Professional Documents
Culture Documents
IJHR-2403-1000(R3)
IJHR-2403-1000(R3)
IJHR-2403-1000(R3)
Cite this article: Ali H. Kasem Alaboudy, Heba A. Mahmoud, Adel A. Elbaset, Montaser Abdelsattar,” LVRT Capability Enhancement of Grid-
Connected DFIG Wind Turbines using Series Resistor “, International Journal for Holistic Research, Vol. 1, No. 1. June 2024.
DOI: 10.21608/ijhr.2024.290318.1014
1
International Journal for Holistic Research, Vol. 1, No. 1. June 2024
of the proposed controllers are to decrease the rotor current properties of a DFIG can be enhanced further when two
and inhibit the DC-link voltage. In Ref. [14], scholars devices with distinct functionalities are used together.
investigate an analytical method to determine the control Thus, it is important to continue this type of research and
parameters of the DFIG subject to the capacity limit of the investigate new combination scheme with better potential.
RSC. Overall, the transient stability support from the Additionally, using one or more expensive devices that can
software solutions towards the DFIG may be relatively effectively handle severe short-circuit problems is the
moderate, and the improvements of optimizing current hardware answer. This paper proposes a protection scheme
reference and introducing over-modulation could be using the Series Resistor to improve the LVRT capacity for
appreciatively done, the software solution is regarding an the Grid-Connected DFIG Wind Turbines. The protection
improved or updated control strategy with less cost, but it scheme ensures the safety of energy converters, rotor
is just suitable for handling moderate fault conditions. circuits, and dc-link capacitors. The protection system is
The hardware solutions based on the voltage simulated with the MATLAB/SIMULINK tool to verify
compensator/restorer, fault current limiter (FCL), and the finding. In this paper, Section 2 presents an overview of
chopper circuit are reviewed below. The efficacy of a DC- the modeling of Grid-Connected DFIG wind turbines.
link chopper in reducing the DC overvoltage is confirmed Section 3 explains the configuration of the Series Resistor
in Ref. [15], yet it is unable to aid in the post-fault and its effects on the DFIG. The simulation findings and
demagnetization of the electrical machine. Ref. [16], the impact of the Series Resistor scheme on DFIG are
proposes a modified DC chopper that can be inserted in a discussed and evaluated in Section 4. The conclusions are
DFIG base series or parallel connection.Although the offered in Section 5.
modified structure makes certain improvements, the rotor 2. System Configuration
current is still around its safety limit (2.0 pu). In Ref. [17],
a minimized series voltage compensator is applied. Since The grid-connected DFIG WT system's schematic
the stator flux is well controlled, the generator is allowed to diagram is displayed in Fig. 1. It is a wind turbine unit made
ride through the grid disturbances as mentioned in the Refs. up of an electric generator, a control system, a power
[18–20], and a bridge-type FCL with a bypass resistor is electronic converter, and wind turbine blades. It exports
applied in a DFIG. The research results confirm its positive
power to the electrical grid via the feeder and is connected
effects on reducing flux and electromagnetic torque
oscillations. It is important to note that some early research to the distribution system. DFIGs are induction generators
on the coordinated control of an energy storage device and with wound rotors by nature, and a power electronic
a fault current limiter for DFIG stabilization has been converter typically regulates the rotor circuit.
published in Refs. [21–25]. It is found that the transitory
Gear
Wind Box
i s, V s
ωt ωg Stator
DFIG
Tm Back to Back
converters
Tem RSG GSC
Common
Vω Vgrid Coupling Point
Pitch angle (β)
Feeder-
Torque and Reactive Collector
Power Control additional
WT units
Tem-ref Qref
Wind Turbine Control
Strategy Other call .
domestic
Feeders
Vω Step-up transformer
Vgrid Transformer
The Control System
2.1 Wind turbine model Where: ρ is the air density, A is the swept area of a wind
According to wind turbine generators'' (WTGs) turbine, Vω is the wind speed, Cp is the power coefficient,
characteristics, mechanical power is given by the β is the blade pitch angle, and λ is the ratio between the
following relations [26]: turbine angular speed and the wind speed.
