEEL CONSTRUCTION OTHER EXTENT OF SERVICE TABLE N5.4-1 TABLE N5.6-1
THAN STRUCTURAL STEEL (CONTINUOUS OR INSPECTION TASKS PRIOR TO WELDING INSPECTION TASKS PRIOR TO BOLTING
REFERENCE: IBC TABLE 1705.2.2 PERIODIC) REFERENCE AISC 360, CHAPTER N REFERENCE AISC 360, CHAPTER N
1. MATERIAL VERIFICATION OF COLD-FORMED STEEL DECK: INSPECTION TASKS PRIOR TO WELDING QC SI INSPECTION TASKS PRIOR TO BOLTING QC SI

A. IDENTIFICATION MARKINGS TO CONFORM TO ASTM STANDARDS SPECIFIED IN THE P WELDING PROCEDURE SPECIFICATIONS (WPS'S) AVAILABLE P P USE OF QUALIFIED WELDERS O P
APPROVED CONSTRUCTION DOCUMENTS.
MANUFACTURER CERTIFICATIONS FOR WELDING CONSUMABLES AVAILABLE P P FASTENERS MARKED IN ACCORDANCE WITH ASTM REQUIREMENTS O O
B. MANUFACTURER'S CERTIFIED TEST REPORTS.
MATERIAL IDENTIFICATION (TYPE/GRADE) O O PROPER FASTENERS SELECTED FOR THE JOINT DETAIL (GRADE, TYPE, BOLT
O O

S
2. INSPECTION OF WELDING AND FASTENERS: LENGTH IF THREADS ARE TO BE EXCLUDED FROM SHEAR PLANE)
WELDER IDENTIFICATION SYSTEM* O O

210106
PROPER BOLTING PROCEDURE SELECTED FOR JOINT DETAIL O O
A. COLD-FORMED STEEL DECK: FIT-UP OF GROOVE WELDS (INCLUDING JOINT GEOMETRY

INTERIOR DESIGN
580 BURBANK ST. SUITE 125, BROOMFIELD, CO 80020 PHONE: 303.465.4306 FAX: 303.465.4382 www.allredarch.com
T
- JOINT PREPARATION CONNECTING ELEMENTS, INCLUDING THE APPROPRIATE FAYING SURFACE CONDITION O O
1) FLOOR AND ROOF DECK WELDS AND FASTNERS. - DIMENSIONS (ALIGNMENT, ROOT OPENING, ROOT FACE, BEVEL) AND HOLE PREPARATION, IF SPECIFIED, MEET APPLICABLE REQUIREMENTS
O O

A
- CLEANLINESS (CONDITION OF STEEL SURFACES)

I
B. REINFORCING STEEL: PRE-INSTALLED VERIFICATION TESTING BY INSTALLATION PERSONNEL OBSERVED
- TACKING (TACK WELD QUALITY AND LOCATION) P O
AND DOCUMENTED FOR FASTENER ASSEMBLIES AND METHOD USED
- BACKING TYPE AND FIT (IF APPLICABLE)

| JOB NO.
P

C
1) VERIFICATION OF WELDABILITY OF REINFORCING STEEL OTHER THAN PROPER STORAGE PROVIDED FOR BOLTS, NUTS, WASHERS AND OTHER FASTENER O O
A706. CONFIGURATION AND FINISH OF ACCESS HOLES O O
COMPONENTS

O
2) REINFORCING STEEL RESISTING FLEXURAL AND AXIAL FORCES IN
INTERMEDIATE AND SPECIAL MOMENT FRAMES, AND BOUNDARY ELEMENTS FIT-UP OF FILLET WELDS WHERE:
- DIMENSIONS (ALIGNMENT, GAPS AND ROOT)

S
OF SPECIAL STRUCTURAL WALLS OF CONCRETE AND SHEAR O O O - OBSERVE THESE ITEMS ON A RANDOM BASIS. OPERATIONS NEED NOT BE DELAYED PENDING THESE
REINFORCEMENT. - CLEANLINESS (CONDITION OF STEEL SURFACES) INSPECTIONS.

S
3) SHEAR REINFORCEMENT. - TACKING (TACK WELDS QUALITY AND LOCATION) P - PERFORM THESE TASKS FOR EACH WELDED JOINT OR MEMBER.

|
4) OTHER REINFORCING STEEL. QC - QUALITY CONTROL INSPECTOR (FABRICATOR OR ERECTOR)

A
CHECK WELDING EQUIPMENT O - SI - SPECIAL INSPECTOR (QUALITY ASSURANCE INSPECTOR)

PLANNING
&
* THE FABRICATOR OR ERECTOR, AS APPLICABLE, SHALL MAINTAIN A SYSTEM BY WHICH A WELDER WHO HAS WELDED A
JOINT OR MEMBER CAN BE IDENTIFIED. STAMPS, IF USED, SHALL BE THE LOW-STRESS TYPE.
INSPECTION OF FABRICATORS AND
FABRICATION PROCEDURES WHERE:
REFERENCE: IBC SECTION 1704.2.5. O - OBSERVE THESE ITEMS ON A RANDOM BASIS. OPERATIONS NEED NOT BE DELAYED PENDING THESE TABLE N5.6-2
INSPECTIONS. INSPECTION TASKS DURING BOLTING

ALLRED
P - PERFORM THESE TASKS FOR EACH WELDED JOINT OR MEMBER. REFERENCE AISC 360, CHAPTER N
QC - QUALITY CONTROL INSPECTOR (FABRICATOR OR ERECTOR)

|
STRUCTURAL STEEL INSPECTION TASKS DURING BOLTING QC SI
SI - SPECIAL INSPECTOR (QUALITY ASSURANCE INSPECTOR)
REFERENCE: IBC SECTION 1705.2.1. INSPECTIONS FOR STRUCTURAL STEEL SHALL BE IN ACCORDANCE WITH QUALITY

ARCHITECTURE
ASSURANCE REQUIREMENTS OF AISC 360, CHAPTER N. FASTENER ASSEMBLIES, OF SUITABLE CONDITION, PLACED IN ALL HOLES AND
O O

PERMIT SET
WASHERS (IF REQUIRED) ARE POSITIONED AS REQUIRED
FABRICATOR AND ERECTOR QUALITY CONTROL PROGRAM JOINT BROUGHT TO THE SNUG-TIGHT CONDITION PRIOR TO THE PRETENSIONING OPERATION O O
REFERENCE AISC 360, CHAPTER N, SECTION N2
TABLE N5.4-2 FASTENER COMPONENT NOT TURNED BY THE WRENCH PREVENTED FROM ROTATING O O
THE FABRICATOR'S QUALITY CONTROL INSPECTOR SHALL INSPECT THE FOLLOWING AS A MINIMUM, AS APPLICABLE:
INSPECTION TASKS DURING WELDING
REFERENCE AISC 360, CHAPTER N FASTENERS ARE PRETENSIONED IN ACCORDANCE WITH RCSC SPECIFICATION, PROGRESSING O O
1. SHOP WELDING, HIGH-STRENGTH BOLTING, AND DETAILS IN ACCORDANCE WITH AISC 360 SECTION N5. SYSTEMATICALLY FROM THE MOST RIGID POINT TOWARD THE FREE EDGES
2. SHOP CUT AND FINISHED SURFACES IN ACCORDANCE WITH AISC 360, SECTION M2. INSPECTION TASKS DURING WELDING QC SI
3. SHOP HEATING FOR STRAIGHTENING, CAMBERING AND CURVING IN ACCORDANCE WITH AISC 360, SECTION WHERE:
M2.1. USE OF QUALIFIED WELDERS O O O - OBSERVE THESE ITEMS ON A RANDOM BASIS. OPERATIONS NEED NOT BE DELAYED PENDING THESE
4. TOLERANCES FOR SHOP FABRICATION IN ACCORDANCE WITH SECTION 6 OF THE CODE OF STANDARD PRACTICE. INSPECTIONS.
CONTROL AND HANDLING OR WELDING CONSUMABLES P - PERFORM THESE TASKS FOR EACH WELDED JOINT OR MEMBER.
THE ERECTOR'S QUALITY CONTROL INSPECTOR SHALL INSPECT THE AS A MINIMUM, AS APPLICABLE: - PACKAGING O O QC - QUALITY CONTROL INSPECTOR (FABRICATOR OR ERECTOR)
- EXPOSURE CONTROL SI - SPECIAL INSPECTOR (QUALITY ASSURANCE INSPECTOR)
1. FIELD WELDING, HIGH-STRENGTH BOLTING, AND DETAILS IN ACCORDANCE WITH AISC 360, SECTION N5. NO WELDING OVER CRACKED TACK WELDS O O

CITY OF THORNTON
2. STEEL DECK AND HEADED STEEL STUD ANCHOR PLACEMENT AND ATTACHMENT IN ACCORDANCE WITH AISC 360,
SECTION N6. ENVIRONMENTAL CONDITIONS

FIRE STATION #7
3. FIELD CUT SURFACES IN ACCORDANCE WITH AISC 360, SECTION M2.2. - WIND SPEED WITHIN LIMITS O O
4. FIELD HEATING FOR STRAIGHTENING IN ACCORDANCE WITH AISC 360, SECTION M2.1. - PRECIPITATION AND TEMPERATURE
5. TOLERANCES FOR FIELD ERECTION IN ACCORDANCE WITH SECTION 7.13 OF THE CODE OF STANDARD PRACTICE. TABLE N5.6-3
WPS FOLLOWED INSPECTION TASKS AFTER BOLTING
- SETTINGS ON WELDING EQUIPMENT REFERENCE AISC 360, CHAPTER N
- TRAVEL SPEED
FABRICATOR AND ERECTOR DOCUMENTS - SELECTED WELDING MATERIALS INSPECTION TASKS AFTER BOLTING QC SI
O O
REFERENCE AISC 360, CHAPTER N, SECTION N3 - SHIELDING GAS TYPE/FLOW RATE
- PREHEAT APPLIED DOCUMENT ACCEPTANCE OR REJECTION OF BOLTED CONNECTIONS P P
SUBMITTALS FOR STEEL CONSTRUCTION AND AVAILABLE DOCUMENTS FOR STEEL CONSTRUCTION SHALL CONFORM TO AISC
360, SECTION N3. - INTERPASS TEMPERATURE MAINTAINED (MIN./MAX.)
WHERE:
- PROPER POSITION (F, V, H, OH)
O - OBSERVE THESE ITEMS ON A RANDOM BASIS. OPERATIONS NEED NOT BE DELAYED PENDING THESE
WELDING TECHNIQUES INSPECTIONS.
INSPECTION AND NONDESTRUCTIVE TESTING PERSONNEL - INTERPASS AND FINAL CLEANING P - PERFORM THESE TASKS FOR EACH WELDED JOINT OR MEMBER.
REFERENCE AISC 360, CHAPTER N, SECTION N4 O O
- EACH PASS WITHIN PROFILE LIMITATIONS QC - QUALITY CONTROL INSPECTOR (FABRICATOR OR ERECTOR)
- EACH PASS MEETS QUALITY REQUIREMENTS SI - SPECIAL INSPECTOR (QUALITY ASSURANCE INSPECTOR)
QUALITY CONTROL INSPECTOR (FABRICATOR OR ERECTOR) QUALIFICATIONS, QUALITY ASSURANCE INSPECTOR (SPECIAL
INSPECTOR) QUALIFICATIONS AND NONDESTRUCTIVE TESTING PERSONNEL (INSPECTION AGENCY PERSONNEL) WHERE:
QUALIFICATIONS SHALL CONFORM TO AISC 360, SECTION N4. O - OBSERVE THESE ITEMS ON A RANDOM BASIS. OPERATIONS NEED NOT BE DELAYED PENDING THESE
INSPECTIONS.
P - PERFORM THESE TASKS FOR EACH WELDED JOINT OR MEMBER.
QC - QUALITY CONTROL INSPECTOR (FABRICATOR OR ERECTOR)
MINIMUM REQUIREMENTS FOR INSPECTION OF STRUCTURAL STEEL BUILDINGS TABLE N6.1
SI - SPECIAL INSPECTOR (QUALITY ASSURANCE INSPECTOR)
REFERENCE AISC 360, CHAPTER N, SECTION N5 INSPECTION OF STEEL ELEMENTS OF COMPOSITE CONSTRUCTION PRIOR TO CONCRETE PLACEMENT
QUALITY CONTROL INSPECTIONS BY THE FABRICATOR'S OR ERECTOR'S QUALITY CONTROL INSPECTOR (QCI) AND REFERENCE AISC 360, CHAPTER N
QUALITY ASSURANCE INSPECTIONS OF FABRICATED ITEMS AND THE ERECTED STEEL SYSTEM BY THE SPECIAL INSPECTOR
INSPECTION OF STEEL ELEMENTS OF COMPOSITE CONSTRUCTION PRIOR TO QC SI
(SI), SHALL CONFORM TO AISC 360, SECTION N5 AND TABLES N5.4-1, N5.4-2, N5.4-3, N5.6-1, N5.6-2, N5.6-3.
CONCRETE PLACEMENT
IN THESE TABLES INSPECTION TASKS ARE AS FOLLOWS:
TABLE N5.4-3
PLACEMENT AND INSTALLATION OF STEEL DECK P P
O-OBSERVE THESE ITEMS ON A RANDOM BASIS. OPERATIONS NEED NOT BE DELAYED PENDING THESE INSPECTIONS. INSPECTION TASKS AFTER WELDING
P-PERFORM THESE TASKS FOR EACH WELDED JOINT OR MEMBER. REFERENCE AISC 360, CHAPTER N PLACEMENT AND INSTALLATION OF STEEL HEADED ANCHORS P P
INSPECTION TASKS AFTER WELDING QC SI DOCUMENT ACCEPTANCE OR REJECTION OF STEEL ELEMENTS P P
NONDESTRUCTIVE TESTING OF WELDED JOINTS WELDS CLEANED O WHERE:
O
O - OBSERVE THESE ITEMS ON A RANDOM BASIS. OPERATIONS NEED NOT BE DELAYED PENDING THESE 10/08/2021
NONDESTRUCTIVE TESTING OF WELDED JOINTS SHALL CONFORM TO AISC 360, SECTION N5 AND SHALL BE PERFORMED BY SIZE, LENGTH AND LOCATION OF WELDS P P INSPECTIONS.
THE SPECIAL INSPECTOR (QUALITY ASSURANCE INSPECTOR) IN ACCORDANCE WITH AWSD1.1. P - PERFORM THESE TASKS FOR EACH WELDED JOINT OR MEMBER.
WELDS MEET VISUAL ACCEPTANCE CRITERIA
QC - QUALITY CONTROL INSPECTOR (FABRICATOR OR ERECTOR)
- CRACK PROHIBITION
SI - SPECIAL INSPECTOR (QUALITY ASSURANCE INSPECTOR)
- WELD/BASE-METAL FUSION REVISION NAME DATE
MINIMUM REQUIREMENTS FOR INSPECTION OF COMPOSITE CONSTRUCTION - CRATER CROSS SECTION P P 1 ADDENDUM #1 2021 1008
REFERENCE AISC 360, CHAPTER N, SECTION N6 - WELD PROFILES
INSPECTION OF COMPOSITE CONSTRUCTION SHALL CONFORM TO AISC 360, SECTION N6 AND TABLE N6.1 - WELD SIZE
- UNDERCUT
- POROSITY

INSPECTION OF FABRICATORS AND FABRICATION PROCEDURES ARC STRIKES P P


REFERENCE IBC SECTION 1704.2.5
K-AREA* P P
INSPECTION OF FABRICATORS AND FABRICATION PROCEDURES SHALL BE PERFORMED BY THE QUALITY ASSURANCE
BACKING REMOVED AND WELD TABS REMOVED (IF REQUIRED) P P ISSUE DATE: 2021 0907
INSPECTOR (SPECIAL INSPECTOR) AND SHALL CONFORM TO IBC SECTIONS 1704.2.5 AND 1704.2.5.1.

SPECIAL INSPECTIONS
REPAIR ACTIVITIES P P
NONCONFORMING MATERIALS AND WORKMANSHIP
REFERENCE AISC 360, CHAPTER N, SECTION N8 DOCUMENT ACCEPTANCE OR REJECTION OF WELDED JOINT OF MEMBER P P

www.TheLefflerGroup.com info@theLefflerGroup.com
165 S. UNION BLVD, STE 360, LAKEWOOD, CO 80228
* WHEN WELDING OF DOUBLER PLATES, CONTINUITY PLATES OR STIFFENERS HAS BEEN PERFORMED IN THE K-AREA,

S0.4
IDENTIFICATION AND REJECTION OF MATERIALS OR WORKMANSHIP THAT IS NOT IN CONFORMANCE WITH THE
CONSTRUCTION DOCUMENTS SHALL BE PERMITTED AT ANY TIME DURING THE PROGRESS OF THE WORK. NONCONFORMING VISUALLY INSPECT THE WEB K-AREA FOR CRACKS WITHIN 3 IN. OF THE WELD.

P - 720.890.4095 © 2021
MATERIAL AND WORKMANSHIP SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE GENERAL CONTRACTOR AND THE
FABRICATOR OR ERECTOR, AS APPLICABLE. NONCONFORMING MATERIAL OR WORKMANSHIP SHALL BE BROUGHT INTO WHERE:
CONFORMANCE, OR MADE SUITABLE FOR ITS INTENDED PURPOSE AS DETERMINED BY THE STRUCTURAL ENGINEER OF O - OBSERVE THESE ITEMS ON A RANDOM BASIS. OPERATIONS NEED NOT BE DELAYED PENDING THESE
RECORD. INSPECTIONS.
P - PERFORM THESE TASKS FOR EACH WELDED JOINT OR MEMBER.
QC - QUALITY CONTROL INSPECTOR (FABRICATOR OR ERECTOR)
SI - SPECIAL INSPECTOR (QUALITY ASSURANCE INSPECTOR)

C ALLRED&ASSOCIATES 2021
F E D C B A
FLOOR LOAD KEY LEGEND

SUPERIMPOSED LOADS
LIVE LOAD
LOAD AREA PATTERN DESCRIPTION OF LOAD
DEAD LOAD (PSF) LIVE LOAD (PSF) REDUCTION

S
1 20 100 NO TYPICAL FLOOR

E
6

210106
INTERIOR DESIGN
580 BURBANK ST. SUITE 125, BROOMFIELD, CO 80020 PHONE: 303.465.4306 FAX: 303.465.4382 www.allredarch.com
T
2 20 125 NO STORAGE

5
3 20 125 NO APPARATUS BAY
A
I

| JOB NO.
C
O
S
1

|
4

PLANNING
&
F E D C B A

ALLRED
|
ARCHITECTURE

PERMIT SET
RTU-1 6
1
5
3

CITY OF THORNTON
FIRE STATION #7
2

2
3
1

FLOOR LOAD MAP MEZZANINE FLOOR LOAD MAP


SCALE: 1" = 10'-0" SCALE: 1" = 10'-0"
NORTH NORTH

10/08/2021

REVISION NAME DATE

1 1 ADDENDUM #1 2021 1008

2 FLOOR LOAD MAP ISSUE DATE: 2021 0907

S0.5 SCALE: 1" = 10'-0"

www.TheLefflerGroup.com info@theLefflerGroup.com
165 S. UNION BLVD, STE 360, LAKEWOOD, CO 80228

S0.5
P - 720.890.4095 © 2021

LOAD MAPS
1 TRASH ENCLOSURE - FLOOR LOAD MAP
S0.5 SCALE: 1" = 10'-0"

C ALLRED&ASSOCIATES 2021
MAP VALUE REPRESENTS MAX TOTAL AT HIGH SIDE OF DRIFT
(FLAT + DRIFT).
NET UPLIFT (ASD)
XX.X PSF ZONE SUCTION
PER MAP 1 -19.0 PSF
2 -35.0 PSF
28 PSF

S
NOTES:

E
1. VALUES BASED ON 10 SF.

210106
2. NET UPLIFT (ASD) = 0.6(D) +0.6(W).

