Professional Documents
Culture Documents
useful information
useful information
Size
1 0.75 2.5 2 1
2 1.5 5 4 2
3 2.2 7.5 6 3
4 3 10 8 4
5 3.7 12.5 10 5
6 4.5 15 12 6
10 7.5 25 20 10
15 11 37.5 30 15
20 15 50 40 20
25 19.6 60.5 50 25
30 22 75 60 30
40 30 100 80 40
50 37 125 100 50
60 45 150 120 60
75 55 187.5 150 75
1. Ability to provide real power required by motor = Motor rated kW. The prime mover (the engine) only provides
real power, kW. KW demand during a motor starting is very low as the power factor is about 0.2.
2. Ability to provide starting kVA for the motor. This is the function of the alternator size.
a. For full voltage (DOL) starting, starting kVA= 6*rated kVAod the motor . Use the nameplate LRA data or Code
letter where available.
b. For Star/delta starting, starting kVA = 2*rated kVA of the motor. (In otherwords, in star connection the starting
current will be 1/3 of the DOL starting (LRA))
c. For any other reduced voltage starting the starting current and torque will be reduced by the square of the
voltage reduction.
d. So obviously one must strive to use reduced voltage starting on a generator, as long as the starting torque
requirements can be meet.
a. While a motor by itself could tolerate 30% to 35% of voltage dip during the start, it could cause starter coil to
drop out. Plus consideration should be given to effect on other systems on the generator such as lighting. Therefore
more realistic value of acceptable voltage dip will be say about 15 to 20%.
b. For finding the per unit voltage drop by calculation you need to know the transient reactances of the generator
(usually 15-20%) and the motor (usually 20-25%).
Rules of Thumb:
Most generators are capable of delivering 300% of the rated current for 10 seconds, which is sufficient time for
most induction motors to get up to the rated speed. So for DOL starting a generator rated 2 to 3 times the kVA of
the motor will easily supply the starting kVA of the motor and for a star/delta start even a generator sized just above
the rated motor kVA will be sufficient. These rules of thumb generally result in generator size that will keep the
voltage dip during the motor starting within acceptable limit.
IEEE red book have some curves indicating voltage at the motor terminals as percentage of the rated voltage for
DOL starting of various size motors.
Of course for more accurate analysis you need to perform some detailed calculations.
Practical Issues:
Theoretically it is possible to show that for most cases a 600kW/750HP motor with a star/delta starter can
satisfactorily be started on an 800kW/1000kVA generator set (800kW engine and 800kW/1000kVA generator).
Or for a DOL starting, an engine-generator set with 800kW engine and 2250kVA rated alternator will suffice. The
problem is that it will be a non-standard set. Most generators set manufacture will not customize their engine-
generator set. So chances are most users will end-up with an 1800kW/2250kVA generator for a 600kW motor,
technically way oversized.
إذا ﻛﺎن اﻟﺣﻣل ﻋﻠﻰ وﺣدة اﻟﺗوﻟﯾد ھو ﻣﺣرك واﺣد ﻛﺑﯾر ،ﻻ ﺳﯾﻣﺎ إذا ﻛﺎن ذﻟك اﻟﻣﺣرك ﯾﺗطﻠب ﻋزم دوران اﻧطﻼق ﻋﺎﻟﻲ high starting
)torqueﻛﺿﺎﻏطﺔ ھواء ﻣﺛﻼ( ،ﯾﻣﻛن أن ﯾﺣدث ﻋددا ﻣن اﻟﻣﺷﺎﻛل .
وھﻲ ﺗﺷﻣل:
•ﻋﻣﻠﯾﺔ ﻣﺳﺗﻣرة ﺑﺟﮭد ﻛﮭرﺑﺎﺋﻲ ﻣﻧﺧﻔض sustained low-voltage operationواﻟﺗﻲ ﯾﻣﻛن أن ﺗﺳﺑب ﻓﻲ ارﺗﻔﺎع درﺟﺔ اﻟﺣرارة.