1
Pm = Cp (λ, β)ρAVω3 (1) R ωt
2 𝜆= (2)
𝑉𝜔
2
International Journal for Holistic Research, Vol. 1, No. 1. June 2024
Where: R is the turbine radius; ωt is the turbine rotational idc The d-axis current flowing through Qnet The total
speed. The power coefficient Cp value is approximated reactive power delivered to the grid.
according to the non-linear function
116 −12.5⁄
𝑐𝑝 = 0.22 ( − 0.4𝛽 − 5) 𝑒 𝜆𝑖 (3)
𝜆𝑖 The DFIG converters' control block diagram is
1 1 0.035
displayed in Fig. 2. To control the rotor currents and
With = − achieve the best rotor flux location concerning the stator
𝜆𝑖 𝜆+0.08𝛽 𝛽 2 +1
flux, the rotor-side converter for the DFIG applies voltage
to the rotor windings. This allows the machine's shaft to
2.2 .Double-fed induction generator model
create the desired torque. For maximum energy capture in
a wind power application, the generator's vector control can
Nowadays, the DFIG is the most used wind power system be integrated into the best power tracking controller [28].
in wind energy farms. The basic configuration of The DFIG The generator's rotational speed and, thus, the wind turbine
model is shown in Fig. 1. DFIG stator windings usually shaft's speed can be adjusted by adjusting the converter's
have a direct grid connection. On the other hand, power active power [29].
converters are coupled to rotor winding using slip rings To extract the greatest power, this can be used to track
[26]. Two voltage-source converters, the RSC and GSC, the ideal tip-speed ratio as the incident wind speed varies.
make up the power electronic converter that connects the Additionally, it offers variable-frequency stimulation based
rotor windings to the grid. A DC-link capacitor is on the circumstances around wind speed. One popular
positioned in between the two converters to store energy implementation of the control mechanism for the induction
and maintain minimal voltage changes, sometimes known generator is a synchronously rotating dq-axis frame with
as ripples, in the DC-link voltage. The modeling equations the d-axis oriented along the stator-flux vector position. We
are created by referring to [27] and are as follows: refer to this as vector control for stator-flux orientation, or
𝑉𝑠→ = 𝑅𝑠 𝑖𝑠→ + 𝑑ψ→ 𝑠
/ 𝑑𝑡 + 𝑗𝜔𝑠 ψ→ 𝑠
(4) SFO. As such, control of active power and reactive power
→ → → →
𝑉𝑟 = 𝑅𝑟 𝑖𝑟 + 𝑑ψ𝑟 /𝑑𝑡 + 𝑗(𝜔𝑠 − ω𝑟 )ψ𝑟 (5) is done separately. By permitting independent control of the
active and reactive power flowing between the grid and the
ψ→
𝑠
= 𝐿𝑠 𝑖𝑠→ + 𝐿𝑚 𝑖𝑟→ (6)
grid-side converter, the grid-side converter maintains the
ψ→
𝑟
= 𝐿𝑚 𝑖𝑠→ + 𝐿𝑟 𝑖𝑟→ (7) DC-link voltage constant (i.e., it is an observer of DC-link
voltage) [30].
