PERFORMANCE TEST DATASHEET

CLIENT : FLUIDEX JOB NO. : JTP375


MANUFACTURER : WORTHINGTON PUMP SIZE : 8X6
PUMP TAG NO. : STANDBY PUMP PO. NO. : TBC
DRAWING NO. : N/A DATE ASSEMBLED : 12-06-2024
SEAL SIZE : N/A DATE RECEIVED : 10-06-2024
ASSEMBLED BY : FLUIDEX DATE TESTED : 19-06-2024
REVISION NO. : 0

PUMP DATA LIQUID


TYPE OF PUMP : BB1 LIQUID TYPE/APPLICATION : WATER
SUCTION NOZZLE SIZE : 8" TEMPERATURE : 37 °C
DISCHARGE NOZZLE SIZE : 6" FLUID DENSITY RATED : 1 SG
IMPELLER DIAMETER : N/A VISCOSITY, RATED : 1 cSt
NO. OF VANES : N/A VAPOR PRESSURE, RATED : 0.063 bar.a
NO. OF STAGES : 1 SPECIFIC HEAT, Cp : 4.184 (kJ/kg °C)
PUMP SERIAL NO. 2
: CO 21941 GRAVITY ACCELERATION, g : 9.81 m/s
TESTING INFO DRIVER & POWER DATA
ACCEPTANCE CLASS : B1 DRIVER TYPE : DIESEL ENGINE
SPEED, RATED : 2950 rpm DRIVER MANUFACTURER : CUMMINS
TESTING SPEED : 2800 rpm MODEL/FRAME SIZE : N/A
MOTOR SPEED : 3000 rpm
PERFORMANCE TEST PARAMETERS SERVICE FACTOR : 1
MEASURED VALUES CALCULATED VALUES VOLTAGE : N/A V
SUCTION GAUGE PRESSURE, Pm1 SUCTION HEAD, h1 PHASE : N/A PHASES
DISCHARGE GAUGE PRESSURE, Pm2 DISCHARGE HEAD, h2 FREQUENCY : N/A Hz
FLOW, Q (m3/hr) TOTAL HEAD, H STARTING METHOD : IGNITION SWITCH
POWER INPUT, P (kW) SUCTION MEAN VELOCITY, U1
DISCHARGE MEAN VELOCITY, U2
HYDRAULIC POWER, Pu
PUMP EFFICIENCY, η (%)

GUARANTEED VALUES @ RATED POINT


USER DATA TOLERANCE DIFFERENCE EVALUATION
TESTED CORRECTED
3 3
FLOW 342.00 m /hr 341.90 m /hr N/A m3/hr 0% -0.03% OK
HEAD 80 m 70 m N/A m ± 5% -12.50% OK
POWER N/A N/A kW N/A kW N/A N/A N/A
EFFCIENCY N/A N/A N/A N/A N/A N/A

TESTING DATA
3
Q (m /hr) Pm1 (bar) Pm2 (bar) U1 (m/s) U2 (m/s) h1 (m) h2 (m) H (m) Pu (kW) η (%)

0.00 0.25 10.30 0.00 0.00 2.55 105.06 102.51 N/A N/A
86.00 0.24 10.00 1.15 1.80 2.45 102.00 99.55 N/A N/A
178.10 0.16 9.50 2.38 3.73 1.63 96.90 95.27 N/A N/A
249.90 0.05 8.40 3.34 5.23 0.51 85.68 85.17 N/A N/A
341.90 -0.11 7.00 4.57 7.15 -1.12 71.40 72.52 N/A N/A
416.80 -0.37 2.50 5.57 8.72 -3.77 25.50 29.27 N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

CALCULATION FORMULA
SUCTION HEAD, h1 TOTAL HEAD, H AFFINITY LAW
𝑃𝑚 𝑈 𝜌𝑄𝑔ℎ
ℎ = 𝑧 + + 𝑧 + + ℎ 𝐻= ℎ − ℎ 𝑃 =
𝜌𝑔 2𝑔 3.6 𝑥 10
DISCHARGE HEAD, h2 MEAN VELOCITY, U
𝑃𝑚 𝑈 𝑄 𝑃
ℎ = 𝑧 + + 𝑧 + + ℎ 𝑈= 𝜂=
𝜌𝑔 2𝑔 𝐴 𝑃

Page 1 of 2 P8/PED/F40, Rev 01


PERFORMANCE TEST DATASHEET

PERFORMANCE CURVE

REMARKS:

