PCTVAU2301

Heat Pump / Heat Recovery 50 Hz

Offers a wide variety of new functions that benefit


Indoor Unit Overview
Contents
everyone involved New Products Information
3
7
9
VRV Development History
13
First launched in Japan in 1982, the Daikin VRV system has been VRV User Benefits
17
embraced by world markets for almost 40 years. Daikin proudly VRV Overview
introduces the advanced VRV system. We provide higher benefits 39
VRV R Series
to various users related to air conditioning systems, for example, 57
VRV H Series
building owners, consultants, installers and even building 69
VRV S High Seasonal Efficiency Series VRV IV S Series
management. 77
VRV IV Q Series
93
VRV IV W Series
107 115
VRV WS Series

For OWNERS For CONSULTANTS For BUILDING FXCQ-B FXNQ-MA Middle Static Pressure Duct

FXEQ-A BSQ-A,BS-Q14B/A Middle Static Pressure Duct

FXDQ-PD/ND Air Handling Unit Middle-High Static Pressure Duct High Static Pressure

FXDQ-T
Air Treatment Equipment Control Systems Duct
Option
FXSQ-PA 4-Way Flow Ceiling Suspended Ceiling Suspended
Engineering Supports
MANAGEM FXDYQ-MA Type Wall Mounted

For ENTS FXMQ-PA Round Flow Cassette with Sensing and Streamer Round Floor Standing
INSTALLERS VRV Indoor Units
FXMQ-P Flow Cassette with Sensing Round Flow Cassette Concealed Floor Standing
FXFTQ-A
FXUQ-A BS Units
FXFSQ-A Compact Multi Flow Cassette Double Flow Cassette
117 123 129 133 135 137 139 141 143
FXHQ-MA/B
FXFQ-A Single Flow Cassette
145 147 149 151 153 155 157 158 159
FXAQ-A
FXZQ-B Slim Duct (Standard)
163 165 183 199 217
FXLQ-MA
Slim Duct (Compact)

Lifecycle Cost & R


Comfort eliability & Comfort
*VRV is a trademark of Daikin Industries, Ltd.

Easy Installation

Flexible Design & Engineering Supports


12

Round Flow Cassette with Sensing and Streamer Type


New Products Information Page
Page
117

Comfort, energy savings by sensing


functions and enhanced maximum
Heat Recovery Heat Pump VRV R Series VRV H Series
Promotion Movie Promotion Movie efficiency in cleaning
VRV R Series Special Site
Built-in streamer function unit for efficient
17 cleaning function Daikin advanced sensing
Page technology dual sensors Individual airflow FXFTQ-A
VRV H Series Special Site
39 direction control

Outdoor-Air Processing Unit FXMQ-AF


Series
Featuring unique functions in a new large Improve IAQ with fresh air ventilation and precise room
capacity casing temperature control

Adopt a new casing to realise a single module of up to 24


class Achieved significant energy savings with improved
technology Defrost functions improved comfort by Page

extending the heating operation time 169


Design flexibility is further improved by simultaneous
extension of height difference and equivalent length.
Sealed electrical component box (IP55) blocks
the ingress of debris
Outdoor-Air Processing Unit

or water, that leads to unexpected failures. Page 183 Special


Outdoor Air Supply Air (Discharge Air) Site
A new electrical component service window
on the front panel allows easy access to the main New be achieved.
board without removing the front panel. Equipped Casing
Heat Exchanger
with various new functions, the new model shows a
significant improvement in total performance.
REYQ-B RXYQ-B
Set point temperature can be selected similar to
standard VRV indoor unit.
Maximum connection ratio increased from 100% to
130%. Stylish Remote
With the VRT control feature, higher efficiency can
Controller
Comfort
Energy Savings
A complete redesigned controller focused to enhance user experience

Design White Black


BRC1H63W BRC1H63K
Two attractive colors to match any interior
Flexibility Reliability Compact, measures only 85 x 85 mm
Timer functions (OFF timer, Weekly schedule timer) Easy setting via smartphone application using Bluetooth®
wireless technology (for Installer/Facility manager) Improved setback function to keep hotel room comfortable
Easy
Installation

34

New Products Information Improving air quality with technology


Equipped with decomposition technology, Streamer is a type of plasma discharge that
Introducing eliminates allergens such as pollen, mould, and mites, as well as, deodorises anti-bacterial dust
Streamer technology to a filters so you can breathe with ease.

Mechanism of decomposition by Streamer

Streamer Technology
maximum efficiency in cleaning, which uses powerful decomposition properties to Excited

wide variety of indoor units decompose substances captured by filter for better air quality.
oxygen
OH
radical
Excited
nitrogen
Daikin Streamer technology enhances Oxygen
radical

electrons.
clean unit built-in
Built-in inside the indoor unit inside the indoor
Page The electrons collide and combine with nitrogen and oxygen in the air to form four kinds of
Streamer emits high-speed
Streamer filter decomposing elements with decomposition power.
The decomposing elements provide decomposition power.

Round 99.93% Inactivation of Omicron variant in 2 hours


Flow
Cassette with Sensing and Streamer 117
unit

Experimental Results 100%


100%
Irradiation with Streamer discharge for two hours inactivated 99.93%, and for four )
hours inactivated 99.97% of the Omicron variant of Coronavirus (SARS-CoV-2), Survival rate (% 75%
when compared to without Streamer discharge. 50%

Inactivation effect against Omicron variant Inactivation More than 99.9%


Test Method one of the acrylic boxes. Seesaw shakers with a 6-well plate were placed in both
hCoV-19/Japan/ TY38-873/2021 strain (Omicron variant) was used. Two acrylic boxes, and 0.5 mL of virus solution was placed in each well of the plate. Streamer

FXFTQ-A
boxes of about 31L were placed in a safety cabinet in the BSL-3 facility, and
Streamer discharge device was installed in
DAIKIN Streamer Research Institute
Option for the indoor unit irradiation was performed on one 6-well plate while stirring with a seesaw shaker.
After 1, 2, and 4 hours, the virus solution was collected, and the virus titer was
measured by the TCID50 method using Vero
Compact Multi Flow Cassette Page 133 25% 0% 10.0%
0.07% 0.03% Test Organization
E6/TMPRSS2 cells. Professor Tatsuo Shioda, Department of Virus
2 3 4 Time (hour)
Double Flow Cassette
Option
Page
01 FXZQ-B Streamer decomposes mould and mites (feces and carcasses) and
Compared with natural attenuation
Infections, Research Institute for Microbial Diseases, Osaka University suppresses the causes of allergies.
*This result was obtained by using a Streamer discharge device for testing in lab conditions.
The effect of products equipped with Streamer technology or results in actual use environments may differ.

Ceiling Suspended Page Streamer Filter Clean Unit Why Daikin Streamer? Test Organization
153 Demonstration test was performed at Wakayama Medical
135 BAPWS55A61 Recognized as clean technology by public bodies
University.
Demonstration of mould Test Method
Picture of mould “Moulds” were placed on the electrodes of a Streamer discharge
unit where they were exposed to Streamer dischage for 15
Before irradiation After irradiation [15minutes]
minutes and photographed with an electron microscope.
FXCQ-B Streamer, a type of plasma

Electron generation area Winner of the 2005


Progress Award, Institute of Electrostatics Japan Patents acquired relating to Streamer technology
discharge, decomposes
Awarded for the development of a domestic air purifier which uses DC Streamer discharge. hazardous chemical substances. The decomposition power is
comparable to thermal energy of about 100,000°C.*

105 Patents Acquired Note:


*Comparison of oxidation decomposition. This does not mean temperature will become high.
FXHQ-B
56
VRV K Plus series VRV IV

VRV Development
Heat Recovery Hot Water System

VRV G series
Heat pump

History
VRV WS series Water cooled system

VRV H series Heat pump

To meet the needs of the times, we've been continuously *VRV is a trademark of Daikin Industries, Ltd.

developing
technologies as the leading air conditioning manufacturer in the
VRV IV
world. Cooling only / Heat pump
VRV II MA series
VRV H series VRV-WII series VRV R series Heat recovery
Made possible to connect
VRV III-C series Low outdoor temp. area use
VRV III Q series Replacement use

VRV L series
Adopted the new R-407C VRV R series Heat recovery

VRV D series

Cooling only 2006 2008


2004

to BMS using the DIII-NET

refrigerant

2011 2014
1982 2016
1988 1984 1990 1995 1999 2002 2005 2007 2010 2015 2018 2022
1992 1996 2000 2012 2020 2023

The 1st Generation VRV F series Cooling only VRV KA series VRV II-S series Connection to residential indoor unit VRV IV W series Water cooled
series system

VRV II M series VRV III series VRV-WIII series

VRV C series Cooling only VRV S


High Seasonal Efficiency
Series
VRV G series Heat
recovery
VRV III-S series
VRV K series VRV III
VRV IV S series VRV H series Heat pump
The birth of innovative products that changed the • 2.5-year development term VRV Multi function series Cooling/heating, hot water supply UAE
VRV series released in 1982 history of air conditioning technology • Completion of development in May, 1982 VRV IV
Saudi Arabia Bahrain
Jordan
Heat recovery Oman
Adopted the new R-410A refrigerant
VRV IV Q series Replacement use

Austria Qatar USA


• Technical award of Japan Society of
country of sale
well
Belgium Mexico
Refrigerating & Air-conditioning Engineers in Bulgaria Canada
Croatia Puerto Rico

Sales
1983 Cyprus
Czech
Middle East

established
Lithuania Macedonia
Netherlands Poland
Asia South America
Portugal

companies
Finland
Greece Japan
Hungary Ireland
China
Romania Serbia
Korea
Slovakia
Italy Taiwan
Sweden
North America
Expansion of the
France Switzerland Turkey
Germany Spain Ukraine
Russia
UK Europe Africa
South Africa
Oceania India Cambodia

Algeria Sudan Myanmar Maldives Nepal


in more than 70 countries
Australia Argentina Chile
Brazil

Burkina Faso Egypt Vietnam Thailand Indonesia Malaysia Singapore Philippine Seychelles Pakistan Sri Lanka Fiji Colombia Panama Peru
Ivory Coast Senegal New Caledonia New Zealand Tahiti

78

VRV User Benefits VRV User Benefits For OWNERS For CONSULTANTS

Lifecycle Cost & Comfort Flexible Design & Engineering Supports


• Further improvement of energy
Large-capacity Single Module Engineering Support Software
• Installation space and cost are reduced by large–capacity casing for
max. 24 class.
Long Refrigerant Piping
• Equivalent length extension max. 190 m
• Height difference extension max. 110 m (20 m longer than
Height
conventional models) difference 110 m
Equivalent length
• By applying for both extensions at the same time, supports a 190 m

Energy Saving Technology wide range of applications.

saving by high efficiency compressor and VRT Smart II control. Model Selection
Efficient Space Utilisation
• Achieves high TCSPF/HSPF, that reduces running cost.
• When construct a large-scale air conditioning system on a single refrigerant system,
space for air conditioning is drastically reduced.
Drawing Supports
Comfort • Defrost operation before the equipment is shut down speeds up the increase of
Cooling tower VRV
Software Technology
VRT Smart II control discharge air temperature of the next heating operation.
• If defrost operation time is short, the system will optimise defrost conditions, extending
the heating operation time.
• Strongly supports for facility design, offering model selection assistance, energy saving • With various types of indoor units available, comfortable airflow is ensured in every
and IEQ simulations, space.
drawing support, etc.

Varied Lineup of Indoor Units


Analysis and Simulation Middle Static
Pressure Duct
• Even
with a 20-storey building all of the outdoor
units can be installed on the rooftop.

Garage

Round Flow Cassette

Compact Multi Flow Cassette

Slim Duct Ceiling Suspended


Wall Mounted
9 10
VRV User Benefits For BUILDING
VRV User Benefits
MANAGEMENTS
For INSTALLERS

Easy Installation Reliability & Comfort


Slimmer Main Piping
• For gas pipe of up to 20 class, the main
piping diameter size can be reduced from
standard size. It enables lowering
installation cost.

Electrical Component
Service Window
temperatures.
• Easy access to the main PCB without Process visualization (Test run only)
removing the front panel.
• Quick field setting and trial • A progress rate (0% to 99%) is indicated
operation. on the PC board for Easy arrangement
for on-site work.
IP55 Sealed
Component Box
• Sealed electrical component box (IP55) blocks the ingress of debris or water, that
leads to unexpected failures.

Progress rate (0% to 99%) ~


Sealed electrical
component box
Refrigerant Piping
Cooling System
• Refrigerant cooling circuit enables operation
Double Backup Operation Functions
in high outdoor
• Unit backup & Compressor backup ensure continuous operation.

Unit backup operation function Compressor backup operation function


Malfunction Emergency
Simple Piping, Easy Wiring Malfunction operation
Emergency operation
• The REFNET piping system and DIII-NET system simplify
refrigerant piping and control wiring installation.

11 12

Wide Variety of Series Total Air Solutions


Models to Supply From residential houses to large buildings,
and from newly constructed to renovated buildings, VRV system meets a wide range of air conditioning needs
and supplies total air solutions.

Heat Recovery Featuring unique functions in a new large capacity casing


Page

Page The VRV R series enables simultaneous operation of cooling and heating within a single refrigerant circuit.
17 Heat Pump

77 For quick & high quality replacement use

By utilising advanced technologies, VRV R series achieves further class 585654525048464442403836343230282624222018161412108 60 RQCEQ-P
valuable functions. 3-phase 4-wire system, 380-415 V, 50 Hz
Heat Recovery
VRV IV Q series / VRV III Q series, a replacement VRV unit, can be installed using existing refrigerant piping, so renovation of
the air conditioning system can be carried out quickly and smoothly. This minimises inconveniences to activities and users in
Lineup the building.
3-phase 4-wire system, 380-415 V, 50 Hz VRV IV Q series
REYQ-B class 48464442403836343230282624222018161412 131086 Pump Space Saving
Type

3-phase Heat Standard


Type
4-wire Lineup
Single RQYQ-T
outdoor
Page Heat Pump 39 Page Heat Pump / Heat Recovery
Significant improvement in total performance
The VRV H series unites a variety of advanced technologies in providing high efficiency
and comfort to cooling and heating.
VRV III Q seriesHeat Recovery

Lineup
93 Water cooled system suitable for tall multi-storied buildings
RXYQ-B class 585654525048464442403836343230282624222018161412108 60

3-phase 4-wire system, units Heat Pump


380-415 V/380 V, 50/60 Hz RWEYQ-T(2)
Water cooled VRV IV W series utilises water as a heat source. The temperature of heat source
water can be from 10°C to 45°C, and outdoor air temperature does not affect cooling capacity.
The outside unit is compact and saves space in the machine room.

Page
57 Lineup
Single outdoor units Double outdoor units Triple outdoor class 363432302826242220181614121086
A(2) options for installation location and application are easily achieved by the
low height casing, long piping length and other features.
Especially designed for residential
houses, Lineup

small office and shops


RSUYQ- VRV S High Seasonal Efficiency series achieves higher energy efficiency
3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz
Heat Pump Heat Recovery
with a variety of function for comfort and high performance. A wide range of
4-6 class 7-8 class Heat Pump Heat Pump Page 107 Heat Pump
: 1-phase, 220-240 V/220-230 V, 50/60 Hz : 3-phase, 380-415 V/380 V, Page 87
50/60 Hz class 654
Water cooled system suitable for residential houses

saving, and offer 6 models to suit your needs. Water cooled VRV WS series outside units are designed to be compact and lightweight, and 3
single phase power supply enables simplified installation in residential applications. Heat Pump
Lineup
class 3.5 9865
4
69 RXYMQ-A(2)/B2 Lineup
class 654

3-4 class: 1-phase, 220-230 V, 50 Hz

Especially designed for residential houses,


small offices and shops
VRV IV S series aims to provide sufficient capacity, along with the compact size required by
RWXYQ-A 1-phase, 220V, 50Hz
residential houses, small offices and shops. Outdoor units are designed to be slim and space

5-6 class: 1-phase, 220-240 V/220-230 V, 50/60 Hz 8-9 class: 3-phase, 380-415 V, 50 Hz Heat Pump

13 14

Wide Range Indoor Unit


Lineup Create Comfortable
Airflow
VRV indoor units New lineup Category

Type 2 2 3 4 5 6 7 8 1 1 1 1 1 1 2
0 5 2 0 0 3 1 0 0 2 4 4 6 8 0
0 5 0 5 0 0 0

Model Name Capacity Range 2. 2. 3. 4. 5. 7. 8 9 1 1 1 1 1 2 2


(kW) 2 8 6 5 6 1 1. 4 6 6. 8 0 2.
2 2 4

Capacity Index 2 2 31 4 5 6 8 1 1 1 1 1 1 2
.2 2.
0 5 5
0 0 0 0 2 4 4 6 8 0
5 7 0 5 0 5 0 0 0
1

Round Flow FXFTQ-AVM


Cassette with
Sensing and
Streamer

Round Flow FXFSQ-AVM


Cassette with
Sensing

Round Flow Cassette FXFQ-AVM

Compact Multi FXZQ-BVM


Flow Cassette

Double Flow FXCQ-BVM


Cassette

Single Flow Cassette FXEQ-AV36

Slim Duct (Standard) FXDQ-PDVE

(700 mm width type)

FXDQ-NDVE

(900/1,100 mm width
type)

Slim Duct (Compact) FXDQ-


TV1C(A)

Middle Static FXSQ-PAVE


Pressure Duct

FXDYQ-
MAV1

Middle-High Static Pressure FXMQ-PAVE


Duct

High Static Pressure FXMQ-PV1A


Duct

Outdoor-Air FXMQ-MFV1
Processing Unit

FXMQ-AFVM

4-Way Flow Ceiling FXUQ-AVEB


Suspended

Ceiling Suspended FXHQ-MAVE

FXHQ-BVM

Wall Mounted FXAQ-AVM

Floor Standing FXLQ-MAVE

Concealed Floor FXNQ-MAVE


Standing

Heat Reclaim Ventilator VAM-HVE Airflow rate 3


/
150-2000 m h

Air Handling Unit AHUR 6-60


class

250
28
250

Ceiling Mounted Cassette

Ceiling Concealed Duct

Ceiling Suspended

Floor Standing

Note: For indoor units connectability, please refer to the indoor unit product lineups under individual outdoor unit series.

15 16

Next Generation VRV system


VRV R Series
Featuring unique functions in a new Heat Recovery 8class–60class New
Casing
(22.4 kW) (168 kW)

large capacity casing Offers a wide variety of new functions that


VRV R Series

benefit everyone involved.


VRV R series enables flexibility through simultaneous cooling and heating operation with
Promotion Movie Special Site a single VRV system. By recovering heat, it is possible significantly to reduce power
consumption. VRV R series adopt a new casing to realise a single module of up to 24
class. In addition, the new models have achieved significant energy savings with
improved technology. The operating performance has been improved in all directions by
introducing unique ideas, technologies and a wide variety of functions to strengthen
design flexibility, easy installation and reliability. We provide higher benefits to various
users related to air conditioning systems, for example, building owners, consultants,
installers and even building management.

Comfort Heat Design


Recovery
Energy Savings
Single outdoor units REYQ8-24BYM9
Flexibility Reliability

Double outdoor units REYQ26-48BYM9

Easy
Triple outdoor units REYQ50-60BYM9 Installation

17 18

BS unit (Single type/Multi type)


Heat Recovery By adding suction gas piping and a BS unit (sold separately),
simultaneous cooling and heating operation can be provided by a

Technologies single system.

VRV R series enables flexibility through


simultaneous cooling and heating
operation with a single VRV system.
See page 159 - 162
Situation

VRV R Series

VRV R Series
Recent office buildings are highly airtight and Single BS unit
Multi BS unit Heat recovery
due to the use of computers, lighting

Outdoor unit Indoor unit Indoor unit Indoor unit Single Single High and low pressure
increases even in winter. BS unit BS unit gas piping
Suction gas piping
Liquid piping

Gas piping

Need Liquid piping

These buildings require flexible


Indoor unit*
cooling and heating operation. (Cooling only)
Outdoor unit Indoor unit (Heating) Indoor unit (Cooling)

Cooling Heating
Solution Heat recovery operation!

• VRV R series enables flexibility through simultaneous cooling and heating operation with a single VRV * For indoor units used for cooling only (do not connect to BS unit when using for heat recovery), total capacity index must be 50% or less than the
capacity index of the outdoor units.

system. • Improves energy efficiency by recycling waste heat. Hot area due to heat released by computers, etc. →Cooling ON Outdoor air processing air
Cold area during winter due to cold air coming from windows Heating ON Application reference
The heat recovery system improves energy efficiency by recycling waste heat. conditioning
Single BS unit Multi BS unit

2 unit heating corridor


heating cooling cooling heating cooling
Outdoor

BS unit Winter season (Office Building) Winter season (Hotel)


1 Cooling Heating • Difference between the load of cold air and heat from room is • Can be used with the outdoor air processing air conditioning
Indoor unit large
• Able to cater to individual heating and cooling requirement

The (cold) waste heat from heating is 2


1 used for the cooling operation.
The waste heat from cooling is used to generate heat that is needed for heating operation while conserving electricity.

19 20

Conventional models New models

New Casing 22, 24 class 22, 24 class

VRV R Series VRV R Series

The larger single module casing reduces installation cost and space also. Large-capacity
single module Offers advanced design and new structure with excellent workability.
8, 10, 12 class 14, 16, 18, 20 class 22, 24 class Single module reduces installation space
REYQ8BYM9 REYQ10BYM9 REYQ22BYM9 REYQ24BYM9 765 mm mm

7% less
Installation space

Machine weight 11% less


1,880 mm
REYQ12BYM9 REYQ14BYM9
REYQ16BYM9 (930 mm + 20 mm + 930 mm)
REYQ18BYM9 REYQ20BYM9
1,750 mm765

System capacity Single module (class)


Outdoor unit combinations units
Number of
1.44 m 460 kg
2 Installation space
1.34 m 2 Machine weight
409
Installation space Machine weight kg
44
117
46
48
123 50
kW 8 10 12 14 16 18

129
22.4 Single

134
28.0

140
33.5

146
New reinforced design
40.0

45.0
152 Triple The frame structure has been strengthened to improve resistance
to earthquakes and wind while protecting against falling damage.
157
50.0

162
56.0

61.5

67.0 Class
8
73.5 Double 10
12
78.5 14
16
1
83.5 18
20
89.5 22
24
96.0 26
28
101 30
32
34
106
36
38 Minimises horizontal wobbling Conventional models
112
40
42 Support via truss shape

52 1
2
54
56
2
58
Minimises vibration from various angles
60168
Each part is screwed
with 2 axes
Conventional models

21 22

High TCSPF / HSPF High Efficiency Compressor New


Energy Savings
Hardware technology

Energy savings during actual operation have been further improved by the evolution of
technologies increase seasonal efficiency and enable a compact design. Improvement
software and hardware technologies.
Achieved high values for TCSPF and HSPF in all series. of the discharge port

VRV R Series VRV R Series

7.15
TCSPF (for commercial use) By improving the shape of the refrigerant discharge port, the pressure increase near the discharge port of the gas refrigerant after
8.00 compression is suppressed and the compression loss is reduced.

6.30
TCSPF 5.64 5.72
4.76 4.90
5.43
Optimising the
6.00 4.00 2.00 0 back pressure
6.42 6.43
control
New oil control
function
In addition to the
5.72
5.15 5.21
conventional
5.67
5.09 5.16
intermediate
6.52
5.93 5.96 pressure adjustment
port, the pressing
pressure of the
orbiting scroll during
operation has been
optimised, and the
newly adopted oil
6.30 5.67 control mechanism
4.99 5.12
5.64 5.72 5.62
4.96 5.08

8 class 12 class 18 class 22 class Model class mechanical loss. Adoption of a high- performance concentrated motor
10 class
14 class 16 class Hot Average Cold
20 class 24 class has reduced gas leakage and

HSPF (for commercial use) 6.00 By adopting it, the coil circumference is greatly reduced, which makes the coil denser and thicker, and the electrical resistance of the
coil is dramatically reduced to improve motor efficiency. Furthermore, the motor is light-weighted and downsized.
4.57 0 3.48 4.18 2.81 3.88 2.62 2.98
Software Refrigerant Control
4.30
4.00
3.80
2.80
3.52
4.02
2.98
2.61
VRT control supply required
HSPF 4.22
4.12 2.76 technology
Optimal exactly capacity of
2.00 3.72
3.22
4.10
3.32 3.41
2.74
4.01

3.05
2.67
3.96
Smart Fully Automatic
Energy-saving meets the indoor units
8 class 10 class 12 class 14 class 16 class 18 class 20 class 22 class 24 class
Hot Average Cold

What are TCSPF and HSPF ?


TCSPF: Total Cooling Seasonal Performance Factor
HSPF: Heating Seasonal Performance Factor
Model class

• Reduces compressor load and minimises operation loss so it is energy saving.


• Controls capacity according to load to ensure a constant room temperature for greater comfort.

Supplying the refrigerant after


temperature control to the indoor unit
Coordinated control
In simple terms, TCSPF & HSPF represents the ratio of the Total Cooling & Heating capacity of the air-conditioner relative to the Total This allows you to determine the performance efficiency of different air-conditioners by comparing their
energy consumed by the air-conditioner during the Total Cooling & Heating operation periods in a year.
Whereas the previous index of AEER & ACOP was calculated using only one representative outdoor temperature (35°C for cooling
and 7°C for heating), the new index of TCSPF & HSPF uses a broader range of annual outdoor temperatures* as stipulated in
AS/NZS 3823.4.1:2014. Room temperature and set temperature
Further, the annual outdoor temperatures are based on zoning Australia/New Zealand into three distinct climate zones
(Hot/Average/Cold).
Determine the target refrigerant temperature

TCSPF & HSPF within the same climate zone. * There are two kinds of annual outdoor temperatures and it’s Calculate Target refrigerant temperature
Indoor airflow rate Control Compressor speed
different for residential and commercial use.

* For the classification of indoor units (VRT smart control and VRT control), refer to the indoor unit lineup.

23 24

Design Flexibility
Simultaneous extension of height difference and
equivalent length
Design flexibility is further improved by simultaneous extension of height difference,
improved from 90 m to 110 m, and equivalent length (up to 190 m).

Long piping length


Long piping length enhances design flexibility, enabling support for large buildings.

Between the outdoor branch


and the last outdoor unit
Max. total

VRV R Series VRV R Series


NEW Max. actual
Height difference Standard 40 m, 50 m
Max. 190 m
Max. 90 m
extension
piping length Standard 90 m
Max. 110 m piping length 1000 m Max. 13 m Max. height difference
Equivalent length 165 m *2 110 m
between the outdoor units and the indoor units
Between the outdoor units Max. 5m
Max. equivalent
extension piping length

190 m
*4

Between the first indoor branch and the farthest Max. height difference between the indoor units

indoor unit *3
• Height difference extension Max. 110 m *1 30 m
Max. 90 m

For height differences exceeding 50 m with the outdoor unit above the indoor unit and 40 m with the outdoor unit below, the main
piping liquid piping size must be increased.

• Equivalent length extension Max. 190 m


Note: The above is just a schematic diagram.
When the equivalent piping length from outdoor unit to indoor unit is 90 m or more, Maximum allowable piping length Maximum allowable height difference 165 m (190 m)*4 1000 m
be sure to increase the main piping liquid piping size. supported Piping branch by REFNET joint is possible 90 m*1
10 m (13 m)
* In addition to increasing the size of the main pipe, there are other piping restrictions regarding height downstream of REFNET header.
difference extension and equivalent length extension. Check the Installation Manual for details. 5m
Actual piping length (Equivalent)
Total piping length 30 m
*2
Between the first indoor branch and the farthest indoor unit Between the outdoor branch and the110 m
last outdoor unit (Equivalent) Between the outdoor units (Multiple use)
REFNET header downstream branching Between the indoor units
Between the outdoor units and the indoor units

The indoor unit REFNET joint


*1. No special requirements up to 40 m. The maximum actual piping length can be 90 m, depending on conditions. Various conditions and
requirements have to be met to allow utilisation of 90 m piping length. Be sure to refer to the Engineering Data Book for details of these conditions
arrangement can be more and requirements. *2. When Height differences above 50 m if the outdoor unit is above the indoor unit and 40 m if the outdoor unit is below the
indoor unit, a dedicated setting on the outdoor unit is required. Refer to the Engineering Data Book and contact your local dealer for more
information.
*3. When Height differences are 15 m or more, maximum actual piping length must be 120 m.
*4. In the case where the equivalent piping length from outdoor unit to indoor unit ≧ 90 m, make sure to up size the liquid pipe of the main pipe. Do not up size the
high/low pressure gas pipe and the suction gas pipe.

flexible.
REFNET header
BS unit Connection ratio
ndoor units 8 - 20
FXDQ FXSQ FXMQ-PA
class

22, 24
200%
class

Double outdoor
REFNET header unitsTriple

3 pipes outdoor units

KHRP25M33H,

Applicable
VRV i

Single
outdoor
units
2 pipes
KHRP26M22H,

Other VRV indoor unit models*1

200%
180%
Indoor unit total capacity at REFNET joint 160%

Connection capacity at maximum is 200%.

Connection ratio 50%–200%


Conditions of VRV indoor unit connection capacity
Indoor units
KHRP25M72H + KHRP25M72TP KHRP25M73H + KHRP25M73TP Connection ratio 130% of outdoor units. Note: If the operational capacity of indoor units is more than 130%, low airflow
KHRP26M33H,KHRP26M72H< 50 KHRP26M73H + KHRP26M73HP ≤ 140 Total capacity index of the indoor units Capacity index of the outdoor units = operation is enforced in all the indoor units. *Refer to page 33 for outdoor unit combination
*1 For the FXF(S)(T)Q25 models, maximum connection ratio is 130 % for the entire range details.

25 26

No drain piping
Improved refrigerant piping workability
Easy Installation Conventional Multi BS unit New Drainless Multi BS unit Drain piping
By dividing piping and wiring holes to the left and right, piping and wiring work can be
easily performed on site.

Conventional models
Drainless Multi BS unit VRV R Series VRV R Series

Drainless function enables a drastic reduction of on-site work since no drain


piping is required.

• Abundant lineup includes port counts of 4, 6, 8, 10, 12, and 16. *

• Drain is eliminated with the use of foam insulation inside the casing. On-
site work has significantly been reduced for lower installation costs.
*Drainless function is available up to 12-port unit. The 16-port unit requires drain piping.

Refrigerant piping Since no drain piping is required, it can be installed flexibly, and installation costs can be hole

BS unit
conventional
Electrical component service window significantly reduced.
Wiring hole
Piping
hole
Refrigerant piping

Drainless Multi BS unit Wiring


hole
Piping

An electrical component service


window is newly
installed on the front
panel.

Main PCB 7-segment LED can be accessed without removing the front panel.
Workability is greatly improved during on-site setting or test run. You can also quickly check the error code during service.
Working in close placed is difficult Work becomes easier with sufficient space

27 28

Access port cover

Reliability
IP55-compliant sealed component box
Electrical component
box cover (lower)

Enables operation
in high outdoor
temperature
VRV R Series VRV R

Series

IP55 sealed component box


protects electrical component
from a cause of failure, that is Electrical component box cover (upper) Electrical component
the ingress of debris (lizards, Three refrigerant cooling circuits enable stable operation even in high box cover (upper)
bugs, sand, water, snow). outdoor temperatures by suppressing a temperature rise for the PCB
mounted in the sealed electrical component box.
Access port cover
Electrical component box Electrical component

What is IP55? The internal mounting plate is hinged, enabling easy


maintenance of the PCB on the back.
box cover (lower)

Electrical component mounting plate


Electrical
PCB Electrical

component box component mounting plate

IP55 is the degrees of dust and water protection for the electrical component box equipped on the product.

IP55

Liquid ingress protection Grade 5


Water projected by a nozzle (6.3 mm) against enclosure from any direction shall have no harmful effects.

Solid particle protection Grade 5


Ingress of dust is not entirely prevented, but it must not enter in sufficient quantity to interfere
with the satisfactory operation of the equipment.

Ingress Protection

*IP55 is the protection degree of the wiring box as a single unit. The protection grade of outdoor unit is IP14 as well as conventional model.

29 30

Outdoor unit multi-defrost function Double backup operation functions


Comfort VRV R Series VRV R Series

Outdoor unit runs defrosting with Image of indoor


temperature effects
Unit backup operation function Compressor backup operation function
indoor air Minimising the cooling of Outdoor multi-defrost Reverse cycle defrost
indoor heat exchangers
Defrost ON
delivers faster startup

outside air
Indoor temperature
heat Indoor decreases as indoor unit
temperature heat exchanger is chilled through

Malfunction

Minimises the cooling of


Malfunction

Emergency
operation

Emergency operation

Improves comfort of defrosting operation The nighttime quiet operation function automatically suppresses the nighttime operating sound by reducing operation
Defrosting in conventional models temporarily reverses the refrigerant cycle to use indoor heat to melt the frost, thus capacity to maintain the quiet environment of the neighborhood. Three selectable modes are available depending on
causing the indoor temperature to fall (reverse cycle defrost). the required level.
The “outdoor multi-defrost function”enables large-capacity casing models of 22 and 24 class and multi outdoor units to use
Load %
outdoor heat for heat exchange and interchange defrost operation while minimising indoor heat absorption and decreases
in indoor temperature. Operating sound dB(A)

*Reverse cycle defrost may also take place to protect the product.

Nighttime quiet operation function

Heating / Defrosting 50%

57 dB(A) 45 dB(A)

Peak in the outdoor


temperature
Heating / Heating Defrosting / Heating
100% 8 hrs*1 10 hrs*2

Night
quiet mode Min. 45 dB(A)*3

8:00 12:00 16:00 20:00 0:00 4:00 8:00


Night mode STARTS Night mode ENDS

*1. Initial setting is 8 hours. Can be selected from 6, 8 and 10 hours.


*2. Initial setting is 9 hours. Can be selected from 8, 9 and 10 hours.
*3. In case of 10 class outdoor unit.

Notes: • This function is available in setting at site.


• The operating sound in quiet operation mode is the actual value measured by our company.
• The relationship of outdoor temperature (load) and time shown above is just an example.

31 32

Outdoor Unit Lineup VRV


class 8 Slim Duct
1 1 1 1 1 2 2 2 2 2 3 3 3 3 3 4 4 4 4 (Standard) FXDQ-PDVE
0 2 4 6 8 0 2 4 6 8 0 2 4 6 8 0 2 4 6

Single outdoor FXDQ-NDVE

R Series units

Double outdoor
Slim Duct FXDQ-TV1C(A)
Capacity range from 8 to 60 class units
(Compact)
Triple outdoor

Indoor Unit Lineup


units Middle Static
Pressure Duct FXSQ-PAVE

FXDYQ-MAV1

60
Middle-High FXMQ-PAVE
Static
Pressure Duct

High Static FXMQ-PV1A


Enhanced range of choices Ceiling Mounted Cassette Pressure Duct
Type
Outdoor-Air FXMQ-MFV1
Processing Unit
FXMQ-AFVM
Model Name
4-Way Flow FXUQ-AVEB
Ceiling
Suspended

Ceiling FXHQ-MAVE
Suspended
Round Flow FXFTQ-AVM FXHQ-BVM
Cassette with
New lineup Sensing and
Wall Mounted
VRV R Series
Streamer
FXAQ-AVM
Round Flow
Cassette with FXFSQ-AVM Floor Standing FXLQ-MAVE
Sensing

Concealed Floor FXNQ-MAVE


Round Flow
FXFQ-AVM Standing
Cassette
VRV R Series
Heat Reclaim VAM-HVE
Compact Multi
Indoor units subject to VRT smart control FXZQ-BVM Ventilator
Flow Cassette
Lineup
Double Flow
Cassette FXCQ-BVM
250
Single Flow FXEQ-AV36
VRV R SERIES
Cassette
Category 250

Outdoor unit multi


Outdoor unit combinations Capacity
Maximum number of
class Model name Combination
connection piping kit*1 Total capacity index of connectable indoor units*2 connectable indoor units*2
index kW
8 200 250 300 350 400 450 500 550 600 REYQ34B REYQ36B REYQ38B REYQ18B REYQ12B + REYQ20B REYQ14B + – BHFP26R135 (1,280) 425 to 1,105 (1,360) 450 to 1,170
650 700 750 800 850 900 950 REYQ8B REYQ20B REYQ20B REYQ16B + REYQ20B – 100 to 260 (400) 125 to 325 (500) 150 to (1,440) 475 to 1,235 (1,520) Ceiling Concealed Duct
10 12 14 16 18 20 22 24 26 28 30 32 34
36 38 REYQ8B REYQ10B REYQ12B REYQ14B REYQ10B REYQ22B REYQ18B + REYQ20B – 390 (600) 175 to 455 (700) 200 to 520 13 (20) 16 (25) 19 (30) 22 (35) 26 (40) 29
22.4 28.0 33.5 40.0 45.0 50.0 56.0 61.5 REYQ16B REYQ18B REYQ20B REYQ12B REYQ24B – – (800) 225 to 585 (900) (45) 32 (50) 35 (49) 39 (54) 42 (52) 45
67.0 73.5 78.5 83.5 89.5 96.0 101 REYQ22B REYQ24B REYQ26B REYQ14B REYQ12B + REYQ14B REYQ12B + – – 250 to 650 (1,000) 275 to 715 (990) 300 to(56) 48 (60) 52 (64) 55 (64) 58 (64) 61
106 REYQ28B REYQ30B REYQ32B REYQ16B REYQ16B REYQ12B + REYQ18B – – 780 (1,080) 325 to 845 (1,040) 350 to 910 (64)
(1,120) 375 to 975 (1,200) 400 to 1,040
40 REYQ40B REYQ20B × 2 500 to 1,300 (1,600)
112 1,000
42 117 1,050 REYQ42B REYQ18B + REYQ24B 44 123 1,100 REYQ44B REYQ52B REYQ12B + REYQ20B × 2 54 152 1,350 REYQ54B REYQ14B + BHFP26R168 64 (64)
Ceiling Suspended
REYQ20B + REYQ24B 46 129 1,150 REYQ46B REYQ22B + REYQ24B 48 REYQ20B × 2 56 157 1,400 REYQ56B REYQ16B + REYQ20B × 2 58 162 525 to 1,365 (1,680) 550 to 1,430 (1,760) 575 to 1,495 (1,840) 600 to 1,560
134 1,200 REYQ48B REYQ24B × 2 1,450 REYQ58B REYQ18B + REYQ20B × 2 60 168 1,500 REYQ60B (1,920) 625 to 1,625 (1,625) 650 to 1,690 (1,690) 675 to 1,755 (1,755) 700
50 140 1,250 REYQ50B REYQ12B + REYQ18B + REYQ20B 52 146 1,300 REYQ20B × 3 to 1,820 (1,820) 725 to 1,885 (1,885) 750 to 1,950 (1,950)
Notes: *1. For multiple connection of 26 class systems and above, the outdoor unit multi connection piping kit (separately sold) is required. *2. Values inside brackets are based on
connection of indoor units rated at maximum capacity, 200% for REYQ8-20BYM9, 180% for REYQ22/24BYM9, 160% for double outdoor units, and 130% for triple outdoor units.
Refer to page 26 for note on connection capacity of indoor units.

Floor Standing

Note: For indoor units without 'VRT Smart', the standard 'VRT' control is available (excludes Heat Reclaim Ventilators).
indoor
Max. 64 • If a system has both outdoor-air processing air conditioners (FXMQ-MF series) and outdoor-air processing type indoor units, VRT smart control and VRT units
• If a system has indoor units subject to both VRT smart and VRT control, the system is operated under VRT control. control are disabled.

33 34

VRV R Series
Outdoor Units VRV R Series
Specifications
VRV R Series
Heat Recovery

Model REYQ8BYM9 REYQ10BYM REYQ12BYM REYQ14BYM REYQ16BYM REYQ18BYM REYQ20BYM9 REYQ22BYM9 REYQ24BYM9 REYQ26BYM9 REYQ28BYM9 REYQ30BYM9 REYQ32BYM9 REYQ34BYM9
9 9 9 9 9

Combination units — — — — — — — — — REYQ12BYM9 REYQ12BYM9 REYQ12BYM9 REYQ12BYM9 REYQ14BYM9

— — — — — — — — — REYQ14BYM9 REYQ16BYM9 REYQ18BYM9 REYQ20BYM9 REYQ20BYM9

Power supply 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz

Cooling capacity Btu/h 76,400 95,500 114,000 136,000 154,000 171,000 191,000 210,000 229,000 251,000 268,000 285,000 305,000 328,000

kW 22.4 28.0 33.5 40.0 45.0 50.0 56.0 61.5 67.0 73.5 78.5 83.5 89.5 96.0

Heating capacity Btu/h 85,300 107,000 128,000 154,000 171,000 191,000 215,000 235,000 256,000 282,000 299,000 319,000 345,000 369,000

kW 25.0 31.5 37.5 45.0 50.0 56.0 63.0 69.0 75.0 82.5 87.5 93.5 101 108

Power Cooling kW 5.17 6.80 8.71 11.2 12.9 14.4 17.5 18.6 21.3 19.9 21.6 23.1 26.2 28.7
consumptio
n
Heating kW 5.68 7.29 9.81 12.8 13.6 14.5 17.2 19.6 22.2 22.6 23.4 24.3 27.3 30.0

Capacity control % 11-100 7-100 6-100 5-100 4-100 3-100 2-100

AEER  Cooling 4.00 3.83 3.61 3.34 3.28 3.27 3.03 3.12 2.98 3.45 3.40 3.39 3.22 3.15

ACOP  Heating 4.09 4.04 3.61 3.32 3.46 3.63 3.47 3.33 3.21 3.44 3.54 3.65 3.52 3.42

TCSPF Hot 6.42 / 5.57 5.93 / 5.27 5.64 / 5.02 5.64 / 4.96 5.15 / 4.58 5.09 / 4.53 4.99 / 4.43 4.96 / 4.43 4.76 / 4.25 5.64 / 4.99 5.35 / 4.76 5.30 / 4.72 5.22 / 4.64 5.25 / 4.64
(Cooling)
Commerci
al / Average 6.43 / 4.55 5.96 / 4.44 5.72 / 4.31 5.72 / 4.14 5.21 / 3.90 5.16 / 3.89 5.12 / 3.84 5.08 / 3.86 4.90 / 3.74 5.73 / 4.22 5.42 / 4.07 5.38 / 4.05 5.34 / 4.01 5.36 / 3.96
Residenti
al
Cold 7.15 / 4.48 6.52 / 4.41 6.30 / 4.32 6.30 / 4.16 5.72 / 3.90 5.67 / 3.90 5.67 / 3.90 5.62 / 3.90 5.43 / 3.80 6.31 / 4.23 5.96 / 4.07 5.91 / 4.06 5.90 / 4.05 5.93 / 4.00

HSPF Hot 4.57 / 4.58 4.12 / 4.13 4.10 / 4.11 4.22 / 4.15 4.18 / 4.18 4.02 / 4.03 3.88 / 3.89 4.01 / 3.93 3.96 / 3.88 4.17 / 4.17 4.16 / 4.16 4.06 / 4.07 3.97 / 3.98 4.02 / 3.96
(Heating)
Commerci
al / Average 4.30 / 4.15 3.72 / 3.59 3.48 / 3.00 3.32 / 2.80 3.52 / 3.01 3.41 / 2.93 2.98 / 2.80 3.05 / 2.51 2.98 / 2.44 3.26 / 3.06 3.51 / 3.01 3.44 / 2.97 3.35 / 2.87 3.12 / 2.61
Residentia
l
Cold 3.80 / 3.53 3.22 / 2.88 2.80 / 2.46 2.76 / 2.36 2.81 / 2.46 2.74 / 2.39 2.62 / 2.29 2.67 / 2.09 2.61 / 2.03 2.86 / 2.52 2.81 / 2.46 2.77 / 2.42 2.69 / 2.35 2.74 / 2.18

Casing colour Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)

Compress Type Hermetically sealed scroll type Hermetically sealed scroll type
or

Motor output kW 4.13 5.87 7.67 8.45 4.44+5.03 4.04+6.56 4.51+7.37 7.06+7.37 7.80+8.11 7.67+8.45 7.67+(4.44+5.03) 7.67+(4.04+6.56) 7.67+(4.51+7.37) 8.45+(4.51+7.37)

Airflow rate /s 2,583 2,812 3,015 4,327 4,428 4,293 5,095 7,170 3,015+4,327 3,015+4,428 3,015+4,293 3,015+5,095 4,327+5,095
m3/ 155 169 181 260 266 258 306 430 181+260 181+266 181+258 181+306 260+306
min

Dimensions (H×W×D) mm 1,660×930×765 1,660×1,240×765 1,660×1,750×765 (1,660×930×765) + (1,660×1,240×765) (1,660×1,240×76


5) +
(1,660×1,240×76
5)

Machine weight kg 227 231 232 281 323 357 409 232+281 232+323 232+357 232+357 281+357

Sound level dB(A 56 57 59 63 62 61 65 67 68 64 63 66 67


)

Sound power dB(A 80 83 85 89 90 86 87 90


)

Opera Cooling ºCD -5 to 49 -5 to 49


tion B
range

Heating ºCW -25 to 15.5 -25 to 15.5


B

Refrigera Type R-410A R-410A


nt

Chargekg 10.6 10.9 11.7 11.7 10.9+11.7 11.7+11.7

Piping Liquid mm 9.5 (Brazing) 12.7 (Brazing) 15.9 (Brazing) 15.9 (Brazing) 19.1 (Brazing)
connectio
ns
Gas mm 19.1 22.2 28.6 (Brazing) 28.6 (Brazing) 34.9 (Brazing)
(Brazing) (Brazing)

High and low mm 15.9 19.1 (Brazing) 22.2 (Brazing) 28.6 (Brazing) 28.6 (Brazing)
pressure gas
(Brazing)

Notes: Specifications are based on the following conditions;


• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions and oil recovery mode.
When there is concern for noise the surrounding area such as residences, we recommend investigating the installation location and taking soundproofing measures.
 Values based on GEMS determination 2019.
TCSPF: Total Cooling Seasonal Performance Factor
HSPF: Heating Seasonal Performance Factor
In simple terms, TCSPF & HSPF represents the ratio of the Total Cooling & Heating capacity of the air-conditioner relative to the Total energy consumed
by the air-conditioner during the Total Cooling & Heating operation periods in a year.
Whereas the previous index of AEER & ACOP was calculated using only one representative outdoor temperature (35°C for cooling and 7°C for heating),
the new index of TCSPF & HSPF uses a broader range of annual outdoor temperatures* as stipulated in AS/NZS 3823.4.1:2014.
Further, the annual outdoor temperatures are based on zoning Australia/New Zealand into three distinct climate zones (Hot/Average/Cold).
This allows you to determine the performance efficiency of different air-conditioners by comparing their TCSPF & HSPF within the same climate zone.
* There are two kinds of annual outdoor temperatures and it’s different for residential and commercial use.

35 36

VRV R Series
Outdoor Units VRV R Series
Specifications
VRV R Series
Heat Recovery

Model REYQ36BYM REYQ38BY REYQ40BY REYQ42BY REYQ44BY REYQ46BYM REYQ48BYM9 REYQ50BYM9 REYQ52BYM9 REYQ54BYM9 REYQ56BYM9 REYQ58BYM9 REYQ60BYM9
9 M9 M9 M9 M9 9

Combination units REYQ16BYM REYQ18BY REYQ20BY REYQ18BYM REYQ20BY REYQ22BYM REYQ24BYM9 REYQ12BYM9 REYQ12BYM9 REYQ14BYM9 REYQ16BYM9 REYQ18BYM9 REYQ20BYM9
9 M9 M9 9 M9 9
REYQ20BYM REYQ20BY REYQ20BY REYQ24BYM REYQ24BY REYQ24BYM REYQ24BYM9 REYQ18BYM9 REYQ20BYM9 REYQ20BYM9 REYQ20BYM9 REYQ20BYM9 REYQ20BYM9
9 M9 M9 9 M9 9

— — — — — — — REYQ20BYM9 REYQ20BYM9 REYQ20BYM9 REYQ20BYM9 REYQ20BYM9 REYQ20BYM9

Power supply 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz

Cooling capacity Btu/h 345,000 362,000 382,000 399,000 420,000 440,000 457,000 478,000 498,000 519,000 536,000 553,000 573,000

kW 101 106 112 117 123 129 134 140 146 152 157 162 168

Heating capacity Btu/h 386,000 406,000 430,000 447,000 471,000 491,000 512,000 536,000 560,000 583,000 601,000 621,000 645,000

kW 113 119 126 131 138 144 150 157 164 171 176 182 189

Power Cooling kW 30.4 31.9 35.0 35.7 38.8 40.2 42.6 40.9 44.0 46.2 47.9 49.4 52.5
consumptio
n
Heating kW 30.8 31.7 34.4 36.7 39.4 41.8 44.4 41.8 44.5 47.2 48.0 48.9 51.6

Capacity control % 2-100 2-100 1-100

AEER  Cooling 3.13 3.13 3.03 3.10 3.00 3.04 2.98 3.22 3.13 3.10 3.09 3.09 3.03

ACOP  Heating 3.50 3.58 3.50 3.42 3.36 3.31 3.25 3.58 3.51 3.45 3.50 3.55 3.50

TCSPF Hot 5.06 / 4.50 5.04 / 4.48 4.99 / 4.43 4.90 / 4.37 4.87 / 4.34 4.85 / 4.33 4.77 / 4.26 5.17 / 4.59 5.12 / 4.55 5.15 / 4.56 5.04 / 4.47 5.02 / 4.46 4.99 / 4.43
(Cooling)
Commerci
al / Average 5.17 / 3.87 5.14 / 3.87 5.13 / 3.84 5.01 / 3.80 5.00 / 3.79 4.98 / 3.80 4.90 / 3.74 5.27 / 3.96 5.25 / 3.94 5.27 / 3.92 5.15 / 3.86 5.14 / 3.86 5.13 / 3.84
Residenti
al
Cold 5.70 / 3.90 5.68 / 3.90 5.68 / 3.90 5.53 / 3.84 5.54 / 3.85 5.52 / 3.85 5.43 / 3.80 5.82 / 3.99 5.82 / 3.99 5.84 / 3.97 5.70 / 3.90 5.68 / 3.90 5.68 / 3.90

HSPF Hot 4.02 / 4.02 3.95 / 3.96 3.89 / 3.90 3.99 / 4.00 3.93 / 3.93 3.99 / 3.91 3.97 / 3.89 3.99 / 4.00 3.94 / 3.95 3.97 / 3.98 3.97 / 3.98 3.93 / 3.94 3.89 / 3.90
(Heating)
Commerci
al / Average 3.09 / 2.90 3.34 / 2.87 2.99 / 2.81 3.04 / 2.84 2.99 / 2.79 3.02 / 2.48 2.99 / 2.45 3.38 / 2.90 3.33 / 2.85 3.07 / 2.88 3.05 / 2.86 3.32 / 2.85 2.99 / 2.81
Residentia
l
Cold 2.71 / 2.36 2.68 / 2.34 2.63 / 2.29 2.67 / 2.31 2.62 / 2.27 2.64 / 2.06 2.61 / 2.03 2.71 / 2.37 2.67 / 2.33 2.70 / 2.36 2.68 / 2.34 2.66 / 2.32 2.63 / 2.29

Casing colour Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)

Compress Type Hermetically sealed scroll type Hermetically sealed scroll type
or

Motor output kW (4.44+5.03)+ (4.04+6.56)+ (4.51+7.37)+ (4.04+6.56)+ (4.51+7.37)+ (7.06+7.37)+ (7.80+8.11)+ 7.67+(4.04+6.56)+ 7.67+(4.51+7.37)+ 8.45+(4.51+7.37)+ (4.44+5.03)+(4.51+7. (4.04+6.56)+(4.51+7. (4.51+7.37)+(4.51+7.
(4.51+7.37) (4.51+7.37) (4.51+7.37) (7.80+8.11) (7.80+8.11) (7.80+8.11) (7.80+8.11) (4.51+7.37) (4.51+7.37) (4.51+7.37) 37)+ (4.51+7.37) 37)+ (4.51+7.37) 37)+ (4.51+7.37)

Airflow rate /s 4,428+5,095 4,293+5,095 5,095+5,095 4,293+7,170 5,095+7,170 7,170+7,170 3,015+4,293+5,095 3,015+5,095+5,095 4,327+5,095+5,095 4,428+5,095+5,095 4,293+5,095+5,095 5,095+5,095+5,095

m3/ 266+306 258+306 306+306 258+430 306+430 430+430 181+258+306 181+306+306 260+306+306 266+306+306 258+306+306 306+306+306
min

Dimensions (H×W×D) mm (1,660×1,240×765) + (1,660×1,240×765) (1,660×1,240×765) + (1,660×1,750×765) + (1,660×930×765) + (1,660×1,240×765) + (1,660×1,240×765) + (1,660×1,240×765)
(1,660×1,750×765) (1,660×1,750×765) (1,660×1,240×765) +
(1,660×1,240×765)

Machine weight kg 323+357 357+357 357+409 409+409 232+357+357 281+357+357 323+357+357 357+357+357

Sound level dB(A 67 66 68 69 70 71 67 69 70


)

Sound power dB(A 90 90 92 91 93 91 93 94


)

Opera Cooling ºCD -5 to 49 -5 to 49


tion B
range

Heating ºCW -25 to 15.5 -25 to 15.5


B

Refrigera Type R-410A R-410A


nt

Charge kg 11.7+11.7 10.9+11.7+11.7 11.7+11.7+11.7

Piping Liquid mm 19.1 (Brazing) 19.1 (Brazing)


connectio
ns
Gas mm 41.3 (Brazing) 41.3 (Brazing)

High and low mm 28.6 34.9 (Brazing) 34.9 (Brazing)


pressure gas
(Brazing)

Notes: Specifications are based on the following conditions;


• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions and oil recovery mode.
When there is concern for noise the surrounding area such as residences, we recommend investigating the installation location and taking soundproofing measures.
 Values based on GEMS determination 2019.
TCSPF: Total Cooling Seasonal Performance Factor
HSPF: Heating Seasonal Performance Factor
In simple terms, TCSPF & HSPF represents the ratio of the Total Cooling & Heating capacity of the air-conditioner relative to the Total energy consumed
by the air-conditioner during the Total Cooling & Heating operation periods in a year.
Whereas the previous index of AEER & ACOP was calculated using only one representative outdoor temperature (35°C for cooling and 7°C for heating),
the new index of TCSPF & HSPF uses a broader range of annual outdoor temperatures* as stipulated in AS/NZS 3823.4.1:2014.
Further, the annual outdoor temperatures are based on zoning Australia/New Zealand into three distinct climate zones (Hot/Average/Cold).
This allows you to determine the performance efficiency of different air-conditioners by comparing their TCSPF & HSPF within the same climate zone.
* There are two kinds of annual outdoor temperatures and it’s different for residential and commercial use.

37 38

Next Generation VRV system


VRV H Series

Significant improvement in total 8 class–60 class (22.4 kW) (168 kW) New
Casing
performance Offers a wide variety of new functions that
benefit everyone involved.

Promotion Movie Special Site VRV H Series


VRV H series enables cooling and heating operation with a single VRV system.
VRV H series adopt a new casing to realise a single module of up to 24 class. In addition,
the new models have achieved significant energy savings with improved technology. The
operating performance has been improved in all directions by introducing unique ideas,
technologies and a wide variety of functions to strengthen design flexibility, easy
installation and reliability.
Heat Pump We provide higher benefits to various users related to air conditioning systems, for
example, building owners, consultants, installers and even building management.

Comfort Design
Energy Savings

Single outdoor units RXYQ8-24BYM


Flexibility Reliability
Double outdoor units RXYQ26-48BYM

Easy
Triple outdoor units RXYQ50-60BYM Installation
39 40

Large-capacity single module Single module reduces installation space 8,14,10,16,1218,class


New Casing 20 class 22, 24 class

VRV H Series VRV H Series Conventional models New models

Offers advanced design and new structure with excellent workability. The larger single
module casing reduces installation cost and space also.

RXYQ8BYM RXYQ10BYM
RXYQ12BYM RXYQ14BYM RXYQ22BYM RXYQ24BYM 765 mm
1,750 mm765 mm
RXYQ16BYM 22, 24 class 22, 24 class
RXYQ18BYM RXYQ20BYM

1,880 mm 7% less
Installation space

(930 mm + 20 mm + 930 mm)


Machine weight 4% less

System capacity Single module (class)


Outdoor unit Number of 1.44 m 400 kg 2 Installation space
1.34 m 2 Machine weight
385
Installation space Machine weight
combination units

kg

48 134

50 139

52 145

54 152 Triple

56 157

58 162

24

New reinforced design


The frame structure has been strengthened to improve resistance
to earthquakes and wind while protecting against falling damage. Minimises horizontal wobbling Conventional models

Support via truss shape

1
60168 2 Conventional models
2 Minimises vibration from various angles

Each part is screwed


with 2 axes

41 42

VRT Smart II control VRV H Series


Energy Savings
Software technology

High TCSPF / HSPF TCSPF (for commercial use)


Further improvement of energy savings is achieved due to optimal control of the outdoor airflow rate. VRV H Series
Energy savings during actual operation have been further improved by the
evolution of software and hardware technologies. Optimal supply exactly meets the required capacity of indoor units
Achieved high values for TCSPF and HSPF in all series.
5
Supplying the refrigerant after
temperature control to the indoor unit

6.55 6.90 6.92 5.97 5.37 5.45 5.49 5.03 4.85 1 Coordinated 4
TCSPF 6.24 6.17
5.886.73
5.99
5.47
6.05
5.55
6.36
5.67
5.60
5.14
5.45
4.99 control Room Determine the target
8.00 6.00 4.00 2.00 temperature and set refrigerant temperature
7.25 temperature
6.55
0 6.17
6.02

8 class 12 class Cold 18 class 22 class Model class Indoor airflow rate 4 2 Compressor speed
10 class 14 class 16 class Hot Average 20 class 24 class
Calculate Control
HSPF (for commercial use)

6.00 4.00 1
HSPF 2.00
Indoor unit will try to
4.51 regulate with fan speed
4.28
control.
0 2
3.78
If fan cannot control
3.64
3.65
speed, indoor unit
4.46
request Te change from
4.12 outdoor unit.
4.28 2.95 3

3.58 Outdoor unit determines


2.84 3.24 the refrigerant
temperature based on
3.60
the demands, and
4.18 2.83 controls the compressor
2.83
speed and
4
3.17
2.75
outdoor airflow rate to
4.03 change the refrigerant
4.30 temperature.
4.35
The outdoor unit supplies
2.67
3.05 the refrigerant adjusted to
3.95
moderate temperature to
2.61
4.26
2.98 the indoor unit. 5
Target refrigerant temperature
3 Indoor unit will calculate
Outdoor airflow rate capacity needed based on
∆T (Room temperature vs
set temperature) and room
temperature trend.
8 class 10 class 12 class 14 class 16 class 18 class 20 class 22 class 24 class
Hot Average Cold
Optimal operating unit number in multi-system
• In outdoor multi-systems, the number of units operated is automatically controlled to ensure the
Hardware technology
High Efficiency Compressor New technologies increase seasonal efficiency and best total efficiency according to the air-conditioning load.
• As the operating efficiency at low loads has been dramatically improved, the system controls
enable a compact design. Improvement of the discharge port each unit automatically in order to maintain operation at a lower load, operating at the highest
Model class possible efficiency.
By improving the shape of the refrigerant discharge port, the pressure increase near the adopted oil control mechanism has reduced gas leakage and mechanical loss. Operation
123
discharge port of the gas refrigerant after compression is suppressed and the
compression loss is reduced.
Overview of multi-unit control for triple units (60 class)
Optimising the back pressure control / Number of units in operation changes
New oil control function before energy efficiency drops.
In addition to the conventional intermediate pressure adjustment port, the pressing
Operation
pressure of the orbiting scroll during operation has been optimised, and the newly
Energy EfficiencyOperation
1 ++
1+2 123

Adoption of a high-performance concentrated motor By adopting it, the coil circumference is greatly reduced, which makes the motor is light-weighted and downsized.
the coil denser and thicker, and the electrical resistance of the coil is dramatically reduced to improve motor efficiency. Furthermore,
20 40 60 Operation Load (class)

43 44

Simultaneous extension of height difference and equivalent length Long piping


Design Flexibility length
VRV H Series VRV H Series

Design flexibility is further NEW


piping length 1000 m Max. 13 m
improved by simultaneous Max. 110 m
extension of height difference, Long piping length enhances design flexibility, enabling support for large buildings
improved from 90 m to 110 m,
and equivalent length (up to
190 m).
Between the outdoor branch
and the last outdoor unit Between the outdoor units Max. 5m
Max. total

Height difference Max. 190 m Equivalent length


Max. 90 m
extension extension Max. actual piping length
Standard Standard Max. height difference between the outdoor units

and the indoor units


90 m

165 m *2
40 m, 50 m 110 m

Max. equivalent
piping length

*4
190 m
• Height difference
extension
Max. 110 m
For height differences exceeding 50 m with the outdoor unit above the indoor unit and 40 m with the outdoor The operating temperature range is up to 49˚C (Outdoor units above indoor units only). Between the first indoor branch and the farthest
Max. height difference between the indoor units
unit below, the main liquid piping size must be increased. The minimum connection capacity index of the indoor unit shall be 63 or more (Outdoor units above indoor units
only).

• Equivalent length Max. 190 m Max. 90 m *3


*1 30 m
indoor unit
When the equivalent piping length from outdoor unit to indoor unit is 90 m or more, be sure to increase the size Maximum allowable piping length Total piping length
of the liquid 165 m (190 m)*4 1000 m
and gas pipes of the main piping.

* In addition to increasing the size of the main pipe, there are other piping restrictions regarding height difference extension and equivalent length.
Check the Installation Manual for details.
Note: The above is just a schematic diagram.

REFNET header downstream branching supported


Piping branch by REFNET joint is possible downstream of REFNET header.
The indoor unit arrangement can be more flexible. Actual piping length (Equivalent)
REFNET joint units (Multiple use)
Between the indoor units
Between the outdoor units and the indoor units

90 m*1

Maximum allowable height difference 10 m (13 m) 5 m


30 m*3
Between the first indoor branch and the farthest indoor unit Between the
110 m*2
outdoor branch and the last outdoor unit (Equivalent) Between the outdoor
REFNET header
KHRP26M22H,KHRP26M33H,KHRP26M72H < 50 KHRP26M73H + KHRP26M73HP ≤ 140

*1. No special requirements up to 40 m. The maximum actual piping length can be 90 m, depending on conditions. Various conditions and requirements have to be met to allow utilisation of 90 m piping length. Be sure to
refer to the Engineering Data Book for details of these conditions and requirements. *2. When Height differences above 50 m if the outdoor unit is above the indoor unit and 40 m if the outdoor unit is below the indoor unit, a
dedicated setting on the outdoor unit is required. Refer to the Engineering Data Book and contact your local dealer for more information.
*3. When Height differences are 15 m or more, maximum actual piping length must be 120 m.
*4. If equivalent piping length from outdoor unit to indoor unit is 90 m or more, make sure to size up the liquid and gas pipes of the main piping.
REFNET header Indoor unit total capacity at REFNET joint

45 46

VRV H Series
Design Flexibility Easy Installation

In the new models, in addition to the actual


Connection ratio step (t01 to t10), a progress rate (0% to 99%)
VRV H Series
~
Connection capacity at maximum is 200%. is available as a guideline when making
arrangements for on-site work. Display of step code and
progress rate alternately
* Effective when test run is carried out independently after manual
refrigerant charging. NEW
Progress rate (0% to 99%)

Connection ratio ~
50%–200%
Electrical component
service window
An electrical component service window is
newly installed on the front panel.
Connection ratio = Total capacity index of Main PCB 7-segment LED can be accessed
the indoor units without removing the front panel.
Capacity index of the outdoor units

Process Workability is greatly improved during


on-site setting or test run.
visualization (Test You can also quickly check the error code
run only*) during service.
Step code (t01 to t10)
Conditions of VRV indoor unit connection capacity Indoor units
Improved refrigerant piping workability

Applicable Other VRV indoor


VRV indoor units

Single
outdoor units
8 - 20 class

22, 24 class

FXDQ FXSQ FXMQ-PA

200%
FXAQ

unit models*1

200%
180%

By dividing piping and wiring holes to


the left and right, piping and wiring
work can be easily performed on site.