Where, 𝑖⃗ ,𝑽 ⃗⃗⃗, R, L are the current, voltage, flux, resistance
⃗⃗,ψ 2.3 Steady-state operation
as well as inductance, respectively. Subscripts s, r are the
stator and rotor, respectively. It is obtained that 𝐿𝑠 = 𝐿𝑠𝜎 + When the machine speed is over or below the
𝐿𝑠𝜎 synchronous speed, the rotor slip "s" determines how much
𝐿𝑚 and 𝐿𝑟 = 𝐿𝑟𝜎 + 𝐿𝑚 , and ⁄𝐿 is the leakage
𝑟𝜎 power is exchanged between the DFIG and the grid in a
inductance. From Eqs. (3) and (4), the stator and rotor steady condition. The following formulas could be used to
currents are signified as: determine the DFIG's mechanical, electrical, and slip (s):
→ →
i→ ̇
𝑠 = ψ𝑠 /𝐿𝑠 − 𝐾𝑟 ψ𝑟 / 𝐿𝑠
̇ (8)
ω𝑠 − ω𝑟
𝑝𝑟 = 𝑝𝑚 − 𝑝𝑠 = 𝑇𝑚 ω𝑟 − 𝑇𝑚 ω𝑠 = −𝑇𝑚 ( ) ω𝑠
i→ → ̇ → ̇ ω𝑠
𝑟 = −𝐾𝑠 ψ𝑠 /𝐿𝑟 − ψ𝑟 / 𝐿𝑟 (9)
= −𝑠𝑇𝑚 ω𝑠 = −𝑆𝑝𝑠 (10)
Where S is defined as the slip of the generator:
Where, 𝐿𝑠̇ = 𝐿𝑠 − L2𝑚 /𝐿𝑟 and 𝐿𝑟̇ = 𝐿𝑟 − L2𝑚 /𝐿𝑠 are
deduced; 𝐾𝑠 and 𝐾𝑟 are expressed as 𝐾𝑠 = 𝐿𝑚 /𝐿𝑠 and 𝜔𝑠 − 𝜔𝑟
𝐾𝑟 = 𝐿𝑚 /𝐿𝑟 respectively.iqr The q-axis current in the rotor 𝑆= (11)
𝜔𝑠
circuit idr The d-axis current in the rotor circuit Where 𝜔𝑟 Rotor Angular Velocity and 𝜔𝑠 The
synchronous speed.
+ +
+
PI -Ls/Lmφs PI
- - + dq-abc
iqr PWM
Transform
ωr (ωs-ωr)(-Ls/Lmφs+σLriqr)
+ + +
Ԛsref PI PI
- - -
idr
Ԛs (ωs-ωr)σLriqr (a)
+ +
PI -
Vdc,re f PI
- +
-
idgc dq-abc
Vdc Vds +ωsLiqgc PWM
Transform
+ -
Ԛgc,re f PI
- +
(b)
Ԛgc Vqs +ωsLidgc
Fig. 2. Control block diagram of the DFIG converters. (a) RSC, (b) GSC [25].
3
International Journal for Holistic Research, Vol. 1, No. 1. June 2024
Gear Box
Series Resistor
RSC GSC
Fig.3.Topological structure of the series resistor protection scheme.
DFIG
Grounding Transformer
RSC GSC
Fig. 4. Single line diagram for the studied system.
4
International Journal for Holistic Research, Vol. 1, No. 1. June 2024
4.1 Study of the symmetrical fault current control. Under these circumstances, the currents
rise as the plunge gets deeper. The scenario that
As a result, the stator flux gradually shifts from the forced
corresponds to the entire decline is the worst. The approved
flux, which rotates at synchronous speed and appears
rate of the dip depth and the rotor converter power rating
during normal machine operation, to the natural flux, a
are fairly proportionate. As seen in Fig. 5, a three-phase
transient flux that appears during voltage dips. In this
fault is simulated to occur at the grid connection point,
instance, dips cause the stator voltage amplitude to decline
starting at t = 0.7s and clearing at t = 0.9s. The system's
from V1 to V2. Its starting value decreases exponentially by
reaction to a 0.95 pu voltage dip lasting 0.2 s using the
the stator time constant and is proportional to the voltage
series resistance protection approach is depicted in this
change. The Vrn is a transitory term brought on by the
figure. The power from the induced voltages in the rotor
natural flux, whereas the Vrf is generated by the new grid
that developed during the fault in this simulation was
voltage and has a tiny amplitude. Since its amplitude (V1 −
dissipated as a result of the rotor circuit's addition of series
V2) is related to the dip's depth, it may be significant. The
resistance. As a result, the rise in the rotor and stator
current is controlled as long as the dip is shallow and the
currents is reduced. For the most critical phase, the stator
voltage caused by the stator flux doesn't surpass the
currents are reduced from 2.66 pu to 2.02 pu. For the worst
maximum voltage that the rotor converter can produceIn
phase, the rotor currents are reduced from 2.5 pu to 1.21 pu.