INTERIOR DESIGN
580 BURBANK ST. SUITE 125, BROOMFIELD, CO 80020 PHONE: 303.465.4306 FAX: 303.465.4382 www.allredarch.com
T
A
I

| JOB NO.
NOTE: THIS LOADING IS TO BE USED FOR THE DRIFT LOADING CONDITION.
RE: GSN FOR BALANCED CONIDTION LOADING.
C
O
F E D C B A F E D C B A S
S

|
A

PLANNING
&

ALLRED
6 6

|
ARCHITECTURE
9'-0"
9'-6"
70.0 PSF ZONE 2

PERMIT SET
5 5

9'-0"
9'-6"

70.0 PSF 9'-0"


9'-6"
ZONE 2

4 4

9'-0"
9'-6"

9'-6" 9'-6"

ZONE 2

CITY OF THORNTON
3 3

FIRE STATION #7
9'-6"

70.0 PSF
9'-6" ZONE 2
9'-0"
9'-6" ZONE 1
9'-0"
70.0 PSF 9'-0"
70.0 PSF
ZONE 2
RTU-1 RTU-1

9'-6"
70.0 PSF ZONE 2

ZONE 1 ZONE 2

9'-0"
9'-6"

9'-0"
70.0 PSF ZONE 2
9'-6"

9'-0"
2 70.0 PSF
2 ZONE 2

1 1

10/08/2021

REVISION NAME DATE

1 ADDENDUM #1 2021 1008

SNOW DRIFT LOAD MAP NET WIND UPLIFT MAP


SCALE: 1" = 10'-0" SCALE: 1" = 10'-0"
NORTH NORTH

ISSUE DATE: 2021 0907

www.TheLefflerGroup.com info@theLefflerGroup.com
165 S. UNION BLVD, STE 360, LAKEWOOD, CO 80228

S0.6
P - 720.890.4095 © 2021

LOAD MAPS
C ALLRED&ASSOCIATES 2021
STEEL COLUMN SCHEDULE (C) INFORMATION ON DRAWINGS
PLAN LEGEND
MARK SIZE BASE PLATE THICKNESS COMMENTS
C1 HSS5X5X1/4 3/4" --- SYMBOL DESCRIPTION REMARKS

S
C2 W12X58 3/4" AESS STEEL AND BASE PLATE
TYPE B1 X
DETAIL CUTS SHOWN ON PLANS

210106
NOTES: X

INTERIOR DESIGN
580 BURBANK ST. SUITE 125, BROOMFIELD, CO 80020 PHONE: 303.465.4306 FAX: 303.465.4382 www.allredarch.com
T
1. ALL ANCHOR RODS TO BE 3/4" DIA. UNO.
2. RE: DETAILS FOR BASE PLATES, ANCHOR RODS AND OTHER
CONCRETE WALL UNO SEE PLANS AND SCHEDULES FOR REINFORCING

A
REQUIREMENTS AT BRACED FRAMES.

I
3. STEEL COLUMNS AT EXTERIOR WALL ARE SUPPORTED ON STEM WALLS
WITHIN WALL STUD CAVITY -TYP. CONTR TO COORD BASE PLATE 8" MASONRY WALL UNO OTHER SIZES ARE DIMENSIONED ON PLANS.

| JOB NO.
C
TYPES B2, B3, & B4 AS REQUIRED TO MATCH GEOMETRY OF STEM
WALL -TYP. 12" MASONRY WALL UNO OTHER SIZES ARE DIMENSIONED ON PLANS.
BASE PLATE TYPES
CL STUD WALL UNO
SEE GSN, PLANS, AND SCHEDULES FOR
O
S
1/4 SIZE AND SPACING OF STUDS.

1 1/2"
CL 1 1/2" 1 1/2"

1 1/2"
S
3"
MECHANICAL EQUIPMENT SEE PLANS FOR UNIT WEIGHTS.

|
1 1/2"
A
1 1/2" 1 1/2"
OPENING IN FRAMING SEE NOTE #4.

3"

PLANNING
2 1/2"
&
Beam Type AT XX" O.C. INDICATES EXTENTS OF MEMBER SEE PLANS.

1 1/2"

2 1/2"
1 1/2"

2 1/2"
1/4

ALLRED
1/4 1 1/2" 1 1/2"
1/4 5 1/2" CL

|
5 1/2"
5 1/2"
1'-0"

ARCHITECTURE
B2 B3 B4

PERMIT SET
B1

WALL STUD SCHEDULE - SUPPORTING BRICK VENEER

WALL HEIGHT FRAMING DEFLECTION TRACK

< 12'-0" 600S162-54 AT 16" OC 600T250-68

> 12'-0" 600S162-68 AT 16" OC 600T250-97

CITY OF THORNTON
JAMB SCHEDULE

FIRE STATION #7
OPENING WIDTH JAMB
MASONRY WALL SCHEDULE, (MW)
<= 6'-0" (2) 600S200-97
TYPE WIDTH REINFORCEMENT

MW1 9-5/8" #5 AT 32" OC <= 10'-0" (2) 600S350-97

MW2 9-5/8" #5 AT 16" OC

MW3 7-5/8" #5 AT 32" OC HORIZONTAL FRAMING SCHEDULE

RE: 1/S4.1 FOR ADD'L INFORMATION - TYP. OPENING WIDTH HEADER SILL

<= 6'-0" (2) 600S162-54 + (2) 600T125-54 600T125-54

<= 10'-0" (2) 600S162-68 + (2) 600T125-68 600T125-97

NOTES:
1. BOT WALL TRACK TO BE T125 w/ THICKNESS TO MATCH WALL STUD UNO - TYP.
2. ALL STUDS TO BE BRIDGED AT 4'-0" OC MAX.

10/08/2021

REVISION NAME DATE

1 ADDENDUM #1 2021 1008

ISSUE DATE: 2021 0907

www.TheLefflerGroup.com info@theLefflerGroup.com
165 S. UNION BLVD, STE 360, LAKEWOOD, CO 80228

S0.7
P - 720.890.4095 © 2021

SCHEDULES
C ALLRED&ASSOCIATES 2021
NOTE:
ACI TENSION LAP SPLICE LENGTHS 1. TABULATED VALUES ARE BASED ON GRADE 60 REINFORCING
BARS AND NORMAL WEIGHT CONCRETE.
f'c = 3,000 PSI OR LESS f'c = 4,000 PSI f'c = 5,000 PSI OR LESS 2. TENSION DEVELOPMENT LENGTHS AND TENSION LAP SPLICE
BAR LAP

S
TOP BARS OTHER BARS TOP BARS OTHER BARS TOP BARS OTHER BARS LENGTHS ARE CALCULATED PER ACI 318-11, SECTIONS 12.2
SIZE CLASS AND 12.15, RESPECTIVELY. TALBULATED VALUES FOR
CASE 1 CASE 2 CASE 1 CASE 2 CASE 1 CASE 2 CASE 1 CASE 2 CASE 1 CASE 2 CASE 1 CASE 2 BEAMS OR COLUMNS ARE BASED ON TRANSVERSE

210106
A 22 32 17 25 19 28 15 22 17 25 13 19 REINFORCEMENT AND CONCRETE COVER MEETING MINIMUM

INTERIOR DESIGN
#3

580 BURBANK ST. SUITE 125, BROOMFIELD, CO 80020 PHONE: 303.465.4306 FAX: 303.465.4382 www.allredarch.com
CODE REQUIREMENTS. LENGTHS ARE IN INCHES.

T
B 28 42 22 32 24 36 19 28 22 33 17 25
3. CASES 1 AND 2, WHICH DEPEND ON THE TYPE OF STRCTURAL
A 29 43 22 33 25 37 19 29 22 33 17 26 ELEMENT, CONCRETE COVER, AND THE CENTER-TO-CENTER
#4

A
B 37 56 29 43 32 48 25 37 29 43 22 33 SPACING OF THE BARS, ARE DEFINED AS:

I
A 36 54 28 41 31 47 24 36 28 42 22 32 BEAMS OR CASE 1: COVER AT LEAST 1.0 db AND c.-c.
#5 COLUMNS: SPACING AT LEAST 2.0 db

| JOB NO.
C
B 47 70 36 54 40 60 31 47 36 54 28 42 CASE 2: COVER LESS THAN 1.0b d OR c.-c.
A 43 64 33 50 37 56 29 43 33 50 26 38 SPACING LESS THAN 2.0 db
#6 ALL CASE 1: COVER AT LEAST 1.0 db AND c.-c.

O
B 56 84 43 64 48 72 37 56 43 65 33 50
OTHERS: SPACING AT LEAST 3.0 db
A 63 94 48 72 54 81 42 63 49 73 37 56 CASE 2: COVER LESS THAN 1.0 d b OR c.-c.
#7

S
B 81 122 63 94 70 106 54 81 63 94 49 73 SPACING LESS THAN 3.0 db
A 72 107 55 82 62 93 48 71 55 83 43 64 4. LAP SPLICE LENGTHS ARE MULTIPLES OF TENSION

S
#8 d
DEVELOPMENT LENGTHS: CLASS A = 1.0 AND

|
B 93 139 72 107 80 121 62 93 72 108 55 83 CLASS B = 1.3d (ACI 318-11, SECTION 12.15.1).

A
A 81 121 62 93 70 105 54 81 63 94 48 72 5. ACI 318-11 DOES NOT ALLOW LAP SPLICES OF #14 OR #18
#9 BARS. THE TABULATED VALUES FOR THOSE BAR SIZES

PLANNING
B 105 157 81 121 91 136 70 105 81 122 63 94 ARE THE TENSION DEVELOPMENT LENGTHS.

&
A 91 136 70 105 79 118 61 91 70 105 54 81 6. TOP BARS ARE HORIZONTAL BARS WITH MORE THAN 12 INCHES
#10
B 118 177 91 136 102 153 79 118 91 137 70 105 OF CONCRETE CAST BELOW THE BARS.
7. FOR LIGHTWEIGHT AGGREGATE CONCRETE, MULTIPLY THE
A 101 151 78 116 87 131 67 101 78 117 60 90
#11 TABULATED VALUES BY 1.3.
B 131 196 101 151 113 170 87 131 101 152 78 117 8. FOR EPOXY-COATED BARS, MULTIPLY THE TABULATED VALUES
#14 N/A 121 181 93 139 105 157 81 121 94 140 72 108 BY ONE OF THE FOLLOWING FACTORS:

ALLRED
#18 CONCRETE COVER AND SPACING TOP BARS OTHER BARS
N/A 161 241 124 186 139 209 107 161 125 187 96 144 COVER < 3.0 db OR c.-c. SPACING < 7.0 db1.7/1.3=1.31 1.50

|
COVER > 3.0 db AND c.-c. SPACING > 7.0 db 1.20 1.20

ARCHITECTURE

PERMIT SET
NOTES:
(1) 1. MASONRY WALL.
2. LINTEL PER SCHED.
NOTES: - GROUT SOLID.
(1) 3. VERTICAL BAR IN GROUTED
1. MASONRY WALL. CELL TO MATCH VERTICAL
2. DEPTH OF MASONRY LINTEL WALL REINFORCING - FULL
BEAM - SEE SCHED AND HEIGHT OF WALL - SEE
DETAILS. SCHEDULE BELOW. ONE BAR
3. LINTEL REINFORCING OR STEEL PER CELL.
LINTEL - SOLID GROUT. 4. (2) #5 BARS IN 8" DEEP
4. VERTICAL BAR IN GROUTED SOLID GROUTED BOND BEAM
CELL TO MATCH VERTICAL - HOOK BARS UP AT
WALL REINFORCING - FULL CORNERS.
HEIGHT OF WALL - SEE SCHEDULE

CITY OF THORNTON
BELOW, ONE BAR PER CELL.

(2)
(2)
5. (2) #5 BARS IN 8" DEEP
SOLID GROUTED BOND BEAM

FIRE STATION #7
(3) JAMB BARS WALL OPENING
- HOOK BARS UP AT
CORNERS. 1 0'-0" 4'-0"
(3)
(4)
JAMB BARS WALL OPENING 2 6'-1" 8'-0"
(4)
1 0'-0" 4'-0" 3 8'-1" 10'-0"

(5) 2 6'-1" 8'-0" 4 10'-1" 12'-0"


3 8'-1" 10'-0" 2 BARS IN FIRST 12'-1" 16'-0"
4 CELLS (8 BARS)
4 10'-1" 12'-0"
2 BARS IN FIRST
(2) BARS IN FIRST 12'-1" 6 CELLS (12 BARS) 16'-1" 20'-0"
14'-0"
(4) CELLS (8 BARS)
24" 24"
FOR OPENINGS LARGER THEN 20'-0" SEE
MIN. MIN. PLAN. IF SPECIAL JAMB BARS ARE NOT
SHOWN. USE WALL BRACES TO STRUCTURE.

24" 24"
MIN. MIN.

LOOSE LINTEL SCHEDULE


OPENING LINTEL BEARING
REMARKS
REINFORCED MASONRY LINTEL SCHEDULE EA. END

NOMINAL 0'-0" - 6'-0" L6x3 1/2x1/4 6" LLH


CLEAR SPAN REINFORCING TYPICAL DETAIL
DEPTH
0'-0" TO 4'-0" 8" (2) #4 BOTTOM OVER 6'-1"
L6x6x1/4 6" ---
THRU 7'-10"
OVER 4'-0" TO 6'-8" 16" (2) #4 TOP & BOTTOM
OVER 7'-10" L6x6x5/16
OVER 6'-8" TO 8'-8" 16" (2) #5 TOP & BOTTOM 6"
THRU 9'-2" OR W6x12
OVER 8'-8" TO 10'-8" 24" (2) #5 TOP & BOTTOM NOMINAL DEPTH OVER 9'-2" L6x6x3/8
6" 10/08/2021
THRU 10'-10" OR W8x15
OVER 10'-8" TO 12'-8" 32" (2) #6 TOP & BOTTOM SEE NOTE 3 FOR
OVER 10'-10" CONT WELDED
W10x15 8" BOT PL AT W
(2) #6 TOP AND BOT, THRU 12'-0"

1" CLR
OVER 12'-8" TO 14'-0" 40" BEAMS.
AND AT 8" OC BETWEEN
OVER 12'-0" REVISION NAME DATE
W12x19 8"
THRU 14'-0" 1 ADDENDUM #1 2021 1008

OVER 14'-0"
W14x22 8"
6" THRU THRU 16'-0"
12"
NOTES:
NOTES: 1. RE: ARCH DWGS FOR LOC AND CLEAR SPAN.
1. SEE ARCH DWG FOR LOCATION AND CLEAR SPAN. 2. PROVIDE (1) ANGLE FOR EA 4" OR LESS THICKNESS OF MASONRY AND (1) BEAM FOR
2. LINTELS SHALL SPAN CONTINUOUS BETWEEN BEARINGS EACH SIDE. EA 12" OR LESS THICKNESS OF MASONRY.
3. PROVIDE 8" MIN BEARING EA END FOR CLEAR SPAN 8'-0" OR LESS. 16" MIN BEARING EA END 3. WHERE W BEAMS ARE USED, PROVIDE CONT BOT PLATE WELDED TO BEAM ISSUE DATE: 2021 0907
FOR CLEAR SPAN GREATER THAN 8'-0". PER 5/S4.3 .
4. EXTEND BOTTOM REINFORCING TO END OF BEARING EACH SIDE - EXTEND TOP REINF WHERE 4. PROVIDE SOLID GROUTED OR SOLID MAS JAMB UNDER LINTEL EA SIDE OF OPNG.
POSSIBLE, 40xBAR DIA INTO WALL EACH SIDE. TERMINATE TOP REINF W/ STD HOOK AT CONTROL 5. FOR OPENINGS THAT ARE LARGER THAN 10'-0", PROVIDE (2) 5/8" DIAx1'-6"
JT OR FREE EDGES. ANCHOR BOLTS AT EA END. SLOT HOLES IN BM.

www.TheLefflerGroup.com info@theLefflerGroup.com
165 S. UNION BLVD, STE 360, LAKEWOOD, CO 80228

S0.8
5. PROVIDE SOLID GROUTED OR SOLID MAS JAMB UNDER LINTEL EACH SIDE OF OPG. 6. LINTELS FOR VENEER APPLICATIONS SHALL BE INSTALLED WITH VERTICAL LEG TIGHT
TO CMU OR STUD BACKUP. CONTR TO COORD LOCS DURING SHOP DWGS.

P - 720.890.4095 © 2021

SCHEDULES
C ALLRED&ASSOCIATES 2021
DRILLED PIER NOTES:

7" 1. VERIFY ALL DIMENSIONS WITH ARCHITECTURAL


17'-9" 17'-9"
DRAWINGS. ALL DIMENSIONS ARE TO CENTER OF

7"
PIER UNO.

DP2 DP2 DP2 2. SCHEDULED MARK DESIGNATIONS ARE TYPICAL


F E D C B A TO THE PROJECT AND MAY NOT NECESSARILY BE
FOUND ON THIS PLAN.

12'-10"
3. DP1, DP2, ETC. - AS SHOWN ON PLAN

210106
27'-8 7/8" 11'-10" 5'-8" 42'-4" INDICATES CONCRETE DRILLED PIER, SEE

INTERIOR DESIGN
580 BURBANK ST. SUITE 125, BROOMFIELD, CO 80020 PHONE: 303.465.4306 FAX: 303.465.4382 www.allredarch.com
T
SCHEDULE ON SHEET.
1'-1 1/8"

A
4. TOP OF PIER ELEVATIONS IS (96'-2") UNO ON

I
DP2 DP2 DP2 PLANS THUS (XX'-XX").
9"

| JOB NO.
9"

C
12'-11 1/2" 14'-11" 5. RE: TYPICAL DRILLED PIER DETAIL BELOW FOR

14'-0"
TYPICAL DRILLED PIER CONFIGURATION.

9"
6
O
S
7"
6'-8"

11'-7 7/8" 3'-10 1/8"

S
7" 8'-8 1/2"
7"

|
7"
DP2

A
5

6'-1 7/8"

PLANNING
DP2 DP2

&

14'-0"

10'-4 1/2"
8'-2"
18'-6 1/2"

DP2 (98'-9 1/2") DP2 (98'-9 1/2")

12'-0 7/8"
DP2 (98'-10") DP2 (98'-10") DP2 (98'-10")

ALLRED
DP2 DP2

|
DP2 DP2
8'-6"

ARCHITECTURE
7"

PERMIT SET
4
6'-2 1/2"

1 DRILLED PIER PLAN 2 DRILLED PIER PLAN

13'-10 1/2"
13'-11 1/2"

14'-3 3/8"
S1.0 SCALE: 1/8" = 1'-0" S1.0 SCALE: 1/8" = 1'-0"

DP2 (98'-10")

3
DP1
DRILLED PIER SCHEDULE (DP)
8'-3"

13'-1 1/2"
12'-8 5/8"
BEDROCK
MARK DIAMETER PENETRATION REINFORCING TIES COMMENTS

CITY OF THORNTON
DP2 (98'-10") DP2 (98'-10") DP1 24" 8'-0" (5) #7 LONG. #4 AT 18" OC

FIRE STATION #7
DP2 12" 8'-0" (2) #8 BUNDLED -
DP1 DP2 (96'-0") DP2 (96'-0") NOTE: ALL DRILLED PIERS DP1 UNO.
16'-0"

13'-1 1/2"
TIES
3" CLR
VERTICAL TO TIES
REINFORCING
52'-10"

DP2 (98'-10") DP2 (98'-10")


DP2 (96'-0") DP2 (96'-0")

13'-1 1/2"
DP2

DP2 DP2
DP1 DP2 (96'-0") DP2 (96'-0")
DP2 (98'-10") DP2 (98'-10")
NOTE: REINF CAGE TO
BE WIRE TIED ONLY -
12'-7"

8 1/4" (4)
WELDING NOT
PERMITTED (3) NOTES:
1. (3) ADDITIONAL TIES AT 4" OC
T.O. DP - TYPICAL.

