Professional Documents
Culture Documents
1EE 8301 Elec.mach.PPT 1 Unit 2Transformer
1EE 8301 Elec.mach.PPT 1 Unit 2Transformer
1EE 8301 Elec.mach.PPT 1 Unit 2Transformer
Unit – II Transformer
Topic: Introduction and construction
P. RAMESH BABU
Faculty of Electrical and Electronics Engineering
Saranathan college of Engineering
Window
Limb
E1 = 4.44fФmax N1 volts (V2 / V1) = (E2 / E1) = (N2 / N1) = (I1 / I2) = K,
Transformation Ratio
E2 = 4.44fФmax N2 volts
5. Voltage ratings
a. up to 1.1 KV ---- Low voltage transformer
b. 1.1 kV to 11 kV -------- Medium voltage
c. greater than 11kV ----- High Voltage
6. Methods of Cooling
a. AN – Air Natural ; b. AB – Air Blast ; c. ON – Oil Natural ; d. OB – Oil
Blast ; e. OF - Forced Oil Cooling ; f. OFW - Oil and Water Cooled
7. Service conditions
a. Power Transformer
b. Distribution Transformer
Explosion vent
2. High Voltage Bushing – this is the terminals where the primary windings of
the transformer terminates and serves as an insulator from the transformer
tank. Its creapage distance is dependent on the voltage rating of the
transformer.
3. Low Voltage Bushing – like the high voltage bushing, this is the terminals
where the secondary windings of the transformer terminates and serves as
an insulator from the transformer tank. Low voltage bushing can be easily
distinguished from its high voltage counterpart since low voltage bushings are
usually smaller in size compared to the high voltage bushing.
6. Conservator Tank – An oil preservation system in which the oil in the main
tank is isolated from the atmosphere, over the temperature range specified, by
means of an auxiliary tank partly filled with oil and connected to the completely
filled main tank.
When the oil cools down, air from the atmosphere is drawn in to the
transformer. This is called breathing in of the transformer.
During the breathing process, the incoming air may consist of moisture and
dirt which should be removed in order to prevent any damage. Hence the air
is made to pass through the silica gel breather, which will absorb the moisture
in the air and ensures that only dry air enters in to the transformer. Silica gel
in the breather will be blue when installed and they turn to pink colour when
they absorb moisture which indicates the crystals should be replaced. These
breathers also have an oil cup fitted with, so that the dust particles get settled
in the cup.
SARANATHAN COLLEGE OF
9/21/2020 10
ENGINEERING/Dept. of EEE
Buchholz relay is used for the protection of
transformers from the faults occurring inside the
transformer. Short circuit faults such as inter turn
faults, incipient winding faults, and core faults may
occur due to the impulse breakdown of the insulating
oil or simply the transformer oil. Buchholz relay will
sense such faults and closes the alarm circuit.
SARANATHAN COLLEGE OF
9/21/2020 11
ENGINEERING/Dept. of EEE
9. Dehydrating Breather – Dehydrating
breathers are used to prevent the
normal moisture in the air from
coming in contact with the oil in
electrical equipment as the load or
temperature changes. This reduces
the degeneration of the oil and helps
maintain its insulation capability.
When used with conservator system
with a rubber air cell it reduces
moisture accumulation in the cell.
Some breathers are designed for
sealed tank transformers and breathe
only at pre-set pressure levels.
12. Control Panel – this houses all of the transformer’s monitoring devices terminals
and auxiliary devices including the terminals of the bushing current transformers and
cooling fans. Control panels are very useful especially when a remote control house is
needed to be constructed, this will serve as their connection point.
13. Surge Arresters – this type of arresters are placed right directly before and after the
transformer terminals in order to minimize the exposure of the transformer. Like any
other surge arresters, its purpose is to clip sudden voltage surge that can be damaging
to the winding of the transformer.
1.Core type : It has two limbs, two yokes and one window.
Around each limb half of LV and half of HV coil
is housed. It has only one magnetic circuit as
denoted by dotted lines in fig. Full value of flux
pass through both limbs and yokes. Since the
yokes do not have any windings around it, its area of
cross-section is little more than the limb to reduce the
flux density and hence magnetic losses
SARANATHAN COLLEGE OF
9/21/2020 14
ENGINEERING/Dept. of EEE
Фm/2
2. Shell type
Berry type transformer are similar to Shell type, only they have a distributed
magnetic circuit. This core construction is similar to spokes of wheel. The
number of magnetic flux path is more than 2. It has one centre limb around
which LV and HV windings are housed
SARANATHAN COLLEGE OF
9/21/2020 18
ENGINEERING/Dept. of EEE
(b) U & T sections and E & I sections for shell type
1. The winding encircles the core The core encircles most part of the The core encircles most part of the
winding winding
2. The cylindrical type of coils are used Multilayer disc type or sandwich Multilayer disc type or sandwich coils
coils are used are used
3. AS windings are distributed, the natural As windings are surrounded by the As windings are surrounded by the
cooling is more effective. core, the natural cooling does not core, the natural cooling does not exist.
exist.