this instance, as in regular operation for deeper dips, the
Consequently, there is a large reduction in both the DC-link
converter's maximum tension is exceeded by the voltage
voltage and the electrical torque variations.
caused by the stator flux, resulting in a temporary loss of
15
1 Active power Ps
Ps (MW),Qs (Mvar)
Reactive power Qs
Grid Voltage (pu)
10
0.5
5
0
0
-0.5
-5
-1 0.4 0.6 0.8 1 1.2 1.4 1.6
Time(s)
0.4 0.6 0.8 Time(s) 1 1.2 1.4 1.6
Active and Reactive power
Grid voltage
2
1500
Stator Current (pu)
1
1000
0
500
-1 0
0
Te(pu), Tm (pu)
0.5
0 -0.5
-0.5 -1
-1
0.4 0.6 0.8 Time(s) 1 1.2 1.4 1.6
0.4 0.6 0.8 Time (s) 1 1.2 1.4 1.6
Rotor current Electrical and mechanical torque
Fig.5. Three-phase 0.95pu voltage dip for 0.2s with Series Resistor protection scheme.
4.2 Study of the asymmetrical fault This symmetrical components theory states that the
positive, negative, and zero sequences are the three
Because they cause larger voltages in the rotor, components that add up to a three-phase voltage system.
asymmetrical dips are more damaging to the generator than Three vectors, one for each component, can be extracted
symmetrical dips. Furthermore, these voltages have a from the stator voltage. Reversible rotation is produced by
distinct nature in that they contain both permanent the negative sequence V2, and rotation is produced by the
components that last the duration of the dip and transitory positive sequence V1. There is no flux generated by the zero
components, like those that originate in symmetrical dips. sequence V0. We shall refer to these fluxes as ψs1 and ψs2,
5
International Journal for Holistic Research, Vol. 1, No. 1. June 2024
respectively. Depending on its amplitude, each flux causes phase-c) fault occurs at t = 0.7 seconds. The responses of
a voltage to be induced in the rotor. Since the Vr1 is modest the system to asymmetrical fault conditions are displayed
and the Vr2 has a factor that is almost equal to 2, its in Fig. 6. The series resistance effectively dissipates the
amplitude may be significant if the dip's asymmetrical ratio induced voltage in the rotor when phases b to c short-
is large. The slip is often minor, therefore its frequency is circuite together. During the worst phase, the stator currents
around twice that of the grid. They cause far higher voltages dropped from 2.09pu to 1.04pu. Additionally, at the most
in the rotor than would be seen during regular operation. serious phase, the rotor currents are reduced from 1.91pu to
Control over the current is lost, maybe permanently, if the 1.104pu. Consequently, DC-link voltage variations and
rotor converter does not make up for these voltages. electrical torque fluctuations are greatly reduced by SR.
Overcurrents arise in this scenario, which could harm the
converter. In the simulation, a double-phase (phase-b and
15
1 Active power Ps
Ps (MW),Qs(Mvar)
Grid Voltage (pu)
Reactive power Qs
0.5 10
0 5
-0.5
0
-1
-5
0.4 0.6 0.8 1 1.2 1.4 1.6 0.4 0.6 0.8 1 1.2 1.4 1.6
Time(s) Time(s)
Mechanical torqueTm
Te(pu), Tm (pu)
0.5
-0.2
0 -0.4
-0.6
-0.5
-0.8
-1 -1
0.4 0.6 0.8 Time(s) 1 1.2 1.4 1.6
0.4 0.6 0.8 Time(s) 1 1.2 1.4 1.6
Fig.6. Phase b to c short circuit for 0.2s with series resistor protection.