9"
SEE PLAN 2. TOP OF BEARING MATERIAL
2

2"
RE: SOIL REPORT FOR DESCRIPTION.
4'-0"

8'-0" 3. TOP OF PIER.


7"

4. SEE DETAILS FOR DOWELS AND


1 (1) LOCATION WHERE VERTICAL REINF
EXTENDS INTO STRUCT ABOVE.
(2)
13'-8 1/2" 5. WHERE SPLICE OF VERTICAL
REINFORCING IS REQUIRED, USE

MINIMUM LENGTH = 20'-0"


10 3/4" 7" CLASS 'B' LAP. 10/08/2021

PENETRATION INTO BEARING MATERIAL


REVISION NAME DATE

1 ADDENDUM #1 2021 1008

3 1/2"
#3 x 4" EXTENSION

4" 6" 6"


DRILLED PIER PLAN PIER

RE: SCHEDULE
REINF.
SCALE: 1/8" = 1'-0"
NORTH ISSUE DATE: 2021 0907

0" TO 1'-0"

DRILLED PIER PLAN


ALIGNMENT BAR DETAIL

www.TheLefflerGroup.com info@theLefflerGroup.com
PLACE AT 1/4 POINTS AROUND

165 S. UNION BLVD, STE 360, LAKEWOOD, CO 80228

S1.0
THE CIRCUMFERENCE TOP &
BOTTOM & MID HEIGHT OF CAGE

P - 720.890.4095 © 2021
TYPICAL DRILLED PIER
3 NO SCALE

C ALLRED&ASSOCIATES 2021
FOUNDATION PLAN NOTES:
36'-8"
1. ELEVATIONS SHOWN ON PLAN ARE BASED ON DATUM ELEVATION
8 SPECIFIC TO THE PROJECT. RE: ARCH/CIVIL DRAWINGS FOR
S4.3 ACTUAL U.S.G.S. ELEVATIONS AND BENCHMARK LOCATION.

2. RE: PLAN FOR STRUCTURAL SLAB THINCKNESS & REINFORCING.


TOP OF SLAB ELEVATION IS 100'-0" UNO.
F E D C B A

14'-0"
3. VERIFY ALL DIMENSIONS WITH ARCHITECTURAL DRAWINGS.

S
8
S4.3
4. SCHEDULED MARK DESIGNATIONS ARE TYPICAL TO THE PROJECT

E
27'-8 7/8" 11'-10" 5'-8" 42'-4"

210106
8 AND MAY NOT NECESSARILY BE FOUND ON THIS PLAN.

INTERIOR DESIGN
580 BURBANK ST. SUITE 125, BROOMFIELD, CO 80020 PHONE: 303.465.4306 FAX: 303.465.4382 www.allredarch.com
F.O. WALL
F.O. GRD BM

F.O. GRD BM

F.O. GRD BM

F.O. GRD BM
S4.3

T
1'-1 1/8"
5. TOP OF FOOTING SHOWN AS (XX'-XX"). FOOTING ELEVATIONS

F.O. WALL
A
SHOWN ARE MAXIMUMS AND MAY NEED TO BE LOWERED DUE TO

I
SOIL CONDITIONS. VERIFY CHANGES WITH ENGINEER OF
5 RECORD. TOP OF EXTERIOR FOOTING ELEVATION SHALL BE

| JOB NO.
C
TYP S3.2 8
98'-0” UNLESS NOTED OTHERWISE. TOP OF INTERIOR FOOTING

42'-0"
TYP 5 2 5 S4.3
4'-9 3/8" ELEVATION SHALL BE 99'-0” UNLESS NOTED OTHERWISE.
S3.4 S3.4 S3.4

O
F.O. GRD BM 2 2 MW2 2 2 GENERATOR ENCLOSURE SLAB: 8"
6 SLAB REINF = #5 AT 12" OC EW T&B. 6. WF1, WF2, ETC - AS SHOWN ON PLAN INDICATES CONTINUOUS

S
7 WALL FOOTING, SEE SCHEDULE FOR SIZE AND REINFORCING.
TYP RE: 1/S5.4
6'-8"

11" 1 TYP MW1 2 5 5 S4.3

S
FOR X BRACE 3
S3.4 2 12'-4" 7. PROVIDE KEYED CONSTRUCTION JOINTS IN WALLS, GRADE

|
F.O. GRD BM S3.4 BEAMS AND SLABS IN STRICT ACCORDANCE WITH THE

A
5 TYP REQUIREMENTS SHOWN IN THESE DOCUMENTS. HORIZONTAL

PLANNING
1 ADD (5) #5 @ 6" TOP EA REINFORCING SHALL BE CONTINUOUS THROUGH VERTICAL KEYED
11"

C1 C1 C1

&
C1 C1 S3.3 WAY CTRD ON PIERS IN CONTROL JOINTS.
ISOLATED FITNESS SLAB.
RE: 1/S5.4 7
18'-6 1/2"

2'-10 3/8" 11 1/2" 11 3/8" 8. C1-X, C2-X, ETC - AS SHOWN ON PLAN INDICATES STEEL
FOR X BRACE 4 S4.3
TYP COLUMN, WHERE 'X' INDICATES BASE PLATE TYPE (PER
1 6 SCHEDULE). SEE COLUMN SCHEDULE FOR MORE INFORMATION.

ALLRED
S3.4 C1 COLUMNS ARE INDENTIFIED AT EACH COLUMN'S LOWEST LEVEL.
TYP 6 TYP 3

|
5
6 9'-10"
6'-3"

S3.2 4 S3.3 4 9. MW1, MW2, ETC - AS SHOWN ON PLAN INDICATES MASONRY


S3.4 S3.4 WALL, SEE SCHEDULE FOR SIZE AND REINFORCING.
MW3

ARCHITECTURE
F.O. WALL

PERMIT SET
4 1 10. VERIFY EXACT LOCATION OF DEPRESSED SLABS WITH
3 ARCHITECTURAL DRAWINGS.
13'-11 1/2"

TYP 1 FOUNDATION PLAN - GENERATOR ENCLOSURE 11. FOR SIDEWALK LOCATION AND DETAILS, SEE ARCHITECTURAL
ADD (5) #5 @ 12" TOP EA MW3 4 TYPICAL 8" SLAB DRAWINGS.
S2.0 SCALE: 1/8" = 1'-0"
WAY CTRD ON PIERS - TYP S3.4 REINF = #5 @ 12" OC
AT ALL 8" SLABS. EA WAY TOP & BOT 1 12. INDICATES CMU CONTROL JOINT. PROVIDE MASONRY
CONTROL JOINTS IN MASONRY WALLS PER G.S.N. AND TYPICAL
F.O. WALL C2 DETAILS. RE: ARCH DRAWING FOR VENEER CONTROL JOINTS.
3 MW3
3
13. VERIFY EXACT SIZE AND LOCATION OF OPENINGS WITH
7 C1 MW1
NOTE: EXPOSED S3.4 ARCHITECTURAL DRAWINGS.
3'-9 1/2"

S3.4
TYP 1 10'-0"
STEEL AT LOW ROOF 6 C1 MECH YARD SLAB: 8"
SHALL BE AESS 1/4" GALV STL PL. RE: 5/S4.1 SLAB REINF = #5 AT 12" OC EW T&B. 14. ALL PRECAST CONCRETE VENEER PIECES SHALL BE
S5.6
CLASS 3 STEEL - FOR TRAINING WALL ANCHORS. RE: TYP 8 CONTINUOUSLY SUPPORTED BY STEEL LEDGER ANGLE.

CITY OF THORNTON
MW1 ARCH FOR EXACT QUANITIY AND LOCS. 5 S4.3 RE: 3/S5.3 FOR MASONRY WALL CONDITION. PROVIDE
TYP. RE: 2 S3.4 LEDGER DIRECTLY WELDED TO CFS FRAMING WITH 1/8" FILLET
SPECIFICATIONS FOR
18'-1"

S3.1

FIRE STATION #7
C2 TOP & BOT AT 32" OC. LEDGER SHALL BE 3/8" THICK WITH
REQ'S.
6" VERTICAL LEG - CONTR TO COORD FINAL HORIZONTAL
TYP
3
14" CONC DIMENSION PRIOR TO PREPARING SHOP DRAWINGS.
7

12'-0"
S3.4 SLAB ON VOID
S3.4 5
S3.2 1
52'-10"

3
1
TYP C1 TYP S5.3 KEYNOTES:
1 TYP
S3.3 5 1 PROVIDE #5 AT 8" OC VERT FULL HT FOR FIRST (3) CELLS.
5 5 S3.4
C1
S3.3 S3.3
2 PROVIDE #6 AT 8" OC VERT FULL HT FOR FIRST (3) CELLS.
SIM TYP
7 1 2
8'-2 1/2"

S3.4
3 PROVIDE #6 VERT FULL HT IN EA CELL.
S4.3
2 FOUNDATION PLAN - TRASH ENCLOSURE
1 4 PROVIDE #3 (EC)X6'-0" AT 12" OC ACROSS THRESHOLD INTO PAVING.
C1 3 S2.0 SCALE: 1/8" = 1'-0"
STAGGER ENDS 1'-0". PLACE BARS 2-1/2" FROM SURFACE.
C2

7 5 5 PL1/2XCONT JAMB AND HEAD PLATE WITH 3/4" DIAX0'-6" ANCHORS AT


S3.4
3 S3.4 2'-0" OC MAX - TYP AT OVERHEAD DOORS. RE: ARCH FOR ADD'L
TYPICAL 14" SLAB REQUIREMENTS.
5
13'-5"

REINF = #5 @ 8" OC S3.2


EA WAY TOP & BOT 6 PROVIDE CONTINUOUS 1/2" ISOLATION JOINT IN SLAB AT INTERIOR
PERIMETER OF FITNESS AREA AS SHOWN PER 6/S3.3 .
4'-7" 6'-5 3/8" 5 5
2 2 3
F.O. GRD BM 3
2 C1 C1
11"
4'-0"

C1 C1 5 4 3 MW2 4 5 2 2
5 2 5
F.O. GRD BM S3.4 S3.4 S3.4
1 TYP
1
6'-9" 14'-5"
S3.4
11"
TYP TYP 5 10/08/2021
S3.2
APPARATUS BAY POUR #1 APPARATUS BAY POUR #2 APPARATUS BAY POUR #1
RE: 1/S5.4
FOR X BRACE

REVISION NAME DATE

1 ADDENDUM #1 2021 1008

FOUNDATION PLAN
SCALE: 1/8" = 1'-0"
NORTH ISSUE DATE: 2021 0907

FOUNDATION PLAN
www.TheLefflerGroup.com info@theLefflerGroup.com
165 S. UNION BLVD, STE 360, LAKEWOOD, CO 80228

S2.0
P - 720.890.4095 © 2021
C ALLRED&ASSOCIATES 2021
FLOOR FRAMING NOTES

S
1. ELEVATIONS SHOWN ON PLAN ARE BASED ON DATUM ELEVATION VERIFY ALL
DIMENSIONS WITH ARCHITECTURAL DRAWINGS. TOP OF CONCRETE = 111'-6"

210106
UNO. TOP OF STEEL = 111'-2 UNO.

INTERIOR DESIGN
580 BURBANK ST. SUITE 125, BROOMFIELD, CO 80020 PHONE: 303.465.4306 FAX: 303.465.4382 www.allredarch.com
T
2. SCHEDULED MARK DESIGNATIONS ARE TYPICAL TO THE PROJECT AND MAY NOT
NECESSARILY BE FOUND ON THIS PLAN.

3. C1, C2, ETC - AS SHOWN ON PLAN INDICATES STEEL COLUMN, SEE SCHEDULE
A
I

| JOB NO.
FOR MORE INFORMATION.

4. FLOOR DECK SHALL BE 1” DEEP TYPE C, 32” TO 36” WIDE, 22 GAGE


C
O
GALVANIZED STEEL, WITH MINIMUM YIELD STRESS OF 33 KSI, WITH MINIMUM S
= 0.130 IN3 AND I = 0.073 IN4 PER FOOT OF WIDTH. DECK SHALL BE

S
F E D C B A ERECTED IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS AS 3 SPAN

S
MINIMUM.

|
27'-8 7/8" 11'-10" 5'-8" 42'-4"

A
5. WELD FLOOR DECK TO SUPPORTING MEMEBERS WITH (4) 5/8" DIAMETER PUDDLE
WELDS PER SHEET AT ENDS, END LAPS AND AT INTERMEDIATE SUPPORTS, AND

PLANNING
1'-1 1/8"

&
AT 12” OC AT PERIMETER BEAMS AND OPENING EDGES RUNNING PARALLEL TO
THE DECK. SIDE SEAM ATTACHMENT SHALL BE #10 SCREWS AT 12" OC.

6. FLOOR SLAB SHALL BE 3” NORMAL WEIGHT CONCRETE ON 1” DECK (4” TOTAL


THICKNESS) REINFORCED WITH WWF 6X6 W2.1XW2.1 CENTERED UNO.

ALLRED
7. FOR STEEL LINTELS, SEE SCHEDULE ON TYPICAL DETAIL SHEET. CONTRACTOR

|
SHALL COORDINATE WITH OTHER TRADES FOR EXACT SIZE AND LOCATION
6 HSS8X6X1/4 HSS10X6X1/4 REQUIREMENTS.

ARCHITECTURE
(114'-10") (114'-10")
6'-8"

PERMIT SET
7 8. FOR MASONRY LINTELS SEE SCHEDULE ON TYPICAL DETAIL SHEET. CONTRACTOR
S4.2 SHALL COORDINATE WITH OTHER TRADES FOR EXACT SIZE AND LOCATION
TYP
REQUIREMENTS.
5
9. FOR CLARITY, DETAILS MAY SHOW ONLY ONE SIDE OF FRAMING CONDITION.

10. FOR CLARITY, ALL FLOOR OPENINGS MAY NOT BE SHOWN ON FLOOR FRAMING
18'-6 1/2"

PLAN. FOR EXACT SIZE, NUMBER AND LOCATION OF OPENINGS, SEE


ARCHITECTURAL, MECHANICAL, PLUMBING, AND ELECTRICAL DRAWINGS. FOR
FRAMING AT OPENINGS, SEE TYPICAL DETAILS.
2'-6 7/8"
TYP 11. CONTRACTOR TO VERIFY, AND BE RESPONSIBLE FOR VARIATIONS IN CONCRETE
5 QUANTITY DUE TO CAMBER, CONSTRUCTION DEAD LOAD DEFLECTIONS, AND/OR
S4.2
STRUCTURAL STEEL TOLERANCES OF STEEL BEAMS AND STEEL DECK. FOR
CONCRETE CONTROL JOINTS, IN CONCRETE SLAB, SEE GSN AND TYPICAL
4 DETAILS.

CITY OF THORNTON
5

FIRE STATION #7
S4.2 12. ALL STAIR STRINGERS ARE 12" CHANNEL SHAPE; ALL STAIR HEADERS ARE 8"
13'-11 1/2"

12K3 CHANNEL SHAPE MINIMUM.

AT 2'-6" OC 13. INDICATES CMU CONTROL JOINT. PROVIDE MASONRY CONTROL JOINTS IN
5
S4.2 MASONRY WALLS PER GSN AND TYPICAL DETAILS. RE: ARCH DRAWING FOR
HSS10X6X3/8 (FLAT) VENEER CONTROL JOINTS.
(111'-11 1/2")
3 2
S4.2
2
S4.2 4 4
5 6
S4.2 S4.2 S4.2 S4.2
W12X35

6 TYP TYP TYP TYP


S5.3

HSS8X6X1/4
5 RE: 5/S4.1
S5.1 FOR TYP TRAINING
5 WALL ANCHORS. RE:
S5.4 ARCH FOR LOCS.
HSS10X6X1/2
HSS10X6X3/8 (FLAT)
(111'-11 1/2")

7
AT 2'-6" OC

S5.3 NOTE: EXPOSED STEEL AT LOW ROOF


HSS6X3X1/4

SHALL BE AESS CLASS 3 STEEL -


TYP. RE: SPECIFICATIONS FOR
REQ'S.

(114'-10")
HSS8X6X1/4
52'-10"

W12X35

5
S5.1
9
S5.2
TYP AT CANOPY
HSS10X6X1/2

7
S4.2
TYP
(114'-10")
HSS8X6X1/4

HSS10X6X3/8 (FLAT) 10/08/2021


6 (111'-11 1/2")
S5.3
HSS8X6X1/4
(110'-5")

TYP REVISION NAME DATE


7 1 ADDENDUM #1 2021 1008
S4.2
HSS10X6X1/4 HSS10X6X1/4
TYP
4 (114'-10") (114'-10") 2
4'-0"

S5.7
HSS8X6X1/4 HSS8X6X1/4 HSS8X6X1/4
(110'-5") (110'-5") (110'-5") 1
8
S5.3
TYP AT SUNSHADES
ISSUE DATE: 2021 0907

www.TheLefflerGroup.com info@theLefflerGroup.com
165 S. UNION BLVD, STE 360, LAKEWOOD, CO 80228

S2.1
FRAMING PLAN
P - 720.890.4095 © 2021
MEZZANINE FRAMING PLAN
SCALE: 1/8" = 1'-0"
NORTH

C ALLRED&ASSOCIATES 2021
ROOF FRAMING NOTES:

1. VERIFY ALL DIMENSIONS WITH ARCHITECTURAL DRAWINGS. ROOF


ELEVATIONS, WHERE SHOWN, ARE TO BE PROVIDED AND VERIFIED
BY THE ARCHITECT.
F E D C B A 2. SCHEDULED MARK DESIGNATIONS ARE TYPICAL TO THE PROJECT

S
AND MAY NOT NECESSARILY BE FOUND ON THIS PLAN.

210106
3. C1, C2, ETC - AS SHOWN ON PLAN INDICATES STEEL COLUMN,
27'-8 7/8" 11'-10" 5'-8" 42'-4"

INTERIOR DESIGN
SEE SCHEDULE FOR MORE INFORMATION.

580 BURBANK ST. SUITE 125, BROOMFIELD, CO 80020 PHONE: 303.465.4306 FAX: 303.465.4382 www.allredarch.com
1'-1 1/8" 4. STEEL ROOF DECK SHALL BE 1.5” DEEP, 36” WIDE, 20 GAGE
T
A
PROVIDE CONT BOT PLATE
GALVANIZED STEEL, WITH MINIMUM YIELD STRESS OF 33 KSI,

I
WELDED AT W BEAM LEDGERS
PER 5/S4.3 - TYP. WITH MINIMUM S = 0.234 IN3 AND I = 0.222 IN4 PER FOOT OF

| JOB NO.
WIDTH. DECK SHALL BE ERECTED IN ACCORDANCE WITH

2'-6 3/8"
1 MANUFACTURER'S RECOMMENDATIONS AS (3) SPAN MINIMUM.
S4.2

O
5. WELD ROOF DECK TO SUPPORTING MEMBERS WITH (7) - 5/8"
6
S
DIAMETER PUDDLE WELDS PER SHEET AT ENDS, END LAPS AND AT
TYP PARAPET COLUMN INTERMEDIATE SUPPORTS, AND AT 12” OC AT PERIMETER BEAMS
6'-8"

AT 5'-0" OC
PER: 8/S5.6 4
2'-3"

S
1 AND OPENING EDGES RUNNING PARALLEL TO THE DECK. SIDE SEAM
S5.3

28K8
S4.2 BOT OF DECK

|
ATTACHMENT SHALL BE #10 AT 12" OC MINIMUM DIAPHRAGM

2'-6"
A
= 23'-6"
5 W18X35 W18X35 SHEAR CAPACITY = 554 PLF.

PLANNING
3'-6"
&
0" A 6. FOR STEEL LINTELS, SEE SCHEDULE ON TYPICAL DETAIL SHEET.
W21X44 1 S2.2 CONTRACTOR SHALL COORDINATE WITH OTHER TRADES FOR EXACT
1'-5"

TYP TYP
3 28KCS5 SIZE AND LOCATION REQUIREMENTS.
18'-6 1/2"

AT 5'-0" OC
S5.2

W18X35

5'-0"
W18X35
28K10
BOT OF DECK 7. FOR MASONRY LINTELS SEE SCHEDULE ON TYPICAL DETAIL SHEET.
TYP

AT 5'-0" OC

ALLRED
6 = 15'-8 5/8" CONTRACTOR SHALL COORDINATE WITH OTHER TRADES FOR EXACT
S5.2 SIZE AND LOCATION REQUIREMENTS.

