AC Distribution Board Wiring for Inverter


feeding split circuits - Essential loads only

www.solarspot.co.za

Inverter
AC Surge Main Export Change-over Switch Pre- Post-
Arrester Switch Blocking Inverter Inverter
Relay * Isolator Isolator
2-pole 2-pole Highly recommended
MCB * for quick restoration 2-pole 2-pole
* Required of direct grid supply MCB MCB
Surge Arresters Required for some in the event of
on all SSEG inverter failure
inverters registra-
for tion
warranty
validity MCB's Relays Changeover Switches MCB's Inverters MCB's

Earth Load Load Load Earth Load Load Load


Leakage / MCB MCB MCB Leakage / MCB MCB MCB
Residual 1-pole 1-pole 1-pole Residual 1-pole 1-pole 1-pole
Current or 2- or 2- or 2- Current or 2- or 2- or 2-
Relay pole pole pole Relay pole pole pole
© Copyright,
5D Innovations cc, 2022

Earth Earth
Leakage Leakage
Non-essential Loads Essential Loads
fed from Grid only fed via Inverter
Disclaimer: This wiring diagram is used entirely at own dicretion and own risk. 5D Innovations cc TA Solar Spot shall not be held responsible for any death, injuries, damages or losses. If discrepancies
exist, SANS 10142 shall take preference, and the stricter of SANS 10142 and product user manual shall apply