Division 083344 - OVERHEAD COILING FIRE CURTAINS
Division 083344 - OVERHEAD COILING FIRE CURTAINS
Division 083344 - OVERHEAD COILING FIRE CURTAINS
PART 1 - GENERAL
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
B. Related Requirements:
1. Division 26 Sections for electrical service and connections for motor operators,
controls, limit switches, and other powered devices and for system disconnect
switches for motorized shade operation.
2. Division 28 Sections for fire alarms.
1.4 COORDINATION
A. Coordinate fire- and smoke-protective curtain assemblies with power, signal, fire-alarm, and
smoke-detection systems specified in Division 26 and Division 28.
B. Coordinate fire- and smoke-protective curtain assemblies with ceilings for operational
clearances and maintenance access requirements.
C. Coordinate fire- and smoke-protective curtain assemblies with walls for support
requirements, rating continuity above ceilings, and recessed wall switches.
D. Coordinate requirements for metal supports required for fire- and smoke-protective curtain
assemblies.
A. Product Data: For each type of fire- and smoke-protective curtain assembly and fire door.
B. Shop Drawings:
C. Product Schedule: For fire-protective curtain assemblies. Use same designations indicated
on Drawings.
D. Product Test Reports: Submit test report by an approved testing laboratory for each type of
fire curtain product. Test report shall include manufacturer name and contacts in addition to
tested product name and detailed description.
B. Evaluation Reports: For curtain assemblies, from ICC-ES or other qualified testing agency.
A. Comply with applicable requirements of the Laws, Codes, and Regulations of Authorities
Having Jurisdiction and requirements of Saudi Building Code, Latest Version.
B. Installer Qualifications: An entity that employs installers and supervisors who are trained
and approved by manufacturer for both installation and maintenance of units required for
this Project.
C. Testing Agency Qualifications: Qualified according to ASTM E329, ISO/IEC 17011 and
ISO/IEC 17025 acceptable to Engineer and Authorities Having Jurisdiction, that has the
experience and capability to satisfactorily conduct the testing indicated.
D. Mockups: Build mockups to verify selections made under sample Submittals and to
demonstrate aesthetic effects and qualities of materials and execution.
1. Build mockups in the location and of the size indicated or, if not indicated, as directed
by Engineer.
2. Approved mockups may become part of the completed Work if undisturbed at time of
Substantial Completion.
1.11 WARRANTY
A. General Warranty: The special warranty specified in this Article shall not deprive Employer
of other rights Employer may have under other provisions of the Contract Documents and
shall be in addition to, and run concurrent with, other warranties made by Contractor under
requirements of the Contract Documents.
B. Special Warranty: Provide complete system warranty in which Manufacturer Installer and
Contractor are jointly and severally responsible and agree to repair or replace, without
limitations, all or any part of the fire curtains system which fails or becomes defective in
materials or workmanship within specified warranty period.
PART 2 - PRODUCTS
A. Source Limitations: Obtain fire-protective curtains from single source from single
manufacturer.
A. Fire-Protective Curtain Assemblies: Complying with NFPA 80; listed and labeled by
qualified testing agency, for fire-protection ratings indicated, based on testing at as close to
neutral pressure as possible in accordance with UL 10D.
1. Oversize Rated Curtain Assemblies: For units exceeding sizes of tested assemblies,
provide certification by a qualified testing agency that curtain assemblies comply
with standard construction requirements for tested and labeled fire-rated curtain
assemblies, except for size.
2. Smoke Control: Provide smoke- and fire-protective curtain assemblies that are listed
and labeled with the letter "S" on the rating label by a qualified testing agency for
smoke- and draft-control based on testing in accordance with UL 1784.
B. Curtain Fabric Fire-Test-Response Characteristics: Provide products that pass NFPA 701, as
determined by testing of fabrics that were treated using treatment-application method
intended for use for this Project by a testing and inspecting agency acceptable to authorities
having jurisdiction.
B. General:
C. Fire-Resistance Ratings: Comply with ASTM E119 (without hose stream test); testing by a
qualified testing agency. Identify products with appropriate markings of applicable testing
agency.
1. Replaceable fusible links with temperature rise and melting point of 74 deg C
interconnected and mounted on both sides of door opening.
2. Manufacturer's standard UL-labeled smoke detector and door-holder-release devices.
3. Manufacturer's standard UL-labeled heat detector and door-holder-release devices.
4. Building fire-detection, smoke-detection, and fire-alarm systems.
G. Push-to-Exit Button: Button briefly opens curtain to allow emergency egress and
automatically recloses curtain after a set period of time.
I. Curtain: Manufacturer's standard multilayer glass-fiber fabric woven with stainless steel
wires and coated on one or both sides.
K. Motor Operator: Provide factory-assembled electric operation system of size and capacity
recommended by curtain manufacturer for assembly specified, with electric motors and
factory-prewired motor controls, control devices, and accessories required for proper
operation.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine substrates, areas, and conditions, with Installer present, for compliance with
requirements for substrate construction and other conditions affecting performance of the
Work.
C. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 INSTALLATION
C. Install anchorage devices to securely fasten assembly to substrate and building framing
without distortion or stress.
E. Fit and align assembly, including vertical guides, level and plumb, to provide smooth
operation.
3.3 DEMONSTRATION