28K8
3 7/8"

|
5
1 3
W18X35

S5.3 8. FOR CLARITY, DETAILS MAY SHOW ONLY ONE SIDE OF FRAMING
S4.2 S4.2

4'-0 1/2"

ARCHITECTURE
CONDITION.

PERMIT SET
4

4'-6 5/8"
2'-8 1/8"
W16X40 2 9. FOR CLARITY, ALL ROOF OPENINGS MAY NOT BE SHOWN ON ROOF
BO DECK = 16'- 1 9/16" S4.3 1 2 FRAMING PLAN. FOR EXACT SIZE, NUMBER AND LOCATION OF
4'-0 5/8"

AT 2'-6" OC
S4.2
13'-11 1/2"

S4.2 OPENINGS, SEE ARCHITECTURAL, MECHANICAL, PLUMBING, AND


S4.2
TYP AT EA ELECTRICAL DRAWINGS. FOR FRAMING AT OPENINGS, SEE

5'-0"
AT 5'-0" OC

10K1
JOIST 7 TYPICAL DETAILS.
18K6

BO DECK = 20'- 5 3/4" S5.4


3

S10X35
4 2 10. EQUIPMENT WEIGHTS SHOWN AS XXK WHERE XX IS IN KIPS.

5'-0"
S4.2 S4.3 2
.2K S5.2 WEIGHT SHOWN INCLUDES ALL INERTIA BASES AND/OR
W12X22 S4.2
2 HOUSEKEEPING PADS. IF WEIGHT OF ACTUAL EQUIPMENT IS
3 S5.3

2'-3 1/2"
1
GREATER THAN SHOWN, OR ADDITIONAL EQUIPMENT NOT SHOWN

4'-6"
.2K S4.2 EXISTS, NOTIFY STRUCTURAL ENGINEER IMMEDIATELY.

8'-5"
6

MAX
S5.4
5'-1 1/8"
7'-6" 2'-6"

1 11. PROVIDE PREFABRICATED BRICK LINTEL SYSTEMS BY H&B MITEK


S4.2
8 (OR APPROVED EQUAL) AS SHOWN ON ARCHITECTURAL DRAWINGS.
FOR LOW ROOF FRAMING.

5'-0" 3'-9" 3'-9"

S5.6 WHERE ARCHED LINTEL SYSTEMS ARE USED, MASONRY OR CFS

CITY OF THORNTON
TYP
4 ROUGH OPENING SHALL BE CONSTRUCTED SUCH THAT A MINIMUM OF
S5.2

FIRE STATION #7
4 6" CLEAR FROM TOP OF KEYSTONE BRICK IS MAINTAINED TO
2.5K
RTU-1 S5.2 BOTTOM OF MASONRY OR CFS FRAMING. 4" CMU INFILL SHALL BE
W18X35

CUT TO FILL THE SPACE BETWEEN THE ARCH AND MASONRY HEAD
BEING CAREFUL TO ALIGN MORTAR JOINTS. CFS INFILL IS
BOT OF DECK AT FO

AT 5'-0" OC
REQUIRED BEHIND 4" SOAPS.
WALL = 15'-10 5/8"

30K11
BOT OF DECK BOT OF DECK AT FO
= 16'-8 1/4" 3 WALL = 23'-4 1/4"
TYP S5.3
1/S2.1

AT 5'-0" OC
52'-10"

3 BOT OF DECK
AT FO WALL =
26K8

S5.2
24'-4"
RE:

1
S4.2

NOTES:
1. L4X4X1/4 W/ PL3/8 EA END WELDED TO CHORDS. WELD TO PANEL POINT T&B AT 4'-0"
MIN, 6'-0" MAX, FULL LENGTH.

2'-6"
RE: 4/S5.1 2. ROOF JOISTS PER PLAN.
W18X35

FOR OPNG FRAMING -TYP 2


S5.3

2'-6"
2'-2 1/4"

2
S4.3
(2)
(1)
2 W18X55

2'-8 7/8"
4'-0"

1
W18X35

S4.2 5k IMPACT
1
2'-0"

W16X40 W16X40
4
S5.3

ROOF BRACING 10/08/2021


A NO SCALE

REVISION NAME DATE


KEY NOTE 1 :
1 ADDENDUM #1 2021 1008
5000LB IMPACT LOADS APPLIED ALONG THIS JOIST
HAVE BEEN INCLUDED IN THE DESIGN OF THIS
FRAMING. RE: A/S2.2 FOR BRACING.

ROOF FRAMING PLAN


ISSUE DATE: 2021 0907
SCALE: 1/8" = 1'-0"
NORTH

ROOF FRAMING PLAN


NOTE:ROOF FRAMING HAS BEEN
DESIGNED FOR AN ADDITIONAL

www.TheLefflerGroup.com info@theLefflerGroup.com
10 PSF DEAD LOAD FOR FUTURE

165 S. UNION BLVD, STE 360, LAKEWOOD, CO 80228

S2.2
SOLAR.

P - 720.890.4095 © 2021
C ALLRED&ASSOCIATES 2021
NOTES:
(2) 6 MIN
1. TYP PIER SEE PLAN. (1) 1 NOTES:
2. SURE TOP, INSTALL IN ACCORDANCE
1. LAP - SEE
WITH MANUF. SPECS. PROTECT FROM BAR OFFSET
SCHEDULE.
MOISTURE AND DAMAGE PRIOR TO (3) 2. MAXIMUM 1/5 LAP
CONCRETE PLACEMENT. (4)
NOTES:
BUT NOT MORE THAN
1. SLAB EDGE. 6".
2. 2 #4 X 4'-0" LONG AT MID DEPTH. 3. WIRE TIES.
4. 1d (1" MINIMUM).
SPLICE DETAIL BAR CLEARANCE
5. RADIUS=3d FOR BARS

6"
NOT OVER #8; 4d

S
(6) FOR #9, #10 AND #

6"
-
11 BARS; 5d FOR #

3'
(5)

E
"d"

210106
"d"
. 14 AND #18 BARS.

(7)
"d"

INTERIOR DESIGN
580 BURBANK ST. SUITE 125, BROOMFIELD, CO 80020 PHONE: 303.465.4306 FAX: 303.465.4382 www.allredarch.com
5d FOR ALL GRADE

T
(5)
45° 40 BARS WITH 180

A
DEGREE HOOK.

I
(2) 6. 4d (4" MINIMUM).
BEND & HOOK DETAILS (5) 7. 12d (90 DEGREE

| JOB NO.
C
HOOK).
(1) (2) (8) (8) 8. 6d (4" MINIMUM).

O
9. 135 DEGREE BEND
10. BEND AROUND 1 1/2"

S
PIN FOR #3 BARS.
BEND AROUND 2" PIN

S
(9) (9) FOR #4 BARS. BEND
(1)

|
(10 AROUND 2 1/2" PIN

A
(10) ) FOR #5 BARS.

PLANNING
PLAN - REENTRANT CORNER REINFORCEMENT COLUMN TIES BEAM STIRRUPS

&
7 THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
NO SCALE
TYPICAL CONCRETE REINFORCING BAR DETAILS
NOT NECESSARILY CUT OR CALLED OUT ON PLANS.
1 THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
NO SCALE
NOTES: TYPICAL VOID FORM DETAIL

ALLRED
1. OPENING MAY HAVE ANY
OTHER SHAPE THAN SHOWN
4 THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
NO SCALE
NOT NECESSARILY CUT OR CALLED OUT ON PLANS.

|
HERE. FOR REINFORCING NOT NECESSARILY CUT OR CALLED OUT ON PLANS.
APPLICATION, USE

ARCHITECTURE
CIRCUMSCRIBING

PERMIT SET
NOTES:
(2) RECTANGLE.
(1) 1. CONC. SLAB ON GRADE.
2. (2) #5 BARS AT CENTER 8"
(3)
OF SLAB - TYP. (2) 2. #4x AT 12" OC - INSTALL W/
3. (1) #5 BAR AT TOP. RE: ARCH'L
2'

STRUCTURAL ADHESIVE PER GSN OR


-0

4. EXTEND TRIMMER BARS (3) PRIOR TO PLACING CONCRETE SLAB.


"

2'-6" MIN BEYOND SIDES

MIN.
NOTES: 3. #4XCONT.

4"
OF OPENING OR AS FAR AS (1)
1. TYP PIER SEE PLAN. 4. #4 AT 12 OC EA WAY TOP.
POSSIBLE AND HOOK.
2. VOID FORM, INSTALL IN

5"
ACCORDANCE WITH MANUF. SPECS.
2'

ø" PROTECT FROM MOISTURE AND


-0
"

CLR. DAMAGE PRIOR TO CONCRETE


PLACEMENT.
3"
4'-0" CURB
MAX.

CITY OF THORNTON
(2)
4" MIN
12" AT EXTRACTOR

FIRE STATION #7
(3) (2)
(4)
(1)
(4)

2"
NOTE: PROVIDE EXTRA BARS (NOT SHOWN) PARALLEL TO SIES OF OPENINGS, EQUAL TO
AREAS OF INTERRUPTED SLAB BARS. EXTEND FULL LENGTH OF SPAN OR OF TOP BARS AS
APPLICABLE. THIS DETAIL IS TYPICAL AT OPENINGS UP TO 4'-0" MAX DIMS EXCEPT AS EQUIPMENT PAD
SHOWN OTHERWISE.

(1)
TYPICAL OPENING IN CONCRETE SLAB CURB AND EQUIPMENT PAD DETAIL
8 THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
NO SCALE 2 NO SCALE
NOT NECESSARILY CUT OR CALLED OUT ON PLANS.

NOTES:
1. DRILLED PIER - RE:PLAN.
2" MIN 2. VOID FORM, INSTALL IN
CLR TO REINF. NOTE: WHERE CLEAR DISTANCE BETWEEN ACCORDANCE WITH MANUF. SPECS.
OR TENDON SLEEVES IS IMPOSSIBLE THIS AREA SHALL BE PROTECT FROM MOISTURE AND
DAMAGE PRIOR TO CONCRETE
TREATED AS A SLAB OR WALL OPENING TYPICAL VOID FORM DETAIL
REINFORCED AS PER TYPICAL OPENING
DETAILS. PRESET ALL SLEEVES PRIOR TO
5 THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
NO SCALE 3.
PLACEMENT.
VOID SEAM.
POURING CONCRETE. NO CORE DRILLING 4. ARC VOID AT DRILLED PEIRS.
NOT NECESSARILY CUT OR CALLED OUT ON PLANS.
ALLOWED WITHOUT STRUCTURAL ENGINEERS 5. CONCRETE FORM.
APPROVAL. NO PIPING OR CONDUIT PERMITTED 6. RE: SCHEDULE FOR DRILLED PIER 10/08/2021
D 3D OR 4" MIN REINFORCING.
IN OR THROUGH CONCRETE BEAMS, JOISTS OR
COLUMNS UNLESS SPECIFICALLY DETAILED ON NOTES:
PIPING THRU SLAB OR WALL STRUCTURAL DRAWINGS OR APPROVED BY THE 1. TYP PIER SEE PLAN.
2. SLAB VOID FORM, INSTALL IN (6)
STRUCTURAL ENGINEER. (2) REVISION NAME DATE
ACCORDANCE WITH MANUF. SPECS.
PROTECT FROM MOISTURE AND (3) 1 ADDENDUM #1 2021 1008
DAMAGE PRIOR TO CONCRETE
PLACEMENT. (5) (4)
CENTERLINE OF SLAB
OR WALL MAX D = T/3
OR 2" WHICH-
EVER IS SMALLER
(2)
"T"

ISSUE DATE: 2021 0907

CONCRETE DETAILS
D 6D OR 8" MIN

www.TheLefflerGroup.com info@theLefflerGroup.com
165 S. UNION BLVD, STE 360, LAKEWOOD, CO 80228

S3.1
PIPING THRU SLAB OR WALL (1) (1)

P - 720.890.4095 © 2021
D = OUTSIDE SLEEVE DIAMETER

PIPING AND CONDUIT IN OR THRU SLAB OR WALL TYPICAL VOID FORM DETAIL TYPICAL VOID FORM DETAIL AT GR BM
9 THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
NO SCALE 6 THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
NO SCALE 3 THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
NO SCALE
NOT NECESSARILY CUT OR CALLED OUT ON PLANS. NOT NECESSARILY CUT OR CALLED OUT ON PLANS. NOT NECESSARILY CUT OR CALLED OUT ON PLANS.
C ALLRED&ASSOCIATES 2021
NOTES:
1. CONC GRADE BM.
2. MAX 12" SQ OR DIAMETER OPNG. GENERAL NOTES:
3. OPNG TO BE LOCATED IN MIDDLE 1/3 DEPTH OF BM.
NOTE: HORIZONTAL CONSTRUCTION
4. LOCATE OPNG IN MIDDLE 1/3 OF BM SPAN. 1. GRADE BEAM. JOINTS IN CONCRETE BEAMS NOT
5. PROVIDE (2) STIRRUPS AT 3" EA SUDE OF OPNG. 2. VOID FORM DISCONTINUOUS AT FTG/PIER/PILE CAP. ALLOWED. - TYP.
3. RE: FTG/PIER/PILE CAP DETAILS FOR DOWEL REQUIREMENTS
(4) INTO GRADE BEAM.
4. TOP REINFORCEMENT SHALL BE SPLICED IN MIDDLE 1/3 OF
(5)
SPAN.
5. BOTTOM REINFORCEMENT SHALL BE SPLICED OVER SUPPORTS.
6. VOID FORM.

d/3
S
E

210106
T.O. GB STEP PER
CL PIER/PILE CAP/FOOTING

d/3
PLAN

INTERIOR DESIGN
d

CL PIER/PILE CAP/FOOTING

580 BURBANK ST. SUITE 125, BROOMFIELD, CO 80020 PHONE: 303.465.4306 FAX: 303.465.4382 www.allredarch.com
T
(3) SPAN

d/3
I
1/3 SPAN MIDDLE 1/3 OF SPAN 1/3 SPAN
(1)

| JOB NO.
C
(2) (7)
CL JT (11) CL OPNG (15)
(1)

O
(8) 2"-4" (4)
(14) (17) (17)

S
OPENING IN CONCRETE GR BM
4
S
NO SCALE
THIS DETAIL IS TYPICAL TO THE PROJECT AND IS

|
NOT NECESSARILY CUT OR CALLED OUT ON PLANS.

D/3
D/3
CLASS B LAP

PLANNING
NOTES:
1.
2.
WALL BEYOND.
#5 AT 8" OC EACH WAY AT MID DEPTH. (13) &

D/3
D/3
3. 12" VOID FORM BETWEEN STOOP WALLS AND 4" VOID

D
FORM UNDER WING WALL.

ALLRED
4. #5 AT MID HEIGHT OF 8" WING WALL WITH 90° HOOK CLASS B LAP
IN GR BM.

|
5. #5 AT 8" VERT IN WING WALL.
(1)

D/3

D/3
6. (2) #5 IN BOTTOM IN 8" WING WALL WITH 90° HOOK
IN GR BM.

ARCHITECTURE

PERMIT SET
7. CONCRETE GRADE BEAM BEYOND.
8. GB REINF CONTINUOUS THROUGH STOOP AREA. (5)

8"
(2)
(3)
(3)
(16)
(6) (17) (17)
(2) (2)

(3) (8) GRADE BEAM STEP GRADE BEAM VERTICAL GRADE BEAM GRADE BEAM
2"
CLR CONSTRUCTION JOINT OPENINGS INTERSECTIONS
(7)
(4) AT GRADE BEAM STEPS: VERTICAL CONSTRUCTION JOINTS:
OPENINGS IN GRADE BEAMS: AT GRADE BEAM INTERSECTIONS:

CITY OF THORNTON
7. STAGGER BOT STEP UP TO 9. HORIZONTAL CONSTRUCTION JOINTS NOT
ALLOWED. 13. 12" SQ. OR DIA. MAX OPNG SIZE. 17. PROVIDE CORNER BARS AT
"D" (GB DEPTH) FROM

FIRE STATION #7
(5) 10. PROVIDE VERTICAL CONSTRUCTION JOINTS 14. OPENINGS SHALL BE LOCATED IN BEAM INTERSECTIONS TO
TOP, OR UNTIL BOTTOM IS
60'-0" O.C. MAXIMUM UNLESS EOR REVIEW MIDDLE 1/3 DEPTH OF GRADE MAINTAIN CONTINUOUS
6" BEYOND PIER/PILE
OF JOINT LAYOUT PLAN SPECIFICALLY BEAMS. HORIZONTAL
CAP/ FOOTING.
ALLOWS GREATER SPACING. 15. OPENINGS SHALL BE LOCATED IN REINFORCEMENT -
(6) 8. (2) #5 W/ STD HOOK.
11. JOINTS SHALL BE LOCATED WITHIN MIDDLE MIDDLE 1/3 OF BEAM SPAN. TYPICAL.
(3) 1/3 OF SPAN OR CENTERED OVER DRILLED 16. PROVIDE 2 STIRRUPS AT 3" EACH
PIER/PILE/FOOTING SUPPORT. SIDE OF OPNGS.
12. LOCATION AND DETAIL OF JOINTS SHALL BE
APPROVED BY ARCHITECT AND ENGINEER
PRIOR TO CONSTRUCTING FORMS OR PLACING
STRUCTURAL STOOP CONCRETE AND SHALL BE SHOWN ON THE
5 NO SCALE TYP GRADE BM SHOP DRAWINGS.
THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
NOT NECESSARILY CUT OR CALLED OUT ON PLANS. 1 THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
NO SCALE
NOT NECESSARILY CUT OR CALLED OUT ON PLANS.

NOTES: NOTES:
1. 12" THICK PIER CAP W/ #5 AT 12" OC EW T&B.
2. 6" VOID FORM. 1. GRADE BEAM.
3. 12" DRILLED PIER DP2. 2. PROVIDE CORNER BARS AT
COORD W/ MFR BEAM INTERSECTIONS -
TYPICAL.
1'-0" 1'-0" NOTES: (1)

MIN MIN (1)


2. TOP & BOTTOM REINF TO RUN (2)
THRU JOINT UNINTERRUPTED.
3. TOP OF BEAM.
(1) (2)
EQ

COORD W/ MFR

NOTE: HORIZONTAL JOINTS NOT


ALLOWED.

(3) NOTE:
10/08/2021
D/6 (2" MIN) • PROVIDE CONSTRUCTION JOINTS 60'-0" OC
EQ

(3) MAX.
• JOINTS SHALL BE LOCATED WITHIN MIDDLE
D/3

1/3 OF SPAN OR CENTERED OVER THE


DRILLED PIER SUPPORT. REVISION NAME DATE
PLAN VIEW (3) • LOCATION & DETAIL OF JOINTS SHALL BE 1
1 ADDENDUM #1 2021 1008
(2)
D/3

APPROVED BY ARCHITECT & ENGINEER PRIOR


D

TO CONSTRUCTING FORMS OR PLACING


(1) CONRETE AND SHALL BE SHOWN ON THE SHOP EXTERIOR INTERSECTION
D/3

DRAWINGS.