Table 1 displays a comparison study between the proposed Series Grid Acceptable Well Acceptable
protection plan and those in the literature [33–35] based on side
simulation results. The proposed method provided better converter
results in terms of damping for the current increase at Feed Acceptable Unacceptable Rather
the generator terminals. Additionally, the crowbar and a forward complicated
DC-chopper protection scheme have built on a simple control
concept. It decreases the cost and complexity of the system. series Good Good Simple
Hence, it contributes to system stability during grid faults. resistor
Table 1. Comparing the results obtained from protection schemes with protection
other works.
5. Conclusion
LVRT Rotor DC-link Simplicity In this paper, protection schemes are investigated to
Techniques Current Voltage of
enhance the DFIG-based wind turbines' performance.
Protection
Scheme Grid faults have a strong impact on both the
Design mechanical and electrical components of the wind
FC L Unacceptable Well Acceptable turbine. The purpose of the protection scheme is to
static Unacceptable Acceptable Acceptable
reduce the voltage induced in the rotor circuit during
synchronous
compensator a fault. The series resistor protection is more effective
Energy Unacceptable Well Rather in terms of damping current increases at the generator
Storage complicated terminals. In addition to that, the SR scheme is based
System
on a simple concept. It decreases the cost and
complexity of the system. It is useful under
6
International Journal for Holistic Research, Vol. 1, No. 1. June 2024
symmetrical and asymmetrical grid faults as it [9] Hazari M.R.; Mannan M.A.; Muyeen S.M.; Umemura
decreases the rotor overcurrent, DC-link overvoltage, A.; Takahashi R.; Tamura J. “Stability Augmentation
of a Grid-Connected Wind Farm by Fuzzy-Logic-
and torque oscillations compared to the other Controlled DFIG-Based Wind Turbines”, Appl. Sci.
schemes. Hence, it contributes to system stability 2018, Vol. 8, pp.20–43.
during grid faults. Therefore, the induced overvoltage [10] Seyed A.; Zahra D.; Mohsen R.; Mohammad S.
will be shared by the resistance. Thus, the power is “Model predictive fuzzy control for enhancing FRT
capability of DFIG-based WT in real-time simulation
dissipated within resistance which reduces rotor environment”, Energy Syst. 2018, Vol. 9, pp.899–
currents better. Recent grid regulations require wind 919.
turbines to remain grid-connected while providing [11] Zou X.; Zhu D.; Hu J.; Zhou S.; Kang Y. “
Mechanism Analysis of the Required Rotor Current
reactive power assistance. As such, the LVRT
and Voltage for DFIG-Based WTs to Ride-Through
capability of DFIG-WTs needs to be equipped to Severe Symmetrical Grid Faults”, IEEE Trans. Power
efficiently fulfill emerging grid requirements. As a Electron. 2018, Vol. 33, pp.7300–7304.
result, future approaches must be built to meet the [12] Graham P.; Bashar Z.; David J.; Petros M. “Evaluation
of the Performance of a DC-Link Brake Chopper as a
needs of power grids. The future direction of LVRT DFIG Low-Voltage Fault-Ride-Through Device”,
solutions is to use exterior LVRT techniques, which IEEE Trans. Energy Conver., 2013, Vol. 28, pp. 535–
are widely used in pre-installed wind turbines for 542.
simplicity. [13] Seyed B.; Michael N.; Kashem M. “A Modified DC
Chopper for Limiting the Fault Current and
References Controlling the DC-Link Voltage to Enhance Fault
[1] Yang B.; Zhang X.; Yu T.; Shu H.; Fang Z. “Grouped Ride-Through Capability of Doubly-Fed Induction-
grey wolf optimizer for maximum power point Generator-Based Wind Turbine”, IEEE Trans. Ind.
tracking of doubly-fed induction generator based Appl. 2019, Vol. 55, pp. 2021–2032.
wind turbine", Energy Convers. Manage. 2017, Vol. [14] Sandro E.; Sidelmo M.; Braz J. “Fault ride-through
133, pp. 427–443. enhancement in DFIG with control of stator flux using
[2] Jerin A.; Kaliannan P.; Subramaniam U.; Moursi M. minimized series voltage compensator”. IET Renew.