Conventional models

H
Double outdoor units Piping
160% hole
Wiring
Triple outdoor units 130% hole
Piping
hole
*1 For the FXF(S)(T)Q25 models, maximum connection ratio is 130 % for the entire range of outdoor units. Note: If the operational capacity of indoor
units is more than 130%, low airflow operation is enforced in all the indoor
units. *Refer to page 53 for outdoor unit combination details. Wiring
hole

Working in closed place is difficult Work becomes easier with sufficient space

47 48

Reliability VRV H Series

Electrical component Electrical component box


IP55-compliant box cover (lower)
sealed component Electrical component box cover (upper) Electrical component

box Enables operation in high outdoor temperature


IP55 sealed component box VRV H Series

protects electrical Three refrigerant cooling circuits enable stable operation even in high
component from a cause of outdoor temperatures by suppressing a temperature rise for the PCB
failure, that is the ingress of mounted in the sealed electrical component box.
debris (lizards, bugs, sand,
water, snow).

Access port cover

Access port cover

Electrical component
box cover (upper)

The internal mounting plate is hinged, enabling easy maintenance of the PCB on the back. Electrical component mounting plate
box cover (lower)

Electrical component box


What is IP55?
temperatures. 52°CDB
PCB Electrical component mounting plate Extended operation temperature range
Upper limit up to 52°CDB in Cooling mode
Operation is now possible on a wider range of outdoor Lower limit down to –25°CWB in Heating mode
–5°CDB
IP55 is the degrees of dust and water protection for the electrical component box equipped on the product. IP55 –20 –10 0 10 20 30 40

Cooling

Liquid ingress protection Grade 5 –20°CWB 15.5°CWB 49°CDB


Water projected by a nozzle (6.3 mm) against enclosure from any direction shall have no harmful effects. Solid particle Ingress Protection
–25°CWB
protection Grade 5 *IP55 is the protection degree of the wiring box as a single unit. The protection grade of outdoor unit is IP14 as well as conventional model.
Heating
Ingress of dust is not entirely prevented, but it must not enter in sufficient quantity to interfere
with the satisfactory operation of the equipment.

Outdoor temperature (°CDB)

49 50

Defrost learning function Double backup operation functions


Comfort VRV H Series VRV H Series

If defrost operation time is short, the system will optimise defrost start conditions for the next cycle, Improving
comfort by extending the heating operation time.

Heating operation time improved by up to 10%!

Heating

Unit backup operation function Compressor backup operation function

Malfunction
Emergency
operation
capacity operation Conventional defrost operation Malfunction Emergency operation
Defrost
operation

Defrost learning operation


Defrost

 And increases the interval


 Defrost operation before the equipment is shut down speeds up the increase of discharge air
System learns the frosting temperature of the next heating operation, and extends the continuous heating operation time
condition from the shortness after restarting, thereby improving comfort.
of the defrost operation time
Heating operation time is improved by up to 30%!

Defrost before stop


until the next defrost operation 100%
Load %
Operating sound dB(A)

Nighttime quiet operation function Peak in the outdoor


temperature

The nighttime quiet operation function automatically suppresses the nighttime operating

50%

Conventional defrost operation Defrost before stop


sound by
8 hrs*1 10 hrs*2
reducing operation capacity to maintain the quiet environment of the neighborhood.
Three selectable modes are available depending on the required level.

Indoor Indoor Restart Heating 57 dB(A)


StopRestart (Heating operation) Stop (Heating operation) operation time Night quiet mode
temperature A temperature A Min. 45 dB(A)*
+30%
3
Defrost operation Defrost operation
t Up to
Defros operation

Due to the low discharge air temperature, the defrost operation starts previous heating operation remains in the heat exchanger before Defrost operation is performed temperature in heating operation rises quickly exchanger before restarting. 8:00 12:00 16:00 20:00 0:00 4:00 8:00 Night mode STARTS
before the room temperature has fully increased. restarting. before the unit is shut down. 45 dB(A)
Frost from the Discharge air There is no frost on the heat Night mode ENDS

* Conditions for effectiveness estimation : Outdoor air temperature 2°C Notes: • This function is available in setting at site.
Round flow cassette with sensing operating at 100% capacity • The operating sound in quiet operation mode is the actual value measured by our company. • The relationship of outdoor temperature
*1. Initial setting is 8 hours. Can be selected from 6, 8 and 10 hours. (load) and time shown above is just an example.
*2. Initial setting is 9 hours. Can be selected from 8, 9 and 10 hours.
*3. In case of 10 class outdoor unit.

51 52

Outdoor Unit Lineup VRV Indoor Unit Lineup Enhanced


VRV H Series
New lineup Indoor units subject to VRT smart control

Lineup

H Series range of choices VRV H SERIES


Capacity range from 8 to 60 class class 8
1 1 1 1 1 2 2 2 2 2 3 3 3 3 3 4 4 4 4

VRV H Series 0 2 4 6 8 0 2 4 6 8 0 2 4 6 8 0 2 4 6
Single outdoor Round Flow Pressure Duct
units Cassette FXFQ-AVM
Outdoor-Air FXMQ-MFV1
Double outdoor Compact Multi Processing Unit
units Flow Cassette FXZQ-BVM
FXMQ-AFVM

Triple outdoor Double Flow


Cassette FXCQ-BVM 4-Way Flow FXUQ-AVEB
units Ceiling
Suspended
Single Flow FXEQ-AV36
Cassette
Ceiling FXHQ-MAVE
Suspended
60 Slim Duct
(Standard) FXDQ-PDVE FXHQ-BVM
Category250
Type Wall Mounted
FXDQ-NDVE FXAQ-AVM

Floor Standing FXLQ-MAVE


Model Name
Slim Duct FXDQ-TV1C(A)
(Compact) Concealed Floor FXNQ-MAVE
Standing

Middle Static Heat Reclaim VAM-HVE


Pressure Duct FXSQ-PAVE Ventilator

Round Flow
FXDYQ-MAV1
FXFTQ-AVM
Cassette with
Sensing and Middle-High
Streamer
FXMQ-PAVE
Static 250
Pressure Duct
Round Flow
Cassette with FXFSQ-AVM
Sensing High Static FXMQ-PV1A
Ceiling Mounted Cassette
Outdoor unit multi
Outdoor unit combinations Capacity
class Maximum number of
index kW Model name Combination Total capacity index of

8 36 38 RXYQ26B RXYQ28B RXYQ30B RXYQ18B – BHFP22R135 400 to 1,040 (1,280) 425 to 1,105 (1,360) 35 (49)
22.4 28.0 33.5 40.0 45.0 50.0 56.0 61.5 RXYQ32B RXYQ34B RXYQ36B RXYQ20B – connectable indoor units*2 100 to 260 (400)
450 to 1,170 (1,440) 475 to 1,235 (1,520) 39 (54) Ceiling Concealed Duct
10 12 14 16 18 20 22 24 26 28 30 32 34
67.0 73.5 78.5 83.5 89.5 96.0 101 RXYQ38B RXYQ22B – 125 to 325 (500) connectable indoor units*2 13 (20) 42 (52)
106 RXYQ24B – 150 to 390 (600) 16 (25) 45 (56)
200 250 300 350 400 450 500 550 RXYQ8B RXYQ12B + RXYQ14B RXYQ12B + – 175 to 455 (700) 19 (30) 48 (60)
600 650 700 750 800 850 900 950 RXYQ10B RXYQ16B RXYQ12B + RXYQ18B – 200 to 520 (800) 22 (35) 52 (64)
RXYQ12B RXYQ12B + RXYQ20B RXYQ14B + – 225 to 585 (900) 26 (40) 55 (64)
RXYQ8B RXYQ10B RXYQ12B RXYQ14B RXYQ20B RXYQ16B + RXYQ20B – 250 to 650 (1,000) 275 to 715 (990) 29 (45) 58 (64)
RXYQ14B RXYQ16B RXYQ18B RXYQ16B RXYQ18B + RXYQ20B 300 to 780 (1,080) 325 to 845 (1,040) 350 32 (50) 61 (64)
RXYQ20B RXYQ22B RXYQ24B connection piping kit*1 – to 910 (1,120) 375 to 975 (1,200)
40 RXYQ40B RXYQ20B × 2 500 to 1,300 (1,600)
112 1,000
42 117 1,050 RXYQ42B 50 139 1,250 RXYQ50B RXYQ12B + RXYQ18B + RXYQ20B 52 145 1,300 BHFP22R168 64 (64)
Ceiling Suspended
RXYQ20B + RXYQ22B 44 123 1,100 RXYQ44B RXYQ20B + RXYQ24B 46 RXYQ52B RXYQ12B + RXYQ20B × 2 54 152 1,350 RXYQ54B RXYQ14B + 525 to 1,365 (1,680) 550 to 1,430 (1,760) 575 to 1,495 (1,840) 600 to 1,560
128 1,150 RXYQ46B RXYQ22B + RXYQ24B 48 134 1,200 RXYQ48B RXYQ20B × 2 56 157 1,400 RXYQ56B RXYQ16B + RXYQ20B × 2 58 162 (1,920) 625 to 1,625 (1,625) 650 to 1,690 (1,690) 675 to 1,755 (1,755) 700
RXYQ24B × 2 1,450 RXYQ58B RXYQ18B + RXYQ20B × 2 60 168 1,500 RXYQ60B to 1,820 (1,820) 725 to 1,885 (1,885) 750 to 1,950 (1,950)
RXYQ20B × 3
Notes: *1. For multiple connection of 26 class systems and above, the outdoor unit multi connection piping kit (separately sold) is required. *2. Values inside brackets are based on
connection of indoor units rated at maximum capacity, 200% for RXYQ8-20BYM, 180% for RXYQ22/24BYM, 160% for double outdoor units, and 130% for triple outdoor units.
Refer to page 47 for note on connection capacity of indoor units.

Floor Standing

Notes: For indoor units without 'VRT Smart', the standard 'VRT' control is available (excludes Heat Reclaim Ventilators).

Max.
• If a system has indoor units subject to both VRT smart and VRT control, the system is operated under VRT control.
• If a system has both outdoor-air processing air conditioners (FXMQ-MF series) and outdoor-air processing type indoor units, VRT smart control and
64 VRT control are disabled.
indoor
units

53 54
In simple terms, TCSPF & HSPF represents the ratio of the Total Cooling & Heating capacity of the air-conditioner relative to the Total

Outdoor Unit Specifications


energy consumed by the air-conditioner during the Total Cooling & Heating operation periods in a year.
Whereas the previous index of AEER & ACOP was calculated using only one representative outdoor temperature (35°C for cooling and 7°C
for heating), the new index of TCSPF & HSPF uses a broader range of annual outdoor temperatures* as stipulated in AS/NZS
3823.4.1:2014.
Further, the annual outdoor temperatures are based on zoning Australia/ New Zealand into three distinct climate zones (Hot/Average/Cold).
 Values based on GEMS determination 2019.
TCSPF: Total Cooling Seasonal Performance Factor
HSPF: Heating Seasonal Performance Factor VRV H Series

Specifications Heat Pump


This allows you to determine the performance efficiency of different air-conditioners by comparing their TCSPF & HSPF within the same climate zone.
* There are two kinds of annual outdoor temperatures and it’s different for residential and commercial use.
Model RXYQ8BYM RXYQ10BYM RXYQ12BYM RXYQ14BYM RXYQ16BYM RXYQ18BYM RXYQ20BYM RXYQ22BYM RXYQ24BYM RXYQ26BYM RXYQ28BYM RXYQ30BYM RXYQ32BYM RXYQ34BYM

Combination units — — — — — — — — — RXYQ12BYM RXYQ12BYM RXYQ12BYM RXYQ12BYM RXYQ14BYM

— — — — — — — — — RXYQ14BYM RXYQ16BYM RXYQ18BYM RXYQ20BYM RXYQ20BYM

Power supply 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz

Cooling capacity Btu/h 76,400 95,500 114,000 136,000 154,000 171,000 191,000 210,000 229,000 250,000 268,000 285,000 305,000 327,000

kW 22.4 28.0 33.5 40.0 45.0 50.0 56.0 61.5 67.0 73.5 78.5 83.5 89.5 96.0

Heating capacity Btu/h 85,300 107,000 128,000 154,000 171,000 191,000 215,000 235,000 256,000 282,000 299,000 319,000 343,000 369,000

kW 25.0 31.5 37.5 45.0 50.0 56.0 63.0 69.0 75.0 82.5 87.5 93.5 100 108

Power Cooling kW 5.17 6.81 8.70 10.7 13.3 14.3 16.9 18.6 21.6 19.4 22.0 23.0 25.6 27.6
consumptio
n
Heating kW 5.33 6.99 9.67 11.0 13.5 14.9 17.0 19.6 22.2 20.7 23.2 24.6 26.7 28.0

Capacity control % 11-100 13-100 12-100 7-100 5-100 4-100 5-100 7-100 6-100

AEER Cooling 4.00 3.83 3.61 3.49 3.18 3.29 3.12 3.12 2.94 3.53 3.35 3.40 3.29 3.26

ACOP Heating 4.33 4.20 3.66 3.82 3.49 3.54 3.50 3.33 3.21 3.74 3.58 3.61 3.58 3.65

TCSPF Hot 6.55/5.69 6.17/5.42 6.02/5.26 5.88/5.07 5.37/4.77 5.45/4.86 5.49/4.18 5.03/4.53 4.85/4.37 5.94/5.16 5.63/4.97 5.67/5.02 5.68/4.98 5.65/4.92
(Cooling)
Commercial
/ Average
Residential
6.55/4.63 6.24/4.55 6.17/4.48 5.97/4.20 5.47/4.04 5.55/4.14 5.67/4.13 5.14/3.95 4.99/3.84 6.06/4.33 5.75/4.23 5.78/4.28 5.85/4.26 5.79/4.16

Cold 7.25/4.58 6.90/4.53 6.92/4.52 6.73/4.19 5.99/4.09 6.05/4.19 6.36/4.21 5.60/4.01 5.45/3.93 6.82/4.34 6.36/4.27 6.37/4.32 6.56/4.33 6.51/4.21

HSPF Hot 4.51/4.53 4.46/4.47 4.28/4.29 4.18/4.19 4.30/4.30 4.35/4.35 4.26/4.26 4.03/3.96 3.95/3.88 4.23/4.24 4.29/4.30 4.33/4.33 4.27/4.27 4.23/4.23
(Heating)
Commerci
al/ Average 4.28/4.17 4.12/3.99 3.65/3.16 3.24/3.05 3.58/3.03 3.60/3.03 3.17/2.94 3.05/2.51 2.98/2.44 3.60/3.11 3.61/3.09 3.62/3.09 3.56/3.02 3.21/2.99
Residentia
l
Cold 3.78/3.54 3.64/3.32 2.95/2.60 2.84/2.48 2.83/2.45 2.83/2.44 2.75/2.36 2.67/2.08 2.61/2.03 2.89/2.54 2.88/2.52 2.88/2.51 2.82/2.44 2.79/2.41

Casing colour Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)

Compress Type Hermetically sealed scroll Hermetically sealed scroll type


or

Motor output kW 4.3 6.2 7.7 3.9+4.4 4.4+5.0 4.0+6.6 4.5+7.4 7.0+7.3 7.7+8.0 7.7+(3.9+4.4) 7.7+(4.4+5.0) 7.7+(4.0+6.6) 7.7+(4.5+7.4) (3.9+4.4)+(4.5+7.4)

Airflow rate /s 2,583 2,817 3,017 4,333 4,433 4,300 5,100 7,167 3,017+4,333 3,017+4,433 3,017+4,300 3,017+5,100 4,333+5,100

m3/ 155 169 181 260 266 258 306 430 181+260 181+266 181+258 181+306 260+306
min

Dimensions (H×W×D) mm 1,660×930×765 1,660×1,240×765 1,660×1,750×765 (1,660×930×765)+(1,660×1,240×765) (1,660×1,240×7


65)+
(1,660×1,240×7
65)

Machine weight kg 215 225 310 340 385 225+310 225+340 310+340

Sound level (Cooling/Heating) dB(A 56/56 57/58 60/62 61/61 65/66 67/67 68/68 64/65 66/67
)

Sound power dB 78 79 83 85 90 90 86 87 91

Opera Cooling ºCD –5 to 52 –5 to 52


tion B
range

Heating ºCW –25 to 15.5 –25 to 15.5


B

Refrigera Type R-410A R-410A


nt

Charge kg 6.9 7.1 7.2 9.7 9.9 11.7 11.7 7.2+9.7 7.2+9.9 7.2+11.7 9.7+11.7

Piping Liquid mm 9.5 (Brazing) 12.7 (Brazing) 15.9 (Brazing) 15.9 (Brazing) 19.1 (Brazing)
connectio
ns
Gas mm 19.1 22.2 28.6 (Brazing) 28.6 (Brazing) 34.9 (Brazing)
(Brazing) (Brazing)

VRV H Series
Model RXYQ36BYM RXYQ38BYM RXYQ40BYM RXYQ42BYM RXYQ44BYM RXYQ46BYM RXYQ48BYM RXYQ50BYM RXYQ52BYM RXYQ54BYM RXYQ56BYM RXYQ58BYM RXYQ60BYM

Combination units RXYQ16BYM RXYQ18BYM RXYQ20BYM RXYQ20BYM RXYQ20BYM RXYQ22BYM RXYQ24BYM RXYQ12BYM RXYQ12BYM RXYQ14BYM RXYQ16BYM RXYQ18BYM RXYQ20BYM

RXYQ20BYM RXYQ20BYM RXYQ20BYM RXYQ22BYM RXYQ24BYM RXYQ24BYM RXYQ24BYM RXYQ18BYM RXYQ20BYM RXYQ20BYM RXYQ20BYM RXYQ20BYM RXYQ20BYM

— — — — — — — RXYQ20BYM RXYQ20BYM RXYQ20BYM RXYQ20BYM RXYQ20BYM RXYQ20BYM

Power supply 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz

Cooling capacity Btu/h 345,000 362,000 382,000 401,000 420,000 439,000 458,000 476,000 496,000 518,000 536,000 553,000 573,000

kW 101 106 112 117 123 128 134 139 145 152 157 162 168

Heating capacity Btu/h 386,000 406,000 430,000 450,000 471,000 491,000 512,000 534,000 558,000 584,000 601,000 621,000 645,000

kW 113 119 126 132 138 144 150 156 163 171 176 182 189

Power Cooling kW 30.2 31.2 33.8 35.5 38.5 40.2 43.2 39.9 42.5 44.5 47.1 48.1 50.7
consumptio
n
Heating kW 30.5 31.9 34.0 37.1 39.2 41.8 44.4 41.6 43.7 45.0 47.5 48.9 51.0

Capacity control % 5-100 4-100 5-100 6-100 5-100 4-100

AEER Cooling 3.15 3.20 3.13 3.13 3.03 3.03 2.94 3.29 3.23 3.21 3.14 3.17 3.13

ACOP Heating 3.53 3.56 3.54 3.45 3.37 3.31 3.25 3.58 3.57 3.61 3.53 3.55 3.54

TCSPF Hot 5.44/4.80 5.47/4.84 5.49/4.82 5.23/4.66 5.12/4.57 4.93/4.44 4.85/4.37 5.59/4.93 5.60/4.91 5.59/4.88 5.46/4.81 5.48/4.83 5.49/4.82
(Cooling)
Commercial
/ Average
Residential
5.58/4.10 5.61/4.14 5.67/4.13 5.38/4.03 5.28/3.97 5.06/3.89 4.99/3.84 5.73/4.22 5.78/4.21 5.75/4.15 5.61/4.11 5.63/4.14 5.67/4.13

Cold 6.19/4.16 6.21/4.21 6.36/4.22 5.94/4.11 5.83/4.06 5.52/3.97 5.45/3.93 6.37/4.28 6.48/4.28 6.45/4.21 6.25/4.18 6.26/4.21 6.36/4.22

HSPF Hot 4.28/4.28 4.30/4.30 4.26/4.26 4.14/4.14 4.09/4.09 4.00/3.92 3.96/3.88 4.30/4.30 4.27/4.27 4.24/4.24 4.27/4.27 4.29/4.29 4.26/4.26
(Heating)
Commerci
al/ Average 3.21/2.98 3.55/2.99 3.18/2.95 3.12/2.90 3.07/2.85 3.02/2.48 2.98/2.45 3.58/3.03 3.54/2.99 3.20/2.98 3.20/2.97 3.54/2.98 3.18/2.95
Residentia
l
Cold 2.79/2.40 2.79/2.40 2.76/2.36 2.72/2.35 2.68/2.30 2.64/2.06 2.61/2.03 2.83/2.44 2.80/2.41 2.78/2.40 2.78/2.39 2.78/2.39 2.76/2.36

Casing colour Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)

Compress Type Hermetically sealed scroll type Hermetically sealed scroll type
or

Motor output kW (4.4+5.0)+ (4.0+6.6)+ (4.5+7.4)+ (4.5+7.4)+ (4.5+7.4)+ (7.0+7.3)+ (7.7+8.0)+ 7.7+(4.0+6.6)+(4.5+7.4) 7.7+(4.5+7.4)+(4.5+7.4 (3.9+4.4)+(4.5+7.4)+ (4.4+5.0)+(4.5+7.4)+ (4.0+6.6)+(4.5+7.4)+ (4.5+7.4)+(4.5+7.4)+
(4.5+7.4) (4.5+7.4) (4.5+7.4) (7.0+7.3) (7.7+8.0) (7.7+8.0) (7.7+8.0) ) (4.5+7.4) (4.5+7.4) (4.5+7.4) (4.5+7.4)

Airflow rate /s 4,433+5,100 4,300+5,100 5,100+5,100 5,100+7,167 7,167+7,167 3,017+4,300+5,100 3,017+5,100+5,100 4,333+5,100+5,100 4,433+5,100+5,100 4,300+5,100+5,100 5,100+5,100+5,100

m3/ 266+306 258+306 306+306 306+430 430+430 181+258+306 181+306+306 260+306+306 266+306+306 258+306+306 306+306+306
min

Dimensions (H×W×D) mm (1,660×1,240×765)+(1,660×1,240×765) (1,660×1,240×765)+(1,660×1,750×76 (1,660×1,750×765)+(1,660×1,750×7 (1,660×930×765)+(1,660×1,240×765)+(1,660×1,240×7 (1,660×1,240×765)+(1,660×1,240×765)+(1,660×1,240×765)


5) 65) 65)

Machine weight kg 310+340 340+340 340+385 385+385 225+340+340 310+340+340 340+340+340

Sound level (Cooling/Heating) dB(A 66/67 68/69 69/70 70/70 71/71 67/68 69/70 70/71
)

Sound power dB 91 93 92 93 94 95

Opera Cooling ºCD –5 to 52 –5 to 52


tion B
range

Heating ºCW –25 to 15.5 –25 to 15.5


B

Refrigera Type R-410A R-410A


nt

Charge kg 9.9+11.7 11.7+11.7 7.2+11.7+11.7 9.7+11.7+11.7 9.9+11.7+11.7 11.7+11.7+11.7

Piping Liquid mm 19.1 (Brazing) 19.1 (Brazing)


connectio
ns
Gas mm 41.3 (Brazing) 41.3 (Brazing)

Notes: Specifications are based on the following conditions; • Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a Height of 1.5 m. During actual operation, these values are normally somewhat higher as a
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m. result of ambient conditions and oil recovery mode.
55 56
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m. When there is concern for noise the surrounding area such as residences, we recommend investigating the installation location and taking soundproofing measures.
VRV S High Seasonal Efficiency Series

The Ideal Air Conditioning System for Heat Pump Energy savings
4class–8class (11.2 kW) (22.4 kW)
& comfort
Residential Houses, The VRV S High Seasonal Efficiency
Small Offices and Shops
Series concept VRV S High Seasonal Efficiency Series
Presentation
Movie New VRV S High Seasonal Efficiency Series achieves higher energy efficiency with a
variety of function for comfort and high performance. A wide range of options for
installation location and application are easily achieved by the low height casing, long
piping length and other features.
Design

RSUYQ4-6A2VMA RSUYQ7-8AYM Energy savings & comfort Extended operation range up to 52°C High voltage shield PCB

High performance Automatic refrigerant charge function Design flexibility of installation


Higher energy efficiency
& reliability VRT Smart Control
Quiet operation
flexibility of installation
High performance & reliability
The high external static pressure of 40 Pa enables installation in small installation spaces where the
airflow direction needs to be diverted to avoid short circuits.
Low height casing design
Increased actual piping length up to 120 m

57 58
Separate
8

Energy Savings &


Collision

Comfort Energy savings Comfort


High seasonal efficiency Quiet operation
The VRT Smart Control enables improvements on efficiency during low load operation,
VRV S High Seasonal Efficiency Series VRV S

achieving high seasonal efficiency.


V-cut & irregular pitch propeller fan
High Seasonal Efficiency Series

EER for 5 class Old New

Air streams collide


5.51
Cooling EER
7654321 4.894.36 and generate lossAir streams are smoothed around V-cut and reduces airflow loss A˚ C˚
4.17 The fan's V-cut enables streamlined and effective airflow.
7.14 B˚
6.32
0 Irregular blade pitch also contributes to reduced airflow noise.
50% 60% 70% 80% 90% 100% Load S SERIES Nighttime quiet operation function
A˚< B˚< C˚

the required level.


VRT Smart Control This function is suitable for use in residential areas.
VRT Smart function is available in the VRV S High Seasonal Efficiency Series for the first time. Coordination between indoor and Cooling Night Quiet
outdoor units minimizes energy consumption by optimising capacity to meet actual operation load.
RSUYQ4/5/6A Mode Min. 40
Supplying the refrigerant after 2
temperature control to the indoor unit dB(A)

RSUYQ7/8A Min. 45 dB(A)

Coordinated control Load %


The nighttime quiet operation function automatically suppresses the nighttime operating sound by reducing operation Operating
sound dB(A)
capacity to maintain the quiet environment of the neighborhood. Three selectable modes are available depending on

100% Peak in the outdoor temperature

Room temperature and set temperature

Determine the target refrigerant temperature 8 hrs 10 hrs

50%

52 dB(A)
Calculate Target refrigerant temperature Notes: • This function is available in setting at site.
Indoor airflow rate
Night Min. 40 dB(A) 40 dB(A)
Control Compressor speed quiet mode
Notes: • For the classification of indoor units (VRT smart control and VRT control), refer to the indoor unit lineup. 8:00 12:00 16:00 20:00 0:00 4:00 8:00 Night mode STARTS Night mode ENDS • In case of 4-6 class outdoor unit
• If a system has indoor units subject to both VRT smart and VRT control, the system is operated under VRT control. • The operating sound in quiet operation mode is the actual value measured by our company.
• If a system has both outdoor-air processing air conditioners (FXMQ-MF series) and outdoor-air processing type indoor units, VRT smart control and • The relationship of outdoor temperature (load) and time shown above is just an example.
VRT control are disabled.

59 60

New swing compressor


High Performance & Reliability High temperature VRV S High Seasonal Efficiency Series VRV S High Seasonal Efficiency Series

operation

Extended operation range up to 52°C High efficiency, high capacity DC inverter swing compressor
The outdoor operation temperature range is now extended to 52ºC. This enables reliable The new compressors offer higher performance compared to that of conventional scroll High-capacity
operation even under high temperature conditions and a wider choice of installation compressors. swing structure
locations. New DC motor
(high wire-efficiency winding/ high-efficiency magnet)

Cooling Outdoor temperature (°CDB)


-5 0 10 20 30 40 46 52°C from 46°C to 52°C.
Improved performance
New VRV S High Seasonal Efficiency Series
The new DC motor designed with
small-diameter bearing and improved
Previous VRV IV S Series
efficiency during low-speed
operation has improved seasonal efficiency.

The refrigerant-cooled PCB and large 3-row heat exchanger


raise the maximum cooling outdoor operation temperature High voltage shield PCB (4-6 class model only)

Refrigerant cooled PCB The high voltage shield PCB protects the electrical parts and prevents malfunctions at * Continuous operation range is 198 to 264 V.
the highest voltage of 440 V.
Daikin’s unique refrigerant cooling helps maintain high cooling capacity Max.
even during 440 V
high outdoor temperatures.
function Contribute to optimised operation efficiency, higher quality and easier installation.
Automatic refrigerant charge

New heat exchanger ・Heat exchanger area 68%UP (4,5 class model only)

Optimised operation efficiency


This function prevents a capacity shortage or energy loss due to
excessive or insufficient refrigerant.
Optimised Operation
Efficiency
Cooling capacity
・2-sided 3-row

Insufficient Excessive
Keep rated cooling capacity in high outdoor refrigerant charge refrigerant charge

Optimal refrigerant amount


temperature up to 43°C Higher quality and easier installation Refrigerant charge amount

Rated cooling capacity can be maintained even when outdoor temperature is up to 43°C. pressing one button.
The automatic refrigerant charge function automates the charging of the proper refrigerant amount and easy start by 1 Start of automatic refrigerant
Cooling New VRV S High Seasonal Efficiency Series in high ambient temperatures.
capacity 43 52 10 35 39
2
Calculation of necessary refrigerant
Previous VRV IV S Series
amount from design drawing
Outdoor
temperature Automatic Refrigerant Charge

100% The large heat exchanger ensures sufficient cooling capacity even
・Automatic completion by proper refrigerant amount ・Monitoring
refrigerant charging is unnecessary

charge operation

R-410A
(°CDB) ・No recalculation of charge amounts due to minor design changes locally

61 62 *If pipe length exceeds 90 m, must use automatic refrigerant charge function. Refer to installation manual for details.

High external static pressure up to 40 Pa and automatic adjustment of external


Design Flexibility of Installation static pressure
The new design has been optimised for the VRV S High Seasonal Efficiency Series with the height of all models reduced to only 870
mm. This low height casing design provides occupants with a clear, unobstructed view of the scenery.
No short circuits Low height casing design
VRV S High Seasonal Efficiency Series VRV S High Seasonal Efficiency Series

The new VRV S High Seasonal Efficiency Series outdoor unit has been achieved high static pressure (Pa) Previous VRV IV S series
external static pressure up to 40 Pa, realizing stable operation in small installation sites Resistance increases
where the air direction when duct is
External installed in the site.
Rated airflow is
adjustment grille or duct is used to avoid short circuits. maintained maintained. 3

The external static pressure automatic adjustment function Airflow (rated) Airflow (m3/min) m
1 1,430 m 870 mm
maintains rated airflow and capacity by automatically adjusting the
external static pressure during the test operation to suit the 2
resistance of the installation site.

4-8 class
Airflow decreases.
m
990 m 1,345 mm 4,5 class 6 class 8 class

Optimum airflow direction with the optional air ・Ideal solution that minimises both visual and sound impact ・Can be installed in a wide variety
of locations and applications ・No space required for multiple outdoor units
direction adjustment grille
When discharged air is blocked by some obstacle, the optional air direction adjustment View from outside View from inside
grille can divert the airflow to one of 4 directions (up, down, left or right) to avoid the
obstacle.

Wind is diverted upwards.


Air direction adjustment grille (option)

Wind is diverted sideways. Window

Outdoor unit

the air direction adjustment grille, installing a field-supplied


Duct installation to duct
stabilize the system can bypass the obstacle. In this way, installation of the
Flange outdoor unit is possible in places like behind an advertising
(Field supply) board.
Duct
(Field supply)
Double-stacking installation
possible The low height casing design allows for compact double-
stacking of outdoor units to
When the obstacle is not avoidable by maximize utilization of installation space.
63 64

Design Flexibility of
Ceiling Mounted Cassette Middle Static
Pressure Duct FXSQ-PAVE
Type Model Name
FXDYQ-MAV1

Middle-High

Installation Increased actual piping length


FXMQ-PAVE
Static
Pressure Duct

High Static FXMQ-PV1A


Pressure Duct
up to 120 m*
Outdoor-Air FXMQ-MFV1
Round Flow FXFTQ-AVM Processing Unit

Indoor Unit Lineup Wide variety


Cassette with
Sensing and
Streamer
FXMQ-AFVM

Round Flow 4-Way Flow FXUQ-AVEB


Cassette with FXFSQ-AVM Ceiling
of indoor unit Sensing Suspended

Round Flow Ceiling FXHQ-MAVE


VRV S High Seasonal Efficiency Series VRV S High Seasonal Efficiency Series
Cassette FXFQ-AVM Suspended
FXHQ-BVM
Compact Multi
Flow Cassette FXZQ-BVM
Wall Mounted
FXAQ-AVM
Double Flow
Cassette FXCQ-BVM
New lineup Indoor units subject to VRT smart control Floor Standing FXLQ-MAVE
Actual piping length increased by 20% allows for various installation! Single Flow FXEQ-AV36
Cassette Concealed Floor FXNQ-MAVE
Standing
Slim Duct
(Standard) FXDQ-PDVE Heat Reclaim VAM-HVE
Ventilator
Previous VRV IV S series
Installation on the rooftop of FXDQ-NDVE

Category
residential apartments 250
Slim Duct FXDQ-TV1C(A)
(Compact) 250

Max. height difference


100 m
120 m*
between the outdoor units
and the indoor units

50 m
Max. height difference
between the indoor units

300 m Max. total


piping length

Max. actual
piping length

120 m*
Max. equivalent piping length

150 m

Ceiling Concealed Duct


Between the first indoor branch and the farthest indoor unit 5-8 class
15 m 4 class 10 m
Max. 40 m
120 m* (150 50 m
m)
40 m
300 m

Note: The above is just a schematic diagram. 40 m

Ceiling Suspended
Maximum allowable piping length Actual piping length (Equivalent) 120 m* (150 m) 300 m
Total piping length 40 m
Between the first indoor branch and the farthest indoor unit Between the indoor units 15 m
Maximum allowable
height difference Between the outdoor units and the indoor units If the outdoor unit is above. If the outdoor unit is below. 50 m 40 m
Floor Standing
* If pipe length exceeds 90 m, must use automatic refrigerant charge function. Refer to installation manual for details. Note: For indoor units without 'VRT Smart', the standard 'VRT' control is available (excludes Heat Reclaim Ventilators).

