aa oes FIRE RESISTANCE TE On Lloydroc Rockwool Panel AS PER BS 476:P20 & 22 : 1987 & ASTM E 119 Ref. No.: IETL/PU-81/22-23 Date: 28.03.2023 Test Report No.: A2304130002-0001 Samples ID: L2/ A2304130002-0001 Date of report Issue: 18.05.2023 ULR No.: TC834223000000679F Study conducted for LLOYD INSULATIONS (INDIA) LIMITED Plot No. 2, Punj Sons Premises, Kalkaji Industrial Area, Kalkaji , New Delhi-110019 Works: ISOLLOYD ENGINEERING TECHNOLOGIES LIMITED Village: Kishanpura, Post office: Gurumajra, Baddi Nalagarh road, Tehsil : Nalagarh, Distt. Solan (H.P.) - 174101 24 lndusral Aen, Sahibabad, Ghasabad UtarPradeh- 201005 Lot , Ghariabad, UttarPradesh-201007

SPTX ES Katdress: L-S1/134 Industrial Aroa, Sabibabad, Ghaziabad, UtiarPradesh-201005 7 £2-13A/08, Site, Industrial Area, Loni Road, Mohan Nagar, Ghaziabad, UttarPradesh-201007 aki@ajeo.co.in , www.ajeo.co.in, Contact No.: +918010296901 Page 2 of 16 Sample Id: A2304130002-0001 i - A JE O Testing Lab And Consuitancy LLP (An ISO Certified Laboratory) FiNo, ATLETCH00 SCOPE OF JOB: Performing Integrity & Insulation test on the sample of Lloydroc Rockwool Panel 50 mm thickness as Per BS 476 part 20 & 22 : 1987 & ASTM E 119. A. PRODUCT DETAILS: Lloydroc Rockwool Panel along with frame & necessary hardware. Schedule of Components a S.No. [Item Description 1, Infill Material Rockwool Slab Water Repellent - _ Density ; 100 + 10 Kg/m? 2. Colour Coated sheet 0.50 mm TCT Ze Lloydroc Rockwool Panel 50 mm thick 4. [L- Angle 75X75X1.5 mm Thick Cold Rolled Steel VR ‘Address: L1-S1/1/34 Industrial Area, Sahibabad, Ghaziabad, UttarPradesh-201005 Nob Ghaziabad, UttarPradesh-201007 0.: +918010296901 Page 3 of 16 ‘Sample Id: A2304130002-0001 A J E 0 Testing Lab And Consultancy LLP (An ISO Certified Laboratory) No, ATLOTCIOO LHS FIXED END R.H.S_ FIXED END abad, UttarPradesh—201005 12-13A/08, Site-I, Industrial Area, Loni Road, Mohan Nagar, Ghaziabad, UstarPradesh-201007 ‘akilajeo.c.in , wwvw.ajeo.co.in, Contact No. +918010296901 Page 4 of 16 ‘Sample 1d: A2304130002-0001 7°. A J EO resting Lab And Consultancy LLP (An ISO Certified Laboratory) FiNo, ATLEITCI00 __INFILL_ MATERIAL—ROCKWOOL SLAB. sO eMeEG) COLOR COATED F—neNSiry.—10010 Kg/M"3 FIRE SIDE —1000— ~ 1022 ——_—_——| ee COLOR COATED NON-FIRE SIDE PIES ‘Address: L1-SU/L/34 Industral Area, Sahibabad, Ghaziabad, UtarPradesh-201005 ~*~ 12-13A/08, Site, Industrial Area, Loni Road, Mohan Nagar, Ghaziabad, UttarPradesh-201007 aki@ajeo.co.in , ww.sieo.co.in, Contaet No. +918010296001 Page 5 of 16 ‘Sample Id: A2304130002-0001 i re A J E O Testing Lab And Consuttancy LLP (An ISO Certified Laboratory) Ne. ATLOTCIOO issu cs Bye 28k Sa Ce ‘STEEL, RESTRAINT. \ esate tw, FIRE SIDE SSS ROLES Biel 75x75a4 eu - Res sects Be tay Gta ROLES Sie LoypRoc ROCKWOOL PANEL: NON-FIRE SIDE SECTION-A-A cs SB7AP EEN SxS Cre \ ZexzSaou THK, FIRE SIDE Ma are pee af STEEL, RESTRAINT. FRAME BaNeL. NON-FIRE SIDE SECTION-B-B Caress: L1-S1/1/34 Industrial Arca, Sahibabad, Ghaziabad, UttarPradesh-201008 12-13A08, Site-, Industrial Area, Loni Road, Mohan Nagar, Ghaziabad, UttarPradesh-201007 , WwWH.ajen.coin, Contact No.! +91 8010296901 Page 6 of 16 ‘Sample Id: A2304130002-0001 A J E 0 Testing Lab And Consultancy LLP (An ISO Certified Laboratory) No, ATLC/TCIOO __Lb@xpRoc Rockwoot, NON-—FIRE SIDE | FIRE SIDE SECTION-C-C (TOP END) NON-FIRE SIDE = FIRE SIDE LugYpROC RockwooL 12—14425MM f ie SO/sT SCREW ‘esd6um “SE | | | es Bb Be 4 zee pe \ zargh NRO rons GTS °ROMES STEEL STEEL RESTRAINT EST RONES STEEL Tk SECTION-D-D (BOTTOM FLOOR END) a a ‘Adldress: L1-S1/1/34 Industrial Area, Sahibabad, Ghaziabad, onetotns me OES 12-13A/08, Site, Industrial Area, Loni Road, Mohan Nagar, Ghaziabad, UttarPradesh-201007 ‘aki@aeo.co.in , www.ajo.co.in, Contact No.: +918010296901 Page 7 of 16 ‘Sample Id: A2304130002-0001 V7 A J EO ‘esting Lab And Consultancy LLP djed (An 180 Certified Laboratory) FN ATLCTCINO Identification: Lloydroc Rockwool Panel and other accessories received as per drawing. Date of Sample received: 13.04.2023 Date of Start: 15.04.2023 Date of Completion: 21.04.2023 B. TEST METHOD & : Evaluation of Fire Resistance Test on Lloydroc Rockwool Panel of size 3M x 1M. x 50 mm thickness for two Panels. Mounted over AAC Block wall on Trolley of Size 3m x 3m for 120 minutes rating as Per BS 476 part 20 & 22: 1987 & ASTME 119. C.CRITERIA OF ACCEPTANCE: As per BS: 476 part 20& 22 : 1987 & ASTM E119. 1: Integrit a) During the test, the 6 mm gap gauge provisions apply to gap (The 6 mm diameter gap gauge shall penetrate a through gap such that the end of the gauge projects into the furnace and the gauge be moved in the gap for a distance of at least 150mm). (OR) b) During the test, the 25 mm gap gauge provisions apply to any gap (The 25 mm diameter gap gauge shall penetrate a through gap such that the end of the gauge projects into the furnace) “Address: L1-S1/1/34 Industral Area, Sahibabatl, Ghaziabad, UttarPradesh-20100S f 12-13A/08, Site-, Industral Area, Loni Road, Mohan Nagar, Ghaziabad, UttarPradesh-201007 ‘aki@ajeo.co.in , www.ajeo.co.in, Contact No.: +918010296901 Page 8 of 16 Sample Id: A2304130002-0001 A J E 0 Testing Lab And Consultancy LLP gjeo (An ISO Certified Laboratory) No. ATLOTC/00 3. Insulation: Failure shall be deemed to have occurred when one of the following occurs: a. If the mean unexposed face temperature increases by more than 140°C above its initial value. b. If the temperature recorded at any position on the unexposed face is in excess of 180°C above the initial mean unexposed face temperature. c. When integrity failure occur. D. TEST SUMMARY: 1. Furnace Details: a. The Fire Resistance Test was carried out as per BS 476 part 20 &22: 1987 & ASTME 119. b. Source of fuel used is PNG gas. c. Size of Furnace used for performing test is 3.0 x 3.0 x 1.25 m, with 06 nos. of burners attached as 03 nos. at left and 03 nos. at the right side wall of the furnace. d. 09 nos. of Thermocouples made of Chromel- Alumel were mountedon there are side of the furnace wall at the locations specified below. Length of thermocouple was kept 155 mm away from the face of the wall. e. The temperature of the furnace was controlled to vary with time as closely as possible in accordance: oY piss: res L1-SU//34 Industral Ave, Saibaba, Ghaziabad, UttarPradesh soe > 134,08, Site, Industrial Area, Loni Road, Mohan Nagar, Ghaziabad, UtarPradesh-201007 ‘aki@ajeo,co.in , www.aj¢o.co.in, Contact No.: +918010296901 Page 9 of 16 fF. Sample Id: A2304130002-0001 A J E 0 Testing Lab And Consultancy LLP (An ISO Certified Laboratory) Ne, ATLOTCIOD Required Temperature as per BS 476 (P-20) & (P-22) & ASTM E 119. ‘200 5 1000 SS = SESS] 800 |___ Ss 600 —, — — =t — == —— 400 == — 200 = a — —- 0 E E i 0 20 40 60 80 100 120 140, Time, Minutes Graph-1 Time, Minutes | Required Temperature,°C | Time, Minutes Required ‘Temperature, °C 5 376 65 957 10 678 70 968 15 739 75 20 781 80 25 815 85 30 842 90. 35 865 95 40 885 700 45 902 105 [50 918 110 55 932 115 60 945 120 By é \atho' y v dress: L1-S1/1/34 Industrial Area, Sahibabad, Ghaziabad, UttarPradesh-201005, 13408 Ste Indra Are, Lol Road Mobas Nap ‘yoaercnn, Contact Noa *918010290501 Page 10 of 16 Ghaziabad, UttarPradesh-201007 ‘Sample Id: A2304130002-0001 A as E 0 Testing Lab And Consultancy LLP djeo (an 180 Ceti atom) ea Required Temperature Table for Furnace as per IS3614 & IS/ISO 3008 (Part-1) Table 1 Acceptable Variation corresponding to required value Permissible maximum and minimum variations: I. For 0 - 10 minute of test +15% IL. For 10 - 30 minute of test +10% IN. Above 30 minute of test + 5% ‘Temperature Requirement with Acceptable Variation corresponding to required value 1200 1000 800 600 Temp. 400 200 0 20 40 60 80 100 120 140 Time Minutes Graph-2 2. Wall Details: a. Specimen mounted over a wall constructed with AAC block of size 150 x 200 x600 mm surrounding the doors. b. Wall was constructed over a boggie with proper alignment. ited on unexposedisideaf the Key | yliress: L1-S1/1/34 Industrial Area, Sahibabad, Ghaziabad, UttarPradesh-201005 yz) 1A/08, Site Il, Industrial Area, Loni Road, Mohan Nagar, Ghaziabad, UttarPradesh-201003——~ ‘akiaajeo.co.in , www.ajeo.co.in, Contact No. +918010296901 Page 11 of 16 ‘Sample Td: A2304130002-0001 A J E 0 Testing Lab And Consultancy LLP aje0 (An 150 Certied Laboratory) ie Arisrone E.RESULTS AND DISCUSSIONS: 1. Results of insulation test a. Results of Exposed Surface: EXPOSED SURFACE TEMPERATURE GRAPH Lower Limit Requiced Temperature The below figure compares the requirements of the standard Vs achieved temperature Plot. The achieved value is well within the permissible limit. Graph-3 b. Results of Unexposed Surface: The below figure gives the plot of temperature of Ten thermocouples on Lloydroc Rockwool Panel mounted on the Un-exposed side for 125 minutes. ‘ahi@iajeo.co.in www.ajeo.co.in, Contact No. +918010296901 Page 12 of 16 Sample Id: A2304130002-0001 A J E 0 Testing Lab And Consultancy LLP ajeo (An ISO Certified Laboratory) No, ATLEMTC/O0 ‘TEMPERATURE GRAPH - UNEXPOSED SURFACE Graph-4 As per the observation graph , average temperature after 125 minutes of test was 154.6°C which is below the permissible limit of (29.9 +140 = 169.9°C). Hence Lloydroc Rockwool panel meets the insulation criteria for the entire test duration of 125 minutes. 2. Results of Integrity Test: Lloydroc Rockwool Panel was well stable after 125 minutes; No flame observed till 125 minutes of test and no deformation of Lloydroc Rockwool panel has taken place during the test cycle of 125 minutes. Hence the Lloydroc Rockwool panel is considered to hold integrity for the 125 mi ves ‘Address: L1-51/1/34 Industrial Area, Sahibabad, Ghaziabad, UttarPradesh—201008 | 2007 1L2-13A/08, Site-II, Industrial Area, Loni Road, Mohan Nagar, Ghaziabad, UttarPrades! ‘aKid’a}eo.co.in , WwW.2}e0,c0.1n, Contact No.: +9180 10296901 Page 13 of 16 ‘Sample Id: A2304130002-0001 A J E 0 Testing Lab And Consultancy LLP D Certified Lab No. ATLETCNOD PHOTOGRAPHS: [1: UNEXPOSED SURFACE BEFORE TESTING 2: EXPOSED SURFACE BEFORE TESTING E2A13Alo, Site, Industral Area, Lon Road Moan Nagar; Chaziabad UtarPradesh-201007 ak@ajeo.co.in , www.ajeo.co.in, Contact No.: +918010296901 Page 14 0f 16 le Id: A2304130002-0001 40 A J E O Testing Lab And Consuttancy LLP ENo, ATLOTC00 “1: UNEXPOSED SURFACE AFTER TESTING 2: EXPOSED SURFACE AFTER TESTING iahad, UttarPradesh-201005 ga, Ghaziabad, UttarPradesh- ‘akiaiajeo.co.in , wWwW.ajeo.co.in, Contact No. +9180 1029690 Page 15 of 16 Sample Id: A2304130002-0001 i ep A J E 0 Testing Lab And Consultancy LLP (An ISO Certified Laboratory) FxNo, ATLCTTCIOO F. CONCLUSION: Lloydroc Rockwool Panel is found safe for 125 minutes rating for integrity & Insulation criteria as per BS 476 part 20 & 22: 1987 & ASTM E 119 during the Fire Resistance Test. Results: Lloydroc Rockwool panel 50 mm thick has successfully withstood the insulation and integrity criteria for 125 minutes and sample is found rated for 125 minutes fire rating as per BS 476 part 20 & 22: 1987 & ASTME 119. ***End of Test Report*** ‘S, ° Cs, Adress: L1-S1/1/34 Industrial Area, Sahibabad, Ghaziabad, UtarPradesh-201008 777% 222/134/08, Site-Il, Industrial Area, Loni Road, Mohan Nagar, Ghaziabad, UttarPradesh-201007 ak@ajeo.co.in , www.ajeo.co.in, Contact No: +918010296901 Page 16 of 16

You might also like