NOTE: ALL CONSTRUCTION JOINT


LOCATIONS SHALL BE SUBMITTED TO
STRUCTURAL ENGINEER FOR REVIEW
(2)
PRIOR TO PLACEMENT. ISSUE DATE: 2021 0907
INTERIOR INTERSECTION
GRADE BEAM
(2)

CONCRETE DETAILS
(3) (3)

www.TheLefflerGroup.com info@theLefflerGroup.com
165 S. UNION BLVD, STE 360, LAKEWOOD, CO 80228

S3.2
P - 720.890.4095 © 2021
TYPICAL GRADE BEAM VERTICAL CONSTRUCTION
1 SECTION VIEW JOINTS PLAN VIEW - GRADE BEAM INTERSECTION
PIVOT GATE FOUNDATION 3 NO SCALE 2 NO SCALE
6 THIS DETAIL IS TYPICAL TO THE PROJECT AND IS NOT
NO SCALE
THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
NOT NECESSARILY CUT OR CALLED OUT ON PLANS.
THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
NOT NECESSARILY CUT OR CALLED OUT ON PLANS.
NECESSARILY CUT OR CALLED OUT ON PLANS.

C ALLRED&ASSOCIATES 2021
NOTES:
1. HANGER BY CONTR - ATTACH TO BOT (9) (10)
REINF ONLY. (8) T/6 (1 1/2" MIN)
(2) 2. COVER TOP OF TRENCH TO ADEQUATELY NOTES:

EQ EQ EQ
(1) SUPPORT WET CONC. NOTES: 1. ADDITIONAL BOT. BARS PER PLAN.
(3) 3. AIR SPACE. 8. TOP OF SLAB. 2. PROVIDE CLASS 'A' SPLICE FOR BOT. BARS
DIRECTLY OVER SUPPORT. AT LEAST TWO

T
4. PIPE OR CONDUIT TO BE FULLY 9. TOP AND BOT REINF TO RUN THRU JT UNINTERRUPTED. BARS SHALL PASS DIRECTLY OVER
SUPPORTED BY FRANULAR VASE AT TOME 10. CONT WATERSTOP REQ'D AT RECESSED FLOOR SLAB COLUMN IN EACH DIRECTION.
OF INSTALLATION. 3. PILE CAP OR GRADE BEAM.
JT. - TYP 4. CONT BOT BARS.
5. 4" MIN GRANULAR FILL (IE SQUEEGEE, 5. STD HOOK TYP.
NOTE: ALL CONSTRUCTION JT LOCS
ETC). 6. ADDITIONAL TOP BARS PER PLAN.

S
SHALL BE SUBMITTED TO STRUCT 7. CONT TOP BARS.
6. 6" VOID FORMS.
ENGINEER FOR REVIEW PRIOR TO

210106
PLACEMENT. CL SUPPORT CL SUPPORT

INTERIOR DESIGN
580 BURBANK ST. SUITE 125, BROOMFIELD, CO 80020 PHONE: 303.465.4306 FAX: 303.465.4382 www.allredarch.com
T
CL SUPPORT CL SUPPORT GREATER OF 0.221 L GREATER OF 0.221 L
0.22 1L

1" CLR.
GREATER OF 0.331 L GREATER OF 0.331 L OR 0.22 2L OR 0.22 2L
0.33 L1

1" CLR.
CL (6)

A
CL SPLICE

TYP
OR 0.33 2L OR 0.33 2L

I
SPLIC (6)

TYP
(6)
(4) E

| JOB NO.
C
(5) 8" MIN. AS REQ'D 8" MIN. (6)

0"
(1) (7) 6"

0"
12" MAX

0"
(7) 6"

0"
(5)
O
S

1" CLR.
(5)
M.E.P. PIPING TRENCH AT STRUCTURAL SLAB ON

TYP
1" CLR.
(1) 6"

TYP
(1)
(1)

S
VOID (4) (2) 6" (4)
3 6"

|
MIN.
MIN.

A
NO SCALE (3)

PLANNING
L1 /2 L1 /2

&
L1 /2 L1 /2
NORTH-SOUTH REINF. PER PLAN EAST-WEST DIRECTION IS HIGHEST LAYER
L1 L2 L1 L2

L L L L

ALLRED
6'-6" EA. SIDE OF PIER CENTERLINE ALL OTHER LOCATIONS

|
EAST-WEST DIRECTION LOWEST LAYER

ARCHITECTURE
TYPICAL STRUCTURAL SLAB REINF PLACING

PERMIT SET
DIAGRAM
1 NO SCALE

SLAB REINF LAYERING GUIDE


4 NO SCALE
NOTES:
1. 14" THICK APPARATUS BAY SLAB - RE: ARCH FOR SLOPE REQUIREMENTS -TYP.
2. TRENCH DRAIN PER PLUMBING DRAWINGS. SET IN SECOND CONCRETE POUR. COL. STRIP MID. STRIP COL. STRIP
3. 30"x30" GRADE BEAM REINF W/ (5) #6 X CONT T&B AND #4 CLOSED STIRRUPS ("L"/2) ("L"/2) ("L"/2)
NOTES:
AT 12" OC.
4. 6" VOID FORM BENEATH STRUCT SLAB. 1. ALL OPENINGS THROUGH STRUCTURAL SLAB SHALL BE SHOWN ON
5. #5 SLAB DWL FULL DEPTH OF GRADE BMX24" AT 12" OC. A706 IF FIELD REINFORCING SHOP DRAWINGS PRIOR TO SUBMITTING TO STRUCTURAL
BENT. ENGINEER FOR REVIEW. CONTRACTOR COORDINATE.
2. TYP. EACH SIDE OF OPENING - ADD 1/2 NUMBER OF BARS INTERRUPTED

CITY OF THORNTON
6. 14"x14" x CONT VOID. BY OPENING - SPACE BARS AT 3" O.C. - DTL. BARS AS "ADD BARS:
7. 4" VOID BENEATH GRADE BM. "L" - RE: PLAN AND DETAILS."

FIRE STATION #7
(1) (5) (2) (5) 3. 3D OR 12" (WHICHEVER IS GREATER).
(6)
INTERSECTING COLUMN STRIPS:
NOT MORE THAN 1/8 OF THE COLUMN

COL. STRIP
("L"/2)
STRIP WIDTH IN EITHER SPAN
DIRECTION SHALL BE INTERRUPTED
BY OPENINGS. OPENINGS MUST BE (2)
REINFORCED AS SHOWN.

INTERSECTING
MIDDLE STRIPS:
OPENINGS OF ANY

MID. STRIP
SIZE ARE

("L"/2)
(4)

"L"
PERMITTED.
OPENINGS MUST BE
REINFORCED AS
SHOWN.

(3)
INTERSECTING COLUMN STRIP AND MIDDLE
STRIP: SLAB OPENING REINFORCING
NOT MORE THAN 1/4 OF THE
COL. STRIP
("L"/2)

REINFORCEMENT IN EITHER STRIP SHALL


BE INTERRUPTED BY OPENINGS.
OPENINGS MUST BE REINFORCED AS
SHOWN. (3)
TRENCH DRAIN FOUNDATION
5 NO SCALE
NOTE:
NO OPENINGS PERMITTED THROUGH PILE CAP - TYP

D
10/08/2021

NOTES: SLAB OPENING SPACING


1. CONCRETE SLAB ON VOID.
1/2"

(1) (4) 2. 1 1/2" LONG MASTIC CAP


REVISION NAME DATE
(2) INSTALL WITH 1/2" GAP AT
END. 1 ADDENDUM #1 2021 1008
3. POLYTHENE WRAP TO ASSURE TYPICAL STRUCTURAL SLAB OPENING
4.
SLIPPAGE.
3/4" DIAx32" LONG SMOOTH
2 NO SCALE
DOWEL AT 8" OC - DOWELS MUST
BE CAREFULLY ALIGNED AND
SUPPORTED DURING CONCRETING
OPERATIONS. MISALIGNED
DOWELS CAUSE CRACKING.
(3) ISSUE DATE: 2021 0907

FOUNDATION DETAILS
ISOLATION JOINT

www.TheLefflerGroup.com info@theLefflerGroup.com
165 S. UNION BLVD, STE 360, LAKEWOOD, CO 80228

S3.3
ISOLATION JOINT AT FITNESS ROOM

P - 720.890.4095 © 2021
6 NO SCALE

C ALLRED&ASSOCIATES 2021
NOTES:
1. MAS WALL BEYOND. NOTES:
1. RE: 4/S3.4 FOR MAS WALL REINF REQ'S WHERE NOTES:
X 2. GRID = FO GRADE BM = FO VENEER - TYP. X 1. FO CFS WALL.
3. 4" CONT VOID AT GR BM - TYP. OCCURS.
2. STRUCTURAL SLAB PER PLAN. 2. GRID = FO GRADE BM = FO VENEER - TYP.
4. 18" WIDE GRADE BM REINF W/ (3) #8 TOP & BOT AND 8" 3. RE: ARCH FOR BRICK VENEER - TYP.
#4 STIRRUPS AT 12" OC - TYP. 3. 6" CONT VOID AT SLAB - TYP. (1)
(2) 4. GR BM PER: 2/S3.4 4. #5 (A706) DOWEL AT 12" OC FULL HT IN GR BM;
5. 6" CONT VOID AT SLAB - TYP. 14" SLAB 8" SLAB (2) CLASS B HORIZ IN SLAB. BAR TO BE IN TOP MAT OF
6. 1/2" ISOLATION JOINT. 5. 4" CONT VOID AT GR BM - TYP.
6. #5 (A706) DOWEL AT 12" OC - ALT BENDS - FULL HT SLAB - TYP.
7. EXTERIOR SLAB BY OTHERS. 5. 4" CONT VOID AT GRADE BM - TYP.
8. #5 (A706) DOWELS AT 12" OC - FULL HT IN GRADE IN GRADE BM; CLASS B HORIZ IN SLAB. BAR TO BE IN
(1) TOP MAT OF SLAB W/ ALT LEGS - TYP. 6. 14" W GRADE BM REINF W/ (2) #8 T&B AND #4
BM; CLASS B HORIZ IN SLAB. BAR TO BE IN TOP (9) STIRRUPS AT 12" OC - TYP.

S
MAT OF SLAB. RE: 1/S3.3 FOR 7. 6" CONT VOID AT SLAB - TYP.
(6)
CONSTRUCTION JOINT

210106
(3) 8. STRUCTURAL SLAB PER PLAN. HOLD EDGE BACK 5" MAX
(7) (2) INFORMATION. FOR BRICK SUPPORT.

INTERIOR DESIGN
580 BURBANK ST. SUITE 125, BROOMFIELD, CO 80020 PHONE: 303.465.4306 FAX: 303.465.4382 www.allredarch.com
(6)

T
RE: PLAN FOR 9. CFS EXTERIOR WALL FRAMING PER PLAN.
CLASS B LAP (1)
DOWELS.

A
(8)

| JOB NO.
C
O
S
S

|
(4)

PLANNING
(5)
2'-4"

&
(3)

2'-10"
2'-4"
(7)

(8) (4)

ALLRED
(6)

|
(4)

(6)

ARCHITECTURE

PERMIT SET
(3)
(5)
1'-6" WIDE (5)

APPARATUS BAY THRESHOLD


5 TYP INTERIOR SLAB TRANSITION TYP EXTERIOR WALL AT CFS/STL COLUMNS
NO SCALE
3 THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
NO SCALE 1 THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
NO SCALE
NOTES: NOT NECESSARILY CUT OR CALLED OUT ON PLANS. NOT NECESSARILY CUT OR CALLED OUT ON PLANS.
1. CONC BENCH REINF W/ (4) #5xCONT EA FACE W/ SMOOTH TROWEL FINISH AND 1/2"
CHAMFER EDGES. RE: ARCH FOR GEOMETRY AND LOC.
2. PAVERS RE: ARCH. NOTES:
3. 12" THICKx2'-6" WIDExCONT FTG W/ #5 TRANS AT 12" OC BOT & (3) #5xCONT BOT 1. FO MAS WALL.
AS SHOWN. PROVIDE #5 VERT DOWELS AT 12" OC EA FACE AS SHOWN. X 2. GRID = FO GRADE BM = FO VENEER - TYP.
4. DRYPACK NON-SHRINK NON-METALLIC 5 KSI GROUT CONT UNDER MONOLITH PIECES. 3. RE: ARCH FOR BRICK VENEER - TYP.
NOTES: 4. DOWELS PER 1/S3.4
MECHANICAL CONNECTION TO FTG BY MFR.

CITY OF THORNTON
1. MAS WALL PER PLAN. 8 3/8" 5. PROVIDE 2"HIGHXCONT BLOCKOUT IN GRADE BM FOR
5. 14" THICKx3'-0" WIDExCONT FTG W/ (4) #5 T&B AND #5 TRANS AT 12" OC T&B. (2)
2. STRUCTURAL SLAB PER PLAN. BRICK COURSING.

FIRE STATION #7
RE: 6/S3.3 3. 4" CONT VOID AT ADE BM - TYP. (1) 6. 4" CONT VOID AT GRADE BM - TYP.
FOR ISOLATION JOINT AT 4. 14" WIDE GRADE BM REINF W/ (2) #8 T&B AND #4 7. 18" WIDE GRADE BM REINF W/ (3) #8 T&B AND #4
FITNESS SLAB. RE: PLAN FOR STIRRUPS AT 12" OC - TYP. STIRRUPS AT 12" OC - TYP.
LOCS. 5. 6" CONT VOID AT SLAB - TYP. 8. 6" CONT VOID AT SLAB - TYP.
6. #5 (A706) DOWEL AT 12" OC - ALT BENDS - FULL HT 9. STRUCTURAL SLAB PER PLAN. HOLD EDGE BACK 5" MAX
(2)
IN GRADE BM; CLASS B HORIZ IN SLAB. BAR TO BE FOR BRICK SUPPORT.
2'-6" MAX

IN TOP MAT OF SLAB - TYP. (3)


(2) (1)
(9)

(4)

(3)

(5)
(5)
2'-10"

(8)
(4) (6)

2'-4"
PLAZA CONC BENCH
6 THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
NO SCALE
(4)

NOT NECESSARILY CUT OR CALLED OUT ON PLANS.


NOTES:
(7)
1. STEEL COLUMN - FOR
DIRECTION OF WEB, SEE
(6) PLAN. (3)
2. CONCRETE CLOSURE POUR -
SEE TYPICAL DETAIL. (6)
1/4 10/08/2021
3. FINISHED GRADE OR CONCRETE
1/4 (1) SLAB WHERE OCCURS. TYP INTERIOR GR BM AT 8" SLAB
4. 3" MINIMUM CONCRETE COVER
AROUND ALL STEEL BELOW
4 THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
NO SCALE TYP EXTERIOR WALL AT CMU
BOTH
FLANGES
1/4
1/4 5.
GRADE.
DRILLED PIER.
NOT NECESSARILY CUT OR CALLED OUT ON PLANS. 2 THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
NO SCALE REVISION NAME DATE

1 ADDENDUM #1 2021 1008


(2) 6. CENTERLINE OF COLUMN AND NOT NECESSARILY CUT OR CALLED OUT ON PLANS.
(8) (7) DRILLED PIER.
(3)
7. STEEL BASE PLATE WITH
DOUBLE NUTS OVER 1 1/2"±
DRYPACK.
8. CONCRETE SLAB ON GRADE.
(4)

ISSUE DATE: 2021 0907

FOUNDATION DETAILS
(5)

www.TheLefflerGroup.com info@theLefflerGroup.com
165 S. UNION BLVD, STE 360, LAKEWOOD, CO 80228

S3.4
P - 720.890.4095 © 2021
EXTERIOR STEEL COLUMN AT DRILLED PIER
7 NO SCALE

C ALLRED&ASSOCIATES 2021
NOTE: MASON TO
ACCOUNT FOR SLOPED
BEARING REQUIREMENTS
WHEN DETERMINING NOTES:
(7) ELEVATIONS AND SIZES (4) 1. VERTICAL WALL REINF. - UNLESS NOTED OTHERWISE IN
(6) (12)
OF BRG SEATS - TYP. THE STRUCTURAL DRAWINGS, PROVIDE (1) #5 IN
CENTER OF GROUT AT CENTER OF WALL, CONTINUOUS
(2) FULL HEIGHT OF WALL AT ALL CORNERS,

S
NOTES: INTERSECTIONS, WALL ENDS, BEAM BEARINGS, JAMBS,
24" TYP.
1. 24" DEEP BOND BEAM w/ 24" TYP. EACH SIDE OF CONTROL JOINTS AND AT INTERVALS NOT

E
ROOF STRUCTURE

210106
(8) #5 REBAR. TO EXCEED 32" O.C. NON-STRUCTURAL PARTITION

INTERIOR DESIGN
580 BURBANK ST. SUITE 125, BROOMFIELD, CO 80020 PHONE: 303.465.4306 FAX: 303.465.4382 www.allredarch.com
2. PL 1/2"x10"x0'-10".

T
WALLS SHALL BE REINFORCED WITH #4 VERT AT 48"
3. PL 1/2"x4"x0'-4" w/ (8) OC.

A
ROUND OR MITER EDGES 2. TIE VERTICAL REINFORCING AT 8'-0" O.C.

I
PER ARCH. (11) VERTICALLY, WITH SINGLE WIRE LOOP TIE BY A.A.
4. 1" DIA HOLE. WIRE PRODUCTS COMPANY.

| JOB NO.
C
1 1/2" (8) 3. HORIZONTAL WALL REINF. - UNLESS NOTED OTHERWISE

24" MIN.
TYP.
(3) NOTE: RE: ARCH FOR IN THE STRUCTURAL DRAWINGS, PROVIDE (2) #5 IN

O
LOCS. ABOVE AND/OR (3) MINIMUM 8" DEEP GROUTED CONTINUOUS BOND BEAM AT
BELOW TRAINING (1)(2) ELEVATED FLOORS AND ROOF LINE AND AT 4'-0" O.C.

S
(4) WINDOWS. 4. PROVIDE (1) #5 IN 8" DEEP BOND BEAM AT TOP OF
(10)

1 1/2"
(1) PARAPET OR FREESTANDING WALL.

S
(5) 5. STANDARD WEIGHT (NO. 9 GAGE WIRE) DUR-O-WAL OR

|
1/4 (2) DUR-O-WIRE (OR EQUIVALENT) LADDER TYPE JOINT

A
(2) REINFORCEMENT AT 16" O.C. IN RUNNING BOND

PLANNING
MASONRY WALLS ABOVE GRADE; 8" O.C. IN STACKED

&
(3) BOND MASONRY WALLS ABOVE GRADE; 8" O.C. BELOW
GRADE.
FOUNDATION 6. CONTROL JOINT.
7. INTERSECTING MASONRY WALL BEYOND.
8. LINTEL - RE: LINTEL SCHEDULE.

ALLRED
9. DOWEL ALL VERTICAL REINFORCING TO FOUNDATION
TRAINING WINDOW WALL SUPPORTS WITH DOWELS TO MATCH VERTICAL REINFORCING SIZE

|
5 THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
NO SCALE
(9) INDICATES GROUTED
CELLS - RE: G.S.N. AND
AND LOCATION.
10. SLAB ON GRADE.

ARCHITECTURE
NOT NECESSARILY CUT OR CALLED OUT ON PLANS. DETAILS FOR SPECIFIC 11. BEAM POCKET - RE: PLAN FOR LOCATIONS.

PERMIT SET
LOCATIONS. 12. EMBED PLATE - RE: PLAN FOR LOCATIONS.
TYPICAL MASONRY WALL CONSTRUCTION
1 THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
NO SCALE
NOT NECESSARILY CUT OR CALLED OUT ON PLANS.
NOTES:
1. MAS. WALL - HOLD BOND BM.
DOWN ONE COURSE FROM TOP.
2. STL. BM.
(2) 3. L4x4x1/4x1'-0" AT 4'-0" O.C.
(3) (1)
(4) (1) NOTES:
1. MASONRY WALL.
2. CONTROL JOINT.
1 1/2"
CLR.

1/4 2 3. CONTROL JOINT MATERIAL PER

CITY OF THORNTON
ARCHITECTURAL DRAWINGS
NOTES: AND SPECIFICATIONS.

FIRE STATION #7
4. 1 VERTICAL BAR EACH SIDE
1. MASONRY WALL. IN SOLID GROUTED CELLS TO
2. BOND BEAM REINFORCING. (3) MATCH VERTICAL WALL
(3) (2) 3. CORNER BARS SAME SIZE REINFORCING.
AND SPACING AS PLAN 5. BOND BEAM BARS. DO NOT
X
HORIZONTAL RUN CONTINUOUS THRU C.J.
REINFORCING - LAP PER
(3) (2)
INTERSECTION (2) G.S.N. (24" MINIMUM).

(1) NOTE: CONTROL JOINT


SPACING NOT TO EXCEED
24'-0" 0.C. - TYP.

NOTE: DO NOT LOCATE


CONTROL JOINTS AT LINTEL
LOCATIONS OR OPENING
MASONRY WALL BRACING AT STEEL BEAM (1)
EDGES. - TYP.
6 THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
NO SCALE (5)
(2)
NOT NECESSARILY CUT OR CALLED OUT ON PLANS. X

CORNER

1'-6" 1'-6"

NOTES: MASONRY BOND BEAM AT INTERSECTING WALLS


1. ANCHOR INSTALLATION NOT ALLOWED IN 3 THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
NO SCALE
SHADED AREAS.
2. CONCRETE MASONRY UNIT (GROUTED). NOT NECESSARILY CUT OR CALLED OUT ON PLANS.
3. MORTAR JOINT. CONTROL JOINT IN MASONRY WALL
2 THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
NO SCALE
NOT NECESSARILY CUT OR CALLED OUT ON PLANS.
(1)
NOTES: 10/08/2021
1. METAL DECK.
(1) 2. BENT PL. 1/4x3x5x1'-0" AT 6'-0" O.C.
1 3/8"

MAX. - INSTALL W/ 2- 1/4" DIA. BOLTS


3. MASONRY WALL. REVISION NAME DATE

1 ADDENDUM #1 2021 1008


1"
1 3/8"

(2)

(3)
(3)
ISSUE DATE: 2021 0907
1 3/8" 1 3/8"
(2)

MASONRY DETAILS
www.TheLefflerGroup.com info@theLefflerGroup.com
165 S. UNION BLVD, STE 360, LAKEWOOD, CO 80228

S4.1
INSTALLATION OF EXPANSION ANCHORS IN

P - 720.890.4095 © 2021
MASONRY WALLS BRACING AT NON STRUCTURAL MASONRY WALL
7 THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
NO SCALE 4 THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
NO SCALE
NOT NECESSARILY CUT OR CALLED OUT ON PLANS. NOT NECESSARILY CUT OR CALLED OUT ON PLANS.

C ALLRED&ASSOCIATES 2021
NOTES:
1. STRINGER.
NOTES:
2. PL PER NOTE 4 ON 4/S4.2 . NOTES:
4/S4.2 1. GUARDRAIL VERT SPACING PER ARCH.
3. WELDED #5 DOWELS EA STRINGER PER NOTE 9 ON . 1. MASONRY WALL.
2. PIPE 1 1/2" STD (INSIDE DIA = 1.61") TO FIT REMOVABLE RAILING. PROVIDE CAP
4. MAS WALL. 2. GROUT CONTINUOUS FROM BOND BEAM TO 4" ABOVE ROOF
PL1/4 W/ WEEP HOLE - TYP.
(3) 3. L4X4X1/4X1'-0" LONG. LINE.
4. PL1/4X6XCONT. 3. CONTINUOUS GROUTED BOND BEAM PER GSN.
5. CONT BOND BEAM. 4. L3x3x1/4xCONT.
6. 3" MIN BEARING. 5. STEEL DECK OR BAR GRATING - FOR DIRECTION, SEE PLAN.
(2)
(1) 7. PL1/2X6X0'-10" w/ 1" ± DRYPACK. 6. (2) 3/4" DIAx5" LONG ANCHORS AT 6" OC - GROUT
8. MEZZANINE FLOOR PER PLAN. MINIMUM 4" ABOVE AND BELOW ANCHORS. SPACE PLATES AT

S
9. (1) #5X2'-0" WELDED TO ANGLE EACH SIDE OF SLEEVE (2 TOTAL REBAR AT EACH 4'-0" OC.
SLEEVE).

210106
3/16 3
10. (1) #4XCONT. (1) (1)

INTERIOR DESIGN
580 BURBANK ST. SUITE 125, BROOMFIELD, CO 80020 PHONE: 303.465.4306 FAX: 303.465.4382 www.allredarch.com
11. 2 1/2" DEEP JOIST SEAT. 3/16 3

T
3/16 3
12. #4 DOWEL x 2 2 AT 6'-4" OC MAX. LOCATE DOWELS AT VERT WALL REINF LOCS.
(2) 3/16 3
(4) (3)
(3)
A
I

| JOB NO.
1/4

C
(1) TYP
1/4

O
(2) 1/4 2 (3)
TYP

S
1/4 2 (5) (5)
(4) (10) (8)
X

S
(3) (6)

|
(6)

PLANNING
(4)

TYPICAL STRINGER AT HEADER


NOTE: AT STEEL BM, PROVIDE PL1/4
RETURN LEG TO BEAM WEB FOR VISUAL
(11)
(7)
(9)
(12) &
6 CLOSURE. DO NOT WELD TO BM.

ALLRED
NO SCALE
NOTES: (6) DECK SPAN PARALLEL TO WALL DECK SPAN PERP. TO WALL

|
1. HSS GIRT PER PLAN.
2. JAMB PLATE AND EMBEDS PER (5)
PLAN KEYED NOTES.

ARCHITECTURE
BETWEEN JOISTS AND AWAY
3. EMBED PL PER 4/S4.3 . CHORD ANGLE AND STEEL DECK AT MASONRY WALL

PERMIT SET
FROM RAILS
NOTE: EXTERIOR FACE OF STEEL
3/16 2-12
1 NO SCALE
TO ALIGN WTIH EXTERIOR FACE OF
MASONRY WALL.

NOTES:
EQ EQ
(2) (1) (3) (1) 1. MASONRY WALL.
2. BOND BEAM PER GSN.
(1) 3. STEEL BEAM.
4. (2) #5X3'-6" LONG IN 8"
(2) DEEPX4'-0" LONG GROUTED
BOND BEAM.
TYP 5. NOT USED.
(10) 6. (2) 3/4" DIA. AUTOMATIC
1/8
WELDED THREADED STUDS
1/4 ON BEAM GAGE (TIGHTEN

CITY OF THORNTON
NUTS FINGERTIGHT).
7. 1 1/2" LONG HORIZONTALLY

FIRE STATION #7
(3)
3/16 3/16 (6) SLOTTED HOLE ON BEAM
1" GAGE - EACH SIDE OF WEB.
(7) CLR. 8. PL3/4X5 1/2X1'-2"
WITH (2) 3/4" DIA ANCHORS
AT APPARATUS BAY OVERHEAD DOORS AT NON-OVERHEAD DOORS AT APPARATUS BAY OPENINGS OVER 1" ±DRYPACK.
9. ADD (4) #5 (1 IN EA. CELL)
CTR'D UNDER BM. IN GROUTED
(4) CELLS.
X 10. GROUT POCKET AFTER ALL
(8)
DEAD LOADS ARE APPLIED -
HSS GIRT TO MASONRY WALL TYP.
7 MEZZANINE EDGE AT GUARDRAIL
NO SCALE
4 NO SCALE
(9)

(8)
NOTES:
NOTES: 1. MAS WALL.
(1) 1. 2-WYTHE TAPERED BRICK SIGN WITH 2. CONT GROUTED BOND BM PER GSN.
SOLID-GROUTED COLLAR JOINT. 3. CONT LEDGER ANGLE.
2. #5 AT 16" VERT - TYP. 4. CONC OVER STEEL DECK. STEEL BEAM AT MASONRY WALL
3.
4.
#4xCONT HORIZ AT 16" OC.
#5 DOWELS AT 16" OC - ALT
5. STEEL DECK - FOR DIRECTION
SEE PLANS.
2 NO SCALE
BENDS - TYP. 6. EMBED PL3/8x4x0'-9" W/ (2)
5. 12" CONC WALL - TYP. 1/2" DIA ANCHORS AT 6" OC -
(7)
6. #5 AT 14" OC TRANSVERSE AND (3) GROUT 4" MIN ABOVE AND BELOW
#5xCONT LONGITUDINAL T&B. ANCHORS.
(4)
7. DUR-O-WALL JOINT REINFORCEMENT 7. (1) #4xCONT.
5'-0" MAX

REQUIRED PER 1/S4.1


8. (1) #5XCONT IN 8" DEEP GROUTED NOTES:
(2) BOND BEAM.
3/16 3 3/16 3 (1) 1. STEEL DECK - FOR DIRECTION
4" MIN 9. (1) COURSE MIN BELOW GRADE - RE: (1)
OF DECK, SEE PLAN.
ARCH. (3) (3) 2. PL3/8x4xCONT.
3/16 3 (1) 3. EMBED PL1/2x6x0'-6"
(9) AT 48" OC WITH (2) 3/4"
(4) (4) 3/16 3 DIA ANCHORS.
(2) 4. CONTINUOUS GROUTED BOND 10/08/2021
BEAM PER GSN.
5. MASONRY WALL.
(2) (2) 6. 1" ± DRYPACK.
(5) (5) 7. RE: ARCH FOR SHORT
(5) (7) (7)
CANTILEVERS AT ROOF EDGE - TYP REVISION NAME DATE

(6) (3) (7) 1 ADDENDUM #1 2021 1008


3'-0" MIN.

(6) (6) (6)


(3)
(4)

(5)
1'-0"

ISSUE DATE: 2021 0907

DECK SPAN PARALLEL TO WALL DECK SPAN PERPENDICULAR TO


3'-0" WALL

MASONRY DETAILS
www.TheLefflerGroup.com info@theLefflerGroup.com
165 S. UNION BLVD, STE 360, LAKEWOOD, CO 80228

S4.2
MONUMENT SIGN
8

P - 720.890.4095 © 2021
NO SCALE
LEDGER ANGLE AND STEEL DECK AT MASONRY
THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
NOT NECESSARILY CUT OR CALLED OUT ON PLANS. WALL STEEL DECK AT MASONRY WALL
5 NO SCALE 3 NO SCALE

C ALLRED&ASSOCIATES 2021
NOTES:
NOTES:
1. BEAM PER PLAN.
1. 2-WYTHE TAPERED BRICK SITE WALL
(2) 2. REINF. PER WALL SCHED.
WITH SOLID-GROUTED COLLAR JOINT.
(1) 3. BOND BEAM PER TYP DETAILS.
2. #6 AT 16" VERT - TYP.
4. (4) #5 (1 IN EACH CELL) CTR'D UNDER BEAM IN
3. (1) COURSE MIN BELOW GRADE - RE:
GROUTED CELLS.
ARCH.
(3) 5. (2) 3/4" DIA ANCHORS.
4. #6 DOWELS AT 16" OC - TYP.
6. PL 3/4"x8"x0'-8" w/ (2) 3/4" DIA THREADE
5. DUR-O-WALL JOINT REINFORCEMENT (1)
NOTES: AUTOMATIC WELDED STUDS ON BEAM GAGE (TIGHTEN
REQUIRED PER 1/S4.1

(1)
(5) 1. OVERSIZE HOLE IN MASONRY NUTS FINGER TIGHT) OVER 1" ± DRYPACK.
6. 4" CONT VOID AT GR BM - TYP. (8)
FACE SHELL TO OBTAIN 1" (MIN) 7. 1-1/2" LONG SLOTTED HOLES.

210106
7. 14" W GR BM REINF W/(2) #8 T&B GROUT ALL AROUND HEADED 8. GROUT POCKET AFTER ALL DEAD LOADS ARE
AND #4 STIRRUPS AT 12" OC - TYP.

INTERIOR DESIGN
(7) (4) STUDS - TYPICAL.

580 BURBANK ST. SUITE 125, BROOMFIELD, CO 80020 PHONE: 303.465.4306 FAX: 303.465.4382 www.allredarch.com
10'-6" MAX
APPLIED - TYP.

T
(2) 2. STEEL EMBED PLATE.
3. MASONRY WALL. (7)

A
4. BOND BEAM REINFORCING.

I
(2)

| JOB NO.
C
(4) (3)
(6)

O
(3)
4" MIN

S
(5) (4)

|
(6)

PLANNING
STEEL BEAM THRU MASONRY WALL
4
TYPICAL EMBED PLATE AT MASONRY WALL
THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
NO SCALE
1 NO SCALE
&
(3) NOT NECESSARILY CUT OR CALLED OUT ON PLANS.

ALLRED
(4)

|
NOTES:
3'-8"

1. WHEN SPAN EXCEEDS 6'-0", SHORE LINTEL AT MIDSPAN.

ARCHITECTURE
2. WELD DOWERLS TO LINTELS TO MATCH AND LAP VERT REINF PER GSN. MASONRY CONTINUES TO

PERMIT SET
3. GROUT ALL CELLS SOLID TO 1'-4" MIN ABV LINTELS. DECK BEARING NOTES:
4. VENEER TIES AT 16" OC EA SIDE OF BM. ELEVATION. - TYP. 1. MASONRY WALL PER PLAN.
5. EXTEND BOT PL TO END OF BM. 2. BEAM PER PLAN.
6. MIN BEARING EA END PER SCHED. 6" MIN EA END. 3. PERIMETER JOIST PER PLAN.
7. INSTALL ON FRESH MORTAR BED. 2" MIN
(2) (3) 4. VERTICAL REINFORCEMENT PER
(7) 8. MAS VENEER. SCHED AND PLAN.
9. MAS WALL. 5. (2) ADD'L #5 IN CELL UNDER BEAM
10. STEEL LINTEL PER SCHED. BRG
11. PL1/4xCONT. WIDTH TO BE 1/2" LESS THAN TOTAL WALL THICKNESS. 6. (2) #3 x IN 8" DEEP x
1" CLR
CONT. BOND BEAM BELOW BEAM BRG.
7. PL. 3/4"x8"x0'-8" w/ (2) 3/4"
(6) DIA x 6" LONG ANCHORS OVER 1" ±
DRYPACK.
3/16 (8) (8) 8. GROUT POCKET AFTER ALL DEAD
COLLAR JOINT MASONRY SITE WALL & TRASH (9)
(7)
(1) LOADS ARE APPLIED - TYP.

CITY OF THORNTON
ENCLOSURE
7 (10)

FIRE STATION #7
NO SCALE 3/16 3-12
3/16 3-12 (6)
3/16 5 WELD EA END
3/16 5 - TYP
NOTES:
1. (1) #4XCONT IN 8" DEEP GROUTED BOND BM.
2. 8" CMU WALL W/ #6 VERTS AT 16" OC. (11)
3. FINISHED GRADE OR EXT SLAB AS OCCURS. (4) (5) (4)
(1) 4. #6 DOWELSx6'-0" AT 16" OC TO LAP VET WALL
REINF PER GSN.
(5) 5. STEPPED MAS VENEER. STEEL LINTEL IN MASONRY AND VENEER WALL BEAM BEARING
6. FO GRADE BM - FO VENEER - TYP. 5 THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
NO SCALE 2 NO SCALE
7. #5 (A706) DOWELS AT 12" OC - FULL HT IN GRADE
BM; CLASS B HORIZ IN SLAB. BAR TO BE IN TOP NOT NECESSARILY CUT OR CALLED OUT ON PLANS.
MAT OF SLAB - TYP.
(2) 8. 4" CONT VOID AT GRADE BM - TYP.
10'-6" MAX

9. 14" WIDE GRADE BEAM REINF W/ (2) #8 T&B AND #


4 STIRRUPS AT 12" OC - TYP. NOTES:
10. 6" CONT VOID FORM AT SLAB - TYP.
1. MASONRY WALL.
(4) 11. STRUCTURAL SLAB PER PLAN. HOLD EDGE BACK 5" 2. SOLID GROUTED BOND BEAM.
MAX FOR BRICK SUPPORT. 3. BOND BEAM REINFORCING.
TYP 4. LAP REINFORCING PER G.S.N.
3/16 (24" MINIMUM).
(1)
(3) NOTES:
(4) (2)
(1) TYP 1. CONNECTION PER TYPICAL
3/16 STEEL BEAM TO BEAM DETAIL. (3)
(11) 2. STEEL BEAM OR JOIST SUPPORT.
(3) 3. 1/4" STEEL EDGE PLATE
NOTE: AT SIM NO STRUCTURAL SLAB. AROUND OPENING - TYPICAL.
GRADE BM CENTERED ON SITE WALL. 4. 12'-6" MAXIMUM.
5. C8 X 11.5 STEEL BEAM.
6. 6'-0" MAXIMUM.
PLAN
X
10/08/2021
(6) (1)
(5)
(7)
REVISION NAME DATE

1 ADDENDUM #1 2021 1008


2'-10"

(10)

(6)
OPEN
(5)

(5)

(9)

(5) ISSUE DATE: 2021 0907


NOTE:
(2) (2) FOR CLARITY, STEEL DECK
X
AND CONCRETE NOT SHOWN. STEPPED MASONRY WALL BOND BEAM
3

MASONRY DETAILS
(4) NO SCALE
(8)

www.TheLefflerGroup.com info@theLefflerGroup.com
165 S. UNION BLVD, STE 360, LAKEWOOD, CO 80228
THIS DETAIL IS TYPICAL TO THE PROJECT AND IS

S4.3
NOT NECESSARILY CUT OR CALLED OUT ON PLANS.

P - 720.890.4095 © 2021
CMU SITE WALL & TRASH ENCLOSURE PLAN VIEW - TYPICAL FRAME OPENING AT LARGE
8 NO SCALE OPENING
6 NO SCALE

C ALLRED&ASSOCIATES 2021
MIN SEAT DEPTH NOTES:

X (in) d (in) 1. 1/2" CAP PLATE.


2. STEEL COLUMN. 3/16
3. FOR SIZE, TYPE AND NUMBER TYP NOTES:
3/8 TO 1/2 3 1/2 3/16

SEAT END
OF BOLTS, SEE TYPICAL BOLT NOTES:
SCHEDULE. 1. STEEL BEAM.
1 TO 2 4 4. STEEL BEAM. 1. SEE PLAN FOR SPACING 1/4 1 1/2" 3" 2. 3/8" STEEL SHEAR PLATE

SEAT END
5. WT5X15 LENGTH PER SCHEDULE. (8'-0" MAXIMUM). (5) MIN. TYP (1) -USE 5/8" STEEL SHEAR
(3) 2. CENTERLINE OF FRAMING PLATE WHERE "D" = 27"
1/4
(2) MEMBER. OR GREATER.
SLOPE12"
(1) 3. L4x4x1/4 TYP- CUT LEGS AS SHOWN. 3. FOR SIZE, TYPE & NUMBER

"d"
"x" (4) (3)
4. FACE OF FRAMING MEMBER. OF BOLTS, SEE TYPICAL
d
(2) BOLT SCHEDULE.

S
(2)

3" TYP
4. "D" = LESSER OF BEAM

1 1/2"
"D"
4" STD

(4)
DEPTHS AS OCCURS.

MIN.

210106
4" STD 5. WELD 3 SIDES TYPICAL -
INSIDE EDGE OF

INTERIOR DESIGN
USE SAME CONNECTION AT

580 BURBANK ST. SUITE 125, BROOMFIELD, CO 80020 PHONE: 303.465.4306 FAX: 303.465.4382 www.allredarch.com
T
BRG. SEA AND (5) STIFFENER PLATES WHEN
SUPPORT STRUCTURE. REQUIRED.

A
I

(1)
3/16 OPENING (3)
(1)

| JOB NO.
JOIST w/OUT EXTENSIONS TYP

C
3/16

O
1/4
3/16 NOTE:

S
END OF SEAT END OF SEAT TYP AT ONE SIDED CONNECTIONS,

"D"

"D"
3/16 INSTALL 3/8" STIFFENER PLATE

S
OPPOSITE SHEAR PLATE.

SEE TBL
SLOPE12"

|
1/4"±
(4)

"d"
"x" NOTE: FOR CLARITY,

A
ROOF DECK OMITTED.

