Professional Documents
Culture Documents
Appendix 2 of Schedule L2
Appendix 2 of Schedule L2
of
Schedule L - 2
Manual for
Testing Instrumented
Safeguarding Systems
Content
SUMMARY..............................................................................................................................................3
RESPONSIBILITIES..............................................................................................................................3
TESTING REQUIREMENTS................................................................................................................3
ADMINISTRATION...............................................................................................................................3
GLOSSARY OF TERMS........................................................................................................................3
REFERENCE DOCUMENTS................................................................................................................3
1. INTRODUCTION...........................................................................................................................4
1.1. BACKGROUND...........................................................................................................................4
1.2. APPLICABILITY..........................................................................................................................4
2. TESTING REQUIREMENTS OF INSTRUMENTED SAFEGUARDING SYSTEMS..........5
2.1. SCOPE OF TESTING AND TEST INTERVAL..................................................................................5
2.1.1 Initiator Testing....................................................................................................................6
2.1.2 Simulated Testing of Instrumented Protective System (IPS)................................................6
2.1.3 ESD Testing..........................................................................................................................7
2.1.4 Proof Testing........................................................................................................................7
2.2 EXTENDING THE CURRENT TEST INTERVAL.....................................................................................7
2.2.1 ESD Testing..........................................................................................................................7
2.2.2 Initiator Testing....................................................................................................................8
2.3 PLANNING......................................................................................................................................8
2.3.1 Scheduled Testing.................................................................................................................8
2.3.2 Deferment of Scheduled Testing...........................................................................................8
SUMMARY
OBJECTIVE
The purpose of this document is to define the method for the Testing and establishing the test
interval of Instrumented Safeguarding Systems in Al Furat Petroleum Company (AFPC) and
thereby allow the Asset Operator to demonstrate optimum technical integrity with maximum
economic benefit.
Adherence to the contents of this Manual is mandatory.
RESPONSIBILITIES
Area Superintendents (OPXs) shall be responsible for ensuring that Testing is executed in
accordance with this document within their own areas and specifically for ensuring that any
deviation to this Manual, Test Interval or Schedule is managed in line with Deviation Control
Procedure ECD-05.
Field Instrument Support (OTS/4) shall be responsible for supporting the Area
Superintendents in the Instrument Safeguarding Testing execution in the reporting and
analysis process.
The document custodian is responsible for the approval of any changes to the process or form
of words herein.
TESTING REQUIREMENTS
All safeguarding systems shall be subject to Initiator Testing at a maximum interval of 12
months dependent on proven reliability and inhibited to ensure no deferment.
Refer to section 2.1.1 Initiator Testing
All safeguarding systems shall be subject to Emergency Shutdown (ESD) Testing at a
maximum interval defined in table 3 dependent on proven reliability.
Refer to section 2.1.3 ESD Testing
All safeguarding systems shall be subject to Simulated Testing during scheduled shutdowns
in accordance with table 2.
Refer to section 2.1.2 Simulated Testing of Instrumented Protective System
All safeguarding systems shall be subject to Proof Testing independent of the Test Interval
where the logic of the system is unknown or in doubt.
ADMINISTRATION
All Instrument Safeguarding System testing shall be administered in order to ensure that
technical integrity is maintained and deferment minimised. All testing executed and changes
made to the systems and test intervals shall be recorded so that analysis and audit may be
carried out and were applicable improvements made.
GLOSSARY OF TERMS
All technical terms and acronyms are set out in the Glossary of terms in appendix 5
REFERENCE DOCUMENTS
All documents referenced in this Manual are detailed in Appendix 6
1. INTRODUCTION
AFPC operates a large number of Oil & Gas productions and related facilities of varying size
and complexity. In order to ensure continued safe and efficient operations it is necessary to
regularly Test the Instrumented Safeguarding Systems.
Such Testing must be properly executed and documented in order to ensure that the
Instrumented Safeguarding Systems remain fit for purpose and that AFPC's requirements for
ensuring technical integrity are met.
This document shall be the Company Manual for the Testing of Instrumented Safeguarding
Systems on all AFPC’s facilities.
