WATER DEMAND CALCULATION FOR TRANSFORMER IBT

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

WATER DEMAND CALCULATION FOR TRANSFORMER (GISTET MUARA KARANG)

Water density for transformer protection


NFPA 15 (2017 Edition) – Clause 7.4.4

- Aplication rate 10,2 l/m x m2 for prism area


- Application rate 6,1 l/m x m2 for non-absorbing area (under the transformers)
LENGTH = 9,800 m
WIDTH = 7,160 m
HEIGHT = 4,500 m

TRANSFORMER :
Q 1.1 = W X H X 2 X density prism area
= 7,16 m X 4,50 m X 2 X 10,2 l/m X m2 = 657, 28 l/m
Q 1.2 = L X H X 2 X density prism area
= 9,80 m X 4,50 m X 2 X 10,2 l/m X m2 = 899,64 l/m
Q 1.3 = L X W X 1 X density prism area
= 9,80 m X 7,16 m X 1 X 10,2 l/m X m2 = 715,71 l/m
Q 1.4 = L X W X 1 X density non-absorbing area
= 9,80 m X 7,16 m X 1 X 6,1 l/m X m2 = 428,02 l/m
_____________
Q1 = 2700,65 l/m

TANK :
LENGTH L = m
DIAMETER d = m
Q 2.1 = π X d X L X density l/m/m2
=
Q 2.2 = (π X d 2 ÷ 4) X (density X 2)
= (π X d 2 ÷ 4) X (10,2 l/m/m2 X 2)

Assumsi kebutuhan untuk konservator sekitar 300 l / m

Total Q1 + Q2 = 2700, 65 l/m + 300 l/m = 3000 l/m

Safety Factor add 10 % dari kapasitas terbesar = 110 % X 3000 l/m = 3300 l/m

FIRE PUMP DATA (PJB BLOK 1)

Electrical Main Pump


Spesifikasi :
- Motor Brook Cromton / T732X
- Pump Worthington /6LN 18 D / 31038 1992
- Capacity 354 m3/h
- Power 110 KW

Diesel Main pump

Spesifikasi :
- Diesel Caterpilar /03Z-11044
- Pump Worthington /6LN 18 D / 31037 1992
- Capacity 354 m3/h
- Power 196 HP 146 KW

Jockey Pump
Spesifikasi :
- Motor Brook Cromton / W315255
- Pump Worthington
- Capacity 9 m3/h
- Power 11 KW

Fire Water Tank


Capacity 1000 m3

You might also like