Professional Documents
Culture Documents
Esr6 rev6
Esr6 rev6
6.1.5.1 For work on High Voltage conductors, the Authorised Electrical Person holding
the Electrical Permit to Work shall implement the following:
(a) Ensure that no person touches or cuts into the insulation of the cable unless
the cable is Dead, Isolated and Earthed.
(b) Identify the cable to be worked on at the point of work, and issue a Sanction
for Test to an Authorised Electrical Person for spiking the cable.
(c) Prove the cable is Dead by Approved spiking equipment.
(d) Cancel the Sanction for Test and issue an Electrical Permit to Work to an
Authorised Electrical Person.
(e) Keep any Safety Padlock keys, withdrawn fuses or links in a Lock Out
Box during progress of work.
(a) Identify the cable to be worked on at the point of work, and issue a
Sanction for Test to an Authorised Electrical Person.
(b) Prove the cable is Dead by Approved spiking equipment.
(c) Keep any Safety Padlock keys, withdrawn fuses or links in a Lock Out
Box during progress of the work.
6.2.3.1 If the excavations are in the vicinity of underground electrical cables, the Senior
Authorised Electrical Person shall specify on the Excavation Certificate the
additional precautions that shall be taken to safeguard the cables.
6.3.1 For work on High Voltage transformers, the Senior Authorised Electrical Person,
in addition to the rules called for in Rule 4.3 shall:
(a) Disconnect the withdrawable High Voltage equipment from all supplies and
where practicable, remove it from its cubicle.
(b) Discharge the conductors to Earth, which need not remain connected to
Earth.
(c) Release stored mechanical energy where applicable.
(d) Ensure shutters or cubicle doors are locked shut.
(a) Ensure that the section of the busbar on which work is to be carried out is
Isolated from all points of supply from which it can be made Live.
(b) Ensure that the Isolating arrangements are secured with Safety Padlocks,
and the shutters of Live spouts locked shut. If not possible to padlock the
shutters, additional barriers and Danger Notices shall be installed.
(c) Attach Caution Notices at all points where the busbars can be made Live.
(d) Attach Danger Notices, where applicable, on or adjacent to equipment
containing Live conductors at the limits of the busbar on which work is to
be carried out.
(e) Test with an Approved voltage testing device that the busbars are Dead,
checking the voltage testing device before and after use.
(f) Earth the busbar and where practicable lock the Circuit Main Earth in
position. Attach a Circuit Main Earth Notice to the circuit breaker or
Earthing device.
(g) Test with an Approved voltage detector every spout where work is to be
carried out, checking the correct operation of the voltage detector before and
after each use.
(h) Issue an Electrical Permit to Work to an Authorised Electrical Person.
(a) Ensure the shutters of the Live busbar spouts are locked shut.
(b) Issue an Electrical Permit to Work to an Authorised Electrical Person.
(a) Identify the safe working area and ensure that Safety Distances called for in
Rule 4.6 can be maintained at all times with particular attention to the tools
and equipment the Working Party are to use.
(b) Approved barriers must be used to define the safe area of work. These
barriers must be clearly visible and shall not be tied or supported by any
structure carrying Live equipment or conductors. The safe area shall be
clearly identified inside the barriers or ropes and Danger Notices attached
to adjoining Live equipment.
(c) Ensure that ladders and scaffolding required for the work are constructed
from non conductive material and kept secure with a Standard Electrical
Padlock when not in use.
(d) Ensure that if ladders, scaffolding, cranes etc., are to be used, that the
position that they shall be placed and the route through the switchyard to
that position shall first be agreed by the Senior Authorised Electrical
Person. Metal housing of cranes and scaffolding etc., shall be connected to
the substation Earth system as soon as they are in position for work to take
place.
6.6.2 PRECAUTIONS
For work on remotely or automatically controlled High Voltage equipment such as
tap-changers, circuit breakers, disconnectors etc., the Senior Authorised Electrical
Person, before work commences, shall:
(a) Ensure that all remote control and automatic features are made inoperable
and where practicable, secured with Safety Padlocks and Caution Notices
attached.
(b) Avoid work being in progress simultaneously on the tap-changer, circuit
breaker etc., and on the controlling equipment, associated wiring or relays,
except when it is undertaken by an Authorised Electrical Person acting
under his direct supervision.
6.7.1 When work has to be carried out on a High Voltage motor, the following precautions
shall be taken. The Senior Authorised Electrical Person shall, in sequence:
(e) Establish that the correct motor has been Isolated by attempting a start at
the local control station when selected to the local position.
Note: Process interlocks may prevent starting.
(f) Ensure that the driven equipment cannot be turned by passage of air, fluid or
mechanical forces acting on the driven unit or its auxilliaries.
(g) Issue an Electrical Permit to Work to an Authorised Electrical Person.
(h) When work is completed, the Authorised Electrical Person will complete
the Hand Back of Work section of the Electrical Permit to Work and
return it to the Senior Authorised Electrical Person.
(i) Notwithstanding the requirements of Rule 4.5.1 and Rule 5.3.1, remove the
Circuit Main Earth and apply an insulation resistance test to the High
Voltage motor circuit.
(j) Cancel the Electrical Permit to Work, remove Safety Padlocks, Caution
Notices, Danger and Circuit Main Earth Notices and restore the circuit
breaker to the service position.
6.7.2 When work has to be carried out on a High Voltage motor supplied from a unit
transformer, then in addition to the precautions in Rule 6.7.1 and prior to the issue of
an Electrical Permit to Work, the following additional precaution shall be taken.
(a) Apply a Circuit Main Earth to the High Voltage motor cable at the motor
terminal box or unit transformer terminal box by Approved Earthing leads.
Attach a Circuit Main Earth Notice to the Earthing leads.
6.8.1 When work is to be carried out on a High Voltage generator, the following
precautions shall be taken.
(a) If the generator neutral is solidly Earthed through a switch and is providing
the system Earth, then this Earth should be transferred to another running
generator.
(b) The generator shall be shut down in accordance with operational
procedures.
(c) Check the identification on the generator matches the supply switchgear
identification and the Work Permit. Check the generator is stationary.
Cable numbers should also be checked to ensure the correct equipment is
selected.
(d) Isolate and Safety Padlock off control and instrumentation voltage
transformer, attach Caution Notices.
(e) Isolate the generator circuit and attach Caution Notices.
(f) Isolate or make inoperable all remote control facilities, and where
practicable, Safety Padlock off and attach Caution Notices.
(g) Lock the switchgear busbar shutters or cubicle door closed with Safety
(i) The excitation equipment shall be Isolated and Safety Padlocked off where
possible.
(j) Adequate precautions must be taken to ensure the prime mover is Isolated.
(k) Ensure all necessary auxilliary equipment, e.g., heaters, lubricating pump,
instrumentation, etc., is Isolated.
6.9.1 Due to the danger of backfeeds on Low Voltage switchboards supplied by two or
more High Voltage transformers or Low Voltage feeders, any work carried out on
the Low Voltage incoming switchgear, busbars or bus couplers of the Low Voltage
switchboard requires strict precautions and the issue of an Electrical Permit to
Work to the Electrical Person in charge of the work.
6.9.2 If the design of the Low Voltage system or switchboard connections are such that
complete Isolation of the incoming switchgear to be worked on requires the
Isolation of the High Voltage winding of a High Voltage transformer, then in
addition to the opening of Low Voltage switchgear units, the following procedure
shall be carried out by a Senior Authorised Electrical Person.
(a) All such Low Voltage switchgear shall be opened, and where practicable, a
Safety Padlock applied and Caution Notices attached.
(b) Danger Notices shall be attached to Live equipment adjacent to the point
of work.
(c) The High Voltage transformer shall be switched off, Isolated, and a
Caution Notice attached at the point of Isolation.
(d) A Circuit Main Earth shall be applied to the High Voltage winding of the
transformer.
(e) An Electrical Permit to Work shall be issued to the person in charge of the
work.
(f) Any Earth applied to the Dead switchboard shall be in accordance with
Rule 4.5.3.
6.10.1 When work is to be carried out on a Low Voltage motor, the following precautions
shall be taken.
(a) Check the identification on the motor matches the supply switchgear
identification and the Work Permit. Check that the motor is not running.
(d) Isolate or make inoperable all remote control facilities, and where
practicable, Safety Padlock and attach Caution Notices.
(e) Ensure that the driven equipment cannot be turned by passage of air, fluid or
mechanical forces acting on the driven unit or its auxilliaries. Particular
attention must be given to fan units.
(f) Ensure all necessary auxilliary equipment, e.g., heaters, lubicating pump,
instrumentation etc., is Isolated.
6.11.1 GENERAL
Due to the inherent dangers present in batteries and battery systems where Live
working is unavoidable, strict precautions must be enforced to reduce the potential
risk of injury to personnel involved in this work.
The Electrical Safety Rules shall not apply to batteries providing motive power. e.g.,
vehicles, pump or generator starting.
6.11.2 A Limitation of Access shall be issued for any work on Live battery systems. The
Senior Authorised Electrical Person, however, may decide at his discretion, that
routine work on batteries e.g., cleaning, topping up and inspection carried out by
Electrical Persons authorised for this work, may be carried out without the issue of
a Limitation of Access.
(a) Isolate battery charger, Safety Padlock off and attach Caution Notices.
(b) Where possible, Isolate battery and attach Caution Notice.
(c) Appropriate protective clothing shall be worn: gloves, full overalls,
protective apron and eye protection.
(g) Be aware of nearest hand basin, eye wash, medication and shower facility.
(h) Batteries shall not be connected in parallel by temporary jump leads.
(i) A fire extinguisher of the correct type shall be readily available whilst work
is in progress.
6.12.1 GENERAL
All electrical work and electrical testing in Al Furat Petroleum Company designated
hazardous areas shall be undertaken in accordance with the requirements of the
All precautions called for in other sections of these Rules that apply to Switching,
work or testing on either High Voltage or Low Voltage equipment, shall apply to all
Electrical Equipment located in hazardous areas.