1.1. Background
The Safeguarding Testing was initially revised to meet the Company requirements as
documented in the Operational Reliability Review, Action Item ORR NGF5, and the Cost
Review, Action Item CR-E4. Following implementation in 1999 a review by the Instrument
Engineers led to Revision 2 in May 2000.
It specifies the role of the Operations department in the execution of Instrumented
Safeguarding Systems Testing with minimal product deferment. It removes the reliance on
prescriptive Test Intervals, which formed the basis under which Emergency Shutdown (ESD)
and Alarm Testing was traditionally carried out in AFPC and upgrades it to a risk based
method of establishing Test Intervals.
1.2. Applicability
This document is applicable to all AFPC installations and the protective instrumentation
normally associated with Emergency Shutdown (ESD), Process Shutdown (PSD) and
Machine Protection functions that could have a significant effect on People, Production or the
Environment if the Instrumented Safeguarding System were to fail.
All Instrumented Safeguarding System functions shall be Tested to demonstrate that there are
no Unrevealed Failures. There shall be 3 separate functional Tests, (Ref. Fig 1 below).
Initiator Testing – The inhibited Testing of all safeguarding initiators to confirm that the
Initiator(s), up to and including the input card/relay, and alarm facility function as per
design.
Simulated Testing – Testing during planned facility shutdowns to demonstrate the entire
Instrumented Safeguarding System functions in accordance with the designed C&E
diagrams.
ESD Testing – The uninhibited Testing of the overall ESD system for a facility initiated
by a single ESD Initiator to confirm that all Final Elements function as per design.
These Tests may be carried out separately or combined, as appropriate to the operational
circumstances of each facility as long as the overall scope and minimum Test Interval
requirements are met. Do not duplicate test requirements. i. e if a simulated test is carried out
there is no requirement for an initiator test to be carried out.
2.1.3ESD Testing
Regular ESD Testing shall be carried out for all facilities at an interval no greater than its
Target Test Interval specified in table 3
Page 7 of 28 772468330.rtf 7/14/24
TESTING OF INSTRUMENTED
SAFEGAURDING SYSTEMS Rev 4
MANUAL
2.3 Planning
3.2 Recording
The completed test sheets shall be signed and dated by OPX/1 confirming compliance of the
Testing execution with the contents of this Manual.
OPX/3 shall ensure that the test results and details of any associated corrective actions shall
be recorded in the EMMS for future reference and statistical analysis. A Test report
summarising the findings with any associated corrective actions shall be provided.
Test results shall be recorded in accordance with Appendix 3 pass/fail criteria.
Test reports shall be archived for at least 10 years or, the life of the Instrument Protective
Function (IPF), whichever is the longer.
Environmental (E)
The AFPC Classification Risk Diagram was used to classify the potential consequences of
failure of a facility ESD System. The results are shown overleaf. The Target Test Interval is
the interval arrived at after a Risk Classification has been carried out.
Classification Basis
In the main, activated by manual pushbuttons, the design intent is to mitigate the
consequences of incidents such as leaks, fires, etc. from escalating and causing
serious/catastrophic loss. This is achieved through the isolation and de-pressurisation of all
process and non-essential utility systems of a production facility.
The potential worst consequences of a failure of an ESD system in all of AFPC facilities, is
considered to be the loss of a single life or, severe injury and the loss of the production
facility. Death of several persons is not considered likely due to the manning philosophy,
facility layout and ease of escape. This is based on an evaluation carried out in Tanak in
November 97 which is taken to be applicable to all AFPC installations for the purpose of Test
Interval selection.
Classification Examples
Using the AFPC Classification Risk Diagram, which has been adapted from Internationally
accepted risk graphs to reflect AFPC's actual situation. The consequence that dictates the Test
Interval for ESD systems is Production Loss, where facility throughput is in excess of 70,000
barrels of oil per day. This figure is defined as maximum risk criteria, which is 20% of
350,000 Barrels Per Day (BPD), AFPC total oil production. Below this threshold the
Personnel Safety & Environmental consequences would dominate. As these consequences
are in general common to all facilities, specific ESD Test Intervals can be determined as per
table 3 (reference 2.1.3).
Note. Consequences can be identified for failures at the Process Shutdown (PSD) or
Machine Protection level e.g. S3 - Death of several people. If this is the case, it will result in
more frequent Testing of the specific loop, which can be done by Inhibited Initiator Testing
and Final Element Testing, possibly without deferment.