•زﯾﺎدة ﻓﺗرة ﺗﺳﺎرع اﻟﺣﻣل ﻣرات ﻋدﯾدةextended load acceleration times .
•اﻧﻔﺗﺎح( اﻧﻌﺗﺎق ) Opiningﻗواطﻊ اﻟدواﺋر اﻟﻛﮭرﺑﺎﺋﯾﺔ أو أﺟﮭزة ﺣﻣﺎﯾﺔ اﻟﻣﺣرﻛﺎت.
•اﺷﺗﻐﺎل )أي ﻋﻣل و ﻏﻠﻖ( ﺣﻣﺎﯾﺔ ﻣﺣرك )اﻟدﯾزل ﻣﺛﻼ( اﻟﻣوﻟدة ،أي ﺗوﻗف وﺣدة اﻟﺗوﻟﯾد.
•وأﻛﺛر ﻣن ذﻟك .
ﻗدرة وﺣدة اﻟﺗوﻟﯾد ﻟﺑدء ﺗﺷﻐﯾل اﻟﻣﺣرﻛﺎت اﻟﻛﺑﯾرة دون ھﺑوط ﻣﻔرط ﻟﻠﺟﮭد و ﺗراﺟﻊ )ھﺑوط( ﻟﻠﺗردد )اﻟذﺑذﺑﺔ( ھﻲ وظﯾﻔﺔ ﻟﻧظﺎم ﻣﺗﻛﺎﻣل ،وھذا
ﯾﺷﻣل:
•ﺗوﻓر واﺗﺎﺣﺔ ﻗوة ﻣﺣرك وﺣدة اﻟﺗوﻟﯾدThe engine power available.
•ﻗدرة اﻟﻣوﻟدThe generator's capacity .
•اﺳﺗﺟﺎﺑﺔ ﻧظﺎم إﺛﺎرة اﻟﻣوﻟدThe response of the generator excitation system .
•اﻟطﺎﻗﺔ اﻟﻣﺧزﻧﺔ ﻓﻲ دوار وﺣدة اﻟﺗوﻟﯾد )اﻟﻘوة اﻟطﺎردة اﻟدوارة( The energy stored in the rotating inertia of the
gen-set .
•ﺗﺳﺎرع اﻟﻣﺣرك وﺣﻣوﻟﺗﮫThe acceleration of the motor and its load.
ﯾﺟب أن ﻧﻧظر ﻓﻲ ﺟﻣﯾﻊ ھذه اﻟﻌواﻣل ﻟﻠﺗﺣﺟﯾم اﻟﺳﻠﯾم ﻟوﺣدة اﻟﺗوﻟﯾد ﻣﺟﻣوﻋﺔ ،و ھﻧﺎ ﻗﺎﻋدة ﺑﺳﯾطﺔ ﻟﺗﻘدﯾر ﺣﺟم ﻣﺣرك وﺣدة اﻟﺗوﻟﯾد ﻟﺑدأ ﺗﺷﻐﯾل
ﻣﺣرك ﻛﮭرﺑﺎﺋﻲ 1 :ﻛﯾﻠو واط ﻣن ﻗدرة اﻟﻣوﻟد ﻟﻛل 4/3اﻟﻰ 1ﺣﺻﺎن ﻣن اﻟﻘدرة اﻷﺳﻣﯾﺔ )ﻣن ﻟوﺣﺔ اﻟﻣﺣرك( kW of generator 1
set rating per each 3/4 to 1 hp of motor nameplate.
•ﯾﺟب ﻋﻠﻰ اﻟﻣﺣرك ﺗطوﯾر ﻋزم دوران أﻛﺑر ﻣﻣﺎ ھو ﻣطﻠوب ﻣن ﻗﺑل اﻟﺣﻣل .ﻣﻧﺣﻧﻰ ﻋزم اﻟدوران ﻟﻠﻣﺣرك و ﺑﺎﻟﺟﮭد اﻟﻛﺎﻣل full
voltageھو ﻓوق ﻣﻧﺣﻧﻰ ﻋزم اﻟدوران اﻟﺣﻣل .
