Professional Documents
Culture Documents
Esr4 rev6
Esr4 rev6
4.1 ACCESS
All busbar shutters shall be locked shut and where the possibility of backfeed exists,
the feeder shutters shall also be locked shut. If the design of switchgear does not
have this locking facility, other precautions to prevent Danger shall be taken e.g.,
padlocking of cubicle doors.
4.2 SWITCHING
4.2.1 GENERAL
Switching shall only be carried out with the agreement of the Control Person
responsible for that section of the electrical system.
4.2.1.3 The Control Person who gives agreement for High Voltage Switching, shall
communicate directly with the person who is to carry out the Switching.
Switching to the instruction of the Control Person or with his consent, shall be
carried out without undue delay.
4.2.1.4 The remote opening and closing of High Voltage circuit breakers may be carried out
by unaccompanied Authorised Electrical Persons.
All other High Voltage Switching shall be carried out by an Authorised Electrical
Person who shall be accompanied by an Electrical Person during the Switching
operations.
4.2.1.5 When operating pole mounted switchgear by mechanical means from ground level,
the Electrical Person shall wear Approved insulated rubber gloves and a safety
helmet.
4.2.1.6 Making Live or Dead by signal or prearranged understanding after an agreed time
interval is strictly forbidden.
4.2.1.7 When switchgear or any other High Voltage or Low Voltage equipment shows any
sign of distress, its condition shall be reported immediately to the responsible Area
Electrical Section Head, Senior Authorised Electrical Person or Control Person
who will conduct an examination of the equipment.
When telephone or radio messages are being used to co-ordinate Switching, each
message shall be repeated in full and written down before Switching is performed.
Each operation shall be reported to the Control Person at the other end before the
next operation is executed.
In all cases when emergency Switching has been carried out to avoid imminent
Danger to persons or equipment, the Control Person or Senior Authorised
Electrical Person for the electrical system concerned shall be informed as soon as
possible of any action taken. The Area Electrical Section Head shall report in
accordance with the Incident Investigation and Reporting Procedure.
4.4.1 Work on Low Voltage equipment such as repairs, maintenance, alterations, cleaning,
testing, etc., may only commence after such part of that equipment has been
subjected to the following:
4.4.3 Notwithstanding the requirements of Rule 4.4.1, essential testing or adjustments may
be made with Low Voltage equipment Live, provided that safe methods are adopted
and suitably insulated tools for the rated voltage of the circuit are used.
Under such conditions, the Electrical Person carrying out testing or adjustment shall
use an Approved insulated mat and wear Approved insulated rubber gloves and
face visor.
If the testing or adjustment of Low Voltage equipment requires covers to be
removed such that Live terminals, windings or connections are exposed, then
suitable precautions shall be taken to prevent persons coming into accidental contact
or interfering with that equipment, and a Limitation of Access shall be issued.
The Electrical Person in charge of the testing or adjustments shall be accompanied
by another Electrical Person during progress of Live testing or adjustment.
4.5 EARTHING
4.5.1 GENERAL
High Voltage Earthing switches shall be operated and Circuit Main Earths shall
be connected or removed by a Senior Authorised Electrical Person. A suitably
authorised Authorised Electrical Person may remove and apply Circuit Main
Earths when working under a Sanction for Test.
for Earthing High Voltage equipment. For High Voltage equipment without
Earthing facilities, the following Approved means of Earthing shall be adopted.
(a) A circuit breaker may be used to make an Earth connection. The circuit
breaker shall have the trip feature made inoperative before closing to Earth,
unless this is not practical, when it shall be done after closing. The circuit
breaker shall be locked closed in the Earth position and a Circuit Main
Earth Notice attached.
or
(b) Apply Approved Earthing leads by an Approved insulated pole to all
phase conductors.
If this method of Earthing is to be used, the following precautions shall be
taken.
(i) Check that the circuit to be Earthed is Isolated.
(ii) Ensure that each phase of the circuit is Dead with an Approved
testing device. The testing device must be checked for correct
operation in accordance with the manufacturer’s instructions,
immediately before and after use.
(iii) Examine the Earthing leads prior to use to ensure that they are of the
correct type and rating and in good condition.
(iv) Connect the Earthing leads to the Earth system before securing them
to the phase conductors. Care must be taken to ensure that good
contact is made.