Appendix 2: Instrumented Protective System Integrity (I) ESD Target Test Intervals
Production & Equipment Loss (L) Class V/IV/III (6, 12, 24 months)
Pass/Fail criteria for instrumented Protection Devices are determined by the inherent accuracy
of the instrument used.
1. Pneumatic and electronic transmitters with receiving switches should be kept within ±
2% of their set point.
2. Direct mounted process switches should be kept within ± 3% of their set point.
3. Level instruments using displacers should be kept within ±5% of their set point. If
levels are measured by DP- instrument criteria (1) shall be applicable.
The following matrix gives an overview of the recommended accuracy bands for the different
instruments:
Type of instrument
Instrument Transmitter with Direct mounted Displacer type level
function receiving switch process switch instrument
If a Test DEFECT or Test FAIL is recorded a corrective job card or, Plant Improvement
Request (PIR) must be raised, as appropriate, and the work carried out at the earliest
opportunity thereafter. It may also be necessary to adjust the maintenance schedule of the
failed components.
STEP DESCRIPTION
1. This MWI has been produced in accordance with OCD 2.OOG.3.002. Any changes to
this MWI shall be made in accordance with the requirements of this document and
approved by the appropriate Authority.
2 These tests shall be conducted under the guidance of a Competent Production Person
who shall be responsible for ensuring the tests are conducted safely and that no
unplanned product deferment is caused.
3. OBJECTIVE - To ensure that the Initiator(s) operate at the required setpoint without
executing trip actions. If the objective is not achieved all necessary actions taken to
return the system to a satisfactory condition must be completed as soon as reasonably
practical and are to be logged in the history section of the EMMS along with the test
results.
4. Comply with the permit to work system and all relevant safety precautions.
5. Inhibit operation and function test each of the following initiators below in turn in
accordance with following instructions.
(Area Instrument Section Head OPX/3 in conjunction with OTS/4 as necessary
shall complete this section to reflect the actual status of the panel being tested)
TRIPPING DEVICE DESCRIPTION
XXXXXXXX XXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXX XXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXX XXXXXXXXXXXXXXXXXXXXXXXXXXXXX
6. Confirm that the following base design documentation and information is current and
available.
Trip setpoint EMMS
Loop Sheets
7. Apply the necessary maintenance over-rides or input isolation links on the specific unit
shutdown panel to ensure that actuation of the trip devices will not cause any
unnecessary plant upset or product deferment.
8. Where Maintenance Over-ride Switches are utilised, confirm the over-ride
indication/alarm is annunciated and the corresponding input indication is identified but
not indicating.
9. To achieve the highest possible test coverage factor, the initiator shall be tested by
adjusting the process, e.g. raising the level in an oil separator were the level can be
raised slowly and under control. If this cannot be achieved safely then a simulated
process condition which replicates as closely as possible the process excursion shall be
used.
Page 19 of 28 772468330.rtf 7/14/24
TESTING OF INSTRUMENTED
SAFEGAURDING SYSTEMS Rev 4
MANUAL
APPENDIX 4:
STEP DESCRIPTION
1. This MWI has been produced in accordance with OCD 2.OOG.3.002. Any changes
to this MWI shall be made in accordance with the requirements of this document and
approved by the appropriate Authority.
2. This test shall be conducted under the guidance of a Competent Production Person
who shall be responsible for ensuring the test is conducted safely and that no
unplanned product deferment is caused.
3. OBJECTIVE - To ensure that all the specified Final Elements achieve their desired
position on operation of an ESD initiator. If the objective is not achieved all
necessary actions taken to return the system to a satisfactory condition must be
completed as soon as reasonably practical and are to be logged in the history section
of the Immpower along with the test results.
4. Comply with the permit to work system and all relevant safety precautions.
5. Choose an initiator by which to initiate the test from one of the following ESD
Initiators. Consult previous work history to select an ESD Initiator that has not been
previously or recently used to initiate this test.
