Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

CLIENT POWER GRID COMPNAY OF BANGLADESH (PGCB)

PROJECT : POWER GRID NETWORK STRENGTHING PROJECT UNDER PGCB PAGE : 1


TITLE: DESIGN CALCULATION OF CORBEL (For Corbel Length =1300mm) DESIGN BY : Gazi Nazmul
DATE : 24.04.24 REVIEW BY :
-------------------------------------------------------------------------------------------
Corbel Design Based on IBC 06 / ACI 318-05 FOR 12 MT EOT CRANE

INPUT DATA & DESIGN SUMMARY


CONCRETE STRENGTH fc' = 4.35 ksi
REBAR YIELD STRESS fy = 72 ksi
Dead Load,DL 1.60 kip 10.00 KN
Live Load,LL 35.97 kip 160.00 KN
Horz Load 0.22 kip 1.00 KN

FACTORED SHEAR LOAD (1.2DL+1.6LL) Vu = 59.474 k


FACTORED TENSILE LOAD N uc = 0.34 k
WIDTH b = 20 in 500.00 mm
EFFECTIVE DEPTH d = 48 in 1200.00 mm
OVERALL DEPTH h = 52 in 1300.00 mm
SHEAR SPAN (Approx) a = 40 in 1000.00 mm
EDGE DEPTH hc = 26 in 650.00 mm
PRIMARY REINFORCEMENT 6 nos # 6
CLOSED STIRRUPS 6 nos # 3

ANALYSIS Bar Number Dia(mm)


CHECK DIMENSIONAL REQUIREMENTS (ACI Sec. 11.9.1 & 11.9.2) 3 9.525
a/d = 0.83 < 1 [SATISFACTORY] 4 12.7
Nuc / Vu = 0.01 < 1 [SATISFACTORY] 5 15.875
hc = 26.00 > 0.5 d [SATISFACTORY] 6 19.05
7 22.225
CHECK SECTION (ACI Sec. 11.9.3.2.1)

Vu < = 576 k [SATISFACTORY]

where  = 0.75

CHECK REINFORCEMENT

2 2
= 0.220 in = 0.787 in

(ACI Sec. 11.9.3.4) (ACI Sec. 11.7.4.3)


where  = 0.75  = 1.4

2
= 0.770 in = 2380 in-k

(ACI Sec. 10.2)

2 2
12 = 2.320 in < 2.640 in
7
(ACI Sec. 11.9.3.5 & 11.9.5) [SATISFACTORY]

= 1.050 in2 < 1.320 in


2

(ACI Sec. 11.9.4) [SATISFACTORY]