Download as pdf
Download as pdf
You are on page 1of 2
Conduit.sire Mathematical and electrical tools, ulators, and references Table 250.122 — Grounding Conductor Size Minimum Size Equipment Grounding Conductors for Grounding Raceway and Equipment Back to all tables Conductor size (AWG or kemil) Max. circuit breaker size Copper Aluminum or copper-clad aluminum 15 #14 #12 20 #12 #10 60 #10 #8 100 #8 #6 200 #6 4 300 4 #2 400 #3 a 500 #2 #110 600 1 #210 800 #110 | #310 1000 #210 | -#AIO 1200 #310 | 250 1600 #410 | 350 2000 250 400 2500 360 600 3000 400 600 4000 500 750 5000 700 1250 6000 800 1250 DISCLAIMER: All tables on this site are based on the 2020 National Electric Code. The law under your local jurisdiction may be different than what is presented here. Check your local jurisdiction's laws before attempting to do electrical work. Please report any discrepancies or feedback to feedback@conduit site