(Area Instrument Section Head OPX/3 in conjunction with OTS/4 as necessary
shall complete this section to reflect the actual status of the panel being tested)
ESD INITIATORS DESCRIPTION
XXXXXX XXXXXXXXXXXXXXXXXXXXXX
XXXXXX XXXXXXXXXXXXXXXXXXXXXX
XXXXXX XXXX XXXXXXXXXXXXXXXXXX
6. Confirm that the following base design documentation and information is current and
available.
Trip setpoint (EMMS)
Loop Sheets
7. To achieve the highest possible test coverage factor, the initiator shall be tested by
adjusting the process, e.g. raising the level in an oil separator were the level can be
raised slowly and under control. If this cannot be achieved safely then a simulated
process condition which replicates as closely as possible the process excursion shall
be used.
If a simulated process condition is used, isolation/blowdown of the
measuring/tripping device, the system of initiation shall be conducted using one of
the following methods.
APPENDIX 4:
By isolating the initiator from the process and carrying out a wet simulation e.g.
introduction of liquid into a float chamber or connection of a portable hydraulic test
unit to the device.
By applying/removing heat, via a safe source, to a temperature sensing device.
By injection of an electrical or pneumatic signal to the tripping device, (dry simulation),
using a suitable piece of test equipment.
The chosen method shall ensure that the input loop is fully tested.
8. Reset any active trip alarms in readiness for the test actuation.
9. Operate the push button or increase or decrease the process or simulated process
value until the trip should have occurred.
10 If the test is not initiated by a push button then note the process value at which a trip
occurs, check this value against the designated Trip Point Set Value and Tolerance
settings. If the trip does not occur within the Trip Set Point Tolerance, the test should
be abandoned, the appropriate failure code recorded and the necessary corrective
actions implemented.
11. If the initiator forms part of a voting configuration, simulate the required set of inputs
to achieve the trips.
12. Check the following events occur after the output signal has been driven to the tripped
state.
All Final Elements achieve their desired position within any stated times.
The appropriate Distributed Control System (DCS) / Supervisory Control and Data
Acquisition (SCADA) indications are obtained.
The control room alarm annunciates.
13. On completion or abandonment of the test ensure that all Initiators, Final Elements
and alarms have been returned to their start-up state; any vents are closed; and that no
additional unrevealed failures have been introduced during the test.
14 Record and update results in the "Work History" section of the EMMS. The test
results shall be recorded utilising the appropriate codes i.e. PASS, FAIL or DEFECT.
15 If calibration or remedial action is required as a result of the test a corrective job card
or, Plant Change Proposal (PCP) must be raised, as appropriate.
APPENDIX 4:
INSTRUMENTED PROTECTIVE SYSTEM (IPS) TEST {SIMULATED TEST}
STEP DESCRIPTION
1. This MWI has been produced in accordance with OCD 2.OOG.3.002. Any changes
to this MWI shall be made in accordance with the requirements of these documents
and approved by the appropriate Authority.
2. These tests shall be conducted under the guidance of a Competent Process Tester who
shall be responsible for ensuring the tests are conducted safely and that no unplanned
product deferment is caused.
3. OBJECTIVE - To ensure that the required trip actions, as illustrated in the current
C&E diagrams, are achieved by the initiation of the input(s). If the objective is not
achieved all necessary actions taken to return the system to a satisfactory condition
must be completed as soon as reasonably practical and are to be logged in the history
section of EMMS along with the test results.
4. Comply with the permit to work system and all relevant safety precautions.
5. Inhibit any plant/equipment not required to be shutdown by this test and initiate
test(s) by the following initiator(s).
(Area Instrument Section Head OPX/3 in conjunction with OTS/4 as necessary
shall complete this section to reflect the actual status of the panel being tested)
INITIATOR DESCRIPTION
XXXXXXXX XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
6. Confirm that the following base design documentation and information is current and
available.
Trip setpoint and tolerances
Cause and Effect Matrices
Loop diagrams
Logic Diagrams
APPENDIX 4:
7 To achieve the highest possible test coverage factor, the initiation shall be caused by
adjusting the process, e.g. raising the level in an oil separator were the level can be
raised slowly and under control. If this cannot be achieved safely then a simulated
process condition which replicates as closely as possible the process excursion shall
be used.
If a simulated process condition is used, isolation/blowdown of the
measuring/tripping device, the system of initiation shall be conducted using one of
the following methods.
