Operating instructions

For the operator

Operating instructions

flexoTHERM exclusive
VWF 57 - 197/4, VWF 57 - 117/4 230V

GB, IE

Publisher/manufacturer
Vaillant GmbH
Berghauser Str. 40 D-42859 Remscheid
Tel. +49 21 91 18‑0 Fax +49 21 91 18‑2810
info@vaillant.de www.vaillant.de
Contents
Contents 6.3 Reading maintenance
messages .................................... 13
1 Safety ............................................ 3 6.4 Checking the system pressure .... 13
1.1 Action-related warnings ................. 3 6.5 Checking the brine circuit's
1.2 Intended use .................................. 3 filling pressure.............................. 13
1.3 General safety information............. 4 7 Troubleshooting ........................ 13
2 Notes on the documentation ...... 7 7.1 Fault message ............................. 13
2.1 Observing other applicable 8 Decommissioning...................... 14
documents ..................................... 7 8.1 Switching off the heat pump ........ 14
2.2 Storing documents......................... 7 8.2 Permanently decommissioning
2.3 Applicability of the instructions....... 7 the product................................... 14
3 System overview.......................... 7 8.3 Recycling and disposal ................ 14
3.1 Heat pump system design ............. 7 9 Guarantee and customer
4 Product description..................... 8 service ........................................ 15
4.1 Product design............................... 8 9.1 Guarantee.................................... 15
4.2 Serial number ................................ 8 9.2 Customer service......................... 15
4.3 Opening the front flap .................... 8 Appendix ............................................... 16
4.4 Operator control panel ................... 8 A Overview of the operator's
operating level ........................... 16
4.5 CE label ......................................... 9
4.6 Safety devices ............................... 9
5 Operating.................................... 10
5.1 Basic display................................ 10
5.2 Operating concept ....................... 11
5.3 Menu display................................ 11
5.4 Operating levels........................... 11
5.5 Starting up the product ................ 12
5.6 Adjusting the target cylinder
temperature ................................. 12
5.7 Yield indicator .............................. 12
5.8 Displaying the Live Monitor.......... 12
5.9 Displaying the building circuit
pressure....................................... 12
5.10 Displaying the environment
circuit pressure ............................ 12
5.11 Reading the operating
statistics ....................................... 12
5.12 Setting the language.................... 12
6 Maintenance and care ............... 13
6.1 Fulfilling requirements for the
installation site ............................. 13
6.2 Caring for the product .................. 13

2 Operating instructions flexoTHERM exclusive 0020213396_02


Safety 1
1 Safety The system is intended as a
1.1 Action-related warnings heat generator with cooling
function for closed heating
Classification of action-re- installations and for hot wa-
lated warnings ter generation. Operation of
The action-related warnings the pump outside the applica-
are classified in accordance tion limits results in the heat
with the severity of the pos- pump being switched off by
sible danger using the following the internal control and safety
warning signs and signal words: devices.
Warning symbols and signal Cooling mode with radiator
words heating systems is not permit-
Danger! ted since radiators do not have
Imminent danger to life an adequate heat transfer sur-
or risk of severe personal face area.
injury
Intended use includes the fol-
Danger! lowing:
Risk of death from electric
– observance of the operating
shock
instructions included for the
Warning. product and any other system
Risk of minor personal components
injury – compliance with all inspection
Caution. and maintenance conditions
Risk of material or envir- listed in the instructions.
onmental damage This product can be used by
1.2 Intended use children aged from 8 years
and above and persons with
There is a risk of injury or death
reduced physical, sensory or
to the user or others, or of dam-
mental capabilities or lack of
age to the product and other
experience and knowledge if
property in the event of im-
they have been given supervi-
proper use or use for which it
sion or instruction concerning
is not intended.
use of the product in a safe way
The system is intended exclus- and understand the hazards in-
ively for domestic use. volved. Children must not play
with the product. Cleaning and

0020213396_02 flexoTHERM exclusive Operating instructions 3


1 Safety
user maintenance work must petrol, paper, paint) in the in-
not be carried out by children stallation room of the product.
unless they are supervised.
1.3.3 Risk of death due
Any other use that is not spe- to changes to the
cified in these instructions, or product or the product
use beyond that specified in this environment
document shall be considered
▶ Never remove, bridge or
improper use. Any direct com-
block the safety devices.
mercial or industrial use is also
▶ Do not tamper with any of the
deemed to be improper.
safety devices.
Caution. ▶ Do not damage or remove
Improper use of any kind is any seals on components.
prohibited. Only authorised competent
1.3 General safety persons or customer services
information may modify sealed compon-
ents.
1.3.1 Danger caused by
▶ Do not make any changes to:
improper operation
– The product itself
Improper operation may present – The product environment
a danger to you and others, and – The brine fluid, air and elec-
cause material damage. tricity supply lines
▶ Carefully read the enclosed – The drain line and expan-
instructions and all other ap- sion relief valve for the heat
plicable documents, particu- source circuit
larly the "Safety" section and – The constructional condi-
the warnings. tions that may affect the
▶ Only carry out the activities operational reliability of the
for which instructions are product
provided in these operating
instructions. 1.3.4 Risk of injury due to
chemical burns caused
1.3.2 Risk of death due to by brine fluid
explosive and flammable
The brine fluid ethylene glycol is
materials
harmful to health.
▶ Do not use or store explosive ▶ Avoid contact with the skin
or flammable materials (e.g. and eyes.

4 Operating instructions flexoTHERM exclusive 0020213396_02


Safety 1
▶ Always wear gloves and pro- ▶ Faults and damage should
tective goggles. be immediately rectified by a
▶ Do not inhale or swallow. competent person.
▶ Observe the safety data sheet ▶ Adhere to the maintenance
that accompanies the brine intervals specified.
fluid.
1.3.7 Risk of material damage
1.3.5 Preventing the risk of caused by frost
injury from freezing ▶ Ensure that the heating in-
as a result of touching stallation always remains in
coolant operation during freezing con-
The product is supplied with an ditions and that all rooms are
operational filling of R 410 A sufficiently heated.
refrigerant. Escaping coolant ▶ If you cannot ensure the op-
may cause freezing if the exit eration, have a competent
point is touched. person drain the heating in-
▶ If coolant escapes, do not stallation.
touch any components of the 1.3.8 Avoid environmental
product. damage caused by
▶ Do not inhale any vapours or escaping coolant
gases that escape from the
The product contains R 410 A
refrigerant circuit as a result
refrigerant. The coolant must
of leaks.
not be allowed to escape into
▶ Avoid skin or eye contact with
the atmosphere. R410A is a
the coolant.
fluorinated greenhouse gas
▶ In the event of skin or eye
covered by the Kyoto Protocol,
contact with the coolant, seek
with a GWP of 2088 (GWP =
medical advice.
global warming potential). If
1.3.6 Risk of injury and this gas escapes into the atmo-
material damage due to sphere, its impact is 2088 times
maintenance and repairs greater than the natural green-
carried out incorrectly or house gas CO2.
not carried out at all Before the product is disposed
▶ Never attempt to carry out of, the coolant that is contained
maintenance work or repairs in it must be completely drained
on your product yourself. into a suitable vessel so that

0020213396_02 flexoTHERM exclusive Operating instructions 5


1 Safety
it can then be recycled or dis-
posed of in accordance with
regulations.
▶ Ensure that only officially cer-
tified competent persons with
appropriate protective equip-
ment carry out maintenance
work on the refrigerant circuit
or access it.
▶ Arrange for the refriger-
ant that is contained in the
product to be recycled or
disposed of by a certified
competent person in accord-
ance with the regulations.

6 Operating instructions flexoTHERM exclusive 0020213396_02


Notes on the documentation 2
2 Notes on the 3 System overview
documentation 3.1 Heat pump system design
2.1 Observing other applicable
documents
▶ You must observe all operating instruc-
tions enclosed with the system compon-
ents.

2.2 Storing documents


▶ Keep this manual and all other applic-
able documents safe for future use.

2.3 Applicability of the


instructions
These instructions apply only to:
Applicability: Great Britain
OR Ireland

Product
VWF 57/4
VWF 87/4
VWF 117/4
VWF 157/4
VWF 197/4
A

Applicability: Great Britain B

OR Ireland

Product
VWF 57/4 230 V
VWF 87/4 230 V
VWF 117/4 230 V
A

The heat pump system consists of the


following components:
– Heat pump
– System controller (from VRC 700)
– Outside temperature sensor with DCF
receiver
– System sensor, if required
– With ground heat source: Ground
sensor

0020213396_02 flexoTHERM exclusive Operating instructions 7


4 Product description
– For the air heat source (only products 4.3 Opening the front flap
with 400 V): Air/brine collector(s) 1. Take hold of the recessed handle in
– With well water heat source: Groundwa- the front flap on the left- or right-hand
ter module side.
There is an opportunity for active cooling 2. Pull the recessed handle.
to take place via circulation reversal for the
heat sources air, ground and groundwater. 4.4 Operator control panel

4 Product description 9

4.1 Product design


1

1
8

7
50 kWh
d
2

6
4

3 5

1
4
2
reset

1 Displays the 5 Reset button


daily environ- 6 Access to the
1 Front flap 3 Control elements mental energy menu for addi-
2 Recessed 4 Plate showing yield tional information
handle the serial num- 2 Display of the 7 Display of the
ber current as- current configur-
signment of ation of the left-
4.2 Serial number the right-hand hand selection
selection button button
The serial number is located on a plate be- 3 Left- and right- 8 Displays the
hind the front flap. The 7th to 16th digits of hand selection symbols for the
the serial number form the article number. buttons current operat-
4 and but- ing status of the
ton heat pump
9 Display

8 Operating instructions flexoTHERM exclusive 0020213396_02


Product description 4
4.5 CE label 4.6.5 Pump- and valve-blocking
protection system
This function prevents the pumps for heat-
ing water and brine and all diverter valves
The CE label shows that the products from sticking. The pumps and the valves,
comply with the basic requirements of the which were out of operation for 23 hours,
applicable directives as stated on the iden- are switched on for 10 - 20 seconds, one
tification plate. after the other.
The declaration of conformity can be
viewed at the manufacturer's site. 4.6.6 High-pressure pressure switch
in the refrigeration circuit
4.6 Safety devices
The high-pressure pressure switch shuts
4.6.1 Frost protection function down the heat pump if the pressure in the
The frost protection function for the system coolant circuit is too high. If the pressure
is controlled via the system controller. If in the heat pump's refrigeration circuit ex-
the system controller fails, the heat pump ceeds the maximum pressure, the high-
guarantees limited frost protection for the pressure pressure switch temporarily shuts
heating circuit. down the heat pump. Following a waiting
period, another attempt is made to start
4.6.2 Protection against low heating the heat pump. After three failed start at-
water pressure tempts in succession, a fault message is
This function continuously monitors the displayed.
pressure of the heating water in order to – Refrigeration circuit pressure max.: 4.60
prevent a possible loss of heating water. MPa (g) (46.00 bar (g))
– Waiting period: 5 minutes (after the first
4.6.3 Brine loss protection system occurrence)
The brine loss protection system continu- – Waiting period: 30 minutes
ously monitors the fluid pressure in the (after the second and every further oc-
environment circuit in order to prevent a currence)
possible shortage of fluid. The fault counter is reset if both of the
4.6.4 Freeze protection following conditions are met:

This function prevents the evaporator from – Heat requirement without switching off
freezing when the heat source temperat- prematurely
ure drops below a certain value. – 60 minutes of uninterrupted operation
The outlet temperature of the heat source 4.6.7 Hot gas thermostat in the
is constantly measured. If the outlet tem- refrigeration circuit
perature of the heat source falls below a
certain value, the compressor temporarily The hot gas thermostat shuts down the
switches off and displays a status mes- heat pump if the temperature in the refri-
sage. If this fault occurs three times in a geration circuit is too high. If the temperat-
row, it is switched off and a fault message ure in the heat pump's refrigeration circuit
is displayed. exceeds the maximum temperature, the
hot gas thermostat temporarily shuts down
the heat pump. Following a waiting period,
another attempt is made to start the heat

0020213396_02 flexoTHERM exclusive Operating instructions 9


5 Operating
pump. After three failed start attempts in Sym- Meaning Explanation
succession, a fault message is displayed. bol
– Max. refrigeration circuit temperature: Compressor – Filled: Com-
135 ℃ pressor in op-
eration
– Waiting period: 5 minutes (after the first – Not filled:
occurrence) Compressor
– Waiting period: 30 minutes not in
(after the second and every further oc- operation
currence) bar Current filling – Permanently
pressure of the on: Filling
The fault counter is reset if both of the heating system pressure in
following conditions are met: The dashed lines the permitted
– Heat requirement without switching off show the permit- range.
prematurely ted range. – Flashing:
Filling pres-
– 60 minutes of uninterrupted operation
sure outside
4.6.8 Safety cut-out (SCO) in the the permitted
range.
heating circuit
Pumps – Left continu-
If the temperature in the heating circuit of ously on: Brine
the internal auxiliary electric heating ex- pump in oper-
ceeds the maximum temperature, the SCO ation
shuts down the auxiliary electric heating as – Right con-
a securing measure. Following a waiting tinuously on:
Heating pump
period, another attempt is made to start
in operation
the auxiliary electric heating. A fault mes-
Auxiliary electric – Flashing: Aux-
sage is displayed that can only be reset by
heating iliary electric
pressing the Reset button or by switching heating in op-
the heat pump off and on again. eration
– Max. heating circuit temperature: 85 ℃ – + : Aux-
iliary electric
heating act-
5 Operating ive for heating
mode
5.1 Basic display – + : Aux-
iliary electric
heating active
for hot water

50 kWh
d Green iQ mode
handling mode
– Product
equipped with
energy-saving
technology
Heating mode – Continuously
on: Heating
mode active

10 Operating instructions flexoTHERM exclusive 0020213396_02


Operating 5
Sym- Meaning Explanation Op- Function
bol erator
Cooling mode – Continuously control
on: Cooling element
mode active + – Calling up the menu
(active or at the
passive) same
Hot water gener- – Continuously time
ation on: Hot water or – Reducing or increasing the set
handling mode value
active – Scrolling through menu entries
Fault in the – Appears in-
product stead of the The current function of the and selec-
F.XXX
basic display, tion buttons is shown on the display.
may be an ex- Adjustable values are always displayed as
planatory plain flashing.
text display
You must always confirm a change to a
The basic display shows you the product's value. Only then is the new setting saved.
operating mode. If you press a selection You can press to cancel a procedure at
button, the activated function is displayed any time.
in the display.
You can switch back to the basic display
5.3 Menu display
by: 4
Xxxx 1
– Pressing to exit the selection levels Xxxxxxxxxxx
– Not pressing any button for longer than Xxxx Xxxxxxx
3
15 minutes. Xxxxxxxxxx
If there is a fault message present, the ba- xxxxxx Xxxxxxx
sic display switches to the fault message.
2

5.2 Operating concept 1 Scroll bar 3 Selection level


Op- Function 2 Current assign- list entries
erator ment of the se- 4 Selection level
control lection buttons
element You can find an overview of the menu
– Displaying the environmental structure in the appendix.
energy yield in heating mode,
hot water handling mode and 5.4 Operating levels
cooling mode
– Cancelling a change to a set
The product has two operating levels.
value The operating level for the operator shows
– Going one selection level the information and offers set-up options
higher that do not require any special prior know-
– Confirm setting ledge.
– Going one selection level lower The operating level for the competent per-
son is protected by a code.
Overview of the operator's operating level
(→ Page 16)

0020213396_02 flexoTHERM exclusive Operating instructions 11


5 Operating
5.5 Starting up the product 5.8 Displaying the Live Monitor
▶ Only start up the product once the cas- Menu → Live Monitor
ing has been completely closed. – You can use the Live Monitor to display
the current status of the product.
5.6 Adjusting the target cylinder
temperature 5.9 Displaying the building circuit
In order to achieve energy-efficient hot pressure
water generation predominantly from the Menu → Live Monitor→ Building circuit
energy extracted from the environment, pressure
the factory setting for the desired hot water
– Current filling pressure of the heating
temperature must be adjusted on the sys-
system
tem controller.
▶ To do this, adjust the cylinder set target 5.10 Displaying the environment
temperatures (Desired DHW circuit circuit pressure
temperature) to between 50 and 55 °C, Menu → Live Monitor→ Environment
for example. circuit pressure
◁ Depending on the source of energy – Current filling pressure in the environ-
obtained from the environment, ment circuit
hot water output temperatures of
between 55 and 62 °C are reached. 5.11 Reading the operating
statistics
5.7 Yield indicator
Menu → Information → Heating op.
Displays the environmental energy yield as hours
a cumulative value for a period of a day,
a month and the total for the heating, hot Menu → Information → DHW operating
water generation and cooling modes. hours
Displays the working figure for a period of Menu → Information → Cooling op.
a month and the total for the heating and hours
hot water generation modes. The work- Menu → Information → Total operating
ing figure is the ratio of thermal energy hours
generated to the operating current used. Operating hours for heating mode, hot
Monthly values may vary considerably water handling mode, cooling mode and
since, for example, in the summer only the overall operation
hot water generation is used. A large num-
ber of factors influence this estimate, e.g. 5.12 Setting the language
the type of heating installation (direct heat- Menu → Basic settings → Language
ing mode = low flow temperature or indir-
– Setting the desired language
ect heating mode via buffer cylinder = high
flow temperature). This figure may there-
fore deviate by up to 20%.
The working figures only record the power
consumption of internal components, not
of external components such as external
heating circuit pumps, valves, etc.

12 Operating instructions flexoTHERM exclusive 0020213396_02


Maintenance and care 6
6 Maintenance and care 6.4 Checking the system pressure

6.1 Fulfilling requirements for the


▶ Check the filling pressure of the heating
installation every day for a week after
installation site initial start-up and maintenance work,
The installation site must be dry and frost- and then twice a year.
proof throughout. – Filling pressure: ≥ 0.07 MPa
Conditions: Outdoor air heat source (≥ 0.70 bar)
Filling pressure too low
The air/brine collector is designed to be ▶ Inform your competent person so
operated with outdoor air. The air intake that he can add heating water and
and blow-off route of the outdoor unit must increase the filling pressure.
be kept clear at all times in order to guar-
antee that the air can flow unhindered and 6.5 Checking the brine circuit's
as intended. Vegetation and, in winter, filling pressure
snowfall, must be cleared.
▶ Check the brine circuit's filling pressure
You are not permitted to make any sub- at regular intervals. Read the brine cir-
sequent structural alterations which cuit's filling pressure in the heat pump's
may result in a reduced room volume display.
or a change to the temperature at the – Brine fluid operating pressure range:
installation site. 0.07 … 0.20 MPa (0.70 … 2.00 bar)
6.2 Caring for the product
Caution. 7 Troubleshooting
Risk of material damage 7.1 Fault message
caused by unsuitable clean-
ing agents. Note
If the heat pump has switched off
▶ Do not use sprays, scouring automatically due to a fault, the
agents, detergents, solvents system controller can be used to
or cleaning agents that con- activate a limp home mode with the
tain chlorine. electric auxiliary heating.

▶ Clean the casing with a damp cloth and If several faults occur at the same time,
a little solvent-free soap. the display shows the corresponding fault
messages for two seconds each in alterna-
6.3 Reading maintenance tion.
messages F.714 Environment circuit: Pressure too
If the symbol is shown in the display, low
the product requires maintenance work. If the filling pressure falls below the min-
The product is not in fault mode; it contin- imum pressure, the heat pump will be
ues to operate. switched off automatically.
▶ Consult a competent person. – Minimum brine fluid pressure:
≥ 0.05 MPa (≥ 0.50 bar)
– Min. brine fluid operating pressure:
≥ 0.07 MPa (≥ 0.70 bar)

0020213396_02 flexoTHERM exclusive Operating instructions 13


8 Decommissioning
▶ Inform your competent person so that 8.2 Permanently
he can top up the brine fluid. decommissioning the product
F.723 Building circuit: Pressure too low 1. Have a competent person permanently
If the filling pressure falls below the min- decommission the product.
imum pressure, the heat pump will be 2. Have the product disposed of by a
switched off automatically. competent person.
– Min. heating circuit pressure: 8.3 Recycling and disposal
≥ 0.05 MPa (≥ 0.50 bar)
– Min. heating circuit operating pressure: ▶ The competent person who installed
≥ 0.07 MPa (≥ 0.70 bar) your product is responsible for the dis-
posal of the packaging.
▶ Inform your competent person so that
he can top up the heating water.
If the product is identified with this
F.1120 Heating rod: Phase failure symbol:
The product has an internal circuit breaker ▶ In this case, do not dispose of the
which switches off the heat pump in the product with the household waste.
event of short circuits or the failure of ▶ Instead, hand in the product to a collec-
one (product with 230 V power supply) or tion centre for old electrical or electronic
several (product with 400 V power supply) appliances.
current-carrying phases. This may be
caused by a defect in the internal auxiliary If the product contains batteries that
electric heater, for example. are marked with this symbol, these bat-
If the auxiliary electric heater is defective, teries may contain substances that are
the Anti-legionella function is not guaran- hazardous to human health and the envir-
teed. onment.
▶ Inform your competent person so that ▶ In this case, dispose of the batteries at
they can rectify the fault and reset the a collection point for batteries.
internal circuit breaker.
8.3.1 Arranging disposal of the
brine fluid
8 Decommissioning The product is filled with the brine fluid
8.1 Switching off the heat pump ethylene glycol, although when using
ground as the heat source, aqueous
8.1.1 Temporarily decommissioning solutions of propylene glycol may also be
the product used as an alternative. Ethylene glycol is
▶ Use the partition that is installed on- harmful to health.
site (e.g. fuses or power switches) to ▶ Brine fluid must only be disposed of by
disconnect the product from the power a qualified competent person.
supply.
8.3.2 Arranging disposal of coolant
8.1.2 Protecting the product against The product is filled with R 410 A refriger-
frost ant.
▶ Observe the installation site require- The coolant must not be allowed to escape
ments for the product. (→ Page 13) into the atmosphere.

14 Operating instructions flexoTHERM exclusive 0020213396_02


Guarantee and customer service 9
▶ Coolant must only be disposed of by a ance. In order to qualify for guarantee after
qualified competent person. one year the appliance must be serviced
in accordance with our installation manual
servicing instructions. The benchmark ser-
9 Guarantee and customer vice history should be completed. Note -
service all costs associated with this service are
excluded from this guarantee.
9.1 Guarantee Failure to install and commission this ap-
Applicability: Great Britain pliance in compliance with the manufac-
turer’s instructions will invalidate the guar-
Vaillant provides a full parts and labour
antee (this does not affect the customer’s
guarantee for this appliance for the dura-
statutory rights).
tion as shown on the enclosed registration
card which must be fully completed and 9.2 Customer service
returned within 30 days of installation. All
Applicability: Great Britain
appliances must be installed by a suitably
competent person fully conversant and To ensure regular servicing, it is strongly
in accordance with all current regulations recommended that arrangements are
applicable to the appliance type installa- made for a Maintenance Agreement.
tion. In the case of gas appliances the Gas Please contact Vaillant Service Solutions
Safety (Installation and Use) Regulations for further details:
1998, and the manufacturer’s instructions. Telephone: 0330 100 3461
In the UK competent persons approved at
the time by the Health and Safety Execut-
ive undertake the work in compliance with
safe and satisfactory standards. Installers
should also be fully conversant with and
competent with all necessary electrical and
building regulations that may apply to the
installation.
In addition all unvented domestic hot water
cylinders must be installed by a compet-
ent person to the prevailing building regu-
lations at the time of installation (G3). All
appliances shall be fully commissioned in
accordance with our installation manual
and Benchmark commissioning check list
(this will be included within the installa-
tion manual). These must be signed and
given to the user for safe keeping during
the hand over process. Installers should
also at this time advise the user of the an-
nual servicing requirements and advise of
appropriate service agreement.
Terms and conditions do apply to the guar-
antee, details of which can be found on the
registration card included with this appli-

0020213396_02 flexoTHERM exclusive Operating instructions 15


Appendix
Appendix
A Overview of the operator's operating level
Setting level Values Unit Increment, se- Default Setting
Min. Max. lect setting
Yield indicator →
Energy yield: Day, Cumulative kWh
Heating value
Energy yield: Day, Do- Cumulative kWh
mestic hot water value
Energy yield: Day, Cumulative kWh
Cooling value
Energy yield: Month, Cumulative kWh
Heating value
Working figure: Month, Cumulative
Heating value
Energy yield: Total, Cumulative kWh
Heating value
Working figure: Total, Cumulative
Heating value
Energy yield: Month, Cumulative kWh
Domestic hot water value
Working figure: Month, Cumulative
Domestic hot water value
Energy yield: Total, Cumulative kWh
Domestic hot water value
Working figure: Total, Cumulative
Domestic hot water value

Live Monitor →
Current status mes- Current value
sage(s)
Building circuit pres- Current value bar
sure
Environment circuit Current value bar
pressure
Switch-on delay Current value min
Flow temp. setpoint Current value ℃
Current flow temp. Current value ℃
Energy integral Current value °min
Environment circuit Current value ℃
inlet temperature
Environment circuit Current value ℃
outlet temperature
Cooling capacity Current value kW

16 Operating instructions flexoTHERM exclusive 0020213396_02


Appendix
Setting level Values Unit Increment, se- Default Setting
Min. Max. lect setting
Electrical power con- Current value kW Total power
sumption consumption of
the heat pump
without any ex-
ternal compon-
ents connected
(as-delivered
condition).
Heating rod power Current value kW

Information →
Contact data Phone number
Serial number Permanent
value
Operating hours total Cumulative h
value
Hours heating Cumulative h
value
DHW operating hours Cumulative h
value
Cooling op. hours Cumulative h
value

Basic settings →
Language Current lan- Languages avail- 02 English
guage able for selection
Display contrast Current value 1 25
15 40
Resets →
Reset anti-cycl. time – Cancel reset Yes/No
anti-cycl. time?

0020213396_02 flexoTHERM exclusive Operating instructions 17


0020213396_02 29.04.2016
Vaillant Ltd.
Nottingham Road Belper Derbyshire DE56 1JT
Telephone 0330 100 3461
info@vaillant.co.uk www.vaillant.co.uk

© These instructions, or parts thereof, are protected by copyright and may be


reproduced or distributed only with the manufacturer's written consent.
We reserve the right to make technical changes.