ﯾﺣدد ﻣﻌدل اﻟﺗﺳﺎرع ﻣن اﻟﻔرق ﺑﯾن ﻋزم اﻟدوران اﻟﻣﺗﻛون ﻓﻲ اﻟﻣﺣرك وﻋزم اﻟدوران اﻟﻣطﻠوﺑﺔ ﻣن ﻗﺑل اﻟﺣﻣل .
ﺣﯾث ﻋزم اﻟدوران ﯾﺗﻧﺎﺳب ﻣﻊ اﻟﺟﮭد ،ﻓﺄي ﺗﺧﻔﯾض ﻓﻲ اﻟﺟﮭد ﯾﻌﻧﻲ ﺗﺧﻔﯾض ﺗﻧﺎﺳﺑﻲ ﻓﻲ ﻋزم اﻟدوران .
•ﯾدﻋم ﺣﺟم وﺣدات اﻟﺗوﻟﯾد اﻟﺻﺣﯾﺢ )اﻟﻣﺣﺳوب ﺑﺻورة ﺻﺣﯾﺣﺔ( ﻣﺗطﻠﺑﺎت اﻟﻛﯾﻠو ﻓوﻟت أﻣﺑﯾر KVAاﻟﻌﺎﻟﯾﺔ ﻟﻠﻣﺣرك ،وﻟﻠﺣﻔﺎظ ﻋﻠﻰ ﻣﺎ ﯾﻛﻔﻲ
ﻣن اﻟﺟﮭد اﻟﻧﺎﺗﺞ ﻟﻠﻣﺣرك ،ﻟذﻟك ﯾﻣﻛن ﺗطوﯾر ﻋزم دوران ﻛﺎف ﻟﺗﺳرﯾﻊ ﺗﺣﻣﯾل اﻟﻣﺣرك إﻟﻰ ﺳرﻋﺗﮫ اﻷﺳﻣﯾﺔ.
ﺗﺳﺗﺧدم ﻛل وﺣدات اﻟﺗوﻟﯾد اﻟﻛﮭرﺑﺎﺋﻲ ﻣوﻟدات ﻣﺗزاﻣﻧﺔ ﻣﻊ ﻣﮭﯾﺞ ﻟﻸﺛﺎرة synchronous generators with exciters .
اﻟﻌدﯾد ﻣﻧﮭﺎ ﺗﺗوﻓر ﻣﻊ ﻣﻐﻧﺎطﯾس داﺋﻣﻲ ﺛﺎﺑت ) (PMGﻛﻧظﺎم ﻟﻺﺛﺎرة ،و اﻟﻣﻐﻧﺎطﯾس اﻟداﺋﻣﻲ PMGﯾوﻓر طﺎﻗﺔ إﺛﺎرة ﻣﺳﺗﻘﻠﺔ ﻟﻠﻣوﻟد ﻋن اﻟﺟﮭد
ﻓﻲ ﻧﻘﺎط اﻻﺗﺻﺎل terminal voltage.
ﻋﻠﻰ ھذا اﻟﻧﺣو ،ﻓﺈﻧﮫ ﯾﻣﻛن اﻟﺣﻔﺎظ ﻋﻠﻰ اﻹﺛﺎرة ﻛﺎﻣﻠﺔ :ﺣﺗﻰ أﺛﻧﺎء اﻟﺗﺣﻣﯾل اﻟﻌﺎﺑر ، transient loadingﻣﺛل ﺗﺷﻐﯾل اﻟﻣﺣرك .
ﻧﺎﺗﺞ ﻛﺎﻣل ﻗوة اﻹﺛﺎرة ھو أﻗل اﺗﺳﺎع ﻟﺗراﺟﻊ اﻟﺟﮭد )اﻧﺧﻔﺎض اﻟﻔوﻟﺗﯾﺔ( voltage dipو ﺗﺣﺳﯾن وﻗت اﻻﻧﺗﻌﺎش.