By isolating the initiator from the process and carrying out a wet simulation e.g. introduction
of liquid into a float chamber or connection of a portable hydraulic test unit to the device.
By applying/removing heat, via a safe source, to a temperature sensing device.
By injection of an electrical or pneumatic signal to the tripping device, (dry simulation) using
a suitable piece of test equipment.
The chosen method shall ensure that the input loop is fully tested.
8. Reset any active trip alarms in readiness for the test actuation.
9. Increase or decrease the process or simulated process value until the trip should have
occurred.
Note the process value at which a trip occurs, check this value against the designated
Trip Set point Value and Tolerance settings. If the trip does not occur within the Trip
Set Point Tolerance, the test should be abandoned, the appropriate failure code
recorded and the necessary corrective actions implemented.
If the initiator forms part of a voting configuration, simulate the required set of inputs
to achieve the trips.
10. Check the following takes place, when the trip is generated.
The relevant trip actions are initiated in accordance with the current C&E Diagram.
The appropriate Distributed Control System (DCS) / Supervisory Control and Data
Acquisition (SCADA) indications are obtained.
The control room alarm annunciates.
11. On completion or abandonment of this test ensure that all Initiators, Final Elements
and alarms have been returned to a state consistent with the plant condition; any
isolation and link test points have been removed; and that no unrevealed failures have
been introduced during testing.
12. Record and update test results in the "Work History" section of the EMMS. The test
results shall be recorded utilising the appropriate codes i.e. PASS, FAIL or DEFECT.
13. If calibration or remedial action is required as a result of the test a corrective job card
or Plant Change Request (PCP) must be raised, as appropriate.
Custodian Comments :
EFFECT Equip no. Equip no. Equip no. Equip no. Equip no. Equip no. Equip no. Equip no. Equip no.
REMARKS
ACTION
DESCRITION
SERVICE
CAUSE
SERVICE TAG
DESCRITION NUMBER
REMARKS
Equip no.
SD GROUP No.
Equip no.
Equip no.
SD GROUP No.
Equip no.
SD GROUP No.
Equip no.
REV NO. TITLE DRAWING NO. DATE DRAWN CHECKED DRAWING NO. REV
APPENDIX 6:
Emergency Shutdown (ESD)
An Emergency Shutdown is defined as the isolation and de-pressurisation of all the process
and non-essential utility systems of a production facility.
EMMS
An Electronic Maintenance Management System, presently Immpower.
Failure on Demand
The designed function fails to respond to a plant condition or event requiring the Instrumented
Protective Function to take action to prevent a Hazard.
Final Element
A device(s) that executes the output command(s) of an Instrument protector System (IPS)
logic solver to cause the process to attain a safe state. The Final Element includes output
cards or output relays, solenoid valves and cabling, as well as valves, pumps and alarms, etc.
Hazard
The potential to cause harm, including ill health and injury; damage to property, products or
the environment; production losses or increased liabilities.
Initiator
A device(s) that measures a process variable and indicates whether a process or piece of
equipment operates outside the specified operating envelope. The Initiator includes input
cards and/or input relays as well as the manual switches, position switches and measurement
systems, (including process connections, sensors, transmitters, cabling, trip amplifier or input
card, etc.).
Instrumented Protective Function (IPF)
A function composed of Initiator(s), an Instrumented Protective System and one or more Final
Elements for the purpose of preventing Hazards.
Instrumented Protective System (IPS)
The pneumatic, relay or electronic logic solver component of the Instrumented Protective
Function complete with input and output equipment.
Instrumented Safeguarding System
The terminology used for a shutdown system designed to operate automatically in case of a
prescribed hazardous event, (collective term for all IPFs within a facility).
Maintenance Over-ride Switches (MOS)
A MOS over-rides an Initiator(s) to enable maintenance or on-line functional Testing without
causing a Trip.
Machine Protection
Protection level below the process protection level specifically for the protection of a unit such
as a gas compressor set or oil transfer pump set and comprises protection for e.g. luboil
pressure, vibration, motor winding temperature, etc.
APPENDIX 6
Operating maintenance Staff
The following operating maintenance staff have been referenced in this document
The following are a list of referenced documents used within this Manual