PLANNING
d

4" STD 4" STD

7
STEEL BEAM TO STEEL COLUMN CONNECTION
4'-0" TYPICAL CONNECTION WIDE FLANGE BEAM TO
&
NO SCALE MAX.
THIS DETAIL IS TYPICAL TO THE PROJECT AND IS

ALLRED
JOIST w/ EXTENSIONS NOT NECESSARILY CUT OR CALLED OUT ON PLANS. BEAM
1

|
PLAN - TYPICAL OPENING IN ROOF FRAMING THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
NO SCALE
TYPICAL SLOPED K SERIES JOIST SEAT 4 NO SCALE NOT NECESSARILY CUT OR CALLED OUT ON PLANS.

ARCHITECTURE
THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
REQUIREMENTS

PERMIT SET
10 NO SCALE NOTES:
NOT NECESSARILY CUT OR CALLED OUT ON PLANS.

1. 1/4" CAP PLATE.


2. STEEL COLUMN.
3. FOR SIZE, TYPE AND NUMBER
OF BOLTS, SEE TYPICAL BOLT 1. STEEL BEAM.
SCHEDULE. 2. (4) 3/4" DIA. BOLTS ON BEAM GAGE.
NOTES:
(3) 4. STEEL BEAM. 3. 1/2" CAP PLATE.
5. 3/8" SHEAR PLATE EACH SIDE. 1. L4x4x1/4xCONT STEEL
4. STEEL COLUMN.
(1) LEDGER ANGLE - TYP UNO.
(4) 5. 3/8 STEEL STIFFENER PLATE BOTH SIDES.
2. PL1/2x2x0'-10".
6. WELD 3 SIDES - TYP.
(1) (1)
(6)
3/16
(3)
NOTES:
1. STEEL BEAM. (5) 3/16 4 (2)

CITY OF THORNTON
2. STEEL JOIST.
3. 1/8" X 1" AT K JOISTS 3/16 4
(2) 1"

FIRE STATION #7
MIN. (5)
3/16 4
3/16 3/16 4
TYP
3/16 1" MAX
(2)
(3)
NOTE: USE THRU PLATE FOR
3/16
HSS THICKNESS ≤ 1/4".
1/4 (2) (1)
3/16

(4)
(1)

SECTION CONTINUOUS CHORD ANGLE/LEDGER ANGLE SPLICE


NOTE:
STEEL DECK NOT SHOWN
X STEEL BEAMS TO STEEL COLUMN CONNECTION 2 NO SCALE
FOR CLARITY. 5 NO SCALE
THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
NOT NECESSARILY CUT OR CALLED OUT ON PLANS.
STEEL BEAMS TO STEEL COLUMN CONNECTION
8 THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
NO SCALE
STEEL JOIST AT STEEL BEAM SLOPED NOT NECESSARILY CUT OR CALLED OUT ON PLANS.
11 NO SCALE NOTES: NOTES:
1. STEEL BEAM.
NOTES: 2. (4) 3/4" DIA BOLTS ON 1. STEEL DECK.
CJP 2. L2x2x3/16 BELOW DECK -
BEAM GAGE.
1. STEEL BEAM. 3. 3/8" STIFFENER PLATE ANGLE MAY BE PLACE ON
2. FOR SIZE, TYPE AND NUMBER BOTH SIDES. OMIT AT TROLLEY BEAMS. TOP OF DECK WITH PRIOR
X (1) OF BOLTS, SEE TYPICAL BOLT 4. WELD (3) SIDES - TYP. APPROVAL OF ARCHITECT.
SCHEDULE. 3. WELD 2" AT EACH RIB -
3. 3/8" STEEL SHEAR PLATE - TYPICAL.
5/8" STEEL SHEAR PLATE OPEN (1)
WHERE "D" = 27" OR (1)
GREATER. 10/08/2021
(2) 4. BACKER PLATE.
"D"

(3)
(2)
X
REVISION NAME DATE
3/16 (1) WEB RIB
(4) 1 ADDENDUM #1 2021 1008
(4) 3/16 (2)
1/4
TYP RIB
1/4 (3) (2)

X
SECTION (3) TYPICAL DECK SECTION
1/8
NOTE:
AN OPENING WHICH CUTS ONE WEB (4" MAX DIMENSION PERPENDICULAR TO RIBS), MAY BE
ISSUE DATE: 2021 0907
(3) CUT IN DECK WITHOUT ANY SPECIAL REINFORCING.

STEEL BEAM TO STEEL BEAM CONNECTION AN OPENING WHICH CUTS TWO WEBS (8" MAX DIMENSION PERPENDICULAR TO RIBS), WILL
6 THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
NO SCALE
REQUIRE ANGLE SUPPORT SHOWN ABOVE.

www.TheLefflerGroup.com info@theLefflerGroup.com
ANY OPENING WHICH CUTS MORE THAN TWO WEBS, FRAME OPENING WITH TYPICAL ANGLE

165 S. UNION BLVD, STE 360, LAKEWOOD, CO 80228

S5.1
NOT NECESSARILY CUT OR CALLED OUT ON PLANS. SUPPORT FRAME, SEE TYPICAL OPENING IN STEEL DECK DETAIL.

STEEL DETAILS
P - 720.890.4095 © 2021
SECTION
X

TYPICAL MOMENT CONNECTION - WIDE FLANGE TYPICAL SMALL OPENING IN STEEL DECK
BEAM TO BEAM
3 THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
NO SCALE
9 NO SCALE NOT NECESSARILY CUT OR CALLED OUT ON PLANS.

C ALLRED&ASSOCIATES 2021
NOTES:
NOTES: 1. ADDITIONAL MEMBER WHEN
1. HSS GIRT PER PLAN. LOAD IS MORE THAN 4"
3 SIDES
2. HSS RAFTER PER PLAN. 3/16 FROM PANEL POINT.
3. CFS WALL FRAMING PER SCHED. 2. STEEL JOIST.
3. L2 1/2x2 1/2x1/4 FROM TOP
4. L8X6X1/4XCONT (LLH) BRICK SUPPORT. CHORD TO NEAREST BOTTOM
5. 600S162-54 STUDS AT 16" OC W/ 600T125-54 T&B AT BRICK CANOPY LEDGER. NOTES: (1)
CHORD PANEL POINT.
6. L3x3x1/4 CHORD ANGLE. 1. CONTINUOUS BOND BEAM 4. 1/2" DIA. ROD FROM BOTTOM
PER G.S.N. CHORD TO NEAREST TOP
(7) 2. (2) 3/4" DIA AUTOMATIC CHORD PANEL POINT - FOR
WELDED THREADED STUDS CONCENTRATED LOAD AT

S
IN 13/16" X 1 1/2" LONG BOTTOM CHORD.
(6) SLOTTED HOLES.

210106
T&B EA 1/8 (1) 3. STEEL PLATE 3/4" X 5" X
14" WITH (2) 3/4" DIA

INTERIOR DESIGN
580 BURBANK ST. SUITE 125, BROOMFIELD, CO 80020 PHONE: 303.465.4306 FAX: 303.465.4382 www.allredarch.com
STUD

T
1/8 (2) ANCHORS AT 8" OC OVER
(4) 1" ± DRYPACK.
(3)

A
4. (2) #5 X 5'-6" LONG IN 6'-0"

I
3/16 2-24 LONG X 8" DEEP BOND BEAM.
(5) 5. MASONRY WALL.

| JOB NO.
(4) 6. STEEL JOIST.

C
(6) (1)
7. CHORD ANGLE. (4) (2)

O
(5) 8. GROUT POCKET AFTER (3)
ALL DEAD LOADS ARE

S
APPLIED - TYP.
(8)
(1)

S
NOTE:

|
PROVIDE THIS DETAIL WHEN

A
(2) CONCENTRATED LOAD
1/4 4

PLANNING
TYP 9 (3) EXCEEDS 100 LBS. -

&
1/4 4 S5.5 NOTIFY ENGINEER WHEN LOAD
TYP EXCEEDS 200 LBS.
(3)

ADDITIONAL WEB MEMBERS FOR CONCENTRATED

ALLRED
BRICK SUPPORT AT CANOPY STEEL JOIST AT MASONRY WALL LOAD OCCURING AWAY FROM JOIST PANEL POINT
9 4 1

|
NO SCALE NO SCALE NO SCALE
THIS DETAIL IS TYPICAL TO THE PROJECT AND IS

ARCHITECTURE
NOT NECESSARILY CUT OR CALLED OUT ON PLANS.

PERMIT SET
NOTES:
1. WP OF KICKER.
2. L4x4x1/4 BETWEEN JOISTS. NOTES:
3. PL 3/8. 1. STEEL JOIST.
(1) 3" MAX (2) (3)
4. PL 3/8x5x5. 2. BRIDGING AS REQUIRED BY
3/16 2
2 SIDES JOIST MANUFACTURER.
3/16 2 3. WALL - FOR SIZE AND TYPE,
(2) SEE PLAN.
4. L3x3x1/4x0'-4" WITH (1) 5/8"
3/16 DIA EXPANSION BOLT (IN
(1) TYP GROUTED CELL AT MASONRY

CITY OF THORNTON
3/16 WALL).
3/16 5. L3x3x1/4 AS REQUIRED WITH (2)

FIRE STATION #7
5/8" DIA EXPANSION BOLTS (IN
3/16 GROUTED CELL AT MASONRY
(3) (4) (4) WALL).

HORIZONTAL BRIDGING AT K SERIES JOIST


3/16 2
3/16 2
3/16 2
TYPICAL STEEL JOIST BRIDGING TO WALL
3/16 2
2 THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
NO SCALE

PARALLEL TO JOIST PERPENDICULAR TO JOIST NOT NECESSARILY CUT OR CALLED OUT ON PLANS.

TYP ANGLE BRACE TO JOIST


5 NO SCALE

NOTES:
1. STEEL BM - RE: PLANS.
2. PL3/8x6x0'-6".
3. L3x3x1/4 BRACE AT 5'-0" OC - TYP. 3/16
4. PARAPET POST PER 8/S5.6 - TYP NOTES:
5. STUD WALL AND DEFLECTION TRACK PER
SCHEDULE AND TYPICAL DETAILS 1. STEEL BEAM.
(3) 2. STEEL JOIST.
1/4 6. L4X4X1/4XCONT CHORD ANGLE. 3. 1/8" X 1" AT K JOISTS
(2) 1"
(4) 4. L4X4X1/4 X CONT. CHORD ANGLE.
TYP MIN.
(6) LOCATE INBOARD FROM PARAPET
3/16
POSTS PER 9/S5.2 - TYP
(2) (4) 10/08/2021

5
S5.2
REVISION NAME DATE

1 ADDENDUM #1 2021 1008


(1)

(1)
(3)
(5)
NOTE:
STEEL DECK NOT SHOWN
3/16 2 FOR CLARITY. ISSUE DATE: 2021 0907
3/16 2

STEEL JOIST AT STEEL BEAM

www.TheLefflerGroup.com info@theLefflerGroup.com
3

165 S. UNION BLVD, STE 360, LAKEWOOD, CO 80228

S5.2
STEEL DETAILS
NO SCALE

P - 720.890.4095 © 2021
TYPICAL BRACE AT STEEL BEAM
6 NO SCALE

C ALLRED&ASSOCIATES 2021
NOTES:
1. STEEL STAIR BEAM.
2. FOR TREADS AND RISERS, SEE
NOTES: ARCH'L DRAWINGS.
1. WELD EA PL. 3. 3/16" CLOSURE PLATE - BUTT
2. STL COL. WELD ALL AROUND.
3. FITTED PL1 EA SIDE OF WEB. 4. L4x4x1/4x0'-4" LONG WITH
NOTES: (1) 1- 3/4" DIA. EXPANSION BOLT w/ 4" EMBEDMENT.
4. FOR SIZE, TYPE, AND NUMBER OF
1. BEAM PER PLAN W/ STIFFENER PL3/8" EA SIDE. 5. CONCRETE SLAB
BOLTS, SEE TYPICAL BOLT SCHED. 8 (2)
2. L3x3x1/4 BRACE AT 5'-0" O.C. - TYP. 6. 3 SIDES.
5. STL BM. S5.6 3. FRAMING PER CFS SCHEDULE.

S
CJP 6. SHEAR PL PER TYP CONNECTION
4. ROOF DECK PER PLAN.
DETAIL.

210106
(6)
7. STL BACKER PL. 3/16

INTERIOR DESIGN
580 BURBANK ST. SUITE 125, BROOMFIELD, CO 80020 PHONE: 303.465.4306 FAX: 303.465.4382 www.allredarch.com
8. CAP PL1.

T
(4) (3)
(4)
(4) (5)

A
(5)

I
(8)
RE: GSN FOR STEEL

| JOB NO.
C
GRATING. -TYP.
(1)
3/4

O
TYP
5/16

S
(1)
(1)

S
3/4 (2) (1)

|
A
(2) 3/16 2
(3) TYP STEEL STAIRS AT GRADE

PLANNING
(6) 3/16 2
1
&
(3) NO SCALE
(7)

CAP PER ARCH


1/4

ALLRED
INSTRUCTIONS
1/4

|
4" STD PIPE DECK PER PLAN
NON BEARING ROOF BRACE
4

ARCHITECTURE
NO SCALE

PERMIT SET
1'-0"
STEEL BEAM TO STEEL COL CONNECTION AT
PATIO
6 NO SCALE

TYP
3/16
NOTES:
1. WELD EA PL.
2. STL COL.
3. FITTED PL1.
4. FOR SIZE, TYPE, AND NUMBER OF BOLTS, SEE TYPICAL BOLT SCHED. BEAM OR JOIST
5. STL BM. TYP PER PLAN
CJP (4) 3/16 1
6. SHEAR PL PER TYPICAL CONNECTION DETAIL.
7. STL BACKER PL. PL 1/4-EA

CITY OF THORNTON
(1)
(4) 8. CAP PL1. SIDE OF PIPE
X 2" TALL-(4)

FIRE STATION #7
(8)
(5) IN TOTAL

1/4 2-24 ANTENNA POST DETAIL


1/4 2-24 2 NO SCALE
5/16
TYP (1)
5/16 1/4

(1)
3/4
(3)
(7) (5) (2)

(6)

(7) (2)

3/16 (3) NOTES:


1. STEEL BM PER PLAN.
3/16 2. JOISTS PER PLAN.
3. BRACE AT 5'-0".
4. PARAPET POST PER: NOTES:
8/S5.6 -TYP.
(2) 5. STUD WALL AND DEFLECTION TRACKS PER SCHEDULE 1. MASONRY WALL.
2. MASONRY VENEER.
INTERMEDIATE STEEL BEAM TO STEEL COL AND TYPICAL DETAILS.
3. CONTINUOUS GROUTED BOND BEAM PER G.S.N.
6. RE: 4/S5.3 3/S5.2 FOR ADDITIONAL
CONNECTION AT PATIO INFORMATION. 4. L8x8x3/8 CONT. LEDGER
7 NO SCALE 7. BENT PL3/8x10x6 (LLH). 5. EMBED PL 1/2X12X1'0 W/(2) 3/4" DIA x 5" LONG ANCHORS
AT 9" GAGE - GROUT MINIMUM 4" ABOVE AND BELOW
ANCHORS. SPACE PLATES AT 4'-0" OC.

(2)

10/08/2021
(1)
3/16 4
(1) 3/16 4
NOTES:
1. HSS GIRT PER PLAN. (4) REVISION NAME DATE

(3) 1 ADDENDUM #1 2021 1008


2. KNIFE PL1/2. CONTR TO COORD SIZE W/ SUNSHADE MFR
AND MAS VENEER DIMS. (2) BOLT MIN CONNECTION TO
ROOF STEP ALONG GRID B
SUNSHADE - CONTR TO COORD MFR REQ'S.
5 NO SCALE
(2)
(1)
(5)

ISSUE DATE: 2021 0907

3/16

www.TheLefflerGroup.com info@theLefflerGroup.com
165 S. UNION BLVD, STE 360, LAKEWOOD, CO 80228
3/16

S5.3
STEEL DETAILS
P - 720.890.4095 © 2021
SUNSHADE SUPPORT
8 NO SCALE LEDGER AT MASONRY WALL
3 NO SCALE

C ALLRED&ASSOCIATES 2021
BEAM PER PLAN
NOTES:
1. STEEL BEAM.
2. 3/4" GUSSET PLATE.
NOTES: 3. BEAM CONTINUES - RE: PLAN. 4 4
4. 2 ROWS OF (4) - 3/4" DIA. BOLTS ON BEAM GAGE. HS S5.4
S5.4 S
1. TROLLEY BEAM PER PLAN. DO NOT INSTALL UNTIL ALL ROOFING DL HAS BEEN 5. 3/4" CAP PLATE. 5X
5X
APPLIED. 6. STEEL COLUMN. 1/
4
2. BEAM PER PLAN. 7. 3/8" STIFFENER PLATE EA. SIDE OF BEAM. BR
8. WELD 3 SIDES - TYP. AC
3. 3/8" STIFFENER EACH SIDE ABOVE TROLLEY LOCATION. E
4. AFTER ALL ROOF DEAD LOAD IS APPLIED, USE LEVELING PL1/2+-X5X0'-8 AS 9. HSS SLOTTED BRACE.

S
REQ'D - VIF.

COL PER PLAN

COL PER PLAN


5. JOISTS PER PLAN.

210106
6. HSS6x6x3/8 x VIF. DO NOT INSTALL UNTIL ROOF BEAM HAS FULL ROOFING (1)

INTERIOR DESIGN
(8)

580 BURBANK ST. SUITE 125, BROOMFIELD, CO 80020 PHONE: 303.465.4306 FAX: 303.465.4382 www.allredarch.com
DEAD LOAD. 3

T
3/16
7. LEVELING PL1/2+-X5X1'-0 AS REQ'D - VIF. S5.4
8. L4X4X1/4 WHEEL STOP EA SIDE.

BR
A CE
HS A
I

| JOB NO.
S

C
W.P. /4 5X
(3) 5 X1 5X
5X 1/
4

O
(7)
H SS BR
(2) AC
E

S
(6) 30"

|
5/16 TYP T&B (3)
1/4

A
5/16 2 2
5/16 (4)
1/4 (5) S5.4 S5.4

PLANNING
5/16
(7) BOTH
SIDES
3/16
3/16
10
10
(4)
1/4
&
TYPICAL X-BRACE ELEVATION

ALLRED
(6)
(2) 1 NO SCALE

|
(8)
(9)

ARCHITECTURE
1'-0" MIN.

PERMIT SET
NOTES:
(1)
4 KIP MAX. 1. HSS FRAME.
CAPACITY 1/4 2. HSS DIAGONAL.
3. CONCRETE GRD BM.
TOP OF BRACED FRAME CONN 1/4 4. EMBED PLATE 1X6.
4 NO SCALE 1'-0" MIN. 5. (4) #5 (A706) X 1'-6" VERTICAL WELDED TO
EMBED PLATE.
TROLLEY BEAM HANGER SUPPORT
6 NO SCALE (6)
(1) 6.
7.
3/4" GUSSET PLATE.
(2) #6 x 6'0" TOP CENTERED ON COLUMN.
NOTES:
1. CANOPY PERIMETER BEAM PER PLAN.
2. CANOPY RAFTER PER PLAN. (2)
W.P.
NOTES: 3. CANOPY BEAM PER PLAN.
1. TROLLEY BEAM PER PLAN. BOTH 3/16 10
4. L3X3X1/4XCONT CANOPY CHORD.