اﯾﺿﺎ اﺳﺗﺧدام ﻣﺣدد اﻟﺗﯾﺎر ﯾﻘﻠل ﻣن ﻋزم دوران اﻟﻣﺣرك اﻟﻣﺗﺎح ﻟﻠﺗﺣﻣﯾل ،و اﻟﺣد واﻟﺗﻘﻠﯾل ﻣن وﻗت ﺗﯾﺎر اﻟﺗﺳﺎرع ﻟﻠﻣﺣرك وﻣن ﺷﺄﻧﮫ أن ﯾؤدي اﻟﻰ
اﻟﺟﮭد اﻷﻗل least voltageو رﺣﻼت اﻟﺗردد frequency excursions.
اﺣد اﻟﺳﻠﺑﯾﺎت اﺳﺗﺧدام اﻟﺑﺎدئ اﻹﻟﻛﺗروﻧﻲ وھو ان SCRsﺗﺳﺑب ﺗﺷوﯾﮫ ﻟﻠﺟﮭد ،وﻟﻠﺗﻌوﯾض ،ﺳﯾﻛون ﻟزاﻣﻧﺎ اﺳﺗﺧدام وﺣدة ﺗوﻟﯾد ﺑﻣوﻟدة أﻛﺑر
ﺣﺟﻣﺎ.
و اﻟﺗوﺻﯾﺔ :ﻣرﺗﯾن ﺗﺷﻐﯾل اﻟﺣﻣل ﻛﯾﻠوواط ،إﻻ إذا اﺳﺗﺧدم ﺗﺟﺎوز ﺗﻠﻘﺎﺋﻲ automatic bypass.
إذا ﻛﺎن ﻟﻠﺑﺎدئ اﻹﻟﻛﺗروﻧﻲ ﺗﺟﺎوز ﺗﻠﻘﺎﺋﻲ ﻓﺳﯾﻛون SCRsھﻲ ﻓﻘط ﻓﻲ اﻟداﺋرة أﺛﻧﺎء اﻻﻧطﻼق ،وﺑﻣﺟرد أن ﯾﺗم ﺗﺷﻐﯾل اﻟﻣﺣرك ،وﯾﻐﻠﻖ اﻟﻣﻔﺗﺎح
ﻓﺳﯾﺗم ﺗﺣﺎوز ، SCRsوﻓﻲ ھذه اﻟﺣﺎﻟﺔ ،ﯾﻣﻛن ﺗﺟﺎھل ﺗﺷوﯾﮫ اﻟﺗﯾﺎر اﻟﻛﮭرﺑﺎﺋﻲ ﺧﻼل اﻧطﻼق ،وﻋﻧدھﺎ ﻻ داﻋﻲ ﻹﺿﺎﻓﺔ ﺳﻌﺔ )ﺗﻛﺑﯾر( ﻟﻠﻣوﻟدة .
ﻟﺣﺳﺎب اﻧطﻼق ﻛﯾﻠوﻓوﻟت أﻣﺑﯾر ) (SkVAواﻟﺑدء ﻛﯾﻠووات ) (SKWﻟﻠﻣﺣرﻛﺎت ،اﺳﺗﺧدام ھذه اﻟﻣﻌﺎدﻻت :
اﻟﺧطوة : 2
اﻟﻣﺷﺎرﻛﺎت ﻓﻲSKW ،RkVA ، RKWوأرﻗﺎم SkVAﻟﺟﻣﯾﻊ اﻷﺣﻣﺎل .
اﻟﺧطوة : 3
اﺧﺗﯾﺎر وﺗﺣدﯾد وﺣدة اﻟﺗوﻟﯾد
ﺑﻣﻘﺎرﻧﺔ ،SKW ،RkVA ، RKWو SkVAﻟﺗﻘﯾﯾﻣﺎت ﻋﻠﻰ ورﻗﺔ ﻣواﺻﻔﺎت اﻟﺷرﻛﺔ اﻟﻣﺻﻧﻌﺔ )ﺑﻌد اﻟﺗﺧﻔﯾﺿﺎت اﻟﻣﻧﺎﺳﺑﺔ ﻟدرﺟﺔ اﻟﺣرارة
اﻟﻣﺣﯾطﺔ واﻻرﺗﻔﺎع( .
