Download as pdf or txt
Download as pdf or txt
You are on page 1of 33

ELECTRIC PLANS.

PROJECT:

SUPPLY AND INSTALL OF OFF-GRID SOLAR SYSTEM FOR


AL-MA'AZIBAH HEALTH CENTER.
FUNDED BY:

WORLD BANK GROUP.


OCTOBER, 2023.
DRAWING LIST:-
NO DRAWING TITLE
S1 - 01 MAIN NOTES
S1 - 02 ELECTRIC PLAN DETAILS.
S1 - 03 PV MODULE DISTRIBUTION ROOFTOP PLAN DETAILS.
S1 - 04 PV STRINGS & COMBINER BOX EARTHING PLAN DETAILS.
S1 - 05 BATTERY ROOM PLAN DETAILS.
S1 - 06 EARTNING PIT AND BUSBAR DETAILS.
S1 - 07 MAIN DISTRIBUTION BOARD DETAILS.
S1 - 08 SOLAR SYSTEM SCHEMATIC DIAGRAM DETAILS.
PREPARED BY : FUNED BY : PROJECT TITLE : DRAWING TITLE: DESIGN BY: STATUS: NORTH: DRAWING NO:
MAIN NOTES. TENDER DOCUMENTS.
YEMEN EMERGENCY ELECTRICITY
ACCESS PROJECT-II CHECKED BY: PROJECT NO: PAPER SIZE:
A3.
PROJECT LOCATION: DRAWING TYPE: APPROVED BY: DATE: SCALE:
AL-MAHWIT CITY-YEMEN ELECTRIC PLANS. OCTOBER,21,2023 AS SHOWEN.
LEGEND:
SYMBOL DESCRIPTION
CONNECTION BUS BAR BETWEEN
CHARGE CONTROLLER AND BATTERY
RACK

BATTERY INVERTER.

CHARGE CONTROLLER.

BATTERY RACK 2V,1200Ah.

MAIN DISTRIBUTION BOARD WALL


MOUNTED.

MANUAL TRANSFER SWITCH


MDB

EARTHING AC COUPLING PANEL


BUS BAR NO.1

TO EARTHING
BUS BAR NO.3 OUTDOOR LIGHTING
1C*10SQ.MM
TO EARTHING
BUS BAR NO.2
1C*10SQ.MM
VENTILATION CONTROL PANEL
CABLE ROUTING
CABLE TRAY EMERGENCY LIGHT
50MMX50MM

TO LIGHTNING RACK HAS


2 LAYERS.
ARRESTER
1C*25 SQ.MM

3
4"PVCPIPE
SCH. 40.

WIRE CONNECTOR ASSORTMENT

NOT SCALED

SCALE: 1:75.
PREPARED BY : FUNED BY : PROJECT TITLE : DRAWING TITLE: DESIGN BY: STATUS: NORTH: DRAWING NO:
FINAL ELECTRIC PLAN DETAILS. TENDER DOCUMENTS.
YEMEN EMERGENCY ELECTRICITY
ACCESS PROJECT-II CHECKED BY: PROJECT NO: PAPER SIZE:
A3.
PROJECT LOCATION: DRAWING TYPE: APPROVED BY: DATE: SCALE:
AL-MAHWIT CITY-YEMEN ELECTRIC PLANS. OCTOBER,21,2023 1:75.
COMBINER BOX

PHOTOVOLTAIC MODULE

GI CABLE TRAY
100MM * 50MM

COMBINER BOX
COLD FORMED STEEL
C CHANNEL

ANCHOR
BOLT SOLAR SINGLE CORE CABLE
1C X 6 SQ.MM (RED COLOR)

SOLAR SINGLE CORE CABLE


NOT TO SCALE.
1C X 6 SQ.MM (BLACK COLOR)

SOLAR SINGLE CORE CABLE


1C X 35 SQ.MM (RED COLOR)

SOLAR SINGLE CORE CABLE


1C X 35 SQ.MM (BLACK
COLOR)

COVER
PERFORATED CABLE TRAY
CABLE TRAY

CABLE TRAY
SUPPORT

ANCHOR
BOLTS

NOT SCALED

SCALE: 1:75.
PREPARED BY : FUNED BY : PROJECT TITLE : DRAWING TITLE: DESIGN BY: STATUS: NORTH: DRAWING NO:
PV MODULE DISTRIBUTION TENDER DOCUMENTS.
YEMEN EMERGENCY ELECTRICITY
ROOFTOP PLAN DETAILS.
ACCESS PROJECT-II CHECKED BY: PROJECT NO: PAPER SIZE:
A3.
PROJECT LOCATION: DRAWING TYPE: APPROVED BY: DATE: SCALE:
AL-MAHWIT CITY-YEMEN ELECTRIC PLANS. OCTOBER,21,2023 1:75.
TO LIGHTNING PIT
1C*25SQ.MM

PHOTOVOLTAIC MODULE

COMBINER BOX

EARTHING BUS BAR


LIGHTNING ARRESTER
SHALL BE 3 MTR ABOVE
MOUNTING STRUCTURE EARTHING CABLE

LIGHTNING ARRESTOR

EARTHING
BUSBAR NO.2

10 sqr.mm

SCALE: 1:75.
PREPARED BY : FUNED BY : PROJECT TITLE : DRAWING TITLE: DESIGN BY: STATUS: NORTH: DRAWING NO:
PV STRINGS & COMBINER BOX TENDER DOCUMENTS.
YEMEN EMERGENCY ELECTRICITY
EARTHING PLAN DETAILS.
ACCESS PROJECT-II CHECKED BY: PROJECT NO: PAPER SIZE:
A3.
PROJECT LOCATION: DRAWING TYPE: APPROVED BY: DATE: SCALE:
AL-MAHWIT CITY-YEMEN ELECTRIC PLANS. OCTOBER,21,2023 1:75.
MCP Bell CONNECTION BOX BETWEEN
CHARGE CONTROLLER AND
BATTERY RACK

BATTERY INVERTER
RACK HAS DC=

2 LAYERS. CHARGE CONTROLLER

BATTERY RACK 2V,2500Ah.

MAIN DISTRIBUTION
BOARD WALL MOUNTED.

INLET FAN

EXHAUST FAN

FIRE EXTINGUISHER

CONVENTIONAL SMOKE
SD
DETECTOR

CONVENTIONAL HEAT
HD
DETECTOR

CONVENTIONAL FIRE
ALARM PANEL

Bell BELL

MANUAL CALL POINT


MCP (BREAK GLASS)

Note:-
1- Ventilation system and Battery room lighting will be supplied
from MDB.

SCALE: 1:25.

PREPARED BY : FUNED BY : PROJECT TITLE : DRAWING TITLE: DESIGN BY: STATUS: NORTH: DRAWING NO:
BATTERY ROOM PLAN DETAILS. TENDER DOCUMENTS.
YEMEN EMERGENCY ELECTRICITY
ACCESS PROJECT-II CHECKED BY: PROJECT NO: PAPER SIZE:
A3.
PROJECT LOCATION: DRAWING TYPE: APPROVED BY: DATE: SCALE:
AL-MAHWIT CITY-YEMEN ELECTRIC PLANS. OCTOBER,21,2023 1:25.
100 cm
40 cm

90mm

250mm 60mm

100mm

SCALE: 1:50.
PREPARED BY : FUNED BY : PROJECT TITLE : DRAWING TITLE: DESIGN BY: STATUS: NORTH: DRAWING NO:
EARTHING PIT AND BUSBAR TENDER DOCUMENTS.
YEMEN EMERGENCY ELECTRICITY
DETAILS.
ACCESS PROJECT-II CHECKED BY: PROJECT NO: PAPER SIZE:
A3.
PROJECT LOCATION: DRAWING TYPE: APPROVED BY: DATE: SCALE:
AL-MAHWIT CITY-YEMEN ELECTRIC PLANS. OCTOBER,21,2023 AS SHOWEN.
Voltage Rating in AC 230V
Busbar Current Rating 160A
Busbar Rating 50kA Conditional
Fully shrouded
Busbar Type
copper and tinned

Inside View

63 A , 15 kA 63 A , 15 kA MDB
32 A , 15 kA 40 A , 15 kA

32 A , 15 kA 40 A , 15 kA

32 A , 15 kA 40 A , 15 kA

32 A , 15 kA 32 A , 15 kA

20 A , 15 kA 32 A , 15 kA

20 A , 15 kA 32 A , 15 kA
20 A , 15 kA
Ventilation 32 A , 15 kA
System
16 A , 15 kA
20 A , 15 kA Battery room
Lighting
20 A , 15 kA 16 A , 15 kA
Fire Alarm Panel

SCALE: 1:50.
PREPARED BY : FUNED BY : PROJECT TITLE : DRAWING TITLE: DESIGN BY: STATUS: NORTH: DRAWING NO:
MAIN DISTRIBUTION BOARD TENDER DOCUMENTS.
YEMEN EMERGENCY ELECTRICITY
DETAILS.
ACCESS PROJECT-II CHECKED BY: PROJECT NO: PAPER SIZE:
A3.
PROJECT LOCATION: DRAWING TYPE: APPROVED BY: DATE: SCALE:
AL-MAHWIT CITY-YEMEN ELECTRIC PLANS. OCTOBER,21,2023 AS SHOWEN.
Connection
DG
PHOTOVOLTAIC MODULE

BATTERY INVERTER
DC=

MANUAL CHANGE OVER


80 A 85A to 100A
ISC:10 kA 150 to 300 VDC
CLASS B 1x35 SQ.mm
SOLAR CABLE XPLE/PVC/AL1.0KV CHARGE CONTROLLER
2 CABLES (RED& BLACK) Off Grid Inverter
10KVA 40A 2P 40A 2P 2x16 SQ.mm
RCCB,300mA MCCB,25KA
HYBRID SOLAR SYSTEM INVERTER OUTPUT
SURGE ARRESTER

SPD SPD
CIRCUIT BREAKER (MCB)
1x35SQ.mm 1x70 SQ.mm
(RED& BLACK) (RED& BLACK)
CIRCUIT BREAKER (RCCB)

NEW MDB
DC FUSE

POSITIVE & NEGATIVE


CONNECTION BUS BAR
Bus Bar 340A
P ositive & Negative DC BREAKER (SWITCH
80 A 85A to 100A
EARTH PIT ISOLATOR)
ISC:10 kA 150 to 300 VDC
CLASS B 1x35 SQ.mm
SOLAR CABLE 1x35SQ.mm
2 CABLES (RED& BLACK)
(RED& BLACK)
DC FUSE
1x70SQ.mm 1x70 SQ.mm
(RED) (BLACK)

SPD SPD

250 A, 2P Shunt
Battery Rack

1x70 SQ.mm

24 Batteries
2V ,1200 Ah
EARTH PIT
48 Volt

PREPARED BY : FUNED BY : PROJECT TITLE : DRAWING TITLE: DESIGN BY: STATUS: NORTH: DRAWING NO:
SOLAR SYSTEM SCHEMATIC TENDER DOCUMENTS.
YEMEN EMERGENCY ELECTRICITY
DIAGRAM DETAILS.
ACCESS PROJECT-II CHECKED BY: PROJECT NO: PAPER SIZE:
A3.
PROJECT LOCATION: DRAWING TYPE: APPROVED BY: DATE: SCALE:
AL-MAHWIT CITY-YEMEN ELECTRIC PLANS. OCTOBER,21,2023 AS SHOWEN.
STRUCTURAL PLANS.
PROJECT:

SUPPLY AND INSTALL OF OFF-GRID SOLAR SYSTEM FOR


AL-MA'AZIBAH HEALTH CENTER.
FUNDED BY:

WORLD BANK GROUP.


OCTOBER, 2023.

DRAWING LIST:-
NO DRAWING TITLE
S2 - 01 MOUNTING STRUCTURE GENERAL SITE PLAN DETAILS.
SCALE: 1:75.
PREPARED BY : FUNED BY : PROJECT TITLE : DRAWING TITLE: DESIGN BY: STATUS: NORTH: DRAWING NO:
MOUNTING STRUCTURE GENERAL TENDER DOCUMENTS.
YEMEN EMERGENCY ELECTRICITY
SITE PLAN DETAILS.
ACCESS PROJECT-II CHECKED BY: PROJECT NO: PAPER SIZE:
A3.
PROJECT LOCATION: DRAWING TYPE: APPROVED BY: DATE: SCALE:
AL-MAHWIT CITY-YEMEN ELECTRIC PLANS. OCTOBER,21,2023 1:75.
ELECTRIC PLANS.
PROJECT:

SUPPLY AND INSTALL OF OFF-GRID SOLAR SYSTEM FOR


BADAH AL-SOFLA'A HEALTH CENTER.
FUNDED BY:

WORLD BANK GROUP.


OCTOBER, 2023.
DRAWING LIST:-
NO DRAWING TITLE
S1 - 01 MAIN NOTES
S1 - 02 ELECTRIC PLAN DETAILS.
S1 - 03 PV MODULE DISTRIBUTION ROOFTOP PLAN DETAILS.
S1 - 04 PV STRINGS & COMBINER BOX EARTHING PLAN DETAILS.
S1 - 05 BATTERY ROOM PLAN DETAILS.
S1 - 06 EARTNING PIT AND BUSBAR DETAILS.
S1 - 07 MAIN DISTRIBUTION BOARD DETAILS.
S1 - 08 SOLAR SYSTEM SCHEMATIC DIAGRAM DETAILS.
PREPARED BY : FUNED BY : PROJECT TITLE : DRAWING TITLE: DESIGN BY: STATUS: NORTH: DRAWING NO:
MAIN NOTES. TENDER DOCUMENTS.
YEMEN EMERGENCY ELECTRICITY
ACCESS PROJECT-II CHECKED BY: PROJECT NO: PAPER SIZE:
A3.
PROJECT LOCATION: DRAWING TYPE: APPROVED BY: DATE: SCALE:
AL-MAHWIT CITY-YEMEN ELECTRIC PLANS. OCTOBER,22,2023 AS SHOWEN.
EARTHING
BUS BAR NO.1

TO EARTHING TO EARTHING
BUS BAR NO.3 BUS BAR NO.2
1C*10SQ.MM 1C*10SQ.MM

RACK HAS
2 LAYERS. SD

LEGEND:
SYMBOL DESCRIPTION
CONNECTION BUS BAR BETWEEN
CHARGE CONTROLLER AND BATTERY
RACK
HD
BATTERY INVERTER.
TO LIGHTNING
ARRESTER
1C*25 SQ.MM CHARGE CONTROLLER.

BATTERY RACK 2V,800Ah.

MAIN DISTRIBUTION BOARD WALL


MOUNTED.

MDB MANUAL TRANSFER SWITCH

AC COUPLING PANEL

OUTDOOR LIGHTING

VENTILATION CONTROL PANEL


3
4"PVC PIPE
SCH. 40. EMERGENCY LIGHT

DOWN

UP

WIRE CONNECTOR ASSORTMENT

NOT SCALED

SCALE: 1:75.
PREPARED BY : FUNED BY : PROJECT TITLE : DRAWING TITLE: DESIGN BY: STATUS: NORTH: DRAWING NO:
FINAL ELECTRIC PLAN DETAILS. TENDER DOCUMENTS.
YEMEN EMERGENCY ELECTRICITY
ACCESS PROJECT-II CHECKED BY: PROJECT NO: PAPER SIZE:
A3.
PROJECT LOCATION: DRAWING TYPE: APPROVED BY: DATE: SCALE:
AL-MAHWIT CITY-YEMEN ELECTRIC PLANS. OCTOBER,22,2023 1:75.
COMBINER BOX

PHOTOVOLTAIC MODULE

GI CABLE TRAY
100MM * 50MM

COMBINER BOX
COLD FORMED STEEL
C CHANNEL

ANCHOR
BOLT SOLAR SINGLE CORE CABLE
1C X 6 SQ.MM (RED COLOR)

SOLAR SINGLE CORE CABLE


NOT TO SCALE.
1C X 6 SQ.MM (BLACK COLOR)

SOLAR SINGLE CORE CABLE


1C X 35 SQ.MM (RED COLOR)

SOLAR SINGLE CORE CABLE


1C X 35 SQ.MM (BLACK
COLOR)

Perforated Cable Tray


COVER

100mm x 50mm PERFORATED


CABLE TRAY
CABLE TRAY

DOWN
CABLE TRAY
SUPPORT

ANCHOR
BOLTS

NOT SCALED

UP

SCALE: 1:50.

PREPARED BY : FUNED BY : PROJECT TITLE : DRAWING TITLE: DESIGN BY: STATUS: NORTH: DRAWING NO:
PV MODULE DISTRIBUTION TENDER DOCUMENTS.
YEMEN EMERGENCY ELECTRICITY
ROOFTOP PLAN DETAILS.
ACCESS PROJECT-II CHECKED BY: PROJECT NO: PAPER SIZE:
A3.
PROJECT LOCATION: DRAWING TYPE: APPROVED BY: DATE: SCALE:
AL-MAHWIT CITY-YEMEN ELECTRIC PLANS. OCTOBER,22,2023 1:50.
1C*10SQ.MM

PHOTOVOLTAIC MODULE

COMBINER BOX

EARTHING
BUSBAR NO.2 EARTHING BUS BAR

EARTHING CABLE

LIGHTNING ARRESTOR

Perforated Cable Tray


100mm x 50mm

TO LIGHTNING PIT

DOWN 1C*25SQ.MM

LIGHTNING ARRESTER
SHALL BE 3 MTR ABOVE
MOUNTING STRUCTURE

UP

SCALE: 1:50.

PREPARED BY : FUNED BY : PROJECT TITLE : DRAWING TITLE: DESIGN BY: STATUS: NORTH: DRAWING NO:
PV STRINGS & COMBINER BOX TENDER DOCUMENTS.
YEMEN EMERGENCY ELECTRICITY
EARTHING PLAN DETAILS.
ACCESS PROJECT-II CHECKED BY: PROJECT NO: PAPER SIZE:
A3.
PROJECT LOCATION: DRAWING TYPE: APPROVED BY: DATE: SCALE:
AL-MAHWIT CITY-YEMEN ELECTRIC PLANS. OCTOBER,22,2023 1:50.
RACK HAS
2 LAYERS. SD CONNECTION BOX BETWEEN
CHARGE CONTROLLER AND
BATTERY RACK

BATTERY INVERTER
DC=

CHARGE CONTROLLER

BATTERY RACK 2V,800Ah.

MAIN DISTRIBUTION
BOARD WALL MOUNTED.

INLET FAN

EXHAUST FAN
HD

FIRE EXTINGUISHER

CONVENTIONAL SMOKE
SD
DETECTOR

CONVENTIONAL HEAT
HD
DETECTOR

CONVENTIONAL FIRE
ALARM PANEL

Bell BELL
MCP
MANUAL CALL POINT
MCP (BREAK GLASS)

Note:-
1- Ventilation system and Battery room lighting will be supplied VENTILATION CONTROL PANEL
from MDB.

SCALE: 1:25.

PREPARED BY : FUNED BY : PROJECT TITLE : DRAWING TITLE: DESIGN BY: STATUS: NORTH: DRAWING NO:
BATTERY ROOM PLAN DETAILS. TENDER DOCUMENTS.
YEMEN EMERGENCY ELECTRICITY
ACCESS PROJECT-II CHECKED BY: PROJECT NO: PAPER SIZE:
A3.
PROJECT LOCATION: DRAWING TYPE: APPROVED BY: DATE: SCALE:
AL-MAHWIT CITY-YEMEN ELECTRIC PLANS. OCTOBER,22,2023 1:25.
100 cm
40 cm

90mm

250mm 60mm

100mm

SCALE: 1:50.
PREPARED BY : FUNED BY : PROJECT TITLE : DRAWING TITLE: DESIGN BY: STATUS: NORTH: DRAWING NO:
EARTHING PIT AND BUSBAR TENDER DOCUMENTS.
YEMEN EMERGENCY ELECTRICITY
DETAILS.
ACCESS PROJECT-II CHECKED BY: PROJECT NO: PAPER SIZE:
A3.
PROJECT LOCATION: DRAWING TYPE: APPROVED BY: DATE: SCALE:
AL-MAHWIT CITY-YEMEN ELECTRIC PLANS. OCTOBER,22,2023 AS SHOWEN.
Voltage Rating in AC 230V
Busbar Current Rating 160A
Busbar Rating 50kA Conditional
Fully shrouded
Busbar Type
copper and tinned

Inside View

63 A , 15 kA 63 A , 15 kA MDB
32 A , 15 kA 40 A , 15 kA

32 A , 15 kA 40 A , 15 kA

32 A , 15 kA 40 A , 15 kA

32 A , 15 kA 32 A , 15 kA

20 A , 15 kA 32 A , 15 kA

20 A , 15 kA 32 A , 15 kA
20 A , 15 kA
Ventilation 32 A , 15 kA
System
16 A , 15 kA
20 A , 15 kA Battery room
Lighting
20 A , 15 kA 16 A , 15 kA
Fire Alarm
System

SCALE: 1:50.
PREPARED BY : FUNED BY : PROJECT TITLE : DRAWING TITLE: DESIGN BY: STATUS: NORTH: DRAWING NO:
MAIN DISTRIBUTION BOARD TENDER DOCUMENTS.
YEMEN EMERGENCY ELECTRICITY
DETAILS.
ACCESS PROJECT-II CHECKED BY: PROJECT NO: PAPER SIZE:
A3.
PROJECT LOCATION: DRAWING TYPE: APPROVED BY: DATE: SCALE:
AL-MAHWIT CITY-YEMEN ELECTRIC PLANS. OCTOBER,22,2023 AS SHOWEN.
Connection

PHOTOVOLTAIC MODULE

BATTERY INVERTER
DC=
50 A 60A to 100A
ISC:10 kA 150 to 300 VDC MANUAL CHANGE OVER
CLASS B 1x25 SQ.mm
SOLAR CABLE
2 CABLES (RED& BLACK)

XPLE/PVC/AL1.0KV CHARGE CONTROLLER


Off Grid Inverter
7KVA
32A 2P 32A 2P 2x10SQ.mm
SPD SPD RCCB,300mA MCCB,25KA
HYBRID SOLAR SYSTEM INVERTER OUTPUT SURGE ARRESTER

CIRCUIT BREAKER (MCB)


1x25SQ.mm
(RED& BLACK) 1x50 SQ.mm
50 A 60A to 100A (RED& BLACK) CIRCUIT BREAKER (RCCB)
ISC:10 kA 150 to 300 VDC
CLASS B 1x25 SQ.mm
SOLAR CABLE NEW MDB
2 CABLES (RED& BLACK)
DC FUSE

POSITIVE & NEGATIVE


SPD SPD CONNECTION BUS BAR
1x25SQ.mm) Bus Bar 240A
P ositive & Negative DC BREAKER (SWITCH
(RED& BLACK) EARTH PIT
ISOLATOR)

DC FUSE
1x50 SQ.mm 1x50 SQ.mm
(RED) (BLACK)

150 A, 1P
Shunt
Battery Rack

1x50 SQ.mm

24 Batteries
2V ,800 Ah
48 Volt

EARTH PIT

PREPARED BY : FUNED BY : PROJECT TITLE : DRAWING TITLE: DESIGN BY: STATUS: NORTH: DRAWING NO:
SOLAR SYSTEM SCHEMATIC TENDER DOCUMENTS.
YEMEN EMERGENCY ELECTRICITY
DIAGRAM DETAILS.
ACCESS PROJECT-II CHECKED BY: PROJECT NO: PAPER SIZE:
A3.
PROJECT LOCATION: DRAWING TYPE: APPROVED BY: DATE: SCALE:
AL-MAHWIT CITY-YEMEN ELECTRIC PLANS. OCTOBER,22,2023 AS SHOWEN.
STRUCTURAL PLANS.
PROJECT:

SUPPLY AND INSTALL OF OFF-GRID SOLAR SYSTEM FOR


BADAH AL-SOFLA'A HEALTH CENTER.
FUNDED BY:

WORLD BANK GROUP.


OCTOBER, 2023.

DRAWING LIST:-
NO DRAWING TITLE
S2 - 01 MOUNTING STRUCTURE GENERAL SITE PLAN DETAILS.
DOWN

UP

SCALE: 1:50.

PREPARED BY : FUNED BY : PROJECT TITLE : DRAWING TITLE: DESIGN BY: STATUS: NORTH: DRAWING NO:
MOUNTING STRUCTURE GENERAL TENDER DOCUMENTS.
YEMEN EMERGENCY ELECTRICITY
SITE PLAN DETAILS.
ACCESS PROJECT-II CHECKED BY: PROJECT NO: PAPER SIZE:
A3.
PROJECT LOCATION: DRAWING TYPE: APPROVED BY: DATE: SCALE:
AL-MAHWIT CITY-YEMEN ELECTRIC PLANS. OCTOBER,22,2023 1:50.
ELECTRIC PLANS.
PROJECT:

SUPPLY AND INSTALL OF OFF-GRID SOLAR SYSTEM FOR


GHAWIAH HEALTH CENTER.
FUNDED BY:

WORLD BANK GROUP.


OCTOBER, 2023.
DRAWING LIST:-
N RA IN TITLE
S1 - 01 MAIN NOTES
S1 - 02 ELECTRIC PLAN DETAILS.
S1 - 03 PV MODULE DISTRIBUTION ROOFTOP PLAN DETAILS.
S1 - 04 PV STRINGS & COMBINER BOX EARTHING PLAN DETAILS.
S1 - 05 BATTERY ROOM PLAN DETAILS.
S1 - 06 EARTNING PIT AND BUSBAR DETAILS.
S1 - 07 MAIN DISTRIBUTION BOARD DETAILS.
S1 - 08 SOLAR SYSTEM SCHEMATIC DIAGRAM DETAILS.
REMARKS: - SUPPLY OF THE SYSTEM SUPPLIER. THE ELECTRICAL ALL LIGHTING FIXTURES.
1. THE LAYOUT DRAWINGS DO NOT SHOW ALL THE CONTRACTOR WILL BE RESPONSIBLE FOR FURNISHING 20. ALL OUTDOOR WIRING ACCESSORIES SHALL BE
SYSTEMS, ITEMS, OR ACCESSORIES COVERED UNDER THE AND INSTALLING THE CABLE FEEDERS TO THESE BOARDS, WEATHER PROOF TYPE.
SCOPE OF ELECTRICAL WORKS TO BE EXECUTED THE HOOKING UP OF EQUIPMENT WILL BE THE SYSTEM 21. FOR GROUND-FAULT CIRCUIT INTERRUPT (GFCI) REFER
LAYOUT DRAWINGS SHALL BE READ IN CONJUNCTION WITH SUPPLIER RESPONSIBILITY. TO PLANS AND PANEL SCHEDULES.
ALL RELEVANT OR SPECIALIST DRAWINGS AND 10. CONDUCTORS FOR SINGLE PHASE SOCKETS OUTLETS 22. THE MINIMUM SEPARATE DISTANCE BETWEEN LOW
SPECIFICATIONS. CIRCUITS SHALL BE 4MM COPPER CONDUCTORS AND CURRENT SYSTEMS & LOW VOLTAGE POWER CABLES IS
2. DO NOT SCALE FROM THE LAYOUT DRAWINGS WORK PROTECTED BY 16A CIRCUIT BREAKERS UNLESS 300MM.
ACCORDING TO ARCHITECTURAL OR ELECTRICAL DETAILS OTHERWISE INDICATED. 23. THE MAXIMUM FILLING RATIO FOR POWER &
UNLESS OTHERWISE AUTHORIZED. 11. IN THE ABSENCE OF ANY INDICATION ON THE DRAWINGS COMMUNICATION CONDUITS IN SITE WORK ARE:
3. ALL EQUIPMENT LAYOUTS ARE PROVISIONAL. FINAL OR THE SPECIFICATIONS, THE INSTALLATIONS SHALL BE · MIN. 50MMD FOR POWER CABLE WITH MAX. 40%
LAYOUT SHALL BE DETERMINED BY THE CONTRACTOR DONE TO THE SATISFACTION OF UNOPS ENGINEER. OF CONDUIT CAPACITY.
FROM THE CONSTRUCTION/SHOP DRAWINGS AND AFTER 12. THE CONTRACTOR SHALL PROVIDE ALL IRON ANGLES, · MIN. 50MMD FOR LOW CURRENT SYSTEMS WITH
COORDINATION WITH OTHER TRADES. AND FIXING ACCESSORIES REQUIRED FOR COMPLETE MAX. 40% OF CONDUIT CAPACITY.
4. THE SIZE OF CONDUITS AND/OR CABLE TRAYS IS IN INSTALLATION OF LIGHTING FIXTURES, OUTLETS & 24. ALL C.BS WITH FRAME RATING LARGER THAN 100A
GENERAL NOT SHOWN ON DRAWINGS. THE SIZE OF ALL ROUTES. SHOULD HAVE ADJUSTABLE THERMAL OVERLOAD SETTING.
CONDUITS AND/OR CABLE TRAYS SHALL BE SELECTED BY 13. FOR EXACT QUANTITY, TYPE & LOCATION OF 25. CONTRACTOR SHALL PROVIDE CONTROL CONDUIT &
THE CONTRACTOR IN ACCORDANCE WITH BOQ, ELECTRICAL OUTLETS REFER TO INTERIOR DESIGN WIRING PER OPERATIONAL REQUIREMENTS SHOWN ON
REGULATIONS AND/OR STANDARDS AND WILL BE DOCUMENT. HVAC AND PLUMBING DRAWING.
FUNCTION OF THE NUMBER AND SIZE OF THE RESPECTIVE 14. THE CONTRACTOR SHALL BE RESPONSIBLE FOR 26. EXACT METHOD OF JOINING CABLE TRAYS,AND CABLE
CONDUCTORS. MODIFYING THE NO. OF CIRCUIT BREAKERS, RATING, AND TRUNKING SHALL BE IN ACCORDANCE WITH THE
5. PERFORATED CABLE TRAY SHALL BE FIXED AND COVER WIRING ACCORDING TO MANUFACTURER DATA WITHOUT RESPECTIVE MANUFACTURERS RECOMMENDATION USING
PROPERLY AND SHALL NOT FIXED DIRECT TO ROOF SLAB. ANY EXTRA COST. PROPER COMPONENT.
6. EARTH CONTINUITY CONDUCTORS ARE NOT INDICATED 15. ALL DISCONNECT SWITCHES FOR A/C SHALL BE 27. THE DISTANCE BETWEEN EARTH PIT SHALL BE DOUBLE
ON THE DRAWINGS, BUT SHALL BE RUN WITH ALL CIRCUITS ADJACENT TO THE UNIT.. OR MORE THAN LENGTH OF EARTHING ROD.
IN ACCORDANCE WITH SPECIFICATIONS, REGULATIONS 16. UNLESS OTHERWISE INDICATED MINIMUM SIZE 28. THE CONTRACTOR SHOULD PROVIDE COMPLETE
AND/OR STANDARDS. CONDUIT; CENTRAL INTERFACE BETWEEN THE SOLAR GENERATION
7. THE COLOR CODE FOR A FOUR WIRE CIRCUIT IS - ONE · FOR EXTERIOR INSTALLATION IS 25 MM SYSTEM & GENERATOR SET.
BLACK, - ONE RED, ONE BLUE AND ONE YELLOW ANY DIAMETER OR AS SHOWN IN PANEL SCHEDULE. 29. THE DIMENSION OF ELECTRICAL PANELS AND
CONDUCTOR INTENDED FOR GROUNDING PURPOSE SHALL · FOR INTERIOR INSTALLATION IS 25 MM EQUIPMENT'S SHALL BE AS PER APPROVED FABRICATOR /
BE GREEN WITH YELLOW STRIPE. DIAMETER OR AS SHOWN IN PANEL SCHEDULE. SUPPLIER SHOP DRAWING.
8. CONTRACTOR RESPONSIBLE TO DISCONNECT ALL 17. CONTRACTOR SHALL PROVIDE MATCHING PLUG IN FOR 30. CONTRACTOR SHALL BE RESPONSIBLE FOR INSTALL
WIRING IN EXISTING DISTRIBUTION BOARD AND ALL SPECIAL OUTLETS. SUITABLE VENTILATION SYSTEM IN BATTERY ROOM TO
RECONNECTED IN NEW DISTRIBUTION BOARD AS PER 18. CONTRACTOR RESPONSIBLE FOR CHANGE ALL EXISTING ASSURING REFRESHING AIR FLOW INSIDE ROOM .
SINGLE LINE DIAGRAM. FLORESCENT TUBE (T8) LIGHT BY LED TUBE (T8) INCLUDE 31. CONTRACTOR RESPONSIBLE TO DISTRIBUTE ALL
9. THE CONTROL AND/OR SWITCHBOARDS FOR THE ALL OPERATION ACCESSORIES FOR ALL LIGHTING DISTANCE BETWEEN ALL SYSTEM COMPONENTS INSIDE
DIFFERENT SYSTEMS SUCH AS THE AIR CONDITIONING FIXTURES AS PER BOQ. BATTERY ROOM AS PER MANUFACTURE INSTALLATION
EQUIPMENT MACHINES, .... ETC. WILL BE IN THE SCOPE OF 19. LED LAMPS SHALL BE FURNISHED AND INSTALLED IN INSTRUCTION.

PREPARED BY: FUNED BY: PROJECT TITLE: DRAWING TITLE: DESIGN BY: STATUS: NORTH: DRAWING NO:
MAIN NOTES. TENDER DOCUMENTS.
YEMEN EMERGENCY ELECTRICITY

OPERATIONALEXCELLENCE
FORRESULTSTHATMATTER.
SANA'A-YEMEN.
WORLDBANKGROUP.
ACCESS PROJECT-II

PROJECT LOCATION:
AL-MAHWIT CITY-YEMEN
DRAWING TYPE:
ELECTRIC PLANS.
CHECKED BY:

APPROVED BY:
PROJECT NO:

DATE:
OCTOBER,21,2023
PAPER SIZE:
A3.

SCALE:
AS SHOWEN.
S1-01
1. ALL DIMENSIONS AND ELEVATIONS ARE IN
CENTIMETERS AND METERS RESPECTIVELY,
UNLESS OVER WISE MENTIONED.
2. ALL DIMENSIONS TO BE CHECKED AND CONFIRMED
ON SITE BEFORE COMMENCEMENT OF ANY WORK.
3. ANY DISCREPANCY TO BE REPORTED TO THE
UNOPS SITE ENGINEER/ PROJECT MANAGER
PROMPTLY BEFORE PROCEEDING.
4. ALL OUTDOOR OUTLETS, SOCKET OR WIRING
ACCESSORIES SHALL BE WEATHER PROOF TYPE.
5. ALL DISTANCE BETWEEN SYSTEM COMPONENTS INSIDE
BATTERY ROOM TO BE DISTRIBUTE AS PER MANUFACTURE
INSTALLATION INSTRUCTION.

LEGEND:
SYMBOL DESCRIPTION
CONNECTION BUS BAR BETWEEN
CHARGE CONTROLLER AND BATTERY
RACK

AC≈ BATTERY INVERTER.


DC =
CHARGE CONTROLLER.

BATTERY RACK 2V,1200Ah.

MAIN DISTRIBUTION BOARD WALL


MOUNTED.

MDB MTS MANUAL TRANSFER SWITCH

MTS
EARTHING AC COUPLING PANEL
BUS BAR NO.1

TO EARTHING
BUS BAR NO.3 OUTDOOR LIGHTING
1C*10SQ.MM
TO EARTHING
BUS BAR NO.2
1C*10SQ.MM
VENTILATION CONTROL PANEL
CABLE ROUTING
CABLE TRAY EMERGENCY LIGHT
50MMX50MM

TO LIGHTNING RACK HAS


ARRESTER 2 LAYERS.

HD
1C*25 SQ.MM
WATER PROOF 30W LED OUTDOOR
BOX 15CM X 15CM R
M
A
L
AREIF
L
N
E
A
P
LIGHTING DEVICE

SD
O
NIT
A
LIN
T
E
V N
GIC
O
L
U
PCA
STEEL SINGLE ARM
L
N
E
A
P
L
N
E
A
PRO
C
L
N
T

AC≈
Ø15 cm WITH 20 DEGREE
DC =

NOT SCALED

3
4"PVCPIPE
SCH. 40.

WIRE CONNECTOR ASSORTMENT

NOT SCALED

SCALE: 1:75.
PREPARED BY: FUNED BY: PROJECT TITLE: DRAWING TITLE: DESIGN BY: STATUS: NORTH: DRAWING NO:
FINAL ELECTRIC PLAN DETAILS. TENDER DOCUMENTS.
YEMEN EMERGENCY ELECTRICITY

OPERATIONALEXCELLENCE
FORRESULTSTHATMATTER.
SANA'A-YEMEN.
WORLDBANKGROUP.
ACCESS PROJECT-II

PROJECT LOCATION:
AL-MAHWIT CITY-YEMEN
DRAWING TYPE:
ELECTRIC PLANS.
CHECKED BY:

APPROVED BY:
PROJECT NO:

DATE:
OCTOBER,21,2023
PAPER SIZE:
A3.

SCALE:
1:75.
S1-02
1. ALL DIMENSIONS AND ELEVATIONS ARE IN
CENTIMETERS AND METERS RESPECTIVELY,
UNLESS OVER WISE MENTIONED.
2. ALL DIMENSIONS TO BE CHECKED AND CONFIRMED
ON SITE BEFORE COMMENCEMENT OF ANY WORK.
3. ANY DISCREPANCY TO BE REPORTED TO THE
UNOPS SITE ENGINEER/ PROJECT MANAGER
PROMPTLY BEFORE PROCEEDING.
4. ALL CABLE SHALL BE ROUTE IN PERFORATED GI
CABLE TRAY.
5. CABLE TRAY SHALL BE FIXED ABOVE UNISTRUT NOT
Perforated Cable Tray DIRECT IN ROOFTOP.

100mm x 50mm

COMBINER BOX

100
PHOTOVOLTAIC MODULE

+
+

_
50
GI CABLE TRAY
100MM * 50MM
DC-COMBINER

DC-COMBINER
-

-
BOX-0X COMBINER BOX

BOX-2
COLD FORMED STEEL

+
C CHANNEL

ANCHOR
BOLT SOLAR SINGLE CORE CABLE
1C X 6 SQ.MM (RED COLOR)

-
SOLAR SINGLE CORE CABLE
NOT TO SCALE.

+
1C X 6 SQ.MM (BLACK COLOR)

SOLAR SINGLE CORE CABLE

DC-COMBINER
1C X 35 SQ.MM (RED COLOR)

BOX-1
SOLAR SINGLE CORE CABLE

+
1C X 35 SQ.MM (BLACK
COLOR)
-

-
-

-
+

+
-

-
COVER
PERFORATED CABLE TRAY
CABLE TRAY
+

CABLE TRAY
SUPPORT

ANCHOR
BOLTS

NOT SCALED

SCALE: 1:75.
PREPARED BY: FUNED BY: PROJECT TITLE: DRAWING TITLE: DESIGN BY: STATUS: NORTH: DRAWING NO:
PV MODULE DISTRIBUTION TENDER DOCUMENTS.
YEMEN EMERGENCY ELECTRICITY

S1-03
ROOFTOP PLAN DETAILS.
ACCESS PROJECT-II CHECKED BY: PROJECT NO: PAPER SIZE:
OPERATIONALEXCELLENCE A3.
FORRESULTSTHATMATTER. WORLDBANKGROUP. PROJECT LOCATION: DRAWING TYPE: APPROVED BY: DATE: SCALE:
SANA'A-YEMEN. AL-MAHWIT CITY-YEMEN ELECTRIC PLANS. OCTOBER,21,2023 1:75.
1. ALL DIMENSIONS AND ELEVATIONS ARE IN
CENTIMETERS AND METERS RESPECTIVELY,
UNLESS OVER WISE MENTIONED.
2. ALL DIMENSIONS TO BE CHECKED AND CONFIRMED
ON SITE BEFORE COMMENCEMENT OF ANY WORK.
3. ANY DISCREPANCY TO BE REPORTED TO THE
UNOPS SITE ENGINEER/ PROJECT MANAGER
PROMPTLY BEFORE PROCEEDING.

Perforated Cable Tray 4. LIGHTNING ARRESTER SHALL BE INSTALL IN


SUITABLE LOCATION AND HEIGHT TO COVER ALL
ROOFTOP AREA.
100mm x 50mm 5. ALL EACH PV STRINGS SHALL BE EARTHED
SEPARATELY UP TO EARTHING BUS BAR IN
ROOFTOP.

+
TO LIGHTNING PIT
1C*25SQ.MM

DC-COMBINER
-

BOX-2
PHOTOVOLTAIC MODULE

+
_
+

+
6sqr.mm DC-COMBINER
BOX-0X COMBINER BOX

-
+

+
EARTHING BUS BAR
LIGHTNING ARRESTER
SHALL BE 3 MTR ABOVE
MOUNTING STRUCTURE EARTHING CABLE

DC-COMBINER
-

BOX-1
+

+
LIGHTNING ARRESTOR

-
EARTHING
BUSBAR NO.2

-
+

+
-

-
10 sqr.mm
+

NOT SCALED

SCALE: 1:75.
PREPARED BY: FUNED BY: PROJECT TITLE: DRAWING TITLE: DESIGN BY: STATUS: NORTH: DRAWING NO:
PV STRINGS & COMBINER BOX TENDER DOCUMENTS.
YEMEN EMERGENCY ELECTRICITY

S1-04
EARTHING PLAN DETAILS.
ACCESS PROJECT-II CHECKED BY: PROJECT NO: PAPER SIZE:
OPERATIONALEXCELLENCE A3.
FORRESULTSTHATMATTER. WORLDBANKGROUP. PROJECT LOCATION: DRAWING TYPE: APPROVED BY: DATE: SCALE:
SANA'A-YEMEN. AL-MAHWIT CITY-YEMEN ELECTRIC PLANS. OCTOBER,21,2023 1:75.
1. ALL DIMENSIONS AND ELEVATIONS ARE IN CENTIMETERS
AND METERS RESPECTIVELY, UNLESS OVER WISE
MENTIONED.
2. ALL DIMENSIONS TO BE CHECKED AND CONFIRMED ON
SITE BEFORE COMMENCEMENT OF ANY WORK.
3. ANY DISCREPANCY TO BE REPORTED TO THE UNOPS SITE
ENGINEER/ PROJECT MANAGER PROMPTLY BEFORE
PROCEEDING.
4. ALL OUTDOOR OUTLETS, SOCKET OR WIRING
ACCESSORIES SHALL BE WEATHER PROOF TYPE.
5. ALL DISTANCE BETWEEN SYSTEM COMPONENTS INSIDE BATTERY ROOM
TO BE DISTRIBUTE AS PER MANUFACTURE INSTALLATION INSTRUCTION.
6. AIR FLOW INSIDE BATTERY ROOM SHALL BE CONSIDER
AND MANUFACTURE INSTRUCTION TO TAKE IN ACCOUNT.

MCP Bell CONNECTION BOX BETWEEN


CHARGE CONTROLLER AND
BATTERY RACK

Emergency Exist sign AC≈


BATTERY INVERTER
RACK HAS DC=

2 LAYERS. CHARGE CONTROLLER

HD
BATTERY RACK 2V,2500Ah.

MAIN DISTRIBUTION
FIREALARM
BOARD WALL MOUNTED.
PANEL

INLET FAN

SD
EXHAUST FAN

VENTILATION ACCOUPLING FIRE EXTINGUISHER


CONTROLPANEL PANEL
CONVENTIONAL SMOKE
AC≈ SD
DETECTOR
DC =
CONVENTIONAL HEAT
HD
DETECTOR

CONVENTIONAL FIRE
ALARM PANEL

Bell BELL

MANUAL CALL POINT


MCP (BREAK GLASS)

CEILING MOUNTED LED


LIGHTING

LIGHTING SWITCH.
Note:-
1- Ventilation system and Battery room lighting will be supplied VENTILATIONCONTROLPANEL
from MDB.

SCALE: 1:25.

PREPARED BY: FUNED BY: PROJECT TITLE: DRAWING TITLE: DESIGN BY: STATUS: NORTH: DRAWING NO:
BATTERY ROOM PLAN DETAILS. TENDER DOCUMENTS.
YEMEN EMERGENCY ELECTRICITY

OPERATIONALEXCELLENCE
FORRESULTSTHATMATTER.
SANA'A-YEMEN.
WORLDBANKGROUP.
ACCESS PROJECT-II

PROJECT LOCATION:
AL-MAHWIT CITY-YEMEN
DRAWING TYPE:
ELECTRIC PLANS.
CHECKED BY:

APPROVED BY:
PROJECT NO:

DATE:
OCTOBER,21,2023
PAPER SIZE:
A3.

SCALE:
1:25.
S1-05
1. ALL DIMENSIONS AND ELEVATIONS ARE IN
CENTIMETERS AND METERS RESPECTIVELY,
UNLESS OVER WISE MENTIONED.
2. ALL DIMENSIONS TO BE CHECKED AND CONFIRMED
ON SITE BEFORE COMMENCEMENT OF ANY WORK.
3. ANY DISCREPANCY TO BE REPORTED TO THE
UNOPS SITE ENGINEER/ PROJECT MANAGER
PROMPTLY BEFORE PROCEEDING.
4. EARTHING PIT SHALL BE CARRY OUT AS BE SITE
ENGINEER INSTRUCTION.

100 cm
40 cm

90mm

250mm 60mm

100mm

SCALE: 1:50.
PREPARED BY: FUNED BY: PROJECT TITLE: DRAWING TITLE: DESIGN BY: STATUS: NORTH: DRAWING NO:
EARTHING PIT AND BUSBAR TENDER DOCUMENTS.
YEMEN EMERGENCY ELECTRICITY

S1-06
DETAILS.
ACCESS PROJECT-II CHECKED BY: PROJECT NO: PAPER SIZE:
OPERATIONALEXCELLENCE A3.
FORRESULTSTHATMATTER. WORLDBANKGROUP. PROJECT LOCATION: DRAWING TYPE: APPROVED BY: DATE: SCALE:
SANA'A-YEMEN. AL-MAHWIT CITY-YEMEN ELECTRIC PLANS. OCTOBER,21,2023 AS SHOWEN.
Voltage Rating in AC 230V 1. ALL DIMENSIONS AND ELEVATIONS ARE IN
CENTIMETERS AND METERS RESPECTIVELY,
UNLESS OVER WISE MENTIONED.
Busbar Current Rating 160A 2. ALL DIMENSIONS TO BE CHECKED AND CONFIRMED
ON SITE BEFORE COMMENCEMENT OF ANY WORK.
Busbar Rating 50kA Conditional 3. ANY DISCREPANCY TO BE REPORTED TO THE
UNOPS SITE ENGINEER/ PROJECT MANAGER
Fully shrouded PROMPTLY BEFORE PROCEEDING.
Busbar Type 4. EARTHING PIT SHALL BE CARRY OUT AS BE SITE
copper and tinned ENGINEER INSTRUCTION.

Inside View Front View Side View

63 A , 15 kA 63 A , 15 kA MDB
32 A , 15 kA 40 A , 15 kA

32 A , 15 kA 40 A , 15 kA

32 A , 15 kA 40 A , 15 kA

32 A , 15 kA 32 A , 15 kA

20 A , 15 kA 32 A , 15 kA

20 A , 15 kA 32 A , 15 kA
20 A , 15 kA
Ventilation 32 A , 15 kA
System
16 A , 15 kA

50
20 A , 15 kA Battery room
Lighting
20 A , 15 kA 16 A , 15 kA
Fire Alarm Panel

ABB
DDA204 AC
In=0.3A

PUSH

RCBO
100A,300mA N

SCALE: 1:50.
PREPARED BY: FUNED BY: PROJECT TITLE: DRAWING TITLE: DESIGN BY: STATUS: NORTH: DRAWING NO:
MAIN DISTRIBUTION BOARD TENDER DOCUMENTS.
YEMEN EMERGENCY ELECTRICITY

S1-07
DETAILS.
ACCESS PROJECT-II CHECKED BY: PROJECT NO: PAPER SIZE:
OPERATIONALEXCELLENCE A3.
FORRESULTSTHATMATTER. WORLDBANKGROUP. PROJECT LOCATION: DRAWING TYPE: APPROVED BY: DATE: SCALE:
SANA'A-YEMEN. AL-MAHWIT CITY-YEMEN ELECTRIC PLANS. OCTOBER,21,2023 AS SHOWEN.
1. ALL DIMENSIONS AND ELEVATIONS ARE IN
CENTIMETERS AND METERS RESPECTIVELY,
UNLESS OVER WISE MENTIONED.
2. ALL DIMENSIONS TO BE CHECKED AND CONFIRMED
ON SITE BEFORE COMMENCEMENT OF ANY WORK.
3. ANY DISCREPANCY TO BE REPORTED TO THE
UNOPS SITE ENGINEER/ PROJECT MANAGER
PROMPTLY BEFORE PROCEEDING.

PV Module Combiner Box Battery Charger Off Grid Inverter Integration With Changeover 4. NEW DISTRIBUTION BOARD SHALL BE INSTALL IN
THE SAME LOCATION OF EXISTING ONE.

Connection Switch and Single Line Diagram


DG
PHOTOVOLTAIC MODULE

+
_
AC≈
BATTERY INVERTER
DC=
Total: 1.1 to 1.34Kwp
2 PV MODULE
STR NO.1

MANUAL CHANGE OVER


_
+

80 A 85A to 100A
ISC:10 kA 150 to 300 VDC
CLASS B 1x35 SQ.mm
SOLAR CABLE XPLE/PVC/CU1.0KV
XPLE/PVC/CU1.0KV XPLE/PVC/AL1.0KV CHARGE CONTROLLER
Off Grid Inverter 4X6 SQ.mm
Total: 1.1 to 1.34Kwp

2 CABLES (RED& BLACK) 3X10 SQ.mm


2x16 SQ.mm
2 PV MODULE

40A 2P 40A 2P
STR NO.2

10KVA
RCCB,300mA MCCB,25KA
AC≈ HYBRID SOLAR SYSTEM INVERTER OUTPUT
SURGE ARRESTER
_

DC =
+

SPD SPD
CIRCUIT BREAKER (MCB)
1x35SQ.mm 1x70 SQ.mm
Total: 1.1 to 1.34Kwp

XPLE/PVC/CU1.0KV
2 PV MODULE
STR NO.3

(RED& BLACK) (RED& BLACK) 3X10 SQ.mm


CIRCUIT BREAKER (RCCB)
_
+

NEW MDB
250A,2P DC FUSE
1x70 SQ.mm
(RED& BLACK)
Total: 1.1 to 1.34Kwp

POSITIVE & NEGATIVE


2 PV MODULE
STR NO.4

CONNECTION BUS BAR


Bus Bar 340A
_
+

Positive & Negative DC BREAKER (SWITCH


80 A 85A to 100A EARTH PIT
ISC:10 kA 150 to 300 VDC ISOLATOR)
CLASS B 1x35 SQ.mm
SOLAR CABLE 1x35SQ.mm
2 CABLES (RED& BLACK)
(RED& BLACK)
DC FUSE
Total: 1.1 to 1.34Kwp
2 PV MODULE
STR NO.5

1x70SQ.mm 1x70 SQ.mm


(RED) (BLACK)
_
+

SPD SPD

250 A, 2P Shunt
Battery Rack
Total: 1.1 to 1.34Kwp
2 PV MODULE
STR NO.6

_
+

1x70 SQ.mm

24 Batteries
2V ,1200 Ah
EARTH PIT
48 Volt

PREPARED BY: FUNED BY: PROJECT TITLE: DRAWING TITLE: DESIGN BY: STATUS: NORTH: DRAWING NO:
SOLAR SYSTEM SCHEMATIC TENDER DOCUMENTS.
YEMEN EMERGENCY ELECTRICITY

S1-08
DIAGRAM DETAILS.
ACCESS PROJECT-II CHECKED BY: PROJECT NO: PAPER SIZE:
OPERATIONALEXCELLENCE A3.
FORRESULTSTHATMATTER. WORLDBANKGROUP. PROJECT LOCATION: DRAWING TYPE: APPROVED BY: DATE: SCALE:
SANA'A-YEMEN. AL-MAHWIT CITY-YEMEN ELECTRIC PLANS. OCTOBER,21,2023 AS SHOWEN.
STRUCTURAL PLANS.
PROJECT:

SUPPLY AND INSTALL OF OFF-GRID SOLAR SYSTEM FOR


GHAWIAH HEALTH CENTER.
FUNDED BY:

WORLD BANK GROUP.


OCTOBER, 2023.

DRAWING LIST:-
N RA N T TL
S MOUNTING STRUCTURE GENERAL SITE PLAN DETAILS.
C1
C1

C1
C1

SCALE: 1:75.
PREPARED BY: FUNED BY: PROJECT TITLE: DRAWING TITLE: DESIGN BY: STATUS: NORTH: DRAWING NO:
MOUNTING STRUCTURE GENERAL TENDER DOCUMENTS.
YEMEN EMERGENCY ELECTRICITY

S2-01
SITE PLAN DETAILS.
ACCESS PROJECT-II CHECKED BY: PROJECT NO: PAPER SIZE:
OPERATIONALEXCELLENCE A3.
FORRESULTSTHATMATTER. WORLDBANKGROUP. PROJECT LOCATION: DRAWING TYPE: APPROVED BY: DATE: SCALE:
SANA'A-YEMEN. AL-MAHWIT CITY-YEMEN ELECTRIC PLANS. OCTOBER,21,2023 1:75.