4. The coils can be easily removed from For removing any winding for the For removing any winding for the
maintenance point of view maintenance, large numbers of maintenance, large numbers of
laminations are required to be laminations are required to be
removed. This is difficult. removed. This is difficult.
5. The construction is preferred for low The construction is preferred for The construction is preferred for high
voltage transformer ( i.e., Distribution high voltage transformer ( i.e., Large voltage transformer ( i.e., Large power
transformer) power transformer) transformer)
6. It has single magnetic circuit It has double magnetic circuit It has more than two magnetic circuit
S.No
Point of comparison Distribution transformer Power transformer
.
1. Capacity Up to 500 kVA Beyond 500kVA up to 500
MVA or more
2. Voltage Rating 11,22, or 33 kV/440 (3phase) 400kV/33kV; 220kV/11kV
etc.,
3. Connection for 3 phase Delta/star -3 phase ,4 wire Delta/Delta; Delta/Star,
system 3phase,3wire system
4. Load 100% for few hours, part of load Nearly on full load
for some time, no load for few
hours
5. Flux density Upto 1.5 Tesla with CROS Upto 1.5 Tesla with CROS
6. Current density Up to 2.6 A/mm2 Up to 3.3 A/mm2
7. Ratio of iron loss to cu.loss 1:3 (approx.) 1:1 (approx.)
8. Regulation 4 to 9% 6 to 10%
9. Cooling Self oil cooled Forced oil and fan cooled
SARANATHAN COLLEGE OF
9/21/2020 23
ENGINEERING/Dept. of EEE
Power transformer
SARANATHAN COLLEGE OF
9/21/2020 24
ENGINEERING/Dept. of EEE
Power transformer
SARANATHAN COLLEGE OF
9/21/2020 25
ENGINEERING/Dept. of EEE
Forced air and oil cooling
SARANATHAN COLLEGE OF
9/21/2020 26
ENGINEERING/Dept. of EEE
Distribution transformers
SARANATHAN COLLEGE OF
9/21/2020 27
ENGINEERING/Dept. of EEE
TANK
COOLING TUBES
SARANATHAN COLLEGE OF
9/21/2020 28
ENGINEERING/Dept. of EEE
SARANATHAN COLLEGE OF
9/21/2020 29
ENGINEERING/Dept. of EEE
Applications
1.Stepping up of voltage
Generally generating stations are situated far away from the consumers,
electrical energy is generated at a voltage of around 11kV,or 22kV. From
transmitting the power from generating stations to the place of use by
long transmission lines, it is more economical to raise the level of voltage
transmission to 220 kV to 440kV. This stepping up of voltage is carried out
by installing transformers.
2.Stepping down of voltage
HT consumers are provided with electric power at 11kV or 6.6kV, 3phase
and LT consumers are provided with electric power at 415 V , 3 phase. This
stepping down of voltage is carried out by installing transformers.
3. Instrument Extension
To measures high currents in the order of several hundred amps and
voltage of several kilo-volts, instrument transformers (CT and PT) are used
along with ammeters and voltmeters of lower range .
9/21/2020 SARANATHAN COLLEGE OF ENGINEERING/Dept. of EEE 30
4. Electrical Isolation
In transformer power is transferred from primary to secondary via
magnetic field. There is no conductive connection between the primary
and secondary.(i.e. Both windings are inductively connected through
core.)
SARANATHAN COLLEGE OF
9/21/2020 31
ENGINEERING/Dept. of EEE
5. Impedance matching
According to maximum power transfer
theorem, maximum power is transferred from
source to load only if load impedance is equal to
source impedance. In case the actual impedance
is not equal to source impedance, in between
source and load, a transformer can be used for
impedance matching. For example , loud
speakers being connected to amplifiers.
SARANATHAN COLLEGE OF
9/21/2020 32
ENGINEERING/Dept. of EEE
6. Link between AC and DC systems
SARANATHAN COLLEGE OF
9/21/2020 33
ENGINEERING/Dept. of EEE
Why transformer rating in kVA?
AS seen , cu. Loss of a transformer depends on
current and iron loss on voltage. Hence, total transformer
loss on volt-ampere (VA) and not on phase angle between
voltage and current i.e. it is independent of load power
factor. That is why rating of transformers is in kVA and not
in kW
SARANATHAN COLLEGE OF
9/21/2020 34
ENGINEERING/Dept. of EEE
What happen if a transformer connected to a DC source?
SARANATHAN COLLEGE OF
9/21/2020 35
ENGINEERING/Dept. of EEE