To calculate starting kilovolt-amperes (SkVA) and starting kilowatts (SkW) for motors,
use these equations:
Step 2:
Total the RkW, RkVA, SkW, and SkVA numbers for all the loads.
Step 3:
Select the gen-set by comparing the RkW, RkVA, SkW, and SkVA to the ratings on the
manufacturer's specification sheets (after appropriate derating for ambient temperature
and altitude).
1 ﻣﺛﺎل
Determine gen-set size for three loads started across-the-line in a single step.
:اﻟﻣﻌﻠوﻣﺎت اﻟﺛﺎﺑﺗﺔ و اﻟﻣﺗوﻓرة
Here's pertinent information:
• Two 200 hp motors, Code G, 92% running efficiency, 0.25 starting PF, 0.91 running
PF.
• Total 100kVA of fluorescent lighting, starting PF of 0.95, and running PF of 0.95
، ﻓﻲ اﻟواﻗﻊ. ﻋﻧد إﺿﺎﻓﺔ اﻷﺣﻣﺎل اﻟﺣرﻛﯾﺔ،، ھﻧﺎ ﻟﻠﺗوﺿﯾﺢ اﺳﺗﺧدم ﻣﺻطﻠﺣﻲ ﻣﻌﺎﻣل ﻗدرة ﺑدء ﺗﺷﻐﯾل و اﻟﺗﺷﻐﯾل ﻷﺣﻣﺎل اﻹﺿﺎءة:( •ﻣﻼﺣظﺔ
Note: We're using the terms ،،، أي،،، 0.95 اﻟﻣﻠف اﻟﺧﺎﻧﻖ واﻟﺻﺎﺑورة ﻷﺣﻣﺎل اﻹﺿﺎءة ﻟﮫ ﻣﻌﺎﻣل ﻗدرة ﺛﺎﺑت وھو
starting and running PF for the lighting load here for clarification when adding the motor
loads. Actually, the ballast for the lighting load has a constant PF of 0.95 ) .
Step 3:
Selection.
At a minimum, the gen-set size to supply the maximum starting (surge) demands and
the steady-state running loads of the connected load equipment. In this example (using
one manufacturer's published data),,,
Select a 750kW generator set with 2944 SkVA available at 90% recovery voltage to
supply the total load SkVA of 2460.
The load totals for RkW, RkVA, and SkW are well within the rating of the 750kW
(938kVA) gen-set you selected.
The running kilowatt load of 420kW is 56% of the 750kW gen-set standby rating.
2 ﻣﺛﺎل
auto-transformer وﻟﻛن اﻵن اﺳﺗﺧدم ﺑﺎدئ ﺗﺷﻐﯾل ﺑﻣﺣول ذاﺗﻲ، 1 ﻟﻧﻔﺗرض أن ﻟدﯾﻧﺎ ﻧﻔس اﻷﺣﻣﺎل اﻟﺛﻼﺛﺔ ﻛﻣﺎ ھو اﻟﺣﺎل ﻓﻲ ﻣﺛﺎل
. ﺑداﯾﺔ اﻟﺟﮭد ﻟﺑدء ﺗﺷﻐﯾل اﻟﻣﺣرﻛﯾن٪65 ﻟﺧﻔض اﻟﺟﮭد اﻟﺗﻲ ﺗم ﺗﻌﯾﯾﻧﮭﺎ ﻓﻲ
you have the same three loads as in example One, but now you're using an ،،،، أي
autotransformer type reduced voltage starter that is set at the 65% starting voltage to
start the two motors. This tap setting will reduce the starting kVA by the square of the
voltage (0.65)squared, or 0.42 times the starting kVA .