“Review on FRT solutions for improving transient Power Gener., 2018, Vol.12, pp.1234–1240.
stability in DFIG-WTs”. IET Renew, Power Gener. [15] Wessels C.; Gebhardt F.; Fuchs F. “Fault ride-through
2018, Vol. 12, pp. 1786–1799. of a DFIG wind turbine using a dynamic voltage
[3] Adel A. Elbaset, Y. S. Mohamed, A.H. M. El-Sayed restorer during symmetrical and asymmetrical grid
and A. E. H. A. Ahmed, “Wind Driven Doubly Fed faults”, IEEE Trans. Power Electron. 2011, Vol. 26,
Induction Generator,” Grid Synchronization and pp. 807– 815.
Control, 1st ed. Springer, UK, (2018). [16] Huang P.; Mohamed S.; Xiao W.; James L. “Sub
[4] Gayen P.K.; Chatterjee D.; Goswami S.K. “An synchronous Resonance Mitigation for Series-
improved low-voltage ride-through performance of Compensated DFIG-Based Wind Farm by Using
DFIG based wind plant using stator dynamic Two-Degree-of-Freedom Control Strategy”,IEEE
composite fault current limiter”. ISA Trans. 2016, Trans. Power Syst. 2015, Vol. 30, pp. 1442–1454.
Vol. 62, pp.333–348. [17] Guo W.; Xiao L.; Dai S.; Xu X.; Li Y.; Wang Y.
[5] Huang Q.; Zou X.; Zhu D.; Kang Y. “Scaled current “Evaluation of the performance of BTFCLS for
tracking control for doubly fed induction generator to enhancing LVRT capability of DFIG”, IEEE Trans.
ride-through serious grid faults”,IEEE Trans. Power Power Electron. 2015, Vol. 30, pp. 3623–3637.
Electron 2016, Vol.31, pp. 2150–2165. [18] Guo W.; Xiao L.; Dai S. “Enhancing low-voltage
[6] Ahmed E.; Istvàn E. “Short-circuit current reduction ride-through capability and smoothing output power
techniques of the doubly-fed induction generator of DFIG with a superconducting fault-current limiter–
based wind turbines for fault ride through magnetic energy storage system”, IEEE Trans.
enhancement”. IET Renew,Power Gener. 2017, Vol. Energy Convers. 2012, Vol. 27, pp. 277–295.
11, pp.1033–1040. [19] Ngamroo, Issarachai, “Optimization of SMES-FCL
[7] Ghafouri M.; Karaagac U.; Karimi H.; Jensen S.; for Augmenting FRT Performance and Smoothing
Mahseredjian J.; Faried S. “An LQR Controller for Output Power of Grid-Connected DFIG Wind
Damping of Sub synchronous Interaction in DFIG- Turbine”, IEEE Transactions on Applied
Based Wind Farms”. IEEE Trans. Power Syst. 2017, Superconductivity, 2016, Vol.26, pp. 1-5.
Vol. 32, pp. 4934–4942. [20] Issarachai, Ngamroo and T. Karaipoom, “Cooperative
[8] Jin P.; Li Y.; Li G.; Chen Z.; Zhai X. “Optimized control of SFCL and SMES for enhancing fault ride
hierarchical power oscillations control for distributed through capability and smoothing power fluctuation
generation under unbalanced conditions”, Appl. of DFIG wind farm”, IEEE Transactions on Applied
Energy 2017, Vol.194, pp.343–352. Superconductivity, 2014, Vol. 24, pp. 1-4.
7
International Journal for Holistic Research, Vol. 1, No. 1. June 2024
[21] X.-Y. Xiao, R.-H. Yang, X.-Y. Chen and Z.-X. doubly fed induction generator during grid faults”.