(v) Earth and short circuit all phases even if work is to be carried out on
one phase only.
(vi) When removing Earthing leads, they shall first be disconnected from
the phase conductors before being disconnected from the Earth
system.
Rule 4.5.2(b), then the Senior Authorised Electrical Person carrying out this
operation shall be accompanied by an Authorised Electrical Person.
4.5.3 EARTHING OF LOW VOLTAGE EQUIPMENT
When work is to be carried out on the incoming switchgear, busbars or bus coupler
of a Low Voltage switchboard supplied by a transformer from a High Voltage
system, the following requirements will apply.
(a) Points of Earthing shall be proved Dead using an Approved testing device
before an Earth is applied.
(b) Apply a Circuit Main Earth to the High Voltage side of the transformer
insulated pole or other Approved equipment to all phase and neutral conductors or
busbars with the following precautions.
(i) Check that the circuit to be Earthed is Isolated.
(ii) Prove that each phase and neutral of the circuit is Dead with an
Approved testing device. The testing device must be checked for
correct operation in accordance with the manufacturer’s instructions,
immediately before and after use.
(iii) Examine the Earthing leads prior to use to ensure that they are of the
correct type and rating and in good condition.
(iv) Connect the Earthing leads to the Earth system before securing them
to the phase and neutral conductors or busbars. Care must be taken to
ensure that good contact is made.
(v) Earth and short circuit all phases and neutral even if work is to be
carried out on one phase or the neutral only.
(vi) When removing Earthing leads, they shall first be disconnected from
the phase and neutral conductors or busbars before being disconnected
from the Earth system.
(a) A Safety Distance of one metre shall be maintained at all system voltage
levels between any part of a person or object, and the nearest Live High
Voltage conductor.
(b) A distance of 30cm shall also be maintained at all system voltages, from the
portion of insulators supporting Live High Voltage conductors which is
outside the appropriate Safety Distance from the conductors. See appendix
4B.
Esr 4 September 2001 Page 6 of 10
ELECTRICAL SAFETY RULES Rev 06
When exposed High Voltage conductors are Isolated but not proved Dead, the only
objects which shall approach them or the insulators supporting them, within the
Safety Distance, shall be Approved voltage detection devices and fuse extractors.
4.7.1 The commissioning and testing of High Voltage equipment, electrically and
physically segregated from existing High Voltage equipment, does not come within
the scope of the Electrical Safety Rules. However, for the commissioning and
testing of High Voltage equipment and for cables to be glanded into existing High
Voltage equipment, a Sanction for Test is required.
4.7.2 The Authorised Electrical Person, when applying a test voltage to High Voltage
equipment, shall ensure that adequate precautions are taken to guard the equipment
to prevent Danger to personnel.
These precautions shall include the following:
(a) Defining the test area by means of barriers to restrict access to authorised
Esr 4 September 2001 Page 7 of 10
ELECTRICAL SAFETY RULES Rev 06
personnel only.
(b) Danger Notices attached to the equipment during the period High Voltage
testing is taking place.
(c) All equipment, particularly cables, is discharged to Earth before and after
the application of the High Voltage test voltage.
(d) Any temporary conductor used for applying a test voltage shall be suitably
insulated and of adequate cross sectional area, installed in a safe manner
observing sufficient clearance and be clearly visible to personnel.
(e) Test connections shall not be applied in a cell or compartment in which
there are exposed Live High Voltage conductors.
When such testing is being carried out, the Authorised Electrical Person shall be
accompanied by another Authorised Electrical Person.
The working and access clearances given in the table of appendix 4A are derived
from the Safety Distance specified in Rule 4.6.1 with the addition of working
distances for the particular activity to be undertaken in High Voltage switchyards
and in the vicinity of exposed Live High Voltage conductors.
IMPORTANT NOTE
This appendix has been produced to give Senior Authorised Electrical Persons
operational guidance when they are issuing Electrical Safety Documents in the
situations covered in this appendix.
The working and access clearance figures should be used as a minimum requirement,
and should be increased if practicable in all such situations.
APPENDIX 4A
APPENDIX 4B
MINIMUM SAFETY
NOMINAL SYSTEM VOLTAGE
DISTANCE ‘X’
Esr 4 September 2001 Page 10 of 10
ELECTRICAL SAFETY RULES Rev 06