:اﻟﺣﺳﺎﺑﺎت
Step 1: Calculations
200 HP motor:
RkW = (200 hp x 0.746 kW/hp) / 0.92 = 162.2kW
RkVA = 162.2kW / 0.91 PF = 178.2kVA
SkVA = 200 hp x 5.9 kVA/hp = 1180 x (0.65)squared = 495kVA
SkW = 495kVA x 0.25 PF = 124kW
Florescent Lighting:
RkW = 100kVA x 0.95 PF = 95kW
RkVA = 100kVA
SkVA = 100kVA
SkW = 100kVA x 0.95 PF = 95kW
Step 2: Totals
Load.......... | RkW.. | RkVA | SkW | SkVA
200hp Motor | 162.2 | 178.2. | 124. | 495
200hp Motor | 162.2 | 178.2. | 124. | 495
Lighting...... | 95..... | 100... | 95... | 100
Totals (kVA) | 420... | 457... | 343. | 1090
Step 3: Selection. Using one manufacturer's published data, you would select a 450kW
gen-set to supply the required starting kVA. The running kilowatt load of 420kW is 93%
of the gen-set's standby rating. So, if you want a margin for future load additions, you
would select a 500kW gen-set running at 84% of rated standby power.
ﻋﺎدة ،ﺳوف ﯾﻛون ھﺑوط ﺟﮭد اﻷﻋﻠﻰ ﻟﻸطراف ﺑﻧﺳﺑﺔ ٪30ﻻ ﯾﺳﺑب ﻟﻠﻔﺎﺋف ﻟﻠﮭﺑوط وھذا ﯾﺳﻣﺢ ﻟﺣواﻟﻲ ٪5اﻧﺧﻔﺎض إﺿﺎﻓﻲ ﻟﻠﺟﮭد ﻓﻲ
اﻟﻣوﺻﻼت ﺑﯾن اﻟﻣوﻟدة واﻟﻣﺣرك .
ﻋﻠﻰ اﻟرﻏم ﻣن أن ھﺑوط اﻟﺟﮭد ﯾرﺟﻊ ذﻟك إﻟﻰ ﺣﻣﺎﯾﺔ ﺗﺣت ﺗردد ، under frequency protectionوﻗد ﯾﻣﺗد اﻟوﻗت ﻣن اﺳﺗﻌﺎدة اﻟﺟﮭد
،ﻛﻣﺎ أﻧﮫ ﯾﺳﻣﺢ ﻟﻠﻣﺣرك إﻟﻰ اﻟﺣﺟم أﻗرب إﻟﻰ اﻟﺣﺎﻟﺔ اﻟﻣﺳﺗﻘرة ﺗﺷﻐﯾل اﻟﺣﻣل ﺑدﻻ ﻣن اﻟﺑدء اﻟﺣﻣل .
وھذا أﻣر ﻣﮭم ﻻ ﺳﯾﻣﺎ ﻣﻊ ﻣﺣرﻛﺎت اﻟدﯾزل ،واﻟﺗﻲ ﻻ ﯾﻧﺑﻐﻲ أن ﯾﺷﻐل ﻧﻔﺳﮫ ﻟﻣدة طوﯾﻠﺔ ﻓﻲ أﻗل ﻣن ٪30ﻣن ﺣﻣوﻟﺗﮫ اﻟﻣﻘﻧﻧﺔ .
اﻟﺗوﺳﻊ ﻓﻲ ﻣﺛل ھذه اﻟﻌﻣﻠﯾﺔ ﻋﻠﻰ ﻣﺣرك اﻟدﯾزل ﻓذﻟك ﯾﻣﻛن أن ﯾؤدي إﻟﻰ ﺗراﻛم اﻟوﻗود ﻏﯾر اﻟﻣﺣﺗرق ﻓﻲ ﻧظﺎم اﻟﻌﺎدم ،وذﻟك ﺑﺳﺑب اﻻﺣﺗراق ﻏﯾر
اﻟﻛﺎﻣل ﻣن درﺟﺎت ﺣرارة اﻻﺣﺗراق ﻣﻧﺧﻔﺿﺔ ،ﻋﻣﻠﯾﺔ اﻟﺗﺣﻣﯾل اﻟﺧﻔﯾﻔﺔ ﯾﻣﻛن أن ﺗؤدي أﯾﺿﺎ إﻟﻰ ﺗﻠف اﻟﻣﺣرك ﻣن اﻟوﻗود واﻟﻣﯾﺎه اﻟﻣﻠوﺛﺔ وزﯾوت
اﻟﺗﺷﺣﯾم.