CITY OF THORNTON
2. L4X4X1/2. 5. L3X3X1/4X0'-4" LONG EA SIDE OF RAFTER. SIDES 3/16 10
3. L8X4X1/2XCONT ATTACHED TO EA (4)

FIRE STATION #7
JOIST. NOTE: ALL EXPOSED 2 .1/2" 6" MIN 6"
. 6" 2. 1/2"
(7)
4. 2" LONG SLOT WITH 3/4" DIA BOLT STEEL TO BE AESS - 1/4
1/4
FINGER TIGHT AND DING. 3/16 2 TYP. RE: ARCH. 1/4 (7)
TYP EA JOIST 3/16 2-18 1/4
2 SIDES - 3/16 2 5. PL1/2X4X0'-6
3/16 2
TYP 6. TOP CHORD OF JOIST - BEYOND.
3/16 2
1/4 2 (5)
TYP TYP
1/4 1/4 2
X
(3) (3) (4)
(5)
(6) (4)

(5) (5)
(6)
1
(5)
1

MAX SLOPE - TYP (2) (3)


(1) (8)

TYP
3/16 3/16 4
1/4
3/16 TYP TYP
(2) 1/4 1/4 1
GC COORD
(3) 1 1/2
REQUIRED CLEAR
3 1/2" MIN

TYP
HEIGHT FOR 3/16 2
(2) (5) BRACED FRAME BOT CONN
TROLLEY.
(3)
2 NO SCALE

(1)

TYP
2
S5.4
TROLLEY BEAM BRACING AT JOISTS X
SECTION AT RAFTER TO BEAM CONNECTION 10/08/2021
7 NO SCALE

(1)
EDGE OF CANOPY FRAMING REVISION NAME DATE

5 NO SCALE NOTES: 1 ADDENDUM #1 2021 1008


1. HSS SLOTTED BRACED FRAME PER:
2. GUSSET PL 3/4".

(2)

N
MI
"
1 YP ISSUE DATE: 2021 0907
2" T
1/ P
TY

www.TheLefflerGroup.com info@theLefflerGroup.com
165 S. UNION BLVD, STE 360, LAKEWOOD, CO 80228

S5.4
STEEL DETAILS
P - 720.890.4095 © 2021
X-BRACE GUSSET PL MIDDLE CONNECTION
3 NO SCALE

C ALLRED&ASSOCIATES 2021
NOTES:
1. INSTALL (2) SCREWS TO WEB OF EACH STUD. (9) (10) NOTES: BRIDGING REQUIRED AT TOP OF WALL WHEN
2. 1 1/2" BRIDGING CHANNEL -CONTINUOUS.
(1) 1. PAF - RE: GSN. DEFLECTION TRACK IS USED.
3. ATTACH BRIDGING CLIP TO BRIDGING CHANNEL (2)
WITH (2) #10 SCREWS AT EACH CLIP. 2. COLD-FORMED STEEL.
4. BRIDGING IS TO BE INSTALLED AT 4'-0" OC MAX 3. KNURLED SHANK.
FROM BOTTOM TRACK OR TOP OF SHEATHING. 4. FASTENERS ARE TO BE DRIVEN
THROUGH THE THICKNESS OF THE
(3) STEEL.
(4) 5. P = PENETRATION.
(2) 6. P MAX = 1/3 OF SLAB
IN STEEL THICKNESS.

S
7. 3" MIN EDGE DISTANCE.

E
8. 4" MIN FASTENER SPACING.

210106
EACH (7) (8) 9. 1/2" MIN EDGE DISTANCE.
(5)

INTERIOR DESIGN
580 BURBANK ST. SUITE 125, BROOMFIELD, CO 80020 PHONE: 303.465.4306 FAX: 303.465.4382 www.allredarch.com
STUD 1/8 (2)

T
10. 1 1/2" MIN FASTENER SPACING.

A
2 1 2 1

I
S5.7 S5.7
S5.6 S5.6
ALTERNATE #1

| JOB NO.
(6) AT MASONRY VENEER,

C
(3)
PROVIDE L4X4X3/16
(1) ALONG SILL & EXTEND

O
(1) 4" BEYOND ROUGH OPNG
"d IN CONCRETE TO SUPPORT VENEER
7

S
"
S5.5 RETURN. WELD W/
1/8" X 1" FILLET T&B

S
EA STUD; 2" LONG EA

|
JAMB. RE: 30/A8.0

A
TYPICAL PAF SPACING
4 FOR ADDITIONAL INFO.

PLANNING
NO SCALE

&
THIS DETAIL IS TYPICAL TO THE PROJECT AND IS 2
NOT NECESSARILY CUT OR CALLED OUT ON PLANS. S5.5

(4)
(2)

NOTES:

ALLRED
10" MIN.
1. CONTINUOUS BOTTOM TRACK.
2. SCREW EACH FLANGE OF STUDS TO TRACK WITH (1)

|
SELF-DRILLING SCREWS - UNO.
3. FASTEN BOTTOM TRACK WITH PAF AT 8" OC FOR WALL

ARCHITECTURE
STUDS. NOTE: RE:

PERMIT SET
4. FASTEN BOTTOM TRACK WITH (3) PAFs FOR OPENINGS ELEVATIONS FOR
<= 6'-0" AND WITH (5) PAFs FOR OPENINGS > 6'-0". SIZES OF TRACKS,
STRUCTURAL STUD BRIDGING 5. JAMB STUDS. (4)
STUDS, JAMBS,
7 THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
NO SCALE 6. END OF WALL STUD SHALL BE SEATED SQUARELY IN THE
TRACK WITH NO MORE THAN A 1/4" GAP BETWEEN THE 5
HEADERS, AND
SILLS - TYP. 5
NOT NECESSARILY CUT OR CALLED OUT ON PLANS. S5.5 S5.5
END OF STUD AND TRACK (AISI S211).
7. WALL STUDS.
NOTES: 8. PAF TYPICAL EMBEDMENT TO BE 1" INTO CONCRETE (5)
1. BRIDGING PER TYPICAL DETAILS. UNO. TYPICAL CFMF NON-BEARING WALL
2. MINIMUM EDGE DISTANCE PER TYPICAL SCREW
SPACING DETAIL.
1 THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
NO SCALE
3. (1) SCREW EACH FLANGE OF TRACK AT EACH STUD. (1) NOT NECESSARILY CUT OR CALLED OUT ON PLANS.
4. CONT BOT. TRACK.
5. DEFLECTION TRACK PER ELEV. (6)
6. CONT. TOP TRACK. (8) (2)

CITY OF THORNTON
7. STRUCTURE ABOVE. NOTES:
(2) 1. STEEL STUD WALL.

FIRE STATION #7
(7)
(6) 2. JAMB.
(5) (3) (5)
GAP

3. SILL.
1"

(4) 4. 6" LONG STUD TO MATCH


WALL STUD TYPE -
12" MAX.

(3) NOTE:
(7) CONNECT TO JAMB W/
TOP TRACK ATTACHMENT TO
NOTE: WHEN SHEATHING (6) #10 TEK SCREWS AT
(3) STRUCTURE IS THE SAME.
IS USED ON BOTH SIDES 2" O.C. VERT., 5" GA.
OF WALL TO BRACE 5. ATTACH SILL TO STUD
STUDS PROVIDE ONE ROW SEGMENT W/ (1) #10
(1)
OF BRIDGING AT TOP OR TEK SCREW EA SIDE
(6)
(1) A NESTED TOP TRACK.
EXTERIOR STRUCTURAL WALL TRACK ATTACHMENT
(2)

(9)
(3)
TOP AT TO CONCRETE
STRUCTURE 5 THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
NO SCALE
TYPICAL SILL CONNECTION
NOT NECESSARILY CUT OR CALLED OUT ON PLANS.
2 THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
NO SCALE
TOP AT PARAPET NOTES: NOT NECESSARILY CUT OR CALLED OUT ON PLANS.
3/4" GAP

(7)
1. STUDS PER ELEVATIONS OR DETAILS.
12" MAX.

(5) 2. L250x250x43MIL BENT CLIP w/ (1) SCREW EA


LEG AT EA STUD - TYP AT OUTSIDE CORNERS.
NOTE: TOP ROW OF 3. (4) SCREWS AT DIAGONAL LAPS - TYP UNO.
10" MIN.

(3) BRIDGING REQUIRED 4. (4) SCREWS AT TYPICAL LAPS - TYP UNO. (1) NOTES:
REGARDLESS OF BRIDGING 1. TEK SCREWS - PENETRATE A MIN. OF 3 THREADS
(1) REQUIREMENTS FOR WALL PAST FINAL PLY.
(2)

STUDS AT DEFLECTION (1) 2. EDGE OF ATTACHED COLD-FORMED STEEL.


(4) (1)
BOTTOM TOP AT STRUCTURE TRACKS. "E"
(4) SCREW SIZE "S"(MIN.) "E"(MIN.)
#10 5/8" 5/16"
(3) (2) #12 3/4" 3/8"
(2)
TYPICAL STUD TO TRACK CONNECTIONS "S" "E" 10/08/2021
8 THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
NO SCALE
NOT NECESSARILY CUT OR CALLED OUT ON PLANS. (1)
TYPICAL SCREW SPACING
3 THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
NO SCALE 1
REVISION NAME

ADDENDUM #1
DATE

2021 1008
TYPICAL LAPPED CONNECTIONS
NOTES:
1. STEEL BEAM, JOIST, DECK OR MISC. STEEL. 6 THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
NO SCALE
NOT NECESSARILY CUT OR CALLED OUT ON PLANS.

2. PAF AT 16" O.C. STAGGERED.


NOT NECESSARILY CUT OR CALLED OUT ON PLANS.
(1) (1)

(2)
1/8 2-16 (2) ISSUE DATE: 2021 0907

1/8 2-16

www.TheLefflerGroup.com info@theLefflerGroup.com
165 S. UNION BLVD, STE 360, LAKEWOOD, CO 80228

S5.5
TRACK WIDER THAN STEEL STEEL WIDER THAN TRACK

P - 720.890.4095 © 2021

CFS DETAILS
TYPICAL TRACK TO STRUCTURE CONNECTION
9 THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
NO SCALE
NOT NECESSARILY CUT OR CALLED OUT ON PLANS.

C ALLRED&ASSOCIATES 2021
NOTES: NOTES:
1. STEEL POSTS AT 10'-0" OC
MAX (BY OTHERS). 1. SCREWS AT 3" OC VERT FULL HT w/
2. T125-68XCONT FOR BOTH 6" 1/2" MIN EDGE DISTANCE.
AND 8" CONDITIONS. 2. MAINTAIN MIN SCREW EDGE DISTANCE
3. AT STRUCTURAL HSS ATTACH (3) PER 3/S5.5
S162-43 FOR BOTH 6" AND 3. STUD FLANGE MUST BE LARGE ENOUGH
8" CONDIONS TO EACH SIDE (5) SINGLE JAMB NOTES: SO SCREWS DO NOT PENETRATE WEB OF
OF STUD W/ (2) PAF AT 12" 5. 8" LONG TRACK MATCH STUD WIDTH AND STUD BEHIND CONNECTION.
OC. THICKNESS, ATTACH W/ (2) #10 SCREWS
(5) (2) 4. T125-43XCONT FOR BOTH 6" EA. SIDE OF TRACK.

S
AND 8" CONDITIONS. 6. SINGLE JAMB STUD.
2" MAX 5. (2) 1/4" DIAx2 1/2" EMBED
(4)

210106
KH-EZ AT 16" OC.
XX 1 1/2-12

INTERIOR DESIGN
XX 1/8

580 BURBANK ST. SUITE 125, BROOMFIELD, CO 80020 PHONE: 303.465.4306 FAX: 303.465.4382 www.allredarch.com
STAGGERED. TYP

T
1/8 1 1/2-12
(1) (1) (6) (3)

6" MIN
I
(3) (3)

| JOB NO.
(3)

C
(1) (1)
(4)
HSS CONNECTION

(2)
XX

O
2" MAX
NOTES:
AT SINGLE JAMBS
DEFLECTION REQ'D IN 1. STEEL STRUCTURE.

S
(2) WDW SYSTEM 2. TSN STIFFCLIP LB SERIES CLIP W/ (4) SCREWS ALT. #2
TO EACH STUD AND (3) PAFs TO STEEL.

S
WALL ABOVE SLAB 3. ADDITIONAL STIFFCLIP AT JAMB STUDS.

|
WALL BELOW SLAB

A
TYPICAL MULTIPLE MEMBERS
1

PLANNING
NO SCALE

&
THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
CANTILEVERED WALL (3) NOT NECESSARILY CUT OR CALLED OUT ON PLANS.
7 NO SCALE
(1)

ALLRED
NOTES:

|
(1)
NOTES: 1. JAMB STUD PER ELEV.
(2)
1. PARAPET WALL INFILL FRAMING TO BE 600S162-54 AT 16" W/ 600T125-54 T&B. 2. CRIPPLE STUDS AS OCCUR.

ARCHITECTURE
2. ONE STUD EA SIDE OF EA POST - 5'-0" OC MAX. 3. TRACK TO MATCH STUD THICKNESS. ATTACH W/ ROWS OF

PERMIT SET
NOTIFY THE STRUCTURAL SCREWS AT 2" OC - (2) SCREWS PER ROW - (3) ROWS MIN.
3. PAFs SPACED AT 12" OC MAX. ENGINEER 4. HEADER PER ELEV.

6" MIN
4. HSS5X5X1/4 POSTS AT 5'-0" OC MAX - TYP IMMEDIATELY WHEN 6" MIN. 5. 68MIL CLIP ANGLE W/ (4) SCREWS INTO HEADER & JAMB
EDGE STUD.
DISTANCE TO PUNCH-OUT (2) 6. 6" LONG STUD TO MATCH WALL STUD TYPE - CONNECT TO
(1) CANNOT JAMB W/ (6) SCREWS AT 2" OC VERT, 5" GA.
BE ACHIEVED. DO NOT
INSTALL
(1) AT BUILT-UP JAMBS AT LAYOUT STUDS
(2) CLIPS WITHOUT ADDITIONAL
(1) (3)
DIRECTION FROM THE
ENGINEER. OR

TYPICAL RIGID BYPASS CONNECTION AT SECTION 'AA'


RE: SCHEDULE FOR
STRUCTURE (6)
4 ACTUAL HEADER

CITY OF THORNTON
NO SCALE CONFIGURATION.
THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
(4) (2)

FIRE STATION #7
NOT NECESSARILY CUT OR CALLED OUT ON PLANS.
(3)
(2)

NOTES: (1) (3)


A
1. 362S162-43 DIAGONAL KICKER AT 16" OC.
2. SIMPSON SJC8.25 CLIP EA. STUD W/ (3) PAFs TO STRUCT. AND (6) SCREWS TO KICKER.
3. TSN LB CLIP EA. STUD W/ (3) PAFs TO STRUCT. AND (4) SCREWS TO KICKER.
(1) (3)
A
1/8
(4)
(1)
PARAPET INFILL FRAMING (5)
8 NO SCALE
1
1 TYPICAL JAMB STUD TO HEADER
2 THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
NO SCALE
NOT NECESSARILY CUT OR CALLED OUT ON PLANS.

STEEL OR
(2) GAGE METAL
(1)

NOTES: 1 CONCRETE
1
1. 362S162-43 AT 16" OC WEB INFILL FRAMING. CFMF KICKER TO STEEL BEAM
2. 362T125-43 X CONT W/ (1) PAF AT 16" OC.
5 NO SCALE
10/08/2021
NOTES:
(2)
(2)
1. 600S162-54 AT 12"
(1) OC. (3)
2. 600T125-54xCONT. REVISION NAME DATE
(2)
(1) 3. TSN CL600-118 CLIP 1 ADDENDUM #1 2021 1008
AT SINGLE AT BUILT-UP AT SINGLE AT BUILT-UP
w/ 1/2" DIA HILTI
JAMBS JAMBS JAMBS JAMBS
KWIK KH-EZ SCREW
ANCHOR W/ 4-1/4" MIN NOTES:
EMBED AT EA STUD 1. TSN SL CLIP (MATCH STUD WIDTH UNO) WITH #12 SCREW
TYP WEB INFILL LOCATION IN EACH SLOT AND (3) PAFs TO STRUCTURE. USE #12
9 NO SCALE (3)
4. (10) #12 SCREWS FROM
2.
SCREWS ILO PAFs WHEN ATTACHING TO GAGE METAL.
CONT TOP TRACK - RE: ELEVATIONS.
CLIP TO STUD.
(4) 3. 6" TRACK SLEEVE THICKNESS TO MATCH JAMB. ATTACH
EACH FLANGE TO JAMB w/ (3) #12 SCREWS. ISSUE DATE: 2021 0907
(2) 4. ATTACH TOP TRACK TO STRUCTURE PER DETAILS

www.TheLefflerGroup.com info@theLefflerGroup.com
165 S. UNION BLVD, STE 360, LAKEWOOD, CO 80228

S5.6
TYPICAL JAMB CONNECTION TO HEAD OF WALL
3

P - 720.890.4095 © 2021

CFS DETAILS
NO SCALE
THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
NOT NECESSARILY CUT OR CALLED OUT ON PLANS.

CANTILIVERED SILL
6 NO SCALE

C ALLRED&ASSOCIATES 2021
NOTES:
1. JAMB PER SCHED.
2. HSS GIRT PER PLAN. NOTES:
3. TSN AL600 W/ (4) #12 SCREWS 1. ATTACH TRACK TO HEADER
(2) WITH SCREWS AT 12" O.C.
TO JAMB AND (4) PAFs TO
(1) 2. TOP AND BOTTOM TRACK TO BE
STEEL T&B.
CUT SHORT TO ALLOW FOR
(1) JAMB TRACK ATTACHMENT.
(4) 3. HEADER OR BOX BEAM.

S
(2) 4. WEB STIFFENER AS REQUIRED
(2)

210106
(3) FOR TYPICAL HEADER TO JAMB

INTERIOR DESIGN
580 BURBANK ST. SUITE 125, BROOMFIELD, CO 80020 PHONE: 303.465.4306 FAX: 303.465.4382 www.allredarch.com
T
CONNECTION, RE: 2/S5.6

STRUCTURAL HEADER ASSEMBLY A


I

| JOB NO.
C
1
S5.6
(3)
1 THIS DETAIL IS TYPICAL TO THE PROJECT AND IS
NO SCALE

O
NOT NECESSARILY CUT OR CALLED OUT ON PLANS.

HSS GIRT TO CFS JAMB S


4
S

|
NO SCALE

PLANNING
NOTES:

&
1. 250S162-43 AT 16" OC INFILL FRAMING.
2. 250T125-43XCONT W/ (1) PAF AT 16" OC INTO STRUCT.
3. 362S162-43 DIAGONAL KICKER AT 16" OC.
4. SIMPSON SJC8.25 CLIP EA STUD W/ (3) PAFs TO STRUCT AND (6) SCREWS TO KICKER.

ALLRED
(2)

|
ARCHITECTURE
(1)

PERMIT SET
(3)

1
1

(2) (3)
(4)

CITY OF THORNTON
1

FIRE STATION #7
1

PERP TO FRAMING PARALLEL TO FRAMING

KICKER TO STEEL JOIST


2 NO SCALE

NOTES:
1. 362S162-43 DIAGONAL KICKER AT 16" OC.
2. TSN LB CLIP W/ (2) 1/4" DIA KH-EZ ANCHORS W/ 3 1/2" MIN EMBED TO SLAB AND (4) SCREWS TO KICKER.
3. SIMPSON SJC8.24 CLIP EA STUD ACROSS (2) LOW HATS OF THE DECK W/ (1) 1/4" DIA KH-EZ ANCHORS W/ 3 1/2" EMBED EA HAT.
4. 68 MIL CONT PLATE ATTACH TO (2) DECK LOW HATS W/ (2) #12 SCREWS AT 12" OC UNO.
5. TSN LB CLIP W/ (4) SCREWS TO PLATE AND (4) SCREWS TO KICKER.

10/08/2021

(1)
(1) (1) (4) REVISION NAME DATE

1 ADDENDUM #1 2021 1008


(3)
(2)
1 1 1 (5)
1 1 1

ISSUE DATE: 2021 0907

KICKER TO STRUCTURAL DECK


3 NO SCALE

www.TheLefflerGroup.com info@theLefflerGroup.com
165 S. UNION BLVD, STE 360, LAKEWOOD, CO 80228

S5.7
P - 720.890.4095 © 2021

CFS DETAILS
C ALLRED&ASSOCIATES 2021