Zheng, “Integrated DFIG protection with a modified IEEE Trans. Power Electron. Vol. 25, (2010), pp
SMES-FCL under symmetrical and asymmetrical 118–130.
faults”, IEEE Transactions on Applied [29] Liang, J.; Qiao, W.; Harley, R.G. “Feed-forward
Superconductivity, 2018. Vol. 28, pp. 1-6. transient current control for low-voltage ride-through
[22] Chen L.; Li G.; Chen H.; Tao Y.; Tian X.; Liu X.; et enhancement of DFIG wind turbines”. IEEE Trans.
al. “Combined Use of a Resistive SFCL and DC-link Energy Convers. 2010, Vol. 25, (2010), pp.836–843.
Regulation of a SMES for FRT Enhancement of a [30] A. Gaillard, P. Poure, S. Saadate, and M.
DFIG Wind Turbine Under Different Faults”, IEEE Machmoum, “Variable speed DFIG wind energy
Trans. Appl. Supercond. 2019, 29, Art. no. 5600408. system for power generation and harmonic current
[23] A. A. B. M. Zin, M. P. HA, A. B. Khairuddin, L. mitigation,” Renew. Energy, vol. 34, no. 6,(2009),
Jahanshaloo, and O. Shariati, “An overview on pp. 1545–1553.
doubly fed induction generators′ controls and [31] M. Kesraoui, A. Chaib, A. Meziane, and A. Boulezaz,
contributions to wind based electricity generation,” “Using a DFIG based wind turbine for grid current
Renewable and Sustainable Energy Reviews, Vol. harmonics filtering,” Energy Convers. Manag., Vol.
27, (2013), pp. 692-708. 78,(2014), pp. 968–975.
[24] Morren J.; Sjoerd W. “Short-Circuit Current of Wind [32] I. Erlich, J. Kretschmann, J. Fortmann, S. Mueller-
Turbines with Doubly Fed Induction Engelhardt, and H. Wrede, “Modeling of wind
Generator”.IEEE Trans. Energy Convers. 2007, Vol. turbines based on doubly-fed induction generators for
22, pp.174–180. power system stability studies,” IEEE Trans. Power
[25] R. Pena, J. C. Clare, and G. M. Asher, “Doubly fed Syst., Vol. 22, No. 3, (2007), pp. 909-919.
induction generator using back-to-back PWM [33] J. Lopez, E. Gubia, P. Sanchis, X. Roboam, and L.
converters and its application to variable-speed wind- Marroyo , (2008). “Wind turbines based on doubly
energy generation,” IEE Proc. Electr.,Power Appl., fed induction generator under asymmetrical voltage
Vol. 143, No. 3, (1996), pp. 231-241. dips,” IEEE Transactions on Energy conversion, Vol.
[26] Adel A. Elbaset, AHM El-Sayed, AEH 23, pp. 321-330.
Abozeid ,“Grid synchronization enhancement of a [34] L.Saihi,Y. Bakou, A. Harrouz,M.Boura, Ilhami Colak
wind driven DFIG using adaptive sliding mode andK.Kayisli, “Robust Sensor-less SMC under Variable-
control,” IET Renewable Power Generation, Vol.11, Speed Wind Turbine Systems of DFIG based on
(2017) ,pp.688-695. FKE”,10th International Conference on Smart Grid
[27] J. Yang, “Fault analysis and protection for wind (icSmartGrid), IEEE, Turkey, 27-29 June 2022.
power generation systems,” PhD thesis Department [35] A. R.Ann J., P. Kaliannan, U. S. and M.S. El Moursi ,“A
of Electronics and Electrical Engineering, Review on FRT solutions for improving transient
University of Glasgow,(2011). stability in DFIG-WTs”, IET Renew. Power Gener.
[28] Lima, F.K.A.; Luna, A.; Rodriguez, P.; Watanabe, ,Vol.12,No. 15 ,pp.1786–1799, October 2018.
E.H.; Blaabjerg, F. “Rotor voltage dynamics in the