ﺑﻌد ھﺑوط اﻟﺟﮭد اﻷوﻟﯾﺔ ،ﻓﺈﻧﮫ ﻣن اﻟﻣﮭم ﻟﻠﻣوﻟدة اﺳﺗﻌﺎدة اﻟﺟﮭد إﻟﻰ اﻟﺣد اﻷدﻧﻰ ﻣن ٪90ﻣن اﻟﻘﯾﻣﺔ اﻷﺳﻣﯾﺔ ﻓﻲ ﺣﯾن ﺗزوﯾد اﻟﻣﺣرﻛﺎت ﺑﻛﯾﻠو ﻓوﻟت
أﻣﺑﯾر اﻟﺑدء ٪90 ،ﻋﻠﻰ اﻷﻗل ﻣن اﺳﺗﻌﺎدة اﻟﺟﮭد اﻟﺿروري ﻟﻠﻣﺣرك ﻟﺗطوﯾر ﻋزم دوران ﻛﺎف ﻟﺗﺳرﯾﻊ ﺣﻣوﻟﺗﮫ إﻟﻰ اﻟﺳرﻋﺔ اﻷﺳﻣﯾﺔ .
ﺑدء واﻧطﻼق ﻣﺣرك ﺑﺣﻣوﻟﺔ ﻋزم اﻟدوران ﻋﺎﻟﯾﺔ ،ﻣﺛل ﺿﺎﻏط ﺗﺣﻣﯾل وھذا ﯾﺗطﻠب ﺟﮭد اﻧﺗﻌﺎش ﻋﺎﻟﻲ ﻣﻊ ﺑدء اﻟﺿﺎﻏطﺔ وھﻲ ﻏﯾر ﻣﺣﻣﻠﺔ
،unloaded compressorوﻛﻠﻣﺎ ﯾﺄﺗﻲ اﻟﻣﺣرك ﻟﯾﺻل إﻟﻰ ﺳرﻋﺗﮫ ،ﺳوف ﯾرﺗﻔﻊ اﻟﺟﮭد ،ﻛﻣﺎ ﯾﻘﻠل ﻣن دﺧل ﺑدء ﻛﯾﻠو ﻓوﻟت أﻣﺑﯾر ،
وﺑﻣﺟرد أن اﻟﻣﺣرك ﯾﺻل اﻟﻰ ﺳرﻋﺔ ،ﯾﻧﺑﻐﻲ ﻟﻠﺟﮭد اﻟﻌودة إﻟﻰ اﻟﻘﯾﻣﺔ اﻟﻣﻘﻧﻧﺔ ،إذا ﻛﺎن ﺣﺟم وﺣدة اﻟﺗوﻟﯾد ﻣﺣﺳوب ﺑﺷﻛل ﺻﺣﯾﺢ .
ﻣﻌﻠوﻣﺔ ﺟﺎﻧﺑﯾﺔ :ﻛﯾف ﯾؤﺛر اﻟﺟﻣود ﻋﻠﻰ وﺣدة اﻟﺗوﻟﯾدHow Inertia Affects Gen-Set Sizing
ﺗﻘدم ﻟﺣظﺔ ﺟﻣود ﻛﺗﻠﺔ اﻟدوارة اﻟﻣﻘﺎوﻣﺔ إﻟﻰ اﻟﺗﺳﺎرع .اﻟﺣﻣل اﻟﻣﺗﺻل اﻟﻰ ﺷﻔت اﻟﻣﺣرك ﻟدﯾﮫ ﻟﺣظﺎﺗﮫ ﻣن اﻟﺟﻣود ،وﻓﻲ ﺣﺎﻻت ﻋﻣﻠﯾﺔ ﻟﻣﻌدات ﻣﻌﯾﻧﺔ
،وھذا ﻗد أو ﻗد ﻻ ﺗﻛون ﻋﮫ اﻟﻣﻌﻠوﻣﺎت اﻟﻣﺗﺎﺣﺔ .
ﻟﺣﺳن اﻟﺣظ ،ﻟﻐرض ﺗﺣﺟﯾم وﺣدة اﻟﺗوﻟﯾد ،أو ﺑﺷﻛل أﻛﺛر ﺗﺣدﯾدا ،ﻟﺗﺣدﯾد ﻗوة اﻟﻣﺣرك اﻟﻼزﻣﺔ ﻟﺑدء وﺗﺳرﯾﻊ ﺗدوﯾر ﺣﻣوﻟﺔ اﻟﻣﺣرك ،ﻟﺣظﺔ
اﻟﺣﻣل ﻣوﺗور ﻣن اﻟﺟﻣود ﺗﺣﺗﺎج ﻓﻘط أن ﺗﺻﻧف ﻋﻠﻰ ﻧطﺎق واﺳﻊ ﻛﺄن اﻟﺟﻣود inertiaﻣﻧﺧﻔﺿﺔ أو ﻋﺎﻟﯾﺔ .
ﺗﺗﻣﯾز اﻷﺣﻣﺎل اﻟﺟﻣود ﻋﺎﻟﯾﺔ ﻣن ﻗﺑل ﻋزم دوران ﻋﺎﻟﯾﺔ اﻟﺗﻲ ﺗﺗطﻠب ﺗﺳرﯾﻊ ﻟﻔﺗرات طوﯾﻠﺔ ،ﺗﺗﻣﯾز اﻷﺣﻣﺎل اﻟﺟﻣود ﻣﻧﺧﻔﺿﺔ ﻋزم ﺑدء دوران
ﻣﻧﺧﻔض ﻣﻠﺻم ،ﻣﻊ زﯾﺎدة ﻋزم اﻟدوران ﻋﻧد ﺳرﻋﺔ اﻟﻣﺣرك ﺗزﯾد ﻣﻣﺎ ﯾؤدى إﻟﻰ اﻟﺗﺳﺎرع إﻟﻰ ﺳرﻋﺔ اﻷﺳﻣﯾﺔ اﻟﻣﻘﻧﻧﺔ .
ﻣﻌﻠوﻣﺔ ﺟﺎﻧﺑﯾﺔ :أﻣﺛﻠﺔ ﻋن اﻟﺟﻣود اﻟﻌﺎﻟﯾﺔ واﻟﻣﻧﺧﻔﺿﺔExamples of High and Low Inertia
اﻷﺣﻣﺎل اﻟﺟﻣود اﻟﻌﺎﻟﯾﺔ وﺗﺷﻣل High inertia loads includeﻣﺎ ﯾﻠﻲ :
•ﻣﺿﺧﺎت أﺣﺎدﯾﺔ وﻣﺗﻌددة اﺳطواﻧﺔSingle- and multi-cylinder pumps
•ﺿواﻏط أﺣﺎدﯾﺔ وﻣﺗﻌددة اﺳطواﻧﺔ دون ﺻﻣﺎﻣﺎت ﺗﻔرﯾﻎ Single -and multi-cylinder compressors without
unloading valves
•اﻟﻛﺳﺎراتCrushers
•اﻟﻣﺻﺎﻋد اﻟﮭﯾدروﻟﯾﻛﯾﺔ دون ﺻﻣﺎﻣﺎت ﺗﻔرﯾﻎHydraulic elevators without unloading valves
ﻣﻼﺣظﺔ :اﻟﻣﺿﺧﺎت اﻟﺗﻲ ﺗﺑدأ ﻓﻲ ﺿﻐط ﻋﻠوي ﻋﺎﻟﻲ واﻟﻣراوح ﻛﺑﯾرة اﻟﻘطر أو ﻣراوح اﻧطﻼق ﻓﻲ ﻣﻧﺎطﻖ ﺗﻘﯾﯾد ﻋﺎﻟﯾﺔ ﯾﺟب أن ﺗﺻﻧف ﻋﻠﻰ أﻧﮭﺎ
ﻣن أﺣﻣﺎل اﻟﺟﻣود ﻋﺎﻟﯾﺔ.