Installation on balconies of

One outdoor unit can provide comfort for

the whole house


residential apartments
• If a system has indoor units subject to both VRT smart and VRT control, the system is operated under VRT control. • If a system has both outdoor-air processing air conditioners (FXMQ-MF series) and outdoor-air
13Max.indoor units processing type indoor units, VRT smart control and VRT control are disabled.

65 66

Heat Pump
VRV S High Seasonal Outdoor unit combinations
Outdoor Units VRV S High Seasonal Efficiency Series VRV S High

Efficiency Series Specifications


Seasonal Efficiency Series

Class 4 5 6 7 8

Capacity index 100 125 150 175 200

Total capacity Combination 50% 50 62.5 75 87.5 100


index of (%)
MODEL RSUYQ4A2VMA RSUYQ5A2VMA RSUYQ6A2VMA RSUYQ7AYM RSUYQ8AYM Power supply 1-phase, 220-240/220-230 V, 50/60 Hz 3-phase, 380-415 V/380 V, 50/60 Hz connectable
indoor units 100 100 125 150 175 200
%
Cooling capacity 38,200 47,800 54,600 68,200 76,400
130 130 162.5 195 227.5 260
Btu/h %

kW 14.0 16.0 20.0 22.4 11.2


Maximum number of connectable indoor 6 8 9 11 13
units
MODEL RSUYQ5A2VMA RSUYQ4A2VMA RSUYQ6A2VMA RSUYQ7AYM RSUYQ8AYM

kW 11.2 14.0 16.0 20.0 22.4

Btu/h 42,700 54,600 61,400 76,400 85,300


Heating capacity
Note: Total capacity index of connectable indoor units must be 50%-130% of the capacity index of the outdoor unit.
kW 16.0 18.0 22.4 25.0 12.5

Power kW
Cooling 2.48 3.36 3.95 5.46 6.61
consumption Heating 3.28 3.90 5.10 5.92
kW 2.51

Capacity control % 23 to 100 15 to 100 9 to 100 AEER★ 4.07 3.81 3.73 3.42 3.19 Cooling

ACOP Heating ★ 4.46 4.42 4.22 4.09 3.95

TCSPF★ (Cooling) Hot 5.85 / 5.29 6.04 / 5.45 6.10 / 5.51 5.34 / 4.87 5.18 / 4.71
Commercial / Average 5.57 / 4.21 5.91 / 4.47 6.04 / 4.60 5.30 / 4.13 5.19 / 4.06
Residential HSPF★ (Heating)
Cold 5.78 / 4.09 6.23 / 4.45 6.39 / 4.63 5.60 / 4.15 5.53 / 4.14 Hot 4.96 / 4.98 4.69 / 4.71 4.37 / 4.39 5.00 / 5.00 4.83 / 4.82
Commercial / Average 4.81 / 4.74 4.55 / 4.50 4.25 / 4.22 4.74 / 4.58 4.58 / 4.41
Residential Cold 4.56 / 4.47 4.28 / 4.18 4.02 / 3.95 4.42 / 4.22 4.27 / 4.07
Casing colour Ivory white (5Y7.5/1) Type Hermetically sealed swing type

Compressor Heating) kW 2.0/2.4 3.1/3.6 3.5/4.0 1.9/2.3 3.2/3.2


Motor output (Cooling /

/s Cooling
1,450 1,400 1,450 2,050

m³/min 87 84 87
123
Airflow rate /s 1,500 1,400 1,567
Heating 2,283 2,417

m³/min 84 94 137
90 145

Dimensions (H×W×D) mm 870×1,100×460

Machine weight kg 95 98 120 dB(A) Sound pressure level

(Cooling/Heating) 52/54 53/54 55/56 58/61 59/63 dB(A) Sound power level

(Cooling/Heating) 73/75 74/75 76/77 79/82 80/84


Operation range Refrigerant °CDB °CWB -20 to 15.5 R-410A
Cooling Heating Type
-5 to 52

Charge 4.0 4.2 5.4 kg

Liquid mm 9.5 (Flare)


Piping
connections Note: 1. Specifications are based on the following conditions;
Gas mm
15.9 (Flare) 19.1 (Brazing)

• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions and oil recovery mode.
When there is concern for noise the surrounding area such as residences, we recommend investigating the installation location and taking soundproofing measures.
• Refrigerant charge is required.
★ Values based on GEMS determination 2019.
TCSPF: Total Cooling Seasonal Performance Factor
HSPF: Heating Seasonal Performance Factor
In simple terms, TCSPF & HSPF represents the ratio of the Total Cooling & Heating capacity of the air-conditioner relative to the Total energy consumed
by the air-conditioner during the Total Cooling & Heating operation periods in a year.
Whereas the previous index of AEER & ACOP was calculated using only one representative outdoor temperature (35°C for cooling and 7°C for heating),
the new index of TCSPF & HSPF uses a broader range of annual outdoor temperatures* as stipulated in AS/NZS 3823.4.1:2014.
Further, the annual outdoor temperatures are based on zoning Australia/ New Zealand into three distinct climate zones (Hot/Average/Cold).
This allows you to determine the performance efficiency of different air-conditioners by comparing their TCSPF & HSPF within the same climate zone.
* There are two kinds of annual outdoor temperatures and it’s different for residential and commercial use.
67 68

VRV IV S Series

Compact & lightweight design


The Ideal Air Conditioning System
for Residential Houses, Small Offices The VRV IV S series is slim and compact, with outdoor units that require minimal
installation space.
VRV IV S Series
1,430 mm

and Shops 990 mm

Heat Pump 3.5 class – 6 class 8class / 9class


3.5class–9class (9 kW) (24 kW)

940 mm 940 mm
320 mm 320 mm

71 kg 78 kg 80 kg
3.5 class / 4 class 5 class 6 class

990 mm 990 mm 990 mm


8 class / 9 class
Height 1,430 mm Product Weight 138 kg 0.30 m2 Footprint 0.30 m2 0.30 m2 0.30 m2

Energy saving

High Energy Efficiency Ratio (EER)


VRV IV S series provides greater energy saving
as compared to VRV III S series.

VRV III S VRV IV S Series

RXYMQ3-4A2V4A RXYMQ5- Cooling Operation EER 3.89 3.55


3.66
3.49

6B2VM RXYMQ8-9AY1 4
3.69
3.8 3.6 3.4 3.2 0 3.77
3.5 class 4 class 6 class 5 class 8 class 9 class
(9.0 kW) (11.2 kW) (14.0 kW) (16.0 kW) (22.4 kW) (24.0 kW)

*Cooling operation conditions: Indoor temp. of 27º CDB,19º CWB, and outdoor temp. of 35º CDB.

69 70

VRV IV S Series
Comfort and Simplified Installation

100%
Quiet operation Load % Makes the long piping design possible
Operating sound dB(A)
Long piping length offers flexibility in the choice of installation Actual piping length
Nighttime quiet operation function positions, and simplifies system planning.
The nighttime quiet operation function automatically suppresses Peak in the outdoor
temperature
the nighttime operating
sound by reducing operation
capacity to maintain the quiet
environment of the 8 hrs 10 hrs
neighborhood.
Max. 100 m
50%
a
bcd

VRV IV S Series

Max.
Three selectable modes are available depending Night j
on the required level. quiet mode 50 m 15 m
This function is suitable for use in residential areas. e g
Equivalent piping length Max. 130 m f h First indoor branch k

Total piping length Max. 300 m i


52 dB(A) Max.

3.5,4 5,6 class


class

a+b+c+d+i 70 m (90 70 m (90


m) m)

a+b+c+d+e+f+g+h+ 250 m 300 m


i

b+c+d+i 40 m 40 m

Min. 43 dB(A) 43 dB(A) 8,9 class

8:00 12:00 16:00 20:00 0:00 4:00 8:00 Actual refrigerant piping length (Equivalent)100 m (130 m)
Night mode STARTS Night mode ENDS
k 30 m
Notes: • This function is available in setting at site.
• The operating sound in quiet operation mode is the actual value measured by our k 30 m
company.
• The relationship of outdoor temperature (load) and time shown above is just an
example.
Max. allowable piping length

300 m 40 m

Max. allowable height difference 15 m 50 m


Total piping length
Between the first indoor branch and the farthest indoor unit

Between the indoor units

If the outdoor unit is above


Between the outdoor unit
j 10 m
• In case of 4 class outdoor unit and the indoor unit
Technologies for efficient and quiet operation If the outdoor unit is below
40 m

Swing compressor (3.5-6 class model only) Sucked gas is compressed in the scrolling part before the heated motor, so that the machine compress the non-expanded
gas, resulting in high efficiency compression.
Daikin swing compressor has integrated the rotor with the blade, completely solving the refrigerant leakage and the wear
8, 9 class
problem caused by the mechanical friction between the rotor and the blade, which enhances the compressor efficiency and Suction
makes the compressor more quiet and durable.
3.5, 4, 5, 6 class
Scroll section

Discharge Motor
Swing compressor section

Scroll
compressor

Smooth air inlet bell mouth and aero spiral fan


The smooth air inlet bell mouth and the aero spiral fan work to minimize turbulence in the airflow and reduce sound.
The structural scroll (8-9 class model only) DC fan motor
Efficiency improved in all areas compared to conventional AC motors, especially at low speeds.

71 72

Enhanced range of choices


Indoor Unit Lineup New lineup

VRV IV S Series

Category

Type 2 2 3 4 5 6 7 8 1 1 1 1 1 1 2
0 5 2 0 0 3 1 0 0 2 4 4 6 8 0
0 5 0 5 0 0 0

Model Name Capacity Range 2. 2. 3. 4. 5. 7. 8 9 1 1 1 1 1 2 2


(kW) 2 8 6 5 6 1 1. 4 6 6. 8 0 2.
2 2 4

Capacity Index 2 2 31 4 5 6 8 1 1 1 1 1 1 2
.2 2.
0 5 0 0 0 0 2 4 4 6 8 0
5
5 7 0 5 0 5 0 0 0
1

Round Flow FXFTQ-AVM


Cassette with
Sensing and
Streamer

Round Flow FXFSQ-AVM


Cassette with
Sensing

Round Flow Cassette FXFQ-AVM

Compact Multi FXZQ-BVM


Flow Cassette

Double Flow FXCQ-BVM


Cassette

Single Flow Cassette FXEQ-AV36


Slim Duct (Standard) FXDQ-PDVE

(700 mm width type)

FXDQ-NDVE

(900/1,100 mm width
type)

Slim Duct (Compact) FXDQ-


TV1C(A)

Middle Static FXSQ-PAVE


Pressure Duct

FXDYQ-
MAV1

Middle-High Static Pressure FXMQ-PAVE


Duct

High Static Pressure FXMQ-PV1A


Duct

Outdoor-Air FXMQ-MFV1
Processing Unit

FXMQ-AFVM

4-Way Flow Ceiling FXUQ-AVEB


Suspended

Ceiling Suspended FXHQ-MAVE

FXHQ-BVM

Wall Mounted FXAQ-AVM

Floor Standing FXLQ-MAVE

Concealed Floor FXNQ-MAVE


Standing

Heat Reclaim Ventilator VAM-HVE Airflow rate 3


/
150-2000 m h

250
28
250

VRV IV S Series

Ceiling Mounted Cassette


Ceiling Concealed Duct

Ceiling Suspended

Floor Standing

14Max.indoor
units

73 74

Outdoor unit
Outdoor Units VRV IV S Series
Heat Pump

combinations
VRV IV S Series
Specifications

MODEL MODELRXYMQ8AY1 Maximum number of connectable indoor units


Btu/h Cold —
RXYMQ3A2V4A RXYMQ4A2V4A RXYMQ5B2VM
RXYMQ9AY1 24.0
RXYMQ6B2VM 10.0 Hot —
9 kW
9.0
215 Average —
Cooling 2.44 5
RXYMQ3A2V4A RXYMQ4A2V4A RXYMQ5B2VM 3.5 kW 89
RXYMQ6B2VM Power supply Cooling capacity 2.28 Cold — 6
Heating
80
1-phase, 220-230 V, 50 Hz 24 to 100
Combination 50% 40 %
(%)
3-phase, 380–415 V, 50 Hz
100 80 Btu/h Cooling — 13
RXYMQ8AY1 RXYMQ9AY1 30,700 81,900 107.5 215
%
Heating — 24.0 280
130 104 9.0
kW
% kW
Hot — 88,700 14
class Total capacity index
34,100 VRV IV S Series
Capacity index Average — of connectable
indoor units
Heating capacity 20 to 100 6.88

6.82
Power consumption


Capacity control AEER★

ACOP★

TCSPF★ (Cooling) Commercial /
Residential —


HSPF★ (Heating) Commercial /
Residential —
Ivory white (5Y7.5/1)
Note: Total capacity index of connectable indoor unit be 50%--130% of the capacity index of the outdoor unit.

Casing colour 26.0

Compressor Airflow rate


Dimensions (H×W×D) Machine weight

Hermetically sealed swing type


Type Hermetically sealed scroll type

Motor 1.92 kW 3.2/3.5 3.7 3.8 4.8


output
(Cooling/He 2,333
ating)
140
1,267 /s 1,350 1,333
1,430×940×320

m /min76
3
81 80 138
Sound level (Cooling/Heating)Sound power
990×940×320
mm
Operation range

71 kg 78 80
Type
58/59
dB(A) 52/54 53/54 55/56 57/58
51/52
76

69 dB(A) 70 74 76 75

Cooling °CDB -5 to 46
R-410A
Heating °CWB -20 to 15.5

Refrigerant 5.8
Liquid mm 9.5 (Flare)
9.5 (Brazing)

Piping connections Gas

Charge 2.9 kg 3.4 4.0 Notes: Specifications are based on the following conditions;
15.9 (Flare)
19.1 (Brazing) 22.2 (Brazing)

• Cooling: Indoor temp. : 27° CDB, 19° CWB, Outdoor temp. : 35° CDB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Heating: Indoor temp.: 20° CDB, Outdoor temp.: 7° CDB, 6° CWB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions and oil recovery mode.
When there is concern for noise the surrounding area such as residences, we recommend investigating the installation location and taking soundproofing measures.
• Refrigerant charge is required.
★ Values based on GEMS determination 2019.
TCSPF: Total Cooling Seasonal Performance Factor
HSPF: Heating Seasonal Performance Factor
In simple terms, TCSPF & HSPF represents the ratio of the Total Cooling & Heating capacity of the air-conditioner relative to the Total energy consumed
by the air-conditioner during the Total Cooling & Heating operation periods in a year.
Whereas the previous index of AEER & ACOP was calculated using only one representative outdoor temperature (35°C for cooling and 7°C for heating),
the new index of TCSPF & HSPF uses a broader range of annual outdoor temperatures* as stipulated in AS/NZS 3823.4.1:2014.
Further, the annual outdoor temperatures are based on zoning Australia/ New Zealand into three distinct climate zones (Hot/Average/Cold).
This allows you to determine the performance efficiency of different air-conditioners by comparing their TCSPF & HSPF within the same climate zone.
75 76 * There are two kinds of annual outdoor temperatures and it’s different for residential and commercial use.

VRV IV Q Series

The VRV IV Q Series concept

For Quick & High Quality


Heat Pump
Standard Type Space Saving Type Reusing existing refrigerant piping minimizes Improvement
Replacement Use 6class–48class (16 installation time and cost in capacity
kW) (135 kW)
An automatic and greater number
refrigerant charge function enables high VRV IV Q Series

quality installation of indoor units

Single outdoor units


RQYQ6-16TY1A(E)

Double outdoor units RQYQ18-32TNY1A(E)

Triple outdoor units


RQYQ34-48TNY1A(E) RQCEQ280-848PY1

Single outdoor units


RQYQ18-20TY1A(E)

Double outdoor units RQYQ30-40TSY1A(E)

Triple outdoor units


RQYQ42-48TSY1A(E) * (E) : anti-corrosion model

Heat Recovery
10class–30class
(28 kW) (84.8 kW)

Quick, quality and economical replacement Reuse


Simple use of existing refrigerant piping
Special equipment and work is no longer required to clean pipes. A new function automatically deals with contamination inside piping during refrigerant charging, eliminating the work involved in cleaning.

Even applicable for non-DAIKIN systems! The Daikin low-cost upgrade solution
Reuse drain pipes
Reuse refrigerant pipes
Pipes used for R-22 and R-407C will also work with VRV IV Q series.

Reuse refrigerant branch pipes


There are no restrictions when upgrading from a
Daikin VRV system. Other VRF systems require branch
pipes withstand pressure up to 3.3 MPa.

Reuse remote control and indoor-outdoor wiring


Reuse wiring when upgrading from a Daikin VRV system.
In other cases, this will depend on the cable type.

Replace indoor units


Replace outdoor units

77 78

Automatic Design flexibility


Benefits of System Replacement Refrigerant charging, cleaning
Significantly more compact outdoor unit enables the effective use of limited space!
and test
operation done with just a single switch.
VRV IV Q Series

The automatic refrigerant charge function automates the charging *(ambient


There are conditions in the range Conventional
temperature, connection
of the proper refrigerant amount and the closing of shut-off valves ratio) in which the automatic VRV K PLUS series: RXY20K VRV IV Q : RQYQ20T 20 class outdoor unit
refrigerant charge can be used. Refer 20 class outdoor unit VRV IV Q Series
by simply pressing a switch after pre-charging. Furthermore, there
is no need to clean inside piping as this is handled automatically by
Compact design
the VRV IV Q unit. enables the
2 1 4 750 mm
Time saving and users in the building. Refrigerant Carry-in and installation of units 2.25m2 Installation space

Enables smooth replacement


recovery and units
removal
VRV IV Q series
for Replacement use
0.95m2
3
Installation of new piping and wiring Refrigerant recovery and units removal Reuse of 58%
1 less space
existing refrigerant piping Carry-in and installation of
of air conditioning
3,005 mm
with less effect on operations 2
Removal of existing piping units Airtightness test
3
Quicker

4
Conventional solution 1,240 mm
Installation space 765 mm

5 5
Airtightness test Vacuum drying High external static pressure 78.4 Pa VRV IV Q Conventional VRV K series
67 Vacuum drying Refrigerant charging and volume measurement Automatic
6
Refrigerant charge, refrigerant pipe cleaning, test operation
49.0Pa 78.4 Pa
8 Quicker Quicker and higher quality installation
Test operation System flexibility
Cost details (10 class example) Piping Duct Overheads 10% Great reduction of work cost Approx.
Cost saving 40%
10% –35%
By the reuse of existing piping, 35% of cost Refrigerant charge 4%

down Removal work


6%
10%
Equipment installation
can be realized compared to installing new Curing
10% 20%

pipes. 10%
20% 8%
More indoor units can be connected Conventional VRV K PLUS series: RXY24–30K
Up to
4%
3% in a single system, enabling VRV IV Q : RQYQ40–48T indoor units 64 connectable
10% An increased number of connectable indoor consolidation of existing piping!
units in a single system
indoor units
Up to
30 connectable

New pipe installation VRV IV Q series


79 80

VRV IV Q Series
Benefits of System Replacement
Enables increased capacity
New technology that enables use of existing piping
VRV IV Q series for replacement use enables the system capacity to be increased without changing
VRV IV Q series only New tested contamination collection method

the refrigerant piping. For example, it is possible to install a 16 class VRV IV Q series using the refrigerant piping of an 10 class R- eliminating compressors and electric valves malfunction.
22 system.
A new method collects contamination from existing piping, Acid Impurities Iron powder

Before replacement Refrigerant pipe


A generously sized filter is provided inside the refrigerant circuit
Reliable and stable
10class
which traps impurities.

Refrigerant
flow
technology High reliability at
Filter high ambient temperatures
Iron powder,
PCB
etc
Impurities
A magnet is installed inside the
accumulator where liquid refrigerant
Pipe size: 28.6, 12.7 accumulates.
The magnet attracts iron powder to
keep the system clean.

VRV IV Q Series
Accumulator
Re Iron
use of existing piping powder

Power Module
To

2.5clas After replacement VRV IV Q Series


s×4 units 16class
Pipe size: 28.6, 12.7

Magnet

Replace Replace
An acid neutraliser agent is added to disable acids
(chlorine ions), which cause corrosion.

Acid (chlorine ion) 4.0class×4 units


Acid
neutraliser

compressor
81% increase
Energy saving Refrigerant Refrigerant Jacket Heat Refrigerant

Higher Energy Efficiency Ratio (EER)

5.0
VRV IV Q series delivers
4.41 4.32 4.07 3.80
(Compared with 8 class model of VRV K(A) )

3.743.46 3.25
3.11

Using refrigerant to cool the inverter power module


helps minimise the size of the electronic
components, and this results in
Control board failure ratio at stable operation is reduced.

highly efficient performance,


contributing to high energy savings.

* Cooling operation conditions:


Indoor temp. of 27º CDB, 19º CWB, and outdoor temp. of 35º CDB.

Cooling Operation EER6 class 8 class 10 class 12 class 14 class 16 class 18 class
20 class

4.0

3.0

2.0

1.0

reduction of airflow resistance and high efficiency of the heat


exchanger.

SMT* packaging technology • Improves the anti-clutter


performance.

This enables
• Suitability for high ambient temperatures • Miniaturization of
electronic components

Computer control board surface adopting SMT packaging technology SMT

packaging material
VRV K(A): RSX-K(A) VRV II: RX-M VRV IV Q Series *SMT: Surface mounted technology
Computer control board
• Protects your computer boards from the adverse
effects of sandy climates and humid weather.

Rotor
VRT Control for optimal annual efficiency Outer Rotor DC Motor (ODM) Rotor HIGHTORQUE
with low energy
VRT automatically adjusts refrigerant temperature to individual Only Daikin has adapted an ODM with the feature of stable F
building and climate requirement, thus further improving annual rotation and volumetric efficiency.
energy efficiency and maintaining comfort. ODM (Outer Type) Conventional Motor (Inner Type) UNIQUE

F
MORE efficient

81 82

Existing Refrigerant Piping


Piping limits for reuse of existing piping
VRV IV Q Series Heat Pump VRV III Q Series Heat Recovery Single use
Guidelines for Reuse of
VRV IV Q Series

Max. Max.
Actual piping length i i
First indoor branch 50 m Single use First indoor branch
s
Max. 150 m fgh
a
bcde
Actual piping length Max. 150 m fgh
r bcde

Equivalent piping length


VRV IV Q Series
Equivalent piping length r
a

Max. 175 m s 15 m
Colours in the diagram above are merely for identifying pipes referenced with symbols such as a .
Max. 175 m

Total piping length Max. 300 m Total piping length Max. 300 m Multiple use
Colours in the diagram above are merely for identifying pipes referenced with
kq symbols such as a .
Multiple use First k
Max.

indoor branch
p 5m
First outdoor branch
af
b
*The rest of indoor units are the same as for single use.
First
p indoor branch
First outdoor branch
af
q *The rest of indoor units are b

Maximum
allowable
piping length
Actual refrigerant piping length (Equivalent)
Total piping length
Between the first indoor branch and the farthest
indoor unit Between the outdoor branch and the last
outdoor unit (Equivalent)
Example
Piping length
q
s (175 m)
150 m
piping length
Between
300 m the first indoor branch and the farthest
indoor unitBetween the outdoor branch and the
40 m
last outdoor unit
10 m (13 m)
f+g+h+i k+p

Example

a+f+g+h+i
a+b+c+d+e+f+g+h+i
f+g+h+i
k+p

Maximum
allowable

Actual refrigerant piping length (Equivalent)

Total piping length


the same as for single use.

Piping length

RQYQ8-48P 150 m (175 m)

RQYQ140P, RQCEQ-P 120 m (150 m)

300 m

10 m (13 m)

Example

a+f+g+h+i

a+b+c+d+e+f+g+h+i

Maximum
Between the outdoor units (Multiple use) Between
the indoor units

Height Difference
allowable
height difference
Between the outdoor units and the indoor units

If the outdoor unit is above. r If the outdoor unit is below. r

Maximum
allowable
height difference

If the outdoor unit is


above.

If the outdoor unit is


below.

Between the outdoor units (Multiple use)


Between the indoor units

Between the outdoor units


and the indoor units
Example q

s
r
r
83 84

Guidelines for Reuse of


Existing Refrigerant Piping
Reusability of existing piping VRV IV Q series Heat
Pump

Outdoor Unit Lineup VRV


IV Q Series Heat Pump Enhanced lineup to 2
types

VRV IV Q Series
Type of piping
26 class X X X X S X X 160 ≤ X < 200 X S X X X X X 250 class X S X X X X X
Capacity Pipi
ng 28 class X X X X S X X 200 ≤ X < 290 X S X X X X
size
30 class X X X X S X X 290 ≤ X < 330 X X S X X X X
Liquid 54.1
X
32 class X X X X S X X 330 ≤ X < 420 X X S X X X X
X
6. 9. 12. 15. 19. 22. 12. 15. X
4 5 7 9 1 2 7 34 class X X X X S X X 420 ≤ X < 480 X X X S X X XX
X
X
6 class X S X X X X 36 class X X X X S X X 480 ≤ X < 640 X X X S X X XX
X
X
8 class X S X X X X 38 class X X X X S X X 640 ≤ X < 900 X X X X S X X

10 class X S X X X X 40 class X X X X S X X 900 ≤ X < 920 X X X X S X Lineup


X

12 class X X S X X X X 42 class X X X X S X X 920 ≤ X X X X S X X

VRV IV Q Series
14 class X X S X X X X 44 class X X X X S X X 20-40 class S X X X X S
class 6 8 1 1 1 1 1 2 2
16 class X X S X X X X 46 class X X X X S X X 50 class S X X X X S 0 2 4 6 8 0 2

18 class X X X S X X X 48 class X X X X S X X 63-80 class X S X X X X S Standard


Type
20 class X X X S X X X < 100 X S X X X X S 100-125 class X S X X X X
Space
22 class X X X S X X X 100 ≤ X < 150 X S X X X X 140-145 class X S X X X X
Saving Type

24 class X X X S X X X 150 ≤ X < 160 X S X X X X X 180 class X S X X X X X

200 class X S X X X X X
48

Main piping X X Capacity Total capacity index of


X Maximum number of
Standard Type
Outdoor unit combinations
Outdoor unit multi
X index class Model name Combination
X X VRV IV Q Series
68 16.0 22.4 RQYQ6T RQYQ8T RQYQ6T RQYQ8T connection piping kit*1 — — 100 to 260 connectable indoor units*2 9
kW 150 200 connectable indoor units*3 75 to 195
13
X 10 —
250 125 to 325 16 28.0

X RQYQ10T RQYQ10T
X 12 —
300 150 to 390 19 33.5

X RQYQ12T RQYQ12T
From X 14 —
350 175 to 455 22 40.0

REFNET X RQYQ14T RQYQ14T


X 16 —
400 200 to 520 26 45.0

to REFNET *1 X RQYQ16T RQYQ16T


18 450 225 to 585 29 50.4
X RQYQ18TN RQYQ8T + RQYQ10T
20 500 250 to 650 32 55.9
RQYQ20TN RQYQ8T + RQYQ12T
22 550 275 to 715 35 61.5
X RQYQ22TN RQYQ10T + RQYQ12T
X 24 600
BHFP22P100300 to 780 39 67.0

From X RQYQ24TN RQYQ12T × 2


X 26 650 325 to 845 42 73.5
REFNET X RQYQ26TN RQYQ12T + RQYQ14T
to indoor unit*2 X 28 700 350 to 910 45 78.5
X RQYQ28TN RQYQ12T + RQYQ16T
30 750 375 to 975 48 85.0
X RQYQ30TN RQYQ14T + RQYQ16T
: Piping size of conventional R-22, R-407C model : Possible 32 800 400 to 1,040 52 90.0
: Piping size of conventional R-410A model : Standard piping size of VRV IV Q series. However, when equivalent piping length between outdoor unit and indoor unit is 90 m RQYQ32TN RQYQ14T + RQYQ18T
: Standard piping size of VRV IV Q series S or more, size of main piping must be increased.
34 850 425 to 1,105 55 95.0
X : Not possible RQYQ34TN RQYQ10T + RQYQ12T × 2
*1 Piping between REFNETs depends on total capacity index of indoor units connected below each REFNET. It cannot exceed piping size of upstream side. 101
36 900 450 to 1,170 58
*2 Piping from REFNET to indoor unit depends on the capacity of the connected indoor unit. It cannot exceed piping size of upstream side. RQYQ36TN RQYQ12T × 3
38 950 475 to 1,235 61 106
RQYQ38TN RQYQ8T + RQYQ12T + RQYQ18T
VRV III Q series Heat Recovery
40 1,000 500 to 1,300 112
RQYQ40TN RQYQ12T × 2 + RQYQ16T BHFP22P151
42
160 ≤ X < 200 X S X X X X X S X X X X X S X X X
119
Capacity Piping 200 ≤ X < 290 X S X X X X X S X X X X X S X X
size
290 ≤ X < 330 X X S X X X X X X S X X X X X S X X
Liquid Suction gas
330 ≤ X < 420 X X S X X X X X X X S X X X X X S X

6 9 1 1 1 2 1 1 1 2 2 2 3 4 9 1 1 1 2 2 2 420 ≤ X < 480 X X X S X X X X X X S X X X X X X S


. . 2. 5. 9. 2. 2. 5. 9. 2. 5. 8. 4. 1. . 2. 5. 9. 2. 5. 8.
4 5 7 9 1 2 7 9 1 2 4 6 9 3 5 7 9 1 2 4 6
480 ≤ X < 640 X X X S X X X X X X S X X X X X X S

10 class X S X X X X X X S X X X X X S X X

640 ≤ X < 700 X X X X S X X X X X X S X X X X X S

13 class X X S X X X X X X S X X X X X S X X
700 ≤ X < 900 X X X X S X X X X X X S X X X X X S

16 class X X S X X X X X X S X X X X X S X
900 ≤ X X X X S X X X X X X S X X X X X X S

18 class X X X S X X X X X X S X X X X X S X
20-40 class S X X X X S X X X X X X

20 class X X X S X X X X X X S X X X X X S
50 class S X X X X S X X X X X X

22 class X X X S X X X X X X S X X X X X X S
63 class X S X X X S X X X X X

24 class X X X S X X X X X X S X X X X X X S
80 class X S X X X X S X X X X X

26 class X X X X S X X X X X X S X X X X X S
100-125 class X S X X X X S X X X

28 class X X X X S X X X X X X S X X X X X X S
140-145 class X S X X X X S X X X

30 class X X X X S X X X X X X S X X X X X X S
180 class X S X X X X X S X X X

< 50 S X X X X S X X X X X X S X X X X X
200 class X S X X X X S X X

50 ≤ X < 100 X S X X X X S X X X X X X S X X X X 250 class X S X X X X X S X X

100 ≤ X < 150 X S X X X X S X X X X S X X X X

150 ≤ X < 160 X S X X X X X S X X X X X S X X X


1,050 525 to 1,365
RQYQ42TN RQYQ12T + RQYQ14T + RQYQ16T
Type of piping 44 64
1,100 550 to 1,430 124
34.9 46 130 RQYQ44TN RQYQ46TN RQYQ12T + RQYQ16T × 2 RQYQ14T × 2 + RQYQ18T 575 to 1,495
1,150
X 48 1,200 600 to 1,560 135
X RQYQ48TN RQYQ14T + RQYQ16T + RQYQ18T

Main piping must not exceed 30% of the capacity index of the outdoor units. And the connection ratio must not exceed 100%.
X X
Notes: *1. For multiple connection of 18 class systems and above, the outdoor unit multi connection piping kit (separately sold) is required. X
X X
*2. Total capacity index of connectable indoor units must be 50%–130% of the capacity index of the outdoor units.
X
Space Saving Type
X
*3. When outdoor-air processing units and standard indoor units are connected, the total connection capacity index of the outdoor-air processing units X X
X Capacity Outdoor unit multi Total capacity index of Maximum number of

connectable indoor units*3 class Combination

From X 100 117 129 48 BHFP22P100


X
REFNET 900 1,050 1,150 X : Not possible
to REFNET *1 36 42 46 Model name
: Possible
: Standard piping size of VRV III Q series. However, when equivalent piping length
between outdoor unit
RQYQ18T RQYQ20T RQYQ30TS
RQYQ32TS RQYQ34TS RQYQ36TS RQYQ38TS
83.5 RQYQ40TS RQYQ42TS RQYQ44TS RQYQ46TS
750 BHFP22P151
RQYQ48TS
From 30
BS X
to indoor unit*2 X 225 to 585 250 to 650 375 to 975
RQYQ18T 400 to 1,040 425 to 1,105 450 to 1,170 475 to
RQYQ20T 1,235 500 to 1,300 525 to 1,365 550 to 1,430 575
: Piping size of conventional R-22, R-407C model : Piping size of
conventional R-410A model : Standard piping size of VRV III Q series 106 RQYQ12T + RQYQ18T to 1,495 600 to 1,560
S 950
kW 38 RQYQ12T + RQYQ20T connectable indoor units*2 29
X
RQYQ16T + RQYQ18T 32
index
89.5
123 RQYQ18T x 2
X 800 48
1,100
X 32 RQYQ18T + RQYQ20T
X 44 52
X RQYQ20T x 2 55
50.0 134 RQYQ12T x 2 + RQYQ18T 58
450 1,200 RQYQ12T x 2 + RQYQ20T
18 and indoor unit is 90 m or more, size of main piping must be increased.
61
X RQYQ12T + RQYQ16T + RQYQ18T RQYQ12T +
RQYQ18T x 2

112 connection piping kit*1 – 64


56.0 95.0 1,000

500 850 40
20 34
X
*1 Piping between REFNETs depends on total capacity upstream side.
index of indoor units connected below each REFNET. It Notes: *1. For multiple connection of 30 class and above the outdoor unit multi connection piping kit (separately sold) is required. *2. Total capacity index of
cannot exceed piping size of upstream side. *2 Piping
from BS to indoor unit depends on the capacity of the connectable indoor units must be 50%–130% of the capacity index of the outdoor units.
connected indoor unit. It cannot exceed piping size of *3. When outdoor-air processing units and standard indoor units are connected, the total connection capacity index of the outdoor-air processing units
85 86 must not exceed 30% of the capacity index of the outdoor units. And the connection ratio must not exceed 100%.

VRV III Q Series


FXDQ-NDVE
Category
10 1 1 1 2 2 2 2 2
3 6 8 0 2 4 6 8
Slim Duct (Compact) FXDQ-
TV1C(A)

Middle Static FXSQ-PAVE


Pressure Duct

FXDYQ-
30 MAV1
Type
Middle-High Static Pressure FXMQ-PAVE
Duct

High Static Pressure FXMQ-PV1A


Model Name Duct

Outdoor Unit Lineup VRV Outdoor-Air


Processing Unit
FXMQ-MFV1

FXMQ-AFVM

III Q Series Heat Recovery Outdoor unit lineup 4-Way Flow Ceiling
Suspended
FXUQ-AVEB

Round Flow FXFTQ-AVM

Indoor Unit Lineup Wide variety


Cassette with Ceiling Suspended FXHQ-MAVE
Sensing and
Streamer
FXHQ-BVM
Round Flow FXFSQ-AVM
Cassette with Wall Mounted FXAQ-AVM
Sensing

of indoor units Round Flow Cassette FXFQ-AVM Floor Standing FXLQ-MAVE

Concealed Floor FXNQ-MAVE

VRV IV Q Series
Compact Multi FXZQ-BVM Standing
New lineup Flow Cassette
Heat Reclaim Ventilator VAM-HVE
Double Flow FXCQ-BVM
Cassette

Single Flow Cassette FXEQ-AV36

250
Slim Duct (Standard) FXDQ-PDVE 28
250
class

Capacity Outdoor unit multi Maximum number of


Outdoor unit combinations class Combination 2 3
Total capacity index of connectable indoor units* *
Ceiling Mounted Cassette
VRV IV Q Series

kW index Model name connection piping kit*1 Combination (%) 50% 100% 130% connectable indoor units

10 28.0 250 RQCEQ280P RQEQ140P+RQEQ140P BHFP26P36C 125 250 325 16

RQEQ180P+RQEQ180P
13 325 RQCEQ360P 162.5 325 422.5 21 36.0

16 18 20 22 24 26 28 30 400 450 500 550 600 650 700 RQCEQ540P RQCEQ636P RQEQ140P+RQEQ140P +RQEQ180P RQEQ140P+RQEQ180P +RQEQ212P+RQEQ212P 200 225 250 275 300 325 350 400 450 500 550 600 650 700 520 585 650 715 780 845 910
+RQEQ180P +RQEQ212P+RQEQ212P Ceiling Concealed Duct
RQEQ212P+RQEQ212P
46.0 50.0 54.0 63.6 71.2 74.4 750 RQCEQ712P RQCEQ744P RQEQ140P+RQEQ180P +RQEQ212P RQEQ180P+RQEQ212P 375 750 975
+RQEQ180P +RQEQ212P+RQEQ212P
RQEQ140P+RQEQ180P
81.6 84.8 RQCEQ460P RQCEQ500P RQCEQ816P RQCEQ848P RQEQ180P+RQEQ180P +RQEQ180P+RQEQ212P RQEQ212P+RQEQ212P BHFP26P63C BHFP26P84C 26 29 32 35 39 42 45 48

*1 The outdoor unit multi connection piping kit (separately sold) is required for multiple connections.
*2 Total capacity index of connectable indoor units must be 50%–130% of the capacity index of the outdoor units. Floor Standing
*3 For indoor units used for cooling only (do not connect to BS unit when using for heat recovery), total capacity index must be 50% or less than the capacity index of the outdoor units.
*4 When outdoor-air processing units and standard indoor units are connected, the total connection capacity index of the outdoor-air processing units must not exceed 30% of the capacity index of the outdoor units. And the
connection ratio must not exceed 100%.
Notes:
Ceiling Suspended 1. It is not possible to combine old R-22 and new R-410A indoor units in one system due to incompatibility of communication. 2. It is not possible to keep R-407C indoor units.
87 88

VRV IV Q Series
Outdoor Units
Specifications
VRV IV Q Series Heat Pump

Standard Type
MODEL RQYQ18TNY1A(E) RQYQ20TNY1A(E) RQYQ22TNY1A(E) RQYQ24TNY1A(E) RQYQ26TNY1A(E) RQYQ28TNY1A(E) RQYQ30TNY1A(E) RQYQ32TNY1A(E)
RQYQ6TY1A(E) RQYQ8TY1A(E) RQYQ10TY1A(E) RQYQ12TY1A(E) RQYQ14TY1A(E) RQYQ16TY1A(E)

— — — — — RQYQ8TY1A(E) RQYQ8TY1A(E) RQYQ10TY1A(E) RQYQ12TY1A(E) RQYQ12TY1A(E) RQYQ12TY1A(E) RQYQ14TY1A(E)

— RQYQ10TY1A(E) RQYQ12TY1A(E) RQYQ12TY1A(E) RQYQ12TY1A(E) RQYQ14TY1A(E) RQYQ16TY1A(E) RQYQ16TY1A(E)

— — — — — — —

3-phase 4-wire system, 380-415 V, 50 Hz 3-phase 4-wire system, 380-415 V, 50

54,600 76,400 95,500 114,000 136,000 154,000 172,000 191,000 210,000 229,000 251,000 268,000 290,000
Btu/h

16.0 22.4 28.0 33.5 40.0 45.0 50.4 55.9 61.5 67.0 73.5 78.5 85.0
kW

61,400 85,300 107,000 128,000 154,000 171,000 193,000 213,000 235,000 256,000 281,000 299,000 324,000
Btu/h

18.0 25.0 31.5 37.5 45.0 50.0 56.5 62.5 69.0 75.0 82.5 87.5 95.0
kW

Cooling 3.63 5.21 7.29 9.01 10.9 13.0 12.5 14.2 16.3 18.0 19.9 22.0 23.9
kW

Heating 3.99 5.69 7.29 9.06 11.1 12.8 13.0 14.8 16.4 18.1 20.2 21.9 23.9
kW

%20-100 16-100 15-100 11-100 10-100 8-100 6-100

Ivory white (5Y7.5/1) I vory white


(5Y7.5/1)

Hermetically Sealed Scroll Type Hermetically Sealed Scroll Type


Type

Motor kW 3.4×1 4.1×1 5.2×1 (2.9×1)+(3.3×1) (3.6×1)+(3.7×1) (3.4×1)+ (3.4×1)+ (4.1×1)+ (5.2×1)+ (5.2×1)+(2.9× (5.2×1)+(3.6× (2.9×1)+(3.3×
2.4×1
output (4.1×1) (5.2×1) (5.2×1) (5.2×1) 1)+ (3.3×1) 1)+ (3.7×1) 1)+
(3.6×1)+(3.7×
1)

1,983 /s 2,616 2,749 2,966 3,883 2,616+2,749 2,616+2,966 2,749+2,966 2,966+2,966 2,966+3,883

119 m³/min 157 165 178 233 157+165 157+178 165+178 178+178 178+233 233

mm 1,657X1,240X765 (1,657×930×765)+(1,657×930×765) (1,657×930×765)+(1,657×1,240×765) (1,657×1,240×765


1,657X930X765
)

185 kg 195 285 185+195 195+195 195+285 285+285

55 dB(A) 56 57 59 60 61 60 61 62 63

75 dB(A) 76 78 79 80 83 80 81 82 83 84

Cooling -5 to 49 -5 to 49
ºCDB

Heating -20 to 15.5 -20 to 15.5


ºCWB

Type R-410A
R-410A

Charge kg5.9 6.0 6.3 10.3 10.4 5.9+6.0 5.9+6.3 6.0+6.3 6.3+6.3 6.3+10.3 6.3+10.4 10.3+10.4

Liquid 9.5(Brazing) 12.7(Brazing) 15.9(Brazing) 19.1(Brazing)


mm

RQYQ14TY1A(E)
Combination units
RQYQ18TY1A(E)

Power supply
307,000
Cooling capacity
90.0
345,000
Heating capacity

VRV IV Q Series
101
26.3
Power

consumption
26.2
Capacity control Operation 3,883+3,883
Casing colour range +233
+(1,657×1,240×765)
Refrigerant
Compressor 285+300
Piping 64
connections 85
Gasmm
Airflow rate 19.1(Brazing) 22.2(Brazing) 28.6(Brazing)
5-100
Dimensions (H×W×D)
Machine weight
10.3+11.7
Sound level
(2.9×1)+(3.3×1)+
Sound power (4.4×1)+(4.0×1) 28.6(Brazing) 34.9(Brazing)

RQYQ44TNY1A(E) RQYQ18TY1A(E) RQYQ20TY1A(E) anti-corrosion specifications. Please refer to


Heat Pump
RQYQ46TNY1A(E)
Notes:
MODEL RQYQ34TNY1A(E) RQYQ36TNY1A(E) RQYQ48TNY1A(E) 1. Models with (E) are
RQYQ38TNY1A(E) RQYQ40TNY1A(E) RQYQ42TNY1A(E) Space Saving Type MODEL the outdoor units with

Heating ºCWB-20 to 15.5


RQYQ10TY1A(E) RQYQ12TY1A(E)
TypeR-410A Cooling capacity
RQYQ12TY1A(E) RQYQ12TY1A(E)
Charge kg6.0+6.3+6.3 6.3+6.3+6.3 Heating capacity
RQYQ12TY1A(E) RQYQ12TY1A(E)
Liquid mm 19.1(Brazing) Power
consumption
Capacity control
191,000 56.0
Btu/h324,000 345,000 215,000 63.0
Combination units
18.0
kW95.0 101 RQYQ14TY1A(E) RQYQ16TY1A(E) RQYQ18TY1A(E) 17.5
Combination units 8-100
Btu/h365,000 386,000 Equivalent piping length: 7.5 m,
Height difference: 0 m.
• Heating: Indoor temp.: 20°CDB,
–– Outdoor temp.: 7°CDB, 6°CWB,
kW107 113 Engineering Data Book for details. 2. Specifications are based on the following Equivalent piping length: 7.5 m,
conditions; Height difference: 0 m.
Cooling kW25.3 27.0 • Cooling: Indoor temp.: 27°CDB, 19°CWB,
Power supply • Sound level: Anechoic chamber
3-phase 4-wire system, 380-415 V, 50 Hz conversion value, measured at
Heating kW25.4 27.2 Power supply a point 1 m in front of the unit at
3-phase 4-wire system, 380-415 V, 50 Hz a height of 1.5 m.
Outdoor temp.: 35°CDB, Casing colour
%5-100
Cooling capacity
Hermetically Sealed Scroll Type
Casing colour
Heating capacity
Type
TypeHermetically Sealed Scroll Type
Power Ivory white (5Y7.5/1)
consumption Hermetically Sealed Scroll Type
Motor (5.2×1)+(5.2× During actual operation, these values are normally somewhat higher as
kW(4.1×1)+(5.2×1)+ Capacity control
output 1)+ (5.2×1)
(5.2×1)
461,000
135
515,000
151
2,749+2,966+2,966 /s 2,966+2,966+2,96 39.3
6 39.0
3-100
m³/min165+178+178 178+178+178 Btu/h171,000

mm(1,657×930×765)+(1,657×930×765)+ kW50.0
(1,657×930×765)
Btu/h191,000
195+195+195 kg
kW56.0
63 64
dB(A)
Cooling kW15.4

83 dB(A) 84
Heating kW15.1

Cooling ºCDB-5 to 49
%10-100
Compressor Airflow rate 4,466
Motor kW 3,883 /s
output
(4.4×1)+(4.0×1) 268
a result of ambient conditions and oil recovery mode. When there is
Compressor Airflow rate m³/min233 concern for noise to the surrounding area such as residences,
(4.6×1)+(5.5×1) we recommend investigating the installation location and taking
(2.9×1)+(3.3×1)+ (3.6×1)+(3.7×1)+ (4.4×1)+(4.0×1)
soundproofing measures.

Dimensions (H×W×D) Dimensions (H×W×D) 1,657×1,240×765


mm

Machine weightSound level


dB(A) Cooling ºCDB
Sound power
62 Machine weight
285+285+300 66
87 Heating ºCWB Sound level
84 dB(A) Sound power
kg 320 65
300 87

Operation range

Refrigerant

R-410A
Operation range

Refrigerant

Type
-5 to 49
-20 to 15.5 R-410A

Piping
10.3+10.4+11.7
9.1(Brazing)
Piping

Charge kg11.7

iquid mm

15.9(Brazing)
11.8
89 90
connections 34.9(Brazing) 41.3(Brazing) 41.3(Brazing) connections Gasmm 28.6(Brazing)
Gasmm

VRV IV Q Series
Outdoor Units
Specifications
VRV IV Q Series Heat Pump
Space Saving Type RQYQ30TSY1A(E) RQYQ32TSY1A(E) RQYQ34TSY1A(E) RQYQ36TSY1A(E)

MODEL
RQYQ38TSY1A(E) RQYQ40TSY1A(E) RQYQ42TSY1A(E) RQYQ44TSY1A(E) RQYQ46TSY1A(E) RQYQ48TSY1A(E)
457,000
195+300 134
RQYQ12TY1A(E) RQYQ12TY1A(E) RQYQ16TY1A(E) 512,000
dB(A) 66
64 150
RQYQ18TY1A(E) RQYQ20TY1A(E) RQYQ18TY1A(E) 39.6
dB(A)85 88 39.3
— — —
Cooling ºCDB-5 to 49
3-phase 4-wire system, 380-415 V, 50 Hz
Heating ºCWB-20 to 15.5 (5.2×1)+(4.4×1)+(4.0×1)+(4.4×1)+(4.0×1)

Btu/h285,000 305,000 324,000


TypeR-410A

kW83.5 89.5 95.0


Charge kg6.3+11.7 6.3+11.8 10.4+11.7

Btu/h319,000 345,000 362,000 Liquid mm 19.1(Brazing) 195+300+300

kW93.5 101 106 VRV IV Q Series

Cooling kW24.2 26.8 28.4


Combination units
Heating kW24.2 26.6 27.9
Power supply

%6-100 5-100 Cooling capacity Sound level


Sound power
Ivory white (5Y7.5/1) Heating capacity Operation
range

TypeHermetically Sealed Scroll Type Power


consumption Refrigerant

Motor kW Capacity control


(5.2×1)+(4.6×1)+(5.5×1) (3.6×1)+(3.7×1)+(4.4×1)+(4.0× Piping
output
(5.2×1)+(4.4×1)+(4.0×1) Casing colour connections
1) Gasmm
34.9(Brazing) 41.3(Brazing)
2,966+3,883 /s 2,966+4,466 Compressor
3,883+3,883 66
88
Airflow rate
m³/min178+233 178+268 233+233

Dimensions (H×W×D)
mm (1,657×1,240×765)+(1,657×1,240×765)
(1,657×930×765)+(1,657×1,240×765)
Machine weight 6.3+11.7+11.7
RQYQ12TY1A(E)
kg 195+320 285+300 RQYQ18TY1A(E) 41.3(Brazing)
RQYQ18TY1A(E)
Notes: 1. Models with (E) are the outdoor units with anti-corrosion specifications. Please refer to Engineering Data Book for details. 2. Specifications are based on the following conditions; 6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB,

VRV III Q Series Heat Recovery During actual operation, these values are normally somewhat higher as a result of ambient conditions and oil recovery mode. When there is concern for noise to the
surrounding area such as residences, we recommend investigating the installation location and taking soundproofing measures.

MODEL

RQCEQ280PY1 RQCEQ360PY1 RQCEQ460PY1 RQCEQ500PY1 RQCEQ540PY1


RQCEQ636PY1 RQCEQ712PY1 RQCEQ744PY1 RQCEQ816PY1 RQCEQ848PY1
RQEQ140PY1 RQEQ180PY1RQEQ140PY1RQEQ140PY1RQEQ180PY1RQEQ212PY1R RQEQ140PY1 RQEQ212PY1
QEQ140PY1 RQEQ180PY1
Combination units
RQEQ140PY1

RQEQ180PY1 RQEQ140PY1 RQEQ180PY1 RQEQ180PY1 RQEQ212PY1RQEQ180PY1



— RQEQ180PY1 RQEQ180PY1 RQEQ180PY1 RQEQ212PY1RQEQ180PY1

— RQEQ212PY1 RQEQ212PY1
————— RQEQ212PY1 RQEQ212PY1
Power supply 3-phase 4-wire system, 380-415 V, 50 Hz 3-phase 4-wire system, 380-415 V, 50 Hz
Btu/h(*1) 96,200 28.2 124,000 36.3 46.0 50.0 54.0 245,000 71.7 71.2 74.4 81.6 84.8
Cooling capacity (*1) (*2) 28.0 36.0 172,000 50.4 186,000 54.4 218,000 64.0 256,000 74.9 280,000 82.2 291,000 85.4
kW (*1) (*2)
158,000 46.3 63.6
Heating capacity Power Btu/h kW
Cooling(*2) 109,000 32.0 7.04 10.3 12.2 13.9 15.5 21.9 21.2 23.3 27.1 29.2
kW
136,000 40.0 177,000 52.0 191,000 56.0 205,000 60.0 229,000 67.2 268,000 78.4 276,000 80.8 298,000 87.2 306,000 89.6
consumption Heating 8.00 10.7 13.4 14.7 16.1 17.7 20.7 21.2 23.1 23.6
Capacity control % Casing colour 13-100 10-100 8-100 Hermetically sealed scroll type
7-100 5-100 Ivory white (5Y7.5/1)
Compressor Type
Ivory white (5Y7.5/1) Hermetically sealed scroll type
Motor output kW 2.8X2 3.3X2 2.8X2+3.3 2.8+3.3X2 3.3X3 3.6X3 2.8+3.3X2+3.6 2.8+3.3+3.6X2 3.3+3.6X3 3.6X4
/s 1583+1583 1833+1833 1583+1583+1833 1583+1833+1833 1833+1833+1833 1583+1833+1833+1833 1833+1833+1833+1833
Airflow rate m3/min 95+95 110+110 95+95+110 95+110+110 110+110+110 95+110+110+110 110+110+110+110
Dimensions (HXWXD) mm (1,680X635X765)+(1,680X635X765) (1,680X635X765)+(1,680X635X765)+(1,680X635X765) (1,680X635X765)+(1,680X635X765)+(1,680X635X765)+(1,680X635X765)
Machine weight kg 175+175+175 179+179+179 175+175+175+179 175+175+179+179 175+179+179+179 179+179+179+179
175+175
Sound level dB(A) 57 61 62 63 65 64 65 66
Operation range Heating ºCDB ºCWB ºCWB -20 to 15.5 -6 to 15.5 R-410A -20 to 15.5 -6 to 15.5 R-410A
Cooling Cooling & Heating Type -5 to 43 -5 to 43
kg 10.3+10.3 10.6+10.6 10.3+10.3+10.6 10.3+10.6+10.6 10.6+10.6+10.6 11.2+11.2+11.2 10.3+10.6+10.6+11.2 10.3+10.6+11.2+11.2 10.6+11.2+11.2+11.2 11.2+11.2+11.2+11.2
Charge Refrigerant
12.7 (Brazing) Piping 15.9 (Brazing) 15.9 (Brazing) 19.1 (Brazing)
connections Suction gas 9.5 (Brazing) 22.2 (Brazing) 25.4 (Brazing) 28.6 (Brazing) 28.6 (Brazing) 34.9 (Brazing)
Liquid mm
High and low pressure gas 19.1 (Brazing) 19.1 (Brazing) 22.2 (Brazing) Note: Specifications are based on the following conditions; 25.4 (Brazing) 25.4 (Brazing) 25.4 (Brazing) 28.6 (Brazing) • Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.
•Cooling:(*1) Indoor temp.: 27°CDB, 19.5°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m. During actual operation, these values are normally somewhat higher as a result of ambient conditions and oil recovery mode.
91 92
(*2) Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m. •Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m.
When there is concern for noise the surrounding area such as residences, we recommend investigating the installation location and taking soundproofing measures.

Water Cooled System Suitable for Tall Heat Pump Heat Recovery
Boiler (for heating)
• Water cooled system does not require

VRV IV W Series
Multi-Storied Buildings
6class–36class (16 kW) (101 kW)

to exchange heat with outdoor air


• Outside units can be installed indoors.
• The air conditioning operation is stable even when the outdoor air temperature is high

• Individual air conditioning is achieved via on-demand operation in each room.


• The length of the refrigerant piping can be minimized by installing outside units in
proximity to indoor units.
• As refrigerant piping is connected to indoor units, it reduces the risks of
Cooling tower (closed type)

Indoor unit
Refrigerant
piping

Water piping

VRV IV W Series
indoor water leakage. Outside unit

Design flexibility High installation


Underground shopping
flexibility

Design flexibility

High-rise buildings Condominiums and


malls and subway Compact outside units can be detached houses

Single outside units Triple outside units balcony required Water pipe
Water pipe

RWEYQ6-12T(2)YM RWEYQ26-36TYM Water inflow

easily installed in the Water outflow


Refrigerant liquid pipe

machine rooms on Refrigerant gas pipe

Double outside units We offer an extensive lineup of


each floor. It is
small capacity outside units.
RWEYQ14-24TYM adaptable to high-rise
As heat exchanging with outdoor air is not
required, individual air conditioning can be
buildings. No easily provided.

Celling height (100-300 mm)


Min. 3,200 mm

(300-400 mm)

* Only for the purpose of illustration.

Drain pipe
Min. 300 mm

93 94

Water Cooled VRV IV as a Retrofit Solution A flexible system convenient for expansion/renovation
VRV IV W Series

Problems with existing water systems can be solved Easy Installation OFF General manager office:
27°C,

with minimal construction work. Individual air conditioning comfort can be realized when
and where it is actually required.
Indoor installation solves the puzzle
of proper placement of outside units Independent control provides greater comfort and convenience.
Each indoor unit can be
It is possible to place the outside unit inside the buildings and open to various kinds of creative independently controlled and adjusted according to Large meeting room: low air volume
Office: 26°C, high air volume
building, it makes easier to adapt to different type of building exteriors. each tenant’s individual needs for
Meeting room Office Actual conditions of the floor Based on cooling condition
Part of the old system can be Higher efficiency with partial
VRV IV W Series
retained load
The water cooled VRV IV W series Cost Saving During actual operation, the load of an
can retain the cooling tower and air conditioning system changes
Retained cooling
boiler of the old system during tower according to variations in weather
renovation, effectively keeping costs conditions outside and indoor unit
down. operation rates. Daikin’s advanced
Retained boiler DC inverter technology and
temperature and air volume.

Before renovation After renovation Air conditioning of the meeting room is normally switched off
Space Saving
advanced refrigerant control technology boasts a higher efficiency under partial load
*System diagram
than in the rated operating conditions.

The compact outside units facilitate the renovation process


• The outside units are conveniently compact so Cooling tower Garage Flexibly satisfies conditions for working
transport by elevator is possible. It also effectively overtime and times of insufficient load
simplifies installation. This also saves a great deal
of time and labor. Each indoor unit can be independently controlled and
• The modular design enables a free and flexible adjusted according to each tenant’s individual needs
configuration of the outside units. Also can save for temperature and air volume.
space for other purposes. • Inconvenient transportation procedures are eliminated.
Saving more space for
• Operation for each indoor unit can be precisely and individually
Cooling tower other purposes
set.
Outside units take up a Example of air conditioning control for different rooms of the same floor 8:00 9:00 10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00 18:00 19:00 20:00 21:00
disproportionately large amount of space for installation.
Can save space

Floor by floor renovation without disturbing other tenants Flexible Renovation Workdays Office During normal work hours, the building's central air conditioner is used
During overtime hours, the water cooled
VRV IV W series operates

Cold source supply


Because equipment can be replaced in Pump Renovation in phases is possible. Phase 1 General manager's office
The water VRV Both theVRV
building's
IV W series
central
phases, installation adapts to the renovation Phase 2 The water VRV At weekends, the VR cooled
operate
water cooled V
plans of the customers and ensures that Pump
cooled
work performed on some floors and zones and the water

will not affect other Weekends


Cooling tower
tenants. Heat source supply Phase 3 Meeting Room
Cold source Boiler
Plate heat
back-flow *System diagram
exchanger
Heat source back-flow IV W series can work to supplement insufficient capacity of the building's central air conditioner
When a large number of people are present, the water cooled VRV
Water cooled VRV IV W series
95 96

Compact and lightweight


Easy Installation & Energy Saving
Compact
Design

1,000 mm

Footprint :
0.43 m 2

VRV IV W Series

Enhanced lineup
Wider capacity

to
range from 6 36 class

DTA104A62
(*For 6 class, 8 class) 146 kg Product Weight :

6, 8, 10, 12 class 14, 16, 18, 20, 22, 24 class 26, 28, 30, 32, 34, 36 class

Interlocking
VRV IV W Series
6 class, 8 class, 10 class, 12 class
Enhanced usability Centralised interlocking function

550 mm

780 mm

Centralised interlocking input operate (DTA104A62). RWEYQ6T2YM RWEYQ8TYM RWEYQ14TYM RWEYQ16TYM RWEYQ20TYM RWEYQ22TYM RWEYQ26TYM RWEYQ28TYM RWEYQ32TYM RWEYQ34TYM
by using an external control adaptor RWEYQ10TYM RWEYQ12TYM RWEYQ18TYM RWEYQ24TYM RWEYQ30TYM RWEYQ36TYM

Control wiring VRV III W series


Energy saving
Higher Energy Efficiency Ratio (EER)
VRT control for optimal annual efficiency
Cooling Operation EER
VRT automatically adjusts refrigerant temperature to individual building and climate
requirement, thus further improving annual
(external-to-external transmission wiring)
18%
Using one external control adaptor circuit board 6.00 2.00
makes centralised interlocking input to multiple units
16%
5.00 1.00 Increase
within the same water system possible.
VRV IV W Series 4.00 0
5.16
3.00 Increase 5.80 4.57
6.20 energy efficiency and maintaining comfort.

6 class 8 class 10 class 12 class


*Cooling : Indoor temp.: 27ºCDB, 19ºCWB/inlet water temp.: 30ºC,
Equivalent piping length: 7.5 m, Height difference: 0 m.

97 98

Flexibility by simultaneous cooling and heating BS unit (Single type/Multi type)


Maximum Comfort via operation By adding suction gas piping and a BS unit (sold separately), simultaneous cooling and
heating

Simultaneous Cooling Situation


Heat recovery system offers simultaneous cooling and

VRV IV W Series
and Heating

See page 159 - 162


Recent office buildings are highly airtight and operation can be provided by a single system.
due to the use of computers, lighting
equipment and other office equipments,
cooling load
heating operation on the same floor!
Single BS unit
Multi BS unit
Gas piping Indoor unit Indoor unit Indoor unit Singlel Indoor unit (Heating) Indoor unit (Cooling) Indoor unit*
increases even in winter. Need BS unit Single (Cooling only)
Heat recovery Outside unit BS unit
Liquid piping
These buildings require flexible VRV IV W Series
High and low pressure
cooling and heating operation. gas piping
Heat pump Outside unit Suction gas piping
Liquid piping

Solution • Improves energy efficiency by Hot area due to heat released by computers, etc. Outdoor air
Cold area during winter due to cold air coming from windows Application reference processing air
• Heat recovery system enables flexibility by Heat recovery operation! conditioning
simultaneous cooling and heating operation just using * For indoor units used for cooling only (do not connect to BS unit when using for heat
one VRV IV W system. recovery), total capacity index must be 50% or less than the capacity index of the
outside units.

recycling waste heat.


→Cooling ON
The heat recovery system improves heating cooling cooling heating
heating
corridor

→Heating ON
Single BS unit Multi BS unit
energy efficiency by recycling waste heat. cooling

Winter season (Office Building) Winter season (Hotel)


2
Outside Cooling Heating Indoor unit • Able to cater to individual heating and cooling requirement
unit • Difference between the load of cold air and heat from room is
large

BS unit • Can be used with the outdoor air processing air conditioning
1

The (cold) waste heat from heating is 2


1 used for the cooling operation.
The waste heat from cooling is used to generate heat that is needed for heating operation while conserving electricity.
99 100

Long piping length Actual piping length SMT* packaging technology


Flexible System Design Max. 120 m
• Improves the anti-clutter performance. • Protects your computer boards from the
adverse effects of sandy climates and humid

Advanced Technologies High efficiency compressor to achieve a


high performance
Single use
The reluctance DC motor uses 2 different types of torque,
VRV IV W Series
Equivalent piping length First indoor branch SMT packaging material
fgh
s
Max. 140 m
neodymium magnet and
r edcb reluctance torque. It generates more power Reluctance DC motor
Total piping length with a smaller electric power and saves weather.
energy.
*SMT: Surface mounted technology
Max. 300 m
Computer control board surface adopting SMT
a packaging technology
i VRV IV W Series
Computer control board
*Colours in the diagram above are merely for identifying pipes
referenced with symbols such as a . Function of information display by luminous digital tube
Actual Example
piping length Equivalent
piping length
120 m a+f+g+h+i

300 m a+b+c+d+e+f+g+ Minimize performance degradation from refrigeration oil in all stages of
h+i operation
90 m*1 f+g+h+i

10 m k+p

2m q

15 m s

50 m r

40 m r

Maximum Maximum Between the first indoor branch and the farthest Between the indoor units — refrigerant cycle. segment digital display to convey
allowable allowable indoor unit Between the first outside branch and 140 m —
Surplus oil is stored in the receiver operational status and facilitate
piping length Refrigerant piping length the last outside unit Between the outside units — Oil separator Compressor
and automatically controls the simple
Total piping length (multiple use) 13 m —
amount of refrigeration oil in the VRV IV W series utilises a bright 7- 7-segment digital display

height difference Between the outside units If the outside unit is above. — This prevents a reduction in installation and after-sales
and the indoor units If the outside unit is below. — performance for heat service. Displays system operation
*1 No special requirements up to 40 m. The maximum actual piping length can be 90 m, depending on conditions. The VRV IV W series is easy to New oil receiver
extend to 90 m by lessening the conditions from conventional VRV III W models. Be sure to refer to the Engineering Data Book for details of these exchanger.
conditions and requirements. information directly

First Priority Priority Automatic sequencing


indoor branch 123 Auto-restart technology Priority
312
af 231
k q p Automatic sequencing
Multiple use operation
Stage 1
Stage 2 power
Automatic sequencing Stage 3
supply

b Power interruption during normal operation recovers


First outdoor branch Keep a record of the operating mode adopted Restore itself back into the recorded operating status
*The rest of indoor units are the same as for single use.

Refrigerant pressure detection technology


• Utilizes temperature sensors to detect the system’s operating status.
• Employs high and low pressure sensors to carry out quick, comprehensive and accurate detection of
the refrigerant status.
101 102
Capacity Range

Outside Unit Lineup VRV IV Indoor Unit LineupEnhanced Category


6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
class

16.0 22.4 28.0 33.5 38.4 44.8 50.4 56.0 61.5 67.0 72.8 78.4 84.0 89.5 95.0 101

W Series kW

Type
range of choices
Lineup Model Name

VRV IV W Series New lineup


Capacity Index

Round Flow FXFTQ-AVM


Cassette with
Sensing and
Streamer

Round Flow FXFSQ-AVM


Cassette with
Sensing

Round Flow Cassette FXFQ-AVM

Compact Multi FXZQ-BVM


Flow Cassette

Double Flow FXCQ-BVM


Cassette

Single Flow Cassette FXEQ-AV36

Slim Duct (Standard) FXDQ-PDVE

FXDQ-NDVE

Slim Duct (Compact) FXDQ-


TV1C(A)

Middle Static FXSQ-PAVE


Pressure Duct

FXDYQ-
MAV1

Middle-High Static Pressure FXMQ-PAVE


Duct

High Static Pressure FXMQ-PV1A


Duct

Outdoor-Air FXMQ-MFV1
Processing Unit
FXMQ-AFVM

4-Way Flow Ceiling FXUQ-AVEB


Suspended

Ceiling Suspended FXHQ-MAVE

FXHQ-BVM

Wall Mounted FXAQ-AVM

Floor Standing FXLQ-MAVE

Concealed Floor FXNQ-MAVE


Standing

Heat Reclaim Ventilator VAM-HVE

250
28
250
VRV IV W SERIES Capacity Total capacity index of
Outside unit combinations class Model Combination Maximum number of VRV IV W Series

Ceiling Mounted Cassette


kW index connectable indoor units*2 connectable indoor units

16.0 150 RWEYQ6T2 RWEYQ6T2 × 1 75 to 195

22.4 200 RWEYQ8T RWEYQ8T × 1 100 to 260

28.0 250 RWEYQ10T RWEYQ10T × 1 125 to 325

33.5 300 RWEYQ12T RWEYQ12T × 1 150 to 390

38.4 350 RWEYQ14T*1 RWEYQ6T2 + RWEYQ8T 175 to 455

44.8 400 RWEYQ16T*1 RWEYQ8T × 2 200 to 520

50.4 450 RWEYQ18T*1 RWEYQ8T + RWEYQ10T 225 to 585

56.0 500 RWEYQ20T*1 RWEYQ10T × 2 250 to 650

61.5 550 RWEYQ22T*1 RWEYQ10T + RWEYQ12T 275 to 715

67.0 600 RWEYQ24T*1 RWEYQ12T × 2 300 to 780

72.8 650 RWEYQ26T*1 RWEYQ8T × 2 + RWEYQ10T 325 to 845

78.4 700 RWEYQ28T*1 RWEYQ8T + RWEYQ10T × 2 350 to 910

84.0 750 RWEYQ30T*1 RWEYQ10T × 3 375 to 975

89.5 800 RWEYQ32T*1 RWEYQ10T × 2 + RWEYQ12T 400 to 1,040

95.0 850 RWEYQ34T*1 RWEYQ10T + RWEYQ12T × 2 425 to 1,105

9
6
13
8
16
10
19
12
22
14
26
16
29
18

Ceiling Concealed Duct


32
20
35
22
39
24
42
26
45
28
48
30
52
32
55
34
58
36101RWEYQ36T*1RWEYQ12T × 3450 to 1,170
900
*1. An outside unit multi connection piping kit (option) is necessary for multiple connections of 14 class systems and above.
*2. Total capacity index of connectable indoor units must be 50%–130% of the capacity index of the outside units.

Ceiling Suspended

Floor Standing
Max.
indoor
58
103 104 units

VRV IV W SeriesHeat Pump / Heat Recovery


Outside Units VRV IV W Series
Specifications

MODEL RWEYQ6T2YM RWEYQ8TYMRWEYQ10TYMRWEYQ12TYMRWEYQ14TYM RWEYQ16TYMRWEYQ18TYMRWEYQ20TYMRWEYQ22TYMRWEYQ24TYM

– – – – RWEYQ6T2YM RWEYQ8TYM RWEYQ8TYM RWEYQ10TYM RWEYQ10TYM

– – – – RWEYQ8TYM RWEYQ8TYM RWEYQ10TYM RWEYQ10TYM RWEYQ12TYM

3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz 3-phase 4-wire system, 380-415 V/380 V,

Btu/h 54,600 76,400 95,500 114,000 131,000 153,000 172,000 191,000 210,000

kW 16.0 22.4 28.0 33.5 38.4 44.8 50.4 56.0 61.5

Btu/h 61,400 85,300 107,000 128,000 147,000 171,000 193,000 215,000 235,000

kW 18.0 25.0 31.5 37.5 43.0 50.0 56.5 63.0 69.0

Cooling kW 2.58 3.86 5.43 7.33 6.44 7.72 9.29 10.9 12.8

Heating kW 2.69 3.98 5.60 7.87 6.67 7.96 9.58 11.2 13.5

lvory white (5Y7.5/1) lvory white (5Y7.5/1)

mm 1,000 × 780 × 550 (1,000 × 780 × 550) × 2

Type Hermetically sealed scroll type Hermetically sealed


scroll type

Motor output kW 1.9 2.8 3.7 4.7 1.9 + 2.8 2.8 × 2 2.8 + 3.7 3.7 × 2 3.7 + 4.7

Liquid mm 9.5 (Flare) 12.7 (Flare) 12.7 (Flare) 15.9 (Flare)

Suction gas *1 19.1 (Brazing) 22.2 (Brazing) 28.6 (Brazing)

High and low pressure 15.9*2, 19.1*3 (Brazing) 19.1*2, 22.2*3 (Brazing) 22.2*2, 28.6* 3
(Brazing)
gas

Water inlet PT1 1/4B intenal thread (PT1 1/4B) × 2 intenal


thread

Water outlet PT1 1/4B intenal thread (PT1 1/4B) × 2 intenal


thread

Drain outlet PS1/2B intenal thread (PS1/2B) × 2 intenal


thread

kg 146 (148) 147 (149) 146 × 2 (148 × 2) 146 + 147 (148 + 149) 147 × 2 (149 × 2)

dB(A 49 50 51 53 53 54 55
)

°C 10 to 45 10 to 45

% 23-100 19-100 23-100 20-100 19-100

Type R-410A R-410A


RWEYQ12TYM
Combination units
RWEYQ12TYM
Power supply
229,000
Cooling capacity
67.0
256,000
Heating capacity
75.0
14.7
Power
consumption

VRV IV W Series
15.7
Casing colour
Dimensions (H × W × D) Water piping 19.1 (Flare)
connections 4.7 × 2 56
Compressor
Machine weight (Operating weight)Sound level
Operation range (Inlet water temp.)Capacity control
Refrigerant piping
connections

Refrigerant kg 3.54.2 3.5 + 3.5 3.5 + 4.24.2 + 4.2


Charge

MODEL RWEYQ26TYMRWEYQ28TYMRWEYQ30TYM RWEYQ32TYMRWEYQ34TYMRWEYQ36TYM

Combination units
kW 72.8 Suction gas *1 Type

Power supply
Btu/h 278,000 High and low pressure 28.6*
Cooling capacity gas

kW 81.5
Heating capacity Water inlet (PT1 1/4B) × 3 intenal thread
RWEYQ12TYM RWEYQ12TYM RWEYQ12TYM
Power Cooling kW 13.2
Water outlet (PT1 1/4B) × 3 intenal thread
consumption
345,000
Casing colour Heating kW 13.6 101
Drain outlet (PS1/2B) × 3 intenal thread
RWEYQ8TYM 386,000
lvory white (5Y7.5/1) 113
kg 146 × 2 + 147 (148 × 2 + 149) 146 + 147 × 2 (148 + 149 × 2)
RWEYQ8TYM 22.0
mm (1,000 × 780 × 550) × 3 23.6
dB(A 55 Notes:
RWEYQ10TYM ) 1. Specifications are based on the following conditions:
Type Hermetically sealed scroll type • Cooling: Indoor temp.: 27ºCDB, 19ºCWB / inlet water temp.:30ºC, Equivalent piping
°C length: 7.5 m, Height difference: 0 m.
3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz • Heating: Indoor temp.: 20ºCDB / inlet water temp.: 20ºC, Equivalent piping length: 7.5 m, Height difference: 0
Motor output kW 2.8 × 2 + 3.7 m.
% 21-100 • Sound level: Anechoic chamber conversion value, measured at a point 1 m in
front of the unit at a height of 1.5
Btu/h 248,000 Liquid mm m.
During actual operation, these
values are normally somewhat
Dimensions (H × W × D) Sound level higher as a result of ambient
Operation range (Inlet water temp.) conditions and oil recovery mode.
Compressor When there is concern for noise to
Capacity control the surrounding area such as
residences, we recommend
Refrigerant piping Refrigerant investigating the installation
3.5 + 4.2 + 4.2
connections location and taking soundproofing
measures.
2. This unit cannot be installed in the outdoors. Install indoors (Machine room, etc).
Water piping 3. Hold ambient temperature at 0 – 40ºC and humidity at 80%RH or less. Heat rejection from the casing: 0.51 kW / 6 - 8 class / hour, 0.58 kW / 10 -
4.7 × 3 58 12 class / hour.
connections
4. Connectable to closed type cooling tower only. *1: In the case of heat pump system, suction gas pipe is not used.
Machine weight (Operating weight) *2: In the case of heat recovery system.
*3: In the case of heat pump system.
Charge kg 3.5 + 3.5 + 4.2 4.2 + 4.2 + 4.2 4.2 + 4.2 + 4.2 • Be sure to refer to the Engineering Data Book for facility design.

105 106

Water Cooled System Suitable for Residential Houses


VRV WS Series Easy Installation & Energy Saving
Compact and lightweight Heat Pump

3class–6class VRV WS Series Service space (Single installation)


(8 kW) (16 kW) Footprint :
0.43 m2
Compact
Design

(For 3 class) 90 kg 1,000 mm


Product Weight :

(For 4/5 class) 94 kg


Product Weight :
550 mm

780 mm
(For 6 class) 99 kg
Product Weight :
30 mm
Service access from the front with minimal space
required at rear of the condenser (30 mm)

550 mm

600 mm
Front
Water piping
space

RWXYQ3-6AV1 Energy saving Higher Energy Efficiency Ratio (EER) Cooling Operation EER
20 mm 780 mm 20 mm

6.00 5.00 4.00 3.00 2.00 1.00 0 5.71 5.59 5.38


5.04

3 class 4 class 5 class 6 class


*Cooling : Indoor temp.: 27ºCDB, 19ºCWB/inlet water temp.: 30ºC,
Equivalent piping length: 7.5 m, Height difference: 0 m.

107 108

Tube-in-Tube Type Heat Exchanger Easy maintenance


Advanced Technologies VRV WS Series
Refrigerant lines spiraling around the water circuit in a counter flow design delivers superior heat exchange. Lower risk of
blockage
The electrical components and the major components are designed in a way that they can be accessed from front for maintenance.

Delivers optimal performance


VRV WS Series

Tube in tube structure for simple installation and maintenance Better tolerance for water quality!

Built in water flow switch


Mechanical water flow switch is built into the system to enhance system reliability.
Reed contact
Use of copper pipes enhances tolerance against corrosive effects of chloride ions Refrigerant cooling technology
Magnet
For activating the
reed contact

Magnet
For generating the
paddle reset force

PCB Pin

Power Module

Heat
Refrigerant Refrigerant Jacket Refrigerant

The main heat generating parts (inverter power module) in


the electric component is adopted to reduce the size of the
refrigerant cooling
Paddle System Reacts to flow

Control board failure ratio at stable operation is reduced.

This enables

• Suitability for high ambient temperatures


• Miniaturization of electronic components
Standard water strainer
A standard water strainer is equipped so it reduces the additional cost and installation time at field.

109 110

Long piping length


Flexible System Design Indoor Unit Lineup Enhanced
range of choices VRV WS Series New lineup

Middle Static FXSQ-PAVE


Pressure Duct
Model Name Capacity Range 2. 2.
(kW) FXDYQ-
2 8
MAV1

Capacity Index 20 25 Middle-High Static Pressure FXMQ-PAVE


Single use Duct

Round Flow FXFTQ-AVM High Static Pressure FXMQ-PV1A


Actual piping length Max. 120 m Cassette with Duct
Sensing and
Streamer
Equivalent piping length Max. 140 m 4-Way Flow Ceiling FXUQ-AVEB
Suspended
Round Flow FXFSQ-AVM
Total piping length Max. 300 m Cassette with
Sensing Ceiling Suspended FXHQ-MAVE

Round Flow Cassette FXFQ-AVM FXHQ-BVM

Wall Mounted FXAQ-AVM


Compact Multi FXZQ-BVM
Flow Cassette
Floor Standing FXLQ-MAVE

Double Flow FXCQ-BVM


Cassette Concealed Floor FXNQ-MAVE
Standing
Single Flow Cassette FXEQ-AV36

Slim Duct (Standard) FXDQ-PDVE (700 mm width type)


180
20
180
FXDQ-NDVE (900/1,100 mm width

type )

Category Slim Duct (Compact) FXDQ-


Ceiling Mounted Cassette
Type 20 25 TV1C(A)

a r i VRV WS Series

Ceiling Concealed Duct


fgh
First indoor branch
edcb s
*Colours in the diagram above are merely for identifying pipes referenced with symbols such as a .

Actual Example
piping length

120 m a+f+g+h+i

300 m a+b+c+d+e+f+g+
h+i

40 m f+g+h+i

15 m s

30 m r

Equivalent
piping length

Ceiling Suspended
Maximum Refrigerant piping length —
allowable Total piping length —
piping length Between the first indoor branch and the farthest indoor unit Between the indoor units —
Maximum Between the outside units

and the indoor units
allowable
140 m Floor Standing
height difference

111 112

Outside Unit Combinations


Outside Units
Total capacity index of connectable indoor units

VRV WS Series
Specifications
Heat Pump

VRV WS Series
Model name kW class Combination (%) 50% 100% 130%
Capacity index Maximum number of connectable indoor units

MODEL RWXYQ3A RWXYQ4A 3456 37.5 50 75 4689


RWXYQ3AV1 RWXYQ4AV1
RWXYQ5A RWXYQ6A 75 62.5 75 100 125 150
8.0 100 125 150 97.5 130
11.2 14.0 16.0 162.5 195

RWXYQ6AV1
Power supply 1-Phase, 220-240 V, 50 Hz Note: Total capacity index of connectable indoor units must be 50%–130% of the capacity index of the outside unit.

Cooling capacity
mm 1,000×780×550 % 20-100

Heating capacity Type Hermetically sealed swing type Type R-410A

Power Motor output kW 1.92 Charge kg 2.2 2.4


consumption Casing colour
Liquid mm 9.5 (Flare)
Btu/ 27,300 38,200 47,800
h
Suction gas 15.9 (Flare) 54,600
kW 8.0 11.2 14.0 16.0
Water inlet PT1B external thread
61,400
Btu/ 30,700 42,700 54,600
h Water outlet PT1B external thread 18.0
3.17
kW 9.0 12.5 16.0 Drain outlet PS1/2B internal thread
2.80

Cooling kW 1.40 2.00 2.60 kg 90 94

Heating kW 1.60 2.10 2.60 dB( 48 50


A)

dB( 66 68
A)
Ivory white (5Y7.5/1)
VRV WS Series
Operation range (Inlet water temp.) °C 15 to 45 (Range for continuous operation)

Dimensions (H×W×D) connections

Compressor
Water piping
connections
Refrigerant piping
Machine weight PT1 1/4B external thread

Sound level PT1 1/4B external thread

Sound power
99

Capacity control

Refrigerant

Rated water flow (Range of water flow) L/min Note :1. Specifications are based on the following conditions ;

2.7
30 (15 to 45) 40 (20 to 60) 50 (25 to 75) 57 (28.5 to 85.5)

·Cooling : Indoor temp. : 27ºCDB, 19ºCWB / inlet water temp. :30ºC, Equivalent piping length : 7.5 m, Height difference : 0 m. ·Heating
: Indoor temp. : 20ºCDB / inlet water temp. : 20ºC, Equivalent piping length : 7.5 m, Height difference : 0 m.
· Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions and oil recovery mode.
When there is concern for noise to the surrounding area such as residences, we recommend investigating the installation location and taking soundproofing measures.
2. This unit cannot be installed in the outdoors. Install indoors (Machine room, etc).
3. Hold ambient temperature at 0-40˚C and humidity at 80% RH or less.
Heat rejection from the casing: 0.21 kW/3 class /hour, 0.28 kW/4 class /hour, 0.31 kW/5 class /hour, 0.35 kW/6 class /hour

113 114

INDOOR UNIT LINEUP


Daikin offers a wide range of indoor units responding to variety of needs of our customers that
require air-conditioning solutions.

VRV indoor units


Round Flow Cassette with Sensing Type 360° airflow for improved comfort supplied from a single system. Page
151
Sensing and Streamer Type Comfort and energy savings by sensing functions Page
169
Page 4-Way Flow Ceiling
Comfort, energy savings by sensing functions and 167
enhanced maximum efficiency in cleaning
Page
129 Outdoor-Air Processing Unit
Suspended Type
Outdoor-Air Processing Unit
Page 123 Improve IAQ with fresh air ventilation and precise
Slim and stylish design, optimum air distribution,
installation without ceiling cavity
117 Round Flow Cassette Type Combine fresh air treatment room temperature control
and air conditioning, Page
Round Flow Cassette with
FXMQ-MFV1

FXFTQ-AVMFXUQ-AVEB

Wall Mounted Type Stylish flat panel design harmonised Slim Duct Air Handling Unit
with your interior décor.
(Standard) Type Middle Static Pressure Duct Type

Page
Floor Standing Type
155
Quiet, compact, and designed for user comfort Suitable for perimeter zone air conditioning

FXCQ-BVM
Compact Multi Flow Cassette Type FXHQ-MAVE FXLQ-MAVE
FXFSQ-AVM Page Page FXHQ-BVM
133 157
Thin, lightweight, and easy to install
in narrow ceiling spaces Slim Duct (Compact) Type
Concealed Floor Standing Type
Double Flow Cassette Type
Page
FXFQ-AVM
135
Slim design for flexible installation

Single Flow Cassette Type


Page FXZQ-BVM
137 FXEQ-AV36
Slim body with quiet and wide airflow. FXAQ-AVM

Ceiling Suspended Type


Page
FXMQ-AFVM
153
Slim design, quietness and ideal for drop-ceilings Page Page High static pressure allows
for flexible duct design.
141
Page FXDQ-NDVE
139 FXNQ-MAVE

Middle Static Pressure Duct Type

FXDQ-PDVE
Middle static pressure and slim design allow flexible
installations.
Middle static pressure and slim design allow flexible installations.
Air treatment equipment Heat Reclaim
Slim and compact design 158 FXDQ-TV1C(A)
for easy and flexible
Page Ventilator
Integrate your air handling unit
in a total solution for large size spaces such as factories and large
stores.

Page
Middle-High Static Pressure Duct Type AHUR

Middle and high static pressure


allows for flexible duct design.

FXSQ-PAVE
143

installation 163 High Static Pressure Duct Type


Suitable for perimeter zone air conditioning

Page 145 Page 147 Page 149 Daikin VAM series ensures fresh air intake and energy savings Page 173

VAM-HVE

FXDYQ-MAV1 FXMQ-PAVE FXMQ-PV1A

115 116
Equipped with decomposition technology, Streamer is a type of plasma
Round Flow Cassette with Sensing and Streamer Type VRV Indoor Units
Streamer Technology

FXFTQ-A Mechanism of decomposition by Streamer

Comfort, energy savings by sensing functions and enhanced maximum efficiency in cleaning
discharge that eliminates allergens such as pollen, mould, and mites, as well as, deodorises anti-bacterial dust filters so you can breathe with ease.

Excited
Introducing Streamer Indoor unit oxygen
OH
Excited
technology to VRV
radical
nitrogen

Oxygen
radical

Streamer emits high-speed electrons.


Daikin Streamer Technology decomposition properties to The electrons collide and combine with nitrogen and oxygen in the air to form four kinds of

enhances maximum efficiency in decompose substances captured by The decomposing elements provide decomposition power.
decomposing elements with decomposition power.

cleaning, which uses powerful filter for better air quality.

STREAMER 99.93% Inactivation of Omicron variant in 2 hours


FXFTQ-AVM Irradiation with Streamer discharge for two hours inactivated cabinet in the BSL-3 facility, and Streamer discharge device was
99.93%, and for four hours inactivated 99.97% of the Omicron installed in
Technology variant of Coronavirus (SARS-CoV-2), when compared to without DAIKIN Streamer Research Institute
Streamer discharge.
Inactivation effect against Omicron variant
Test Method
Experimental Results hCoV-19/Japan/ TY38-873/2021 strain (Omicron variant) was
used. Two acrylic boxes of about 31L were placed in a safety

Streamer filter clean unit irradiates Streamer when the fan and air )
Survival rate (% 75% Inactivation More than 99.9% Indoor Units
conditioning operation are stopped. Streamer fumigates the cabin 50% one of the acrylic boxes. Seesaw shakers with a 6-well plate were placed in both stirring with a seesaw shaker. After 1, 2, and 4 hours, the virus solution was
and sterilizes the filter. boxes, and 0.5 mL of virus solution was placed in each well of the plate. Streamer collected, and the virus titer was measured by the TCID50 method using Vero
100% irradiation was performed on one 6-well plate while E6/TMPRSS2 cells.
25%
100%

0% Test Organization Professor Tatsuo Shioda, Department of Virus


10.0%
0.07% 0.03%

Streamer filter clean unit built-in inside the indoor unit Remarks: Compared with natural attenuation *This result was obtained by using a Streamer discharge device for testing in lab conditions.
01 The effect of products equipped with Streamer technology or results in actual use environments may differ.
Infections, Research Institute for Microbial Diseases, Osaka University
2 3 4 Time (hour)

1) Only the remote controller BRC1H63W(K) can be connected for ON/OFF operation of the streamer. Streamer decomposes mould and mites (feces and carcasses) and suppresses the causes of allergies.
2) The Streamer function operates only when the fan and air conditioning operation are stopped.
The maximum operation of streamer is 180 minutes per day. (This function is available only when the remote Picture of mould
controller BRC1H63W(K) is connected.) Before irradiation After irradiation [15minutes]
Test Method
“Moulds” were placed on the electrodes of a Streamer discharge unit where they were exposed to Streamer
dischage for 15 minutes and photographed with an electron microscope.

Demonstration of mould Test Organization


Demonstration test was performed at Wakayama Medical University.

Stylish Remote Controller BRC1H63W/K Recognized as clean technology by public bodies Streamer, a type of plasma
Streamer ON/OFF setting and status icon are available.
Why Daikin Streamer?
Electron generation area Winner of the 2005
Progress Award, Institute Awarded for the development of a domestic air purifier which uses
of Electrostatics Japan DC Streamer discharge.
105 Patents Acquired
Patents acquired relating to Streamer technology hazardous chemical substances. The decomposition power is Note:
discharge, decomposes *Comparison of oxidation decomposition. This does not mean temperature will become high.
comparable to thermal energy of about 100,000°C.*

117 118

Comfort and energy saving by sensing functions


Round Flow Cassette with Sensing and
Streamer Type Daikin advanced sensing Infrared presence sensor
Detecting the presence

technology Comfortable air conditioning for all room layouts and


conditions
VRV Indoor Units

Easy setting is possible with a wired remote controller


Individual airflow direction control
Airflow direction can be individually adjusted
dual sensors for each air discharge outlet to deliver optimal air distribution.

Position 0

Infrared floor C (Highest point) (Fixed airflow to highest position) Swing (Up/down) Position 4
BDA Position 1 No individual setting
sensor (Auto airflow)
Position 2
Detecting the average Position 3
temperature of indoor floor Position 4 (Lowest point)
Individual airflow settings Swing
of people in 4 areas
No individual setting (Auto airflow) Position 0 Individual settings are possible as stated above.

Comfort is provided to the entire room When there are no people in a room, the set 27°C Swing
Sensing sensor mode (Fixed airflow to the lowest position) temperature is shifted automatically. • Cooling setpoint: 26°C Swing is set for meetings near
Energy saving Indoor Units
• Shift temperature: 1.0°C • Shift time: 30 min. the windows.
• Limit cooling temperature: 30°C 28°C
28
27
by individual setting corresponding to 4-way
Example flow conditions.
Sensing sensor low mode (default: OFF)
No individual setting (Auto airflow)
26
Setpoint (°C)
26°C 26°C Automatically

Occupied Unoccupied Position 0 The airflow is at the highest


reverts when people return.

After Sensing sensor stop mode (default: OFF) After Time to meeting areas near windows.
30 min another 30 min Large blow is provided setting (Position 0)
for people who dislike air blowing directly on them.

Based on preset user conditions, the system automatically stops operation if the room is unoccupied. *Adjustment is possible for shift time and set temperature by local setting. No individual setting (Auto airflow)
Blow reduced for areas with few people.
119 120

VRV Indoor Units


Round Flow Cassette with Sensing and
Streamer Type Other functions
Quick and easy installation Panel (Option)
Installable in tight ceiling spaces accessory with 850 mm lift. Standard panel with sensing
BYCQ125EEF (Fresh White)
850 mm
Min. of 261 mm* ceiling space when using standard panel. * For FXFTQ25-80A models.
175 mm
Specifications
Drain pump is equipped as standard

Standard panel with sensing BYCQ125EEK (Black)

Power supply MODEL FXFTQ25AVM FXFTQ32AVM FXFTQ40AVM FXFTQ50AVM FXFTQ63AVM FXFTQ80AVM FXFTQ100AVM FXFTQ125AVM FXFTQ140AVM 1-phase, 220-240 V/220-230 V, 50/60 Hz

7.1
Easy maintenance 9.0
11.2
Btu/h 14.0
9,600 16.0
12,300
15,400 Just open the suction grille!
19,100
24,200
30,700
38,200 Btu/h
47,800 27,300
54,600 34,100
Cooling capacity 42,700
kW 54,600
2.8 10,900
3.6 13,600
4.5 17,100
5.6 21,500
Heating capacity
8.0
kW 3.2 4.0 5.0 6.3 10.0 12.5 16.0
Cooling 0.061
Drain pan and drain water check 0.092 0.164 0.170
0.028 0.035 0.056
Power consumption kW 0.194

Drain outlet (with rubber plug) Casing


The condition of the drain pan and drain water can be 0.026 0.034 0.056 0.060 0.092 0.144 0.159 0.183 Galvanised steel plate
Heating

checked by Indoor Units


removing the
suction grille and
drain plug.
Note: For inquiries concerning
auto grille panel installations,
please contact your local dealer
or

Airflow rate (H/HM/M/ML/L)

Sound level (H/HM/M/ML/L)

/s
m3/min dB(A)
217/208/192/183/167
13/12.5/11.5/11/10
30/29.5/28.5/28/27
283/225/208/200/183 17/13.5/12.5/12/11
35/29.5/29/28/27
383/342/317/242/183 23/20.5/19/14.5/11
38/35/34.5/29.5/27
392/350/333/267/225 23.5/21/20/16/13.5
38/36/35.5/31.5/28
408/367/342/333/250 24.5/22/20.5/20/15
39/37/36/35.5/31
558/508/450/392/350
33.5/30.5/27/23.5/21 44/41/38/35/33
575/525/475/425/383
34.5/31.5/28.5/25.5/23
45/42.5/39.5/37/35

592/542/492/442/383
35.5/32.5/29.5/26.5/23
46/43.5/40.5/38/35
Daikin representative. mm kg 256×840×840 298×840×840 19
Dimensions (H×W×D) Machine weight 24 22 25 26

Piping Liquid (Flare) 6.4 9.5

connections 12.7 15.9 VP25 (External Dia. 32/Internal Dia. 25)


Gas (Flare) Drain mm

Notes: Specifications are based on the following conditions;


Cleanliness • Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m,
Height difference: 0 m. • Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.) • Sound level: Anechoic chamber conversion
value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
Silver ion anti-bacterial drain pan

Prevents the growth of slime, bacteria, and mould that cause odours and clogging. * Drain pan Panel (Option) Model Function List
should be changed once every two to three years. BYCQ125EEF (Fresh White) Wired remote controller BRC1H63W(K)

Standard with Model Dual sensors *1


BAF552A160
panel sensing High Performance Prefilter Dimensions(H×W×D) Weight Auto airflow function (Draft prevention) *1 Sensing sensor low mode *1
Filter has mm kg Sensing sensor stop mode *1

anti- (MERV 8) (Option) See page 209This filter can Individual airflow direction control
mm kg Switchable 5 step fan speed
mould and catch more harmful substances in the air such as 50×950×950 Auto airflow rate

antibacterial PM2.5.
5.5 Auto swing
BYCQ125EEK (Black) 50×950×950 High ceiling application
treatment Dimensions(H×W×D) Weight 5.5 *1. Applicable when sensing panel is installed.
Streamer function unit

121 122

Auto airflow function Daikin advanced sensing technology dual


Round Flow VRV Indoor Units
sensors
Cassette with
Sensing Type
FXFSQ-A Comfort and energy saving by sensing functions
*When human is not detected for 5 minutes, the unit automatically returns to controlling the flaps for an unoccupied room.

When human presence not detected.

Comfort and energy saving by sensing functions Direct Airflow (default: OFF) Cooling Dry

Comfort When human presence detected. Deliver cool air to users

Infrared presence sensor Detecting the presence Optimal air direction by “Auto” Optimal air direction by “Auto” (narrow)
Swing

Infrared floor sensor of people in 4 areas BDA (default: OFF) downward When human presence detected. Prevent Blown downward Blown horizontally
cold drafts Indoor Units
Detecting the average temperature of Heating
C Draft prevention function
indoor floor
When human presence not detected. Blown
Comfort and energy saving preventing over cooling/heating Comfort Energy saving
Sensing sensor mode
Sensors detecting human presence and temperatures Without sensing function With sensing function Sensing sensor low mode (default: OFF) Example
• Cooling setpoint: 26°C
near the floor provide comfortable spaces without uneven
temperatures.
Cooling When there are no people in a room, the set temperature is • Shift temperature: 1.0°C • Shift time: 30 min.
shifted automatically. • Limit cooling temperature: 30°C

30°C near ceiling Even when room 30°C near ceiling To prevent an excessive drop in temperature, room 28 27 28°C 27°C
too cold temperature is detected at 30°C, the floor temperature is

20°C near floor temperature may be as low as 20°C, causing the feet area to 24°C near floor vicinity. 26
be cold. calculated at 27°C when people are in the Setpoint (°C)
26°C 26°C Automatically

Uneven temperatures enable minimal drafts, Occupied Unoccupied reverts when people return.
Heating

17°C near floor but the feet area becomes cold. When you try to eliminate uneven 20°C near floor reduce drafts and ensure the feet area is After 30 min another 30 min
feet are cold strong draft The sensing function controls airflow to warm.
Sensing sensor stop mode (default: OFF)
After Time

temperatures, drafts Based on preset user conditions, the system automatically stops operation if the room is unoccupied. *Adjustment is possible for shift time and set
become strong.
20°C near floor temperature by local setting.

123 124

Circulation airflow*1 Individual airflow direction control


Round Flow Cassette with Sensing Type VRV Indoor Units controller BRC1E63 or BRC1H63W(K) is used.
* Applicable when wired remote

Configurations of circulation airflow


Comfortable air conditioning for all room layouts and conditions Comparison Conditions

Room size: Width 7.5m x depth 7.5m x height 2.6m Indoor unit capacity: 71 class
Circulation airflow cools the entire room to deliver comfort that never feels cold. Outdoor air temperature: 35°C Easy setting is possible with a wired remote controller
Hot outdoor 22.0
Cooling air
Airflow rate and air direction: high / swing 21.0 Position 0 No individual setting
20.0
(Fixed airflow to highest position)
During 2-way horizontal flow 30.0 Airflow direction can be individually adjusted
29.0
28.0 for each air discharge outlet to deliver optimal air
27.0
26.0 distribution.
25.0
Airflow effectively avoids blowing air directly on people. 24.0
23.0
4-way cassette (Swing)
Cool air moves down along the walls and to every corner of the room. 30.0 29.0 28.0 27.0 26.0 25.0 24.0 23.0 airflow)
Cools by airflow blocking out hot air near windows and walls.

Circulation Airflow
(2-way horizontal + 4-way swing) Individual airflow settings
reduce uneven temperatures Approx. 5% No individual setting (Auto airflow) Position 0
(Highest point)
Position 1
Position 2
(Auto
Comfort without cold air pockets at floor level. Airflow When the target Swing (Up/down) Position 4
direction
changes temperature is reached, (Fixed airflow to the lowest position) Indoor Units
22.0 21.0 20.0
Operation (at start) energy savings*2
Position 3
Performs repeatedly Position 4 (Lowest point)
*2Calculated under the following comparison conditions: When the average temperature
at a height of 0.6m above the floor reaches set temperature. (26°C) Swing

Individual settings are possible as stated above.

Cools areas around walls using swing flow 2-way horizontal flow
2-way horizontal flow Cools entire room using 4-way
normal operation Comfort is provided to the entire by individual setting corresponding to
Cools entire room using 4-way Cools areas around walls using swing flow (all-round flow) begins. Comparison Conditions room 4-way flow conditions.
Room size: Width 7.5m x depth 7.5m x height 2.6m Indoor unit capacity: 71 class
Circulation airflow warms the entire room starting from your feet. Outdoor air temperature: 5°C

During 2-way horizontal flow Airflow effectively avoids blowing air directly on people. Airflow rate and air direction: high / Down blow 30.0
Heating 28.0
4-way cassette (Down blow) Cool outdoor air
26.0
24.0
20.0
18.0
14.0
12.0 Swing No individual setting (Auto airflow)
22.0 16.0 10.0
Swing is set for meetings near the windows.

Airflow quickly makes the entire room warm and comfortable. Circulation Airflow 30.0 28.0 26.0 24.0 22.0 20.0 18.0 16.0
The airflow is at the highest
Warms by airflow blocking out cool air near windows and walls. reduce uneven temperatures Approx. 15% Position 0
(2-way horizontal + 4-way swing)
Warmth reliably reaches feet.

Operation (at start)


Performs repeatedly
Airflow
direction
changes
energy savings*3

*3Calculated under the following comparison conditions: When the average temperature at a height of 0.6m
above the floor reaches set temperature. (22°C)

When the target


temperature is reached,
normal operation
14.0

Large blow is provided


12.0
10.0

to meeting areas near windows.

No individual setting
(Auto airflow)
setting (Position 0)
for people who dislike air
blowing directly on them.

Blow reduced for areas


with few people.
Warms areas around walls using Warms the middle of the room using 4-way Warms areas around walls using Warms the middle of the room using 4-way down flow
2-way horizontal flow down flow 2-way horizontal flow (all-round flow) begins.

*1 125 Conditions apply for the circulation airflow function. Please contact your local sales office for details. 126

VRV Indoor Units


Round Flow Cassette
with Sensing Type Other
functions
Comfort
From All-round flow to 2-way flow, various airflow patterns available. All-

Standard panel with sensing

round flow 3-way flow L-shaped 2-way flow Opposite 2-way flow
Panel (Option) Standard panel with sensing

(E.g., installed in middle of ceiling) (E.g., installed near a wall) (E.g., installed in a corner) 4-way flow also possible. (E.g., installed in a long room) BYCQ125EEF (Fresh White)
BYCQ125EEK (Black)

* Whatever the discharge direction, the same type of panel is used. If installing for other than all-round flow, an air discharge outlet sealing material (option) must be used to close each unused outlet.
Specifications
Suitable for high ceilings MODEL FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM FXFSQ50AVM FXFSQ63AVM FXFSQ80AVM FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM

Even in spaces with high ceilings, a comfortable airflow is carried down to the floor level.
Power supply 1-phase, 220-240 V/220-230 V, 50/60 Hz
Btu/h
9,600
12,300
15,400
19,100
24,200
30,700
38,200
47,800
54,600
Cooling capacity
kW
2.8
3.6
4.5
5.6
7.1
9.0
11.2
14.0
16.0

Quick and easy installation


Btu/h
27,300
34,100
42,700
54,600
10,900
13,600
17,100
21,500
Heating capacity
8.0
kW 3.2 4.0 5.0 6.3 10.0 12.5 16.0
Cooling 0.061 0.092 0.164 0.170
0.028 0.035 0.056
Installable in tight ceiling spaces 850 mm
Power consumption kW 0.194

Heating Casing
0.026 0.034 0.056 0.060 0.092 0.144 0.159 0.183 Galvanised steel plate
13/12.5/11.5/11/10
Min. of 261 mm* ceiling space when Indoor Units
30/29.5/28.5/28/27
using 283/225/208/200/183 17/13.5/12.5/12/11

standard 35/29.5/29/28/27
383/342/317/242/183 23/20.5/19/14.5/11
panel. * For 38/35/34.5/29.5/27

FXFSQ25-80A
392/350/333/267/225 23.5/21/20/16/13.5
models. 38/36/35.5/31.5/28
175 mm 408/367/342/333/250 24.5/22/20.5/20/15
39/37/36/35.5/31
Airflow rate
(H/HM/M/ML/L) 558/508/450/392/350 33.5/30.5/27/23.5/21

Sound level 44/41/38/35/33


(H/HM/M/ML/L) 575/525/475/425/383 34.5/31.5/28.5/25.5/23

/s 45/42.5/39.5/37/35

m3/min dB(A)
592/542/492/442/383 35.5/32.5/29.5/26.5/23
217/208/192/183/167
46/43.5/40.5/38/35
Dimensions (H×W×D) Machine weight 19
Drain pump is equipped as standard mm kg
accessory with 850 mm lift. 256×840×840 298×840×840 24 22 25 26

Piping 6.4 9.5


Liquid (Flare)
mm
Gas (Flare)
connections
Easy maintenance
Drain 12.7 15.9 VP25 (External Dia. 32/Internal Dia. 25)

Notes: Specifications are based on the following conditions;


Drain pan and drain water check • Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Heating: Indoor temp.:
20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Capacity of indoor unit is only for reference.
Just open the suction grille! Drain outlet Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.) • Sound level: Anechoic chamber
conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.

Note: For inquiries concerning auto grille panel installations,


The condition of the drain pan and removing the and drain plug. please
BYCQ125EEF (Fresh White) Wired
Wireless
drain water can be checked by suction grille (with rubber plug) Function List Remote controller
Panel (Option) Model
contact your local dealer or Daikin Standard panel Model 50×950×950 BYCQ125EEK (Black) Auto airflow function (Direct airflow) *1 BRC7M634F(K) —
representative. with mm kg BRC1E63
5.5 —
Dimensions(H×W×D) Weight BRC1H63W(K) —
Dual sensors *1
sensing 50×950×950 Auto airflow function (Draft prevention) *1 —
Dimensions(H×W×D) mm
* Drain pan should be changed once every two to three years. ——
Cleanliness Silver ion anti-bacterial drain pan
Sensing sensor low mode *1 Sensing sensor stop mode *1 Circulation airflow
5.5 Prevents the growth of slime, bacteria, and mould that cause Individual airflow direction control Switchable 5 step fan speed Auto airflow rate
kg
Weight
odours and clogging. Auto swing
Selectable airflow pattern
————

Filter has anti-mould and antibacterial treatment BAF552A160


High Performance Prefilter (MERV 8) (Option) See page 209 This filter can catch more harmful substances in the
air such as PM2.5.
High ceiling application — *1. Applicable when sensing panel is installed.

127 128

Individual airflow direction control


Round Flow * Applicable when wired remote controller BRC1E63 or BRC1H63W(K) is used.

VRV Indoor Units


360° airflow for improved comfort Position 0

Circulation airflow*1 Comparison Conditions


Room size: Width 7.5m x depth 7.5m x height 2.6m Indoor unit capacity: 71 class

Comfortable air conditioning for all room layouts and


Configurations of circulation airflow conditions
Circulation airflow cools the entire room to deliver comfort that never feels cold.
Easy setting is possible with a wired remote controller
Airflow direction can be individually adjusted
for each air discharge outlet to deliver optimal air distribution.

Cooling
Hot outdoor
air
Outdoor air temperature: 35°C
20.0
Position 1 No individual setting (Auto airflow)
Airflow rate and air direction: high / swing Position 2
During 2-way horizontal flow (Fixed airflow to highest position)
4-way cassette (Swing) 30.0 29.0
28.0
27.0
26.0
Individual airflow settings
25.0
Airflow effectively avoids blowing air directly on people. 24.0 No individual setting (Auto airflow) Position 0 (Highest
23.0
22.0
point)
21.0
Cool air moves down along the walls and to every corner of the room. Circulation
Airflow 30.0 29.0 28.0 27.0 26.0 25.0 24.0 23.0
Position 4 (Lowest point) Individual settings are possible as stated above.
Cools by airflow blocking out hot air near windows and walls. reduce uneven temperatures Approx. 5% Position 3 Position 4
(2-way horizontal + 4-way swing) Swing
Comfort without cold air pockets at floor level. changes When the target Comfort is provided to the entire room
energy savings*2 temperature is reached,
Performs repeatedly (Fixed airflow to the lowest position) Indoor Units
Operation 22.0
*2 Calculated under the following comparison conditions: When the average temperature at a height of 0.6m
Swing (Up/down)
(at start) Airflow direction
above the floor reaches set temperature. (26°C)
21.0
20.0

Cools areas around walls using swing flow 2-way horizontal flow
2-way horizontal flow Cools entire room using 4-way
normal operation by individual setting corresponding to4-way flow conditions.
Cools entire room using 4-way Cools areas around walls using swing flow (all-round flow) begins. Comparison Conditions

Room size: Width 7.5m x depth 7.5m x height 2.6m Indoor unit capacity: 71 class
Circulation airflow warms the entire room starting from your feet. Outdoor air temperature: 5°C Swing
Cool outdoor 30.0 20.0
Heating No individual setting air
28.0 18.0
4-way cassette (Down blow) 26.0
During 2-way horizontal flow (Auto airflow) Airflow rate and air direction: high / Down blow 24.0 Swing is set for meetings near the windows.
22.0

Airflow effectively avoids blowing air directly on people. 16.0 14.0 12.0 10.0

Airflow quickly makes the entire room warm and comfortable. (2-way horizontal + 4-way swing) 30.0 28.0 26.0 24.0 22.0 20.0 18.0 16.0 14.0
Large blow is provided for people who dislike air blowing directly on
Warms by airflow blocking out cool air near windows and walls. Approx. 15% Position 0
Circulation Airflow reduce uneven temperatures energy savings*3 to meeting areas near windows. The airflow is at the highest setting (Position 0) them.
Warmth reliably reaches feet. Airflow direction changes No individual setting (Auto airflow) Blow reduced for areas with few people.
12.0
When the target
Performs repeatedly
10.0
temperature is reached,
Operation (at start) *3 Calculated under the following comparison conditions: When the average temperature
normal operation
at a height of 0.6m above the floor reaches set temperature. (22°C)
(all-round flow) begins.
Warms areas around walls using Warms the middle of the room using 4-way down flow 2-way horizontal flow
2-way horizontal flow Warms areas around walls using Warms the middle of the room using 4-way down flow

*1 129 Conditions apply for the circulation airflow function. Please contact your local sales office for details. 130

Decoration Panel (Option)


Round Flow Cassette Type Other functions Standard panel

Comfort
From All-round flow to 2-way flow, various airflow patterns available.
VRV Indoor Units

All-round flow 3-way flow L-shaped 2-way flow Opposite 2-way flow Standard panel
Standard panel

(E.g., installed in middle of ceiling) (E.g., installed near a wall) (E.g., installed in a corner) (E.g., installed in a long room) * Whatever the discharge direction, the same type of panel is used. If installing for other than all-round flow, an air discharge outlet sealing material BYCQ125EAK (Black)
(option) must be used to close each unused outlet.
4-way flow also possible.
BYCQ125EAF (Fresh White) Auto grille panel

Suitable for high ceilings Grille and air filter cleaning can be performed without need for a stepladder by lowering the grille.

Even in spaces with high ceilings, a comfortable airflow is carried down to the floor level. Quick and easy installation A dedicated remote controller for the auto grille panel is included.
Operation is not possible using other remote controllers.

Installable in using standard panel. * For FXFQ25-80A mm lift. Specifications Grille panel can be lowered to a maximum of 3.9 m.
models. BYCQ125EBSF (Fresh White)
tight ceiling
spaces 850 mm
Drain pump is equipped as Wireless Remote
Min. of 261 mm* standard accessory with 850 175 mm Controller
ceiling space when Indoor Units

Power supply FXFQ125AVM FXFQ140AVM 1-phase, 220-240 V/220-230 V, 50/60 Hz


Easy maintenance MODEL FXFQ25AVM FXFQ32AVM FXFQ40AVM FXFQ50AVM FXFQ63AVM FXFQ80AVM FXFQ100AVM

Cooling capacity 9,600 15,400 54,600


Just open the suction grille! Btu/h 12,300 19,100 24,200 30,700 38,200 47,800
kW 2.8 3.6 4.5 5.6 7.1 9.0 11.2 14.0 16.0
Btu/h 10,900 13,600 17,100 21,500 27,300 34,100 42,700 47,800 54,600
Heating capacity 4.0 5.0 8.0 10.0 12.5 14.0 16.0
Drain pan and drain water check 3.2 kW
6.3

The condition of the drain pan and drain water can be checked by (with rubber plug) Power consumption Cooling Heating
Galvanised steel plate

removing the suction grille and drain plug. Note: For inquiries concerning auto
Casing
0.029 0.036 0.040
Drain outlet kW 0.063 0.096 0.158 0.178 0.203 0.027 0.036 0.040 0.063 0.096 0.150 0.166 0.191

/s 217/208/192/183/167 283/225/208/200/183 383/342/317/242/183 408/367/342/333/250 558/508/450/392/350 575/525/475/425/383 592/542/492/442/383


grille panel installations, please 392/350/333/267/225
m 18/17/13.5/12.5/11 3/min Airflow rate (H/HM/M/ML/L)
contact your local dealer or 13/12.5/11.5/11/10 17/13.5/13/12/11 21/20/16/15/13.5 22.5/21.5/21/20/15 32/29/26/23/21 33/30.5/28/25.5/21 35.5/32.5/29.5/26.5/23
Daikin representative. Sound level (H/HM/M/ML/L) dB(A) 30/29.5/28.5/28/27 35/29.5/29/28/27 35/33.5/29.5/28.5/27 46/43.5/40.5/38/35
36/35.5/31.5/31/28 37/36.5/36/35.5/29.5 43/40.5/37.5/35/33 44/41.5/39/36.5/33

Dimensions (H×W×D) Machine weight 19


Cleanliness 256×840×840 298×840×840
mm
kg
22 25 26

Piping connections mm 6.4 12.7 VP25 (External Dia. 32/Internal Dia. 25) 9.5 15.9
Liquid (Flare) Gas (Flare) Drain

Notes: Specifications are based on the following conditions;


Silver ion anti-bacterial drain pan • Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB,
Equivalent piping length: 7.5 m, Height difference: 0 m. • Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data
Prevents the growth of slime, bacteria, and mould that cause odours and clogging. Book for details.) • Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
* Drain pan should be changed once every two to three years.

Filter has anti-mould and antibacterial treatment Decoration Panel (Option) Function List

209 Dimensions(H×W×D) Weight BYCQ125EAF (Fresh White ) / BYCQ125EAK (Black) Remote controller Circulation airflow BRC1E63 BRC1H63W(K) —
BAF552A160 Performance Prefilter
High 50×950×950 Wireless
(MERV 8) (Option) See page Standard panel
Model mm kg 5.5
Wired
BRC7M634F(K) —
Model BYCQ125EBSF (Fresh White) Individual airflow direction control —
Auto
grille Dimensions(H×W×D) 105×950×950 Switchable 5 step fan speed
This filter can catch more harmful substances in the air such as PM2.5. mm
panel
8
kg —

Auto airflow rate


Auto swing
Selectable airflow pattern High ceiling application
Weight

131 132

Compact Multi Flow Cassette Type FXZQ-B

Quiet, compact, and designed for user comfort

Compact & elegant design


VRV Indoor Units

• Fully-flat integration in standard architectural ceiling tiles, leaving only 8 mm

• Remarkable blend of iconic design and engineering excellence with an elegant finish in white

• The newly designed panel integrates fully within one ceiling tile enabling lights, speakers and sprinklers to be installed in the
adjoining ceiling tiles.

Efficiency & comfort


Dual sensors (Option)
8 mm
Specifications Cooling capacityBtu/h 7,500 9,600 12,300 15,400 19,100
kW 2.2 2.8 3.6 4.5 5.6
MODEL FXZQ20BVM FXZQ25BVM FXZQ32BVM FXZQ40BVM FXZQ50BVM
Power supply 1-phase, 220-240 V/220-230 V, 50/60 Hz Heating capacityBtu/h 8,500 10,900 13,600 17,100 21,500
kW 2.5 3.2 4.0 5.0 6.3

• Two optional intelligent efficiency and Cooling


kW0.043 0.045 0.059 0.092 Indoor Units
sensors improve energy Power
Heating 0.036 0.038 0.053 0.086
consumption
comfort. Casing Galvanised steel plate

Airflow rate (H/M/L) 145/125/108 150/133/108 167/142/117 192/158/133 242/208/167 /s

• An optional presence and floor sensor kit can be fitted to the cassette Individual airflow direction control*
for draught prevention, energy-saving operation and to provide optimal m³/min 8.7/7.5/6.5 9.0/8.0/6.5 10.0/8.5/7.0 11.5/9.5/8.0 14.5/12.5/10.0 Sound level (H/M/L) dB(A) 32.0/29.5/25.5 33.0/30.0/25.5 33.5/30.0/26.0 37.0/32.0/28.0 43.0/40.0/33.0 Sound power (H) dB(A) 49
control of airflow. 50 51 54 60 Dimensions (H×W×D) mm 260×575×575 (For depth add 63 mm for electrical box) Machine weight kg 15.5 16.5 18.5
Liquid (Flare) 6.4

• Airflow direction can be individually adjusted for distribution. Gas (Flare) 12.7 mm
Piping
each air discharge outlet to deliver optimal air connections
Drain VP20 (External Dia. 26/Internal Dia. 20)

*Applicable when wired remote controller BRC1E63 or BRC1H63W(K) is used. Notes: Specifications are based on the following conditions;
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB,
6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See
Engineering Data Book for details.) • Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
Auto swing (up/down) During actual operation, these values are normally somewhat higher as a result of ambient conditions.

Possibility to select automatic vertical moving of the air discharge flaps for efficient air
and temperature distribution throughout the room. Panel (Option)
Panel type Grid ceiling panel

Cleanliness

Streamer filter clean unit (Option)


See page 5-6

Appearance
Remarks:
Daikin Streamer technology enhances maximum efficiency in cleaning, which uses 1) Only the stylish remote controller BRC1H63W(K) can be connected for ON/OFF operation of the streamer. 2) The Streamer function operates only when the fan and air conditioning operation are stopped. The
powerful decomposition properties to decompose substances captured by the filter maximum operation of Streamer is 180 minutes per day.

Model Ceiling soiling prevention


for better air quality. Prevents air from blowing against the ceiling to prevent ceiling stains.
Dimensions (H×W×D) mm 46×620×620
Weight kg 2.8

Colour
BYFQ60CAW White (N9.5)
BAPW55A61

133 134
• The flat flaps close entirely when the unit is not
Comfort
Double Flow operating and there are no air intake grilles visible.
• Depth of all units is 620 mm, ideal for narrow spaces

Cassette Easy maintenance


Type FXCQ-B • The flap parts are easy to clean because it is hard to condensate and get dirty. • Check
contamination in drain pan by simply removing suction grille and panel.

Thin, lightweight, and easy to install in narrow • Adjuster pockets mount at four corners of the unit enable to adjust the main unit without
ceiling spaces removing the panel.

Flexible installation
Stylish design
• Drain pump is equipped as standard accessory with 850 mm lift.
• Stylish unit blends easily with any interior.
Cleanliness

Adjuster Pocket Drain socket part


VRV Indoor Units

Individual airflow direction control* Streamer filter clean unit (Option) See page 5-6

• Airflow direction can be individually Position 0 Position 4 (Lowest point) 1) Only the stylish remote controller BRC1H63W(K) can be connected for ON/OFF
operation of the streamer. 2) The Streamer function operates only when the fan and air
adjusted for each air discharge Swing
conditioning operation are stopped. The maximum operation of Streamer is 180 minutes
per day.
outlet to Individual settings are possible as stated above.
deliver optimal air Individual airflow settings Swing
distribution. Daikin Streamer technology enhances maximum
No individual setting (Auto airflow)
efficiency in cleaning, which uses powerful
Silver ion anti-bacterial drain pan
*Applicable when wired remote BAPW55A61
controller Position Position 0 (Highest point) decomposition properties to decompose substances • Prevents the growth of slime, bacteria, and mould that
BRC1E63 or BRC1H63W(K) is Position 1 Indoor Units
used.
Position 2 captured by the filter for better air quality.
cause odours and clogging. * Drain pan should be changed once every
Position 3 Remarks:
two to three years.

(Fixed airflow to highest position) 5-step & auto airflow control (Up / Down)
Filter has anti-mould and antibacterial treatment Specifications

• Control of airflow rate has been improved from 3-step to 5-step. Auto airflow rate is newly available. Power supply
MODEL FXCQ20BVM FXCQ25BVM FXCQ32BVM FXCQ40BVM FXCQ50BVM FXCQ63BVM FXCQ80BVM FXCQ125BVM 1-phase, 220-240 V/220-230 V, 50/60 Hz
7,500
9,600
12,300
15,400
19,100
24,200
30,700
47,800
Btu/h
Cooling capacity
2.2
2.8
3.6
4.5
5.6
7.1
9.0
14.0
kW

Suitable for high ceilings


Heating capacity Btu/h
8,500 10,900 13,600 17,100 21,500 27,300 34,100 54,600 2.5 3.2 4.0 5.0 6.3 8.0 10.0 16.0 kW
Power consumption kW 0.039 0.041 0.063 0.090
• Even in spaces with high ceilings maximum 3.5 m, a comfortable airflow is carried down to the floor level. Cooling 0.031 0.059 0.149
Heating Casing
0.028 0.035 0.037 0.056 0.060 0.086 0.146 Galvanised steel plate

300 comparison (Cooling) 278 Airflow rate (H/HM/M/ML/L) Sound /s 175/158/150/133/125 10.5/9.5/9/8/7.5 192/175/158/142/133 34/33/31/30/29 34/33/32/31/30 250/233/217/192/175 15/14/13/11.5/10.5 267/250/233/208/192 16/15/14/12.5/11.5 433/400/375/342/308 26/24/22.5/20.5/18.5 533/492/458/417/375 32/29.5/27.5/25/22.5
m3/min dB(A) 32/31/30/29/28 11.5/10.5/9.5/8.5/8 200/183/175/158/142 12/11/10.5/9.5/8.5 37/36/35/33/31 39/38/37/35/32 42/40/38/36/33 46/44/42/40/38
Power consumption level (H/HM/M/ML/L)
36/35/33/32/31
Dimensions (H × W × D) 305×775×620
Power consumption (W)
Energy saving mm 305×990×620 305×1,445×620

200 Machine weight VP25 (External Dia. 32/Internal


Dia. 25)
• Power consumption is Piping
25
connections
significantly Liquid (Flare) Gas (Flare) Drain 33
9.5
216 kg
15.9
mm
38
132 132157 19
6.4
12.7
22
149
reduced by specially developed small motor. 100 90
31 39 41 59 63
Panel
Model Colour
BYBCQ63CF BYBCQ125CF
95 81 Fresh white (6.5Y 9.5/0.5)
tube heat exchanger and DC fan BYBCQ40CF

0 (Option) Dimensions (H×W×D) Weight mm kg 55×1,070×700 10 55×1,285×700 11 55×1,740×700 13

20 Notes: Specifications are based on the following conditions;


• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m.
25/32 40 50 63 80 125
Conventional model: FXCQ-M New model: FXCQ-B Model class only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.) • Sound level:
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Capacity of indoor unit is Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
135 136 During actual operation, these values are normally somewhat higher as a result of ambient conditions.

Single Flow
Cassette Type FXEQ-A

Slim design for flexible installation

Slim design
Trave

VRV Indoor Units

• The body features a compact design with a height of just 200 mm and depth 470 mm, making the installation possible in Indoor unit
200 mm
255 mm
tight ceiling spaces. 80 mm
840 mm 470 mm 255 mm

• The novel smooth panel design makes dust difficult to accumulate,


thus causing the cleaning more conveniently.

Comfort
• The swinging of horizontal and vertical swing flaps can be adjusted freely with the Specifications Btu/h
Heating capacity
remote controller, providing 3D airflow to every corner of the room. MODEL
Indoor Units
Power supply FXEQ20AV36 FXEQ25AV36 FXEQ32AV36 FXEQ40AV36 FXEQ50AV36 FXEQ63AV36 1-phase, 220-240 V, 50 Hz
• Control of airflow rate can be selected from 5-step control, Automatic and quiet Btu/h 7,500 9,600 12,300 15,400 19,100 24,200 2.2 2.8 3.6 4.5 5.6 7.1 8,500 10,900 13,600 17,100 21,500 27,300
operation mode, which provides comfortable airflow. Cooling capacity
kW
Front view Side view
kW 2.5 3.2 4.0 5.0 6.3 8.0
• DC motor is adopted both in the fan and drain pump of the indoor unit, not only Power Cooling Heating kW 0.034 0.046 0.048 0.067 0.030 0.042 0.044 0.063
consumption 0.026 0.027 0.022 0.023
enhancing the energy saving performance, Casing Galvanised steel plate

but also reducing the operating sound Vertical swing flaps, swinging to Horizontal swing flaps, swinging between Airflow rate m3/min /s 133/125/117/105/92 163/147/130/117/103 15.0/13.6/12.2/11.0/9.8 143/133/123/112/100
(H/HM/M/ML/L) 100/90/82/73/67 115/107/97/88/80 6.0/5.4/4.9/4.4/4.0 208/190/173/158/145 150/227/203/183/163 8.0/7.5/7.0/6.3/5.5 170/155/140/127/113 233/213/193/178/163
and the vibration incurred to the unit. Cooling /s
6.9/6.4/5.8/5.3/4.8 100/93/85/78/70 120/112/102/93/83 9.8/8.8/7.8/7.0/6.2 12.5/11.4/10.4/9.5/8.7 282/255/227/205/183

• While creating a cozy indoor environment, left or right within Heating 32/31/30/29/28 16.9/15.3/13.6/12.3/11.0 35/34/33/32/30 38/37/35/33/31

45° 20° to 70° m3/min 6.0/5.6/5.1/4.7/4.2 7.2/6.7/6.1/5.6/5.0 30/29/28/27/26


8.6/8.0/7.4/6.7/6.0 10.2/9.3/8.4/7.6/6.8 14.0/12.8/11.6/10.7/9.8 38/37/35/33/31 43/41/39/37/35

the unit can prevent the suspended ceiling Sound level


38/36/34/33/31 41/39/37/35/33 41/39/37/36/34 46/44/42/40/38 dB(A) Cooling
from being soiled by adjusting its louvre (H/HM/M/ML/L) Heating 33/31/29/28/26 35/33/31/30/28

angle. Dimensions (H×W×D) mm Machine weight kg 200×840×470 200×1,240×470 17 18 23

Piping Liquid (Flare) 6.4 9.5


Drain PVC26 (External Dia. 26/Internal Dia. 20)
Easy maintenance connections mm
Gas (Flare) Model
12.7
BYEP40AW1 BYEP63AW1
15.9

• Drain pump is equipped as standard accessory • Maintenance operations can be (Option) Fresh white 8.0 10.0
Colour 80×950×550 80×1,350×550 kg
with 850 mm lift. Panel
Dimensions(H×W×D) Weight mm
performed by
removing the front
panel.
Notes: Specifications are based on
the following conditions;
• Cooling: Indoor temp.: 27°CDB,
19°CWB, Outdoor temp.: 35°CDB,
Equivalent piping length: 7.5 m,
Height difference: 0 m. • Heating:
Indoor temp.: 20°CDB, Outdoor
temp.: 7°CDB, 6°CWB, Equivalent
piping length: 7.5 m, Height
differencee: 0 m. • Capacity of
indoor unit is only for reference.
Actual capacity of indoor unit is
based on the total capacity index. (See Engineering Data Book for details.) • Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward.

137 138

Slim Duct (Standard) Type FXDQ-PD / ND

Slim design, quietness and ideal for drop-ceilings

Comfort
• Control of the airflow rate can be selected from 3-step control
and Auto. Auto airflow rate control can be selected with wired remote controller.

• Low operation sound level: down to 23 dB(A)

Installation flexibility
• Only 200 mm in height, this model can be installed in rooms with as little as 240 mm in height for the ceiling space between the
drop-ceiling and ceiling slab.

Great for
hotel use!
VRV Indoor Units

Indoor Units

FXDQ20-32PD

200 mm 200 mm
FXDQ40/50ND
Specifications MODEL FXDQ20PDVE FXDQ25PDVE FXDQ32PDVE FXDQ40NDVE FXDQ50NDVE FXDQ63NDVE

1,100 mm in width for

Only 700 mm the FXDQ63ND model.


Power supply
Btu/h 7,500 9,600 Heatin
g
0.067

900 mm Cooling capacity


kW 2.2 2.8

Btu/h 8,500 10,900


Heating capacity Power consumption
Galvanised steel plate
kW 24,200 7.1
2.5 3.2
Casing
27,300 8.0
1-phase, 220-240 V/220 V, 50/60 Hz
Coolin kW 0.086 0.181 0.168
g

Sound level (HH/H/L)


• Drain pump is equipped as standard accessory with 750 mm lift. mm Sound power (HH/H/L)
/s Dimensions (H×W×D)
kg
Machine weight
m3/
min Liquid (Flare) Piping
275/241/216 16.5/14.5/13.0
Pa Gas (Flare) mm

33/31/29
13
dB(A) 61/59/57
200×1,100×620 31
dB(A) Airflow rate (HH/H/L) 9.5
External static pressure 15.9
connections Notes: Specifications are based on the following conditions;
Drain
VP20 (External Dia. 26/Internal Dia. 20)

• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
• Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
*1: Values are based on the following conditions: FXDQ-PD: external static pressure of 10 Pa; FXDQ-ND: external static pressure of 15 Pa.
*2: External static pressure is changeable to set by the remote controller. This pressure means "High static pressure - Standard". (Factory setting is
10 Pa for FXDQ-PD models and 15 Pa for FXDQ-ND models.)
*3: The values of operation sound level represent those for rear-suction operation. Sound level values for bottom-suction operation can be obtained by adding 5 dB(A).

139 140

Easy maintenance
Slim Duct (Compact)
Auto clean air filter module (Option)
VRV Indoor Units
Type FXDQ-T

Slim and compact design for easy and flexible installation

• A unique rear suction mounted motorised filter cleaning module with included polyester
Energy saving filter for convenient filter maintenance to ensure optimal performance and increased
energy savings.
• Adoption of a DC motor for both the fan motor and the drain pump has greatly reduced
power consumption.
)
Power consumption (W 70 Model Compatibility HxWxD (mm) BAE20A62 20-32 Class 210x840x188 BAE20A82 40-50 Class 210x1,040x188
100 BAE20A102 63 Class 210x1,240x188

75 50 25 0 75 32 Cooling Mounts to the rear of the indoor unit with the vacuum port Dust in the dust box can be emptied by vacuuming out the
dust via the vacuum port
Heating
30
2537 45 50 Cleaning unit moves across the filter removing dust which is
collected in the dust box

20
Comfort Design flexibility Two series available
25/32 40 50/63 Model class

5-step & auto airflow control • Control of airflow rate can be selected from 5-step and Auto to provide comfortable airflow. 3-D auto
swing discharge grille (Option) Indoor Units
FXDQ-TV1CA – Features Built-in Multi Tenancy Kit
• Motorised louvres provide 3-D airflow Multi Tenancy Kit allows an independent 24V power source to be supplied to the indoor unit PCB
distribution. in conjunction with 1 phase power from the tenants board. This ensures critical operations, such as
Operations via BRC1E63 with functions oil return are not affected should there be an interruption to the main indoor unit power.
including
FXDQ-TV1C – Standard Model Specifications
Horizontal louvers
3-D Swing, Horizontal Auto Swing, Vertical Auto with 0° to 60° 180x722x70 BDG20A15 40-50 Class 180x922x70 Btu/h FXDQ40TV1C(A) FXDQ50TV1C(A) FXDQ63TV1C(A) 1-phase,
variability

Auto Swing & Fixed Positioning. kW 220-240/220-230 V, 50/60 Hz


Vertical louvers
with -45° to 45° Power supply Cooling capacity Btu/h 7,500 9,600 12,300 15,400 19,100 24,200 2.2 2.8 3.6 4.5 5.6
Model Compatibility HxWxD (mm) BDG20A09 20-32 Class FXDQ20TV1C(A) FXDQ25TV1C(A) FXDQ32TV1C(A) 7.1 8,500 10,900 13,600 17,100 21,500 27,300
MODEL
variability
2.5 3.2 4.0 5.0 6.3 8.0
BDG20A20 63 Class 180x1,122x70 kW Heating capacity
kW 0.050 0.075
Installation flexibility Power consumption *1
Cooling
0.030 0.037

Heating Casing
0.025 0.032 0.045 0.070 Galvanized steel plate

Airflow rate 135 150 210 250 325 /s

• Slim and compact design with a height of only 200 to 200 mm m3/min Pa 12.6
dB(A) 8.1
mm and the depth of only 450 mm which is suitable 9.0 15.0 19.5 40-10*2 50-10*2 60-10*2 45-10*2 33/30.5/28 34/31.5/29
External static pressure

install in limited spaces. Sound level (HH/H/L)*1 *3 Dimensions (H×W×D) Machine weight 18 21 24
32/30/28 35/32.5/30 37/35/33 mm
200×700×450 200×900×450 200×1,100×450 kg

450 mm
Only 700 mm*
*For FXDQ20-32TV1C(A) models Piping Liquid (Flare) Gas (Flare) Drain 6.4 PVC26 (External Dia. 26 / Internal Dia. 20)
• Features rear or bottom return to suite site constraints.
connections mm 12.7 9.5 15.9

Duct Air suction


point 1.5 m downward from the unit centre.
Air filter included Notes: Specifications are based on the following conditions; During actual operation, these values are normally somewhat higher as a result of ambient conditions.
Air
Air discharge •Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 5 m, Height *1: Values are based on external static pressure of 10 Pa. For FXDQ-TV1CA models, +0.0005kW on top of
discharge
Duct difference: 0 m. cooling/heating power consumption values. *2: External static pressure is changeable to set by the remote
•Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 5 m, Height controller. This pressure means “High static pressure - Standard”. (Factory setting is 10 Pa ) *3: The values of
Canvas bellows
and air suction
difference: 0 m. operation sound level represent those for rear-suction operation. Sound level values for bottom-suction
Air suction panel •Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. operation can be obtained by adding 5 dB(A).
(See Engineering Data Book for details.) •Sound level: Anechoic chamber conversion value, measured at a

Clip-on resin net filter attached to the rear of the unit as standard.

• Drain pump is equipped as standard accessory with 750 mm lift.

141 142

Installation flexibility
Middle Static Pressure Duct Type
FXSQ-PA Slim design
• With a height of only 245 mm,
Middle static pressure and slim design allow flexible installations installation is possible
VRV Indoor Units • Control of the airflow rate can be selected from 3-step control. Auto airflow rate control can be selected with wired remote controller.
• Lower sound level: down to 28 dB(A)
Separate drain pipe and inspection opening

Easy maintenance
Comfort • Inspection and cleaning is facilitated by separating the drain pipe
and inspection opening and by the drain pan maintenance check hole.
Drain pan maintenance check hole
even in buildings with narrow ceiling spaces.
Cleanliness
245 mm
Standard DC drain pump Joist Air conditioner Indoor Units
Specifications
• DC drain pump is equipped as standard accessory
Air suction MODEL FXSQ20PAVE FXSQ25PAVE FXSQ32PAVE FXSQ40PAVE FXSQ50PAVE
with 850 mm lift. ceiling

Silver ion anti-bacterial drain pan


Bottom suction possible
• Prevents the growth of slime, bacteria, and mould that cause odours and clogging.
• Bottom suction is possible which facilitates installation and maintenance. Wiring * Drain pan should be changed once every two to three years.
connections and maintenance of control box can be done from under the unit with an
optional shield plate for side plate. Filter has anti-mould and antibacterial treatment
Design flexibility Adjustable
external static pressure

Adjustable external static pressure 30Pa*


150Pa
Power supply Cooling capacity

Heating capacity

Power
consumption Casing
1-phase, 220-240 V/220 V, 50/60 Hz
Btu/h 7,500 9,600

kW 2.2 2.8

Btu/h 8,500 10,900

kW 2.5 3.2

Coolin kW 0.058*1
g

Heatin 0.053*1
g

Galvanised steel plate


19,100 5.6
21,500 6.3
0.075* 1 0.070* 1
• Using a DC fan motor, the external static m3/ 9/7.5/6.5 mm 245×550×800 Gas (Flare) mm
pressure can be controlled within a range of min

30 Pa* to 150 Pa.


Pa kg
* 30 Pa–150 Pa for FXSQ20-40PAVE 50 Pa–150 Pa for FXSQ50-125PAVE
50 Pa–140 Pa for FXSQ140PAVE Airflow rate (H/M/L)
dB(A) 33/30/28 Liquid
(Flare)
/s 150/125/108 External static pressure
dB(A) 61 Sound level (H/M/L)
283/242/192 17/14.5/11.5 50-150 (50) *2 34/32/29
Sound power (H) 62 Notes:
connections VP25 (External Dia. 32/Internal Dia. 25)
at field setting
Easy installation Dimensions (H×W×D)Machine 245×1,000×800
35
Drain
Specifications are based on the following conditions;
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height
weight difference: 0 m.
• Heating: Indoor temp.: 20°CDB, Outdoor
“Airflow rate auto adjustment function” Piping

Duct resistance at Power supply FXSQ140PAVE 1-phase, 220-240 V/220 V, 50/60 Hz


(local setting by remote controller) FXSQ63PAVE FXSQ80PAVE FXSQ100PAVE FXSQ125PAVE
MODEL temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m.

*This function can only be set via wired remote Various adjustments are Cooling capacity Heating capacity 54,600 16.0
required (Due to excess or kW 7.1 kW 8.0 Heatin 0.101*
deficiency of g 61,400
controller. Field setting • Capacity of indoor unit is only for reference.
Btu/h 24,200 Btu/h 27,300 Cooling kW 0.106* Actual capacity of indoor unit is based on the
Actual duct total capacity index. (See Engineering Data Book
rpm 1 rpm 2
resistance for details.) • Sound level: Anechoic chamber

External static pressure (ESP) designing system


Design
Installation
without “airflow rate auto adjustment
function”

Field setting
airflow) e.g. Duct re-construction, Motor
replacement, Damper
replacement, etc.

Innovating

rpm 7

System

Power
consumption Casing

Galvanised steel plate

Liquid
(Flare)

Gas (Flare)

18.0
0.222*1
0.217*1

650/558/467
conversion value, measured at a point 1.5
m downward from the unit centre. During
actual operation, these values are normally
somewhat higher as a
result of ambient conditions.

*1: Power consumption values are based


Installation auto adjustment function” by remote controller operation Airflow rate (H/M/L) External static pressureSound level (H/M/L) 39/33.5/28 50-140 (50) *2 43/40/36 on conditions of rated external static pressure.
Function! *2: External static pressure can be modified using a
with “airflow rate rpm 8 remote controller
Sound power (H) 71 that offers thirteen (FXSQ20-40PA),
<Mechanism> 2. External static pressure is estimated from power input of DC fan Rated airflow Dimensions (H×W×D)Machine weight eleven (FXSQ50-125PA) or ten (FXSQ140PA) levels of control. These
1. During field setting, power input of DC fan is detected. because PCB Airflow values indicate the lowest and highest
245×1,550×800 52
of FXSQ-PA has table of external static to produce rated airflow. Piping static pressure is 50 Pa.
pressure vs. power input of DC fan. 3. Actual Notes: ”Airflow rate auto adjustment function” can be adjusted within ±10% of rated airflow. (Refer to connections
duct resistance is calculated according to 1 Engineering Data Book for details) Drain
possible static pressures. The rated
VP25 (External Dia. 32/Internal Dia. 25)
and 2. 4. Fan speed is automatically adjusted ”Airflow rate auto adjustment function” should be used at field setting only.
143 144

Static Pressure Duct Type FXDYQ-MA

Middle static pressure allows for flexible duct design.


VRV Indoor Units

Middle Specifications

Power supply MODEL FXDYQ80MAV1 FXDYQ100MAV1 FXDYQ125MAV1 FXDYQ145MAV1 1-phase, 220-240 V, 50 Hz


Casing /s
Energy saving 30,000 38,200 47,400 54,600 8.8 11.2 13.9 16.0 33,800 42,700 54,600 62,800 9.9 12.5 16.0 18.4 0.415 0.700 0.780 0.880 0.415 0.700
0.780 0.880 Galvanised steel plate
510 778 852 957

• High efficiency Hi-X heat exchanger coils that provide even


more energy savings.
Cooling capacity Btu/h kW

Heating capacity Btu/h kW

Power consumption kW Cooling Heating


Airflow rate (H) 3 30.6
m /min 46.7 51.1 57.4
External static pressure Pa 120
1

Sound level (H) 240 V dB(A) Dimensions (H×W×D) mm 45 46 48 360×1478×899


360×1168×869 51

Machine weight kg 50 60 65 66

Piping Liquid (Flare) 9.5


Note: Specifications are based on the following conditions;
connections Gas (Flare) mm 15.9
Drain VP25 (External Dia. 32/Internal Dia. 25)

•Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m.
•Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m.
•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
•Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.

1: External static pressure is changeable to change over the connectors inside electrical box (High static pressure-Standard static pressure).
The data above is for high static pressure setting.

Indoor Units

Installaion flexibility
• High external static pressure of 120 Pa allows comprehensive duct layout for various applications.

• Two external static pressure settings for added flexibility.

• Return air spigots included for ease of installation.

• Quiet yet powerful supply air fan.

• High strength galvanised steel casing.


145 146

VRV Indoor Units


Middle-High Static Pressure
Duct Type Cleanliness
FXMQ-PA Silver ion anti-bacterial drain pan
Middle and high static pressure allows for flexible duct Prevents the growth of slime, bacteria, and mould that cause odours and clogging.
design *Drain pan should be changed once every two to three years.

Filter has anti-mould and antibacterial treatment

Design flexibility
Using a DC fan motor, the external static pressure can
be controlled within a range of 30 Pa* to 200 Pa*. Specifications

Adjustable external static pressure


*30 Pa – 100 Pa for FXMQ20PA-32PA

30Pa 200Pa * MODEL FXMQ20PAVE FXMQ25PAVE FXMQ32PAVE FXMQ40PAVE FXMQ50PAVE Power supply 1-phase, 220-240 V/220 V, 50/60 Hz

*30 Pa – 160 Pa for FXMQ40PA *50 Pa – 200 Pa for FXMQ50PA-125PA *50 Pa – 140 Pa for
FXMQ140PA kW 2.2 2.8 Coolin kW 0.056 *1
g 19,100 5.6
Cooling capacity Heating capacity
Btu/ 8,500 10,900 21,500 6.3
h Heatin 0.044 *1
g
Btu/ 7,500 9,600
h kW 2.5 3.2

“Airflow rate auto adjustment function” at field setting


Easy installation Power consumption0.128 *1 0.116 *1
Casing Galvanised steel plate

mm 300x550x700 300x700x700
/s 150/125/108 158/133/116 267/216/183
kg 25 27
m3/ 9/7.5/6.5 9.5/8/7 16/13/11
min
Liquid (Flare) 6.4
Pa 30-100 (50) * 2
30-160 (100) * 2

Gas (Flare) mm 12.7


dB( 33/31/29 34/32/30 39/37/35
A)

dB( 51 52 57
A) 300/275/250

rpm 1 designing system


(local setting by remote controller) *This function is not available with FXMQ140PAVE. Duct resistance at
Airflow rate (HH/H/L)
18/16.5/15 Indoor Units
Actual duct External static pressure 50-200 (100) *2
*This function can only be set via wired remote controller. rpm 2 resistance Sound level (HH/H/L) 41/39/37
External static pressure (ESP)

Various adjustments are required Sound power (H) 59

Design Design Installation Installation Field setting Field setting replacement, etc. rpm 7 System operation Piping VP25 (External Dia. 32/Internal Dia. 25)
without “airflow rate auto adjustment function” with “airflow rate connections
rpm 8 Drain
300x1,000x700 35
auto adjustment function”
(Due to excess or deficiency of Innovating Dimensions (H×W×D)Machine weight
airflow) e.g. Duct re-construction, Motor replacement, Function!
Damper

by remote controller Rated airflow Power supply 1-phase, 220-240 V/220 V, 50/60 Hz
MODEL FXMQ63PAVE FXMQ80PAVE FXMQ100PAVE FXMQ125PAVE FXMQ140PAVE Airflow
<Mechanism>
1. During field setting, power input of DC fan is detected. ”Airflow rate auto adjustment function” should be used at field setting only. 61,400 18.0
2. External static pressure is estimated from power input of DC fan because PCB of kW 8.0 10.0
FXMQ-PA has table of external static pressure vs. power input of DC fan. 3. Actual duct Cooling capacity Heating capacity
resistance is calculated according to 1 and 2.
4. Fan speed is automatically adjusted to produce rated airflow. Coolin kW 0.138 *1 0.185 *1
g
Notes: ”Airflow rate auto adjustment function” can be adjusted within ±10% of rated Btu/ 24,200 30,700
airflow. (Refer to Engineering Data Book for details) h Heatin 0.127 *1 0.173 *1
g
kW 7.1 9.0

Btu/ 27,300 34,100


h
54,600 16.0
• All models are only 300 mm in height and the weight of the FXMQ40-140PA has
been reduced. • Drain pump is equipped as standard accessory with 700 mm lift.
Power consumption Casing

0.405 *1
0.380 *1
Galvanised steel plate

Comfort
• Control of the airflow rate can be selected from 3-step control and Auto. Auto airflow
rate control can
/s 32.5/292/267

m3/ 19.5/17.5/16
min

Pa

dB( 42/40/38
A)

dB( 60
A)

mm

kg

Liquid (Flare)

Gas (Flare) mm

Airflow rate (HH/H/L)

External static pressure


Sound level (HH/H/L)
767/649/533 46/39/32
50-140 (100) *2 46/45/43
be selected with wired remote controller. Sound power (H) 64 Dimensions (H×W×D)

Separate drain pipe and inspection opening Notes: Specifications are based on the following conditions;
• Low operation sound level: down to 29 dB(A)
Energy saving Machine weight 46

• DC fan motor is used to realise energy-saving operation. Piping


connections
Drain VP25 (External Dia. 32/Internal Dia. 25)

• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)

Easy maintenance • Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual operation,
these values are normally somewhat higher as a result of ambient conditions.
*1: Power consumption values are based on conditions of rated external static pressure.
Inspection and cleaning is facilitated by separating the drain pipe and inspection opening and by the drain pan maintenance check *2: External static pressure can be modified using a remote controller that offers seven (FXMQ20-32PA), thirteen (FXMQ40PA), fourteen (FXMQ50-125PA) or
ten (FXMQ140PA) levels of control.
hole. These values indicate the lowest and highest possible static pressures. The rated static pressure is 50 Pa for FXMQ20-32PA and 100 Pa for FXMQ40-140PA.
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m. Drain pan maintenance
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m. check hole
147 148
High static pressure allows for flexible duct design.

High Static Pressure Duct


Design flexibility
Type FXMQ-P
VRV Indoor Units

• Using a DC fan motor, the external static pressure can be controlled within a range of 50 Pa* to 250 Pa*.
Easy installation
Adjustable external static pressure 50Pa 250Pa
*60 Pa – 217 Pa for FXMQ160P *50 Pa – 210 Pa for FXMQ180P *50 Pa – 250 Pa for FXMQ200P-250P

rpm 2
“Airflow rate auto adjustment function” at field setting External static pressure (ESP)
(local setting by remote controller) Duct resistance at
designing system
Actual duct
resistance

rpm 1 Indoor Units


*This function can only be set via wired remote controller.

Design Various adjustments are required (Due to excess rpm 7 System MODEL FXMQ160PV1A FXMQ180PV1A FXMQ200PV1A FXMQ250PV1A
Installation or deficiency of airflow) e.g. Duct re-construction,
Field setting Motor replacement, Damper replacement, etc.
without “airflow rate auto adjustment function”
Specifications
Innovating operation
Power supply 1-phase, 220-240 V, 50 Hz
Field setting 61,400 68,200 76,400 95,500
Cooling capacity Btu/h
rpm 8
Design with “airflow rate Function! kW 18.0 20.0 22.4 28.0
Installation
auto adjustment function” by remote controller 68,200 76,400 85,300 107,500

Heating capacity Btu/h


kW 20.0 22.4 25.0 31.5
<Mechanism> Rated airflow Airflow 0.650 0.640 0.810
Power consumption kW Cooling
0.650 0.810 1
1. During field setting, power input of DC fan is detected. Heating of FXMQ-P has table of external static pressure vs. power input of DC fan. 3. Actual duct resistance is Airflow rate (HH/H/L)
2. External static pressure is estimated from power input of DC fan because PCB calculated according to 1 and 2. 4. Fan speed is automatically adjusted to produce rated airflow. m /min 3

Casing 1,120/955/790 1,160/995/820 1,200/1,025/850 1,400/1,200/1,000 67.2/57.3/47.4 69.6/59.7/49.2


”Airflow rate auto adjustment function” should be used at field setting only.
Notes: ”Airflow rate auto adjustment function” can be adjusted within ±10% of rated airflow. (Refer to 0.640
Engineering Data Book for details)
72.0/61.5/51.0 84.0/72.0/60.0
Galvanized steel plate /s
External static pressure Pa 60-217 (138) 50-210 (130) 50-250 (150) 2
Sound level (HH/H/L) dB(A) 45/41.5/38 44/40.5/37 46/42.5/39
• Drain pump kit is available as optional accessory with 750 mm lift. Sound power (H) dB(A) 73 72 74
Dimensions (H×W×D) mm Machine weight kg 470x1,133x919 470x1,333x919 70 79 85

Heat exchanger section Piping Liquid 9.5 (Brazing)


• Each model can be separated into 2 sections for
9.5 (Flare)

Fan deck section 15.9 (Flare) 19.1 (Brazing) 22.2 (Brazing) BSP 3/4 internal thread (OD 32.7)
convenient handling connections Gas mm Drain
through openings in the ceiling. Notes: Specifications are based on the following conditions;
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
• Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
Separated into 2 sections
*1: Power consumption values are based on conditions of rated external static pressure.
*2: These values indicate the lowest and highest possible static pressures. The rated static pressure is 138 Pa for FXMQ160P, 130 Pa for FXMQ180P and 150 Pa for FXMQ200-250P.
149 150

Slim and stylish design, optimum Specifications Specifications Power supply

4-way air distribution,


installation without ceiling cavity
VRV Indoor Units

Flow Slim and stylish


design
Ceiling • Unit body and suction panel have
round shapes that form a slim
design, that fits various locations
such as the ceilings without cavity.
• Flaps close automatically when the
unit stops, which gives a simple
appearance.
• All models have a unified slim
height of 198 mm that gives a
similar impression even when
models with different capacities are
installed in the same area.

Comfort
Suspended Type FXUQ-A • Airflow direction adjustment can be individually adjusted for each air discharge outlet to
deliver
MODEL FXUQ71AVEB FXUQ100AVEB 1-phase, 220-240 V/220-230 V, 50/60 Hz

optimal air distribution. 5 directions of airflow and Cooling capacity Heating capacity
kW 8.0 Coolin kW 0.090
auto-swing can be selected with BRC1E63 or g Fresh white
Power consumption Casing 38,200 11.2
BRC1H63W(K). Btu/h 30,700
Heatin 0.073
g 42,700 12.5
• Control of the airflow rate can be selected from 3- Btu/h 27,300 kW 9.0 0.200 0.179
step control. Auto airflow rate control can be
Indoor Units
selected with wired remote controller.

Flexible installation dB(A) 40/38/36 Gas (Flare) mm

dB(A) 58/56/54
/s 375/325/267

mm Airflow rate (H/M/L)

m3/min kg 26 Sound level (H/M/L)


22.5/19.5/16
517/433/350 31/26/21
Liquid (Flare) 47/44/40

• Drain pump is equipped as a standard accessory with 600 mm lift. Sound power (H/M/L) 65/62/58

• Depending on installation site requirements or room conditions, 4-way flow 3-way flow L-shaped 2-way flow Piping
connections
9.5

2-way, 3-way and 4-way discharge patterns are available. Dimensions (H×W×D) Drain 15.9
Machine weight Notes: VP20 (External Dia. 26/Internal Dia. 20)
Specifications are based on the following conditions; 27
198×950×950

Cleanliness
Silver ion anti-bacterial drain pan
• Prevents the growth of slime, bacteria, and mould that cause odours and clogging. * Drain pan should be
changed once every two to three years.

Filter has anti-mould and antibacterial treatment


• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.) • Sound level: Anechoic chamber conversion
value, measured at a point 1 m in front of the unit and 1 m downward. During actual operation, these values are normally somewhat higher as a result of ambient conditions
151 152
FXHQ50 / 80MA

Ceiling Suspended Type


VRV Indoor Units

FXHQ-MA / B

Slim body with quiet and wide airflow

Comfort FXHQ32 / 63 / 100MA FXHQ125 / 140B

• Specifications MODEL
Installation flexibility
30 mm

Auto swing (up and down) and louvers (left and right by hand) bring comfort to the room.
• Louver manually adjusts for straight or wide angle airflow.

FXHQ32MAVE FXHQ50MAVE FXHQ63MAVE FXHQ80MAVE FXHQ100MAVE FXHQ125BVM FXHQ140BVM

• Flexible installation or more 30 mm or more Power supply 1-phase, 220-240 V/220 V, 50/60 Hz 1-phase, 220-240 V/220-230 V, 50/60 Hz

*Water used in the test-run can be drained 600 mm


The unit fits more snugly • Drain pump kit (option) connection can be done from the air discharge opening rather than
12,300 3.6 21,500 6.3 30,700 9.0 42,700 12.5 52,900 15.5
24,200 7.1 48,000 14.1
into tight spaces. can be easily inside the unit. from the side as was formerly the case. Cooling capacityBtu/h kW 13,600 4.0 34,100 10.0 58,000 17.0
incorporated. Drain pipe 19,100 5.6 27,300 8.0 38,200 11.2 54,600 16.0
Heating capacityBtu/h kW
Power kW 0.100 0.115 0.126 0.135 0.168 0.181
Refrigerant and drain pipe outlets are at the same opening. Cooling 0.111
Drain pump kit Heating 0.100 0.135 Sheet Metal / White (10Y9/0.5) Sheet Metal / White
• All wiring and internal servicing can be done from under the unit. consumption Casing Indoor Units
0.111 0.115 0.126 0.168 0.181
3
(built inside the unit) Airflow rate (H/M/L) Sound level (H/M/L) m /min dB(A) 36/-/31 37/-/32 416/-/325 25/-/19.5 45/-/37 46/41/37 48/42/37
New 125 / 140 greater capacity for 250/-/200 15/-/12 291/-/233 17.5/-/14 39/-/34 600/450/333 36/27/20
200/-/166 12/-/10 567/433/333 34/26/20
models provide large spaces /s 392/-/283 23.5/-/17 43/-/35

• The technology of the DC fan motor, exchanger combine for greater Dimensions (H × W × D) Machine weight mm kg 6.4 195×1,400×680 33 235×1,590×690 41
Liquid (Flare) 195×960×680 24 195×1,160×680 28
wide sirocco fan, and large heat airflow and quiet operation. 9.5

connections mm 15.9 VP20 (External Dia. 26/Internal Dia. 20)


• Sophisticated design: Flap neatly closes when not in use. 12.7
Piping Gas (Flange) Drain

• Suitable for high ceilings: maximum 4.3 m


• Control of the airflow rate can be selected from 3-step control.
Cleanliness Notes: Specifications are based on the following conditions;
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB,
• Drain pump kit (option) includes a silver ion antibacterial agent that assists in preventing the growth of slime, bacteria, and 6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See
Engineering Data Book for details.) • Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward.
mould that cause smells and clogging. During actual operation, these values are normally somewhat higher as a result of ambient conditions.

• The rear side removable frame allows ease of access for piping work.
Easier piping work

Streamer filter clean unit (Option) for new 125 / 140 models See page 5-6
Daikin Streamer technology enhances maximum efficiency in cleaning, which uses
powerful decomposition properties to decompose substances captured by
the filter for better air quality.
Remarks:
1) Only the stylish remote controller BRC1H63W(K) can be connected for ON/OFF operation of the streamer.
2) The Streamer function operates only when the fan and air conditioning operation are stopped. The maximum operation of
Streamer is 180 minutes per day.

BAPW55A61

153 154
Gas pipe
• An invisible air intake at the top of the unit External EV kit (for heating operation) (Option)
Wall Mounted This product, which is concealed in ceilings or corridors for quieter
heating operation, is used to connect indoor units in places where 5 m - 10 m
Liquid pipe

quiet environment is required such as residential


VRV Indoor Units
Type
living rooms.
FXAQ-A

Stylish flat panel design harmonised


with your interior décor * This option is only effective for reducing operation sound
during heating operation. Therefore it is ineffective when
connected to cooling only outdoor units.

Comfort
Higher airflow
Max 4 m

An invisible air intake at the top of the unit Specifications

BEV15/30D
External EV kit(for heating operation)

Power supply 1-phase, 220-240 V/220-230 V, 50/60 Hz


• Vertical auto-swing enables efficient air and temperature distribution throughout the MODEL FXAQ25AVM FXAQ32AVM FXAQ40AVM FXAQ50AVM FXAQ63AVM
room. • The louver closes automatically when the unit stops. FXAQ20AVM

• Enhanced comfort is achieved. Cooling capacityBtu/h kW9,600 2.8 12,300 3.6 15,400 4.5 19,100 5.6 24,200 7.1
Indoor Units
7,500 2.2
• 5 step discharge angles can be set by remote controller. Heating capacityBtu/h kW
8,500 10,900 13,600 17,100 21,500 27,300 2.5 3.2 4.0 5.0 6.3 8.0
Cooling
• Discharge angle is automatically set at the Power
same angle as previous operation when kW
0.040 0.040 0.040 0.050 0.060 0.100
restart.
consumption Heating 0.040 0.040 0.050 0.050 0.070 0.110
Casing Resin / White N9.5

Airflow rate (H/L) /s 151/116 156/116 163/116 203/161 250/200 316/233


m3/min 9.1/7.0 9.4/7.0 9.8/7.0 12.2/9.7 15.0/12.0 19.0/14.0
Lower sound level
Sound level Cooling 33.0/28.5 35.0/28.5 37.5/28.5 37.0/33.5 41.0/35.5 46.5/38.5 dB(A)
(H/L)
34.0/28.5
38.0/33.5
42.0/35.5
47.0/38.5
36.0/28.5
38.5/28.5
• Whisper quiet in operation, with sound levels as low as 28.5 dB(A)*
Heating

*Sound level for FXAQ20-32A Machine weight Liquid (Flare) 12


spaces, including individual office spaces. mm kg
Dimensions (H × W × D)
• An ideal solution for a wide range of commercial 290×795×266
6.4 290×1,050×269 15 9.5
Piping Gas (Flange) Drain mm VP13 (External Dia. 18/Internal Dia. 15) 15.9
connections
12.7

be easily removed and washed for more thorough cleaning.


Stylish design and cleanliness • Drain pan and air filter can be kept clean by mould-proof polystyrene.
Notes: Specifications are based on the following conditions;
• Stylish flat panel design creates a graceful harmony that enhances any interior space. • Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB,
6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See
Engineering Data Book for details.) • Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward.
• Flat panel can be cleaned with only the single pass of a cloth across their smooth surface. Flat panel can also During actual operation, these values are normally somewhat higher as a result of ambient conditions.

• Drain pump kit is available as optional accessory, which lifts the drain 1,000 mm from 1,000
Flexible installation the bottom of the unit. mm
Height of drain-up
• Drain pipe can be fitted to from either left or right sides.
Drain pump kit
Indoor unit

155 156
Designed to be concealed in the perimeter skirting-wall

Floor Standing Standing Type FXNQ-MA

Type FXLQ-MA

Suitable for perimeter zone air conditioning VRV Indoor Units

Concealed Floor
• Floor Standing types can be hung on the wall for easier cleaning. Running the piping from the back allows the unit to be port faces downward, greatly facilitating on-site piping work.
hung on walls. Cleaning under the unit, where dust tends to accumulate, is considerably easier.
• A long-life filter (maintenance free up to one year*) is equipped as standard accessory. *8 hr/day, 25 day/month. For
• The adoption of a fibre-less discharge grille featuring an original design to prevent condensation also helps prevent dust concentration of 0.15 mg/m3
staining and makes cleaning easier.

• A long-life filter (maintenance free up to one year*) is equipped as standard accessory. *8 hr/day, 25 day/month. For
dust concentration of 0.15 mg/m3

Specifications
Specifications
• The unit is concealed in skirting-wall of perimeter, that enables to create high class interior design. • The connecting
MODEL Heating capacity Heating capacity
FXLQ20MAVEFXLQ25MAVE Btu/h 8,500 Btu/h 8,500 10,900
FXLQ32MAVE Power
0.110 Power
0.110
FXLQ40MAVE consumption Casing kW 2.5 0.110 consumption Casing kW 2.5 0.110
3.2
FXLQ50MAVE Ivory white (5Y7.5/1) Galvanised steel plate
1-phase, 220-240 V/220 V, 50/60 Hz 1-phase, 220-240 V/220 V, 50/60 Hz
FXLQ63MAVE Cooling kW Cooling kW 0.049
MODEL FXNQ20MAVE FXNQ25MAVE Btu/h 7,500 Btu/h 7,500 9,600
FXNQ32MAVE FXNQ40MAVE FXNQ50MAVE 24,200 7.1 24,200 7.1
FXNQ63MAVE Heating 27,300 8.0 Heating 0.049 27,300 8.0
kW 2.2 kW 2.2 2.8
Power supply Cooling capacity Power supply Cooling capacity
Indoor Units

Airflow rate (H/L) Sound level (H/L) 240 V m3/min dB(A) 116/100 7/6 37/34 133/100 8/6 183/141 11/8.5 40/35 233/183 14/11 41/36 266/200 16/12 42/37 Airflow rate (H/L) Sound level (H/L) 240 V m3/min dB(A)
/s /s
116/100 7/6 37/34 133/100 8/6 183/141 11/8.5 40/35 233/183 14/11 41/36 266/200 16/12 42/37
Dimensions (H × W × D) Machine weight Liquid (Flare) 600×1,000×222 25 6.4 9.5 Liquid (Flare) 610×930×220 19.0 610×1,070×220 23.0 6.4 9.5
mm kg 600×1,420×222 36 Dimensions (H × W × D) Machine weight mm kg 610×1,350×220 27.0
600×1,140×222 30
Piping Gas (Flare) mm Drain 12.7 21O.D. Piping Gas (Flare) mm Drain 12.7 21O.D.
connections connections
15.9 15.9

Notes: Specifications are based on the following conditions; Notes: Specifications are based on the following conditions;
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, • Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB,
6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See 6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See
Engineering Data Book for details.) • Sound level: Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m. Engineering Data Book for details.) • Sound level: Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions. During actual operation, these values are normally somewhat higher as a result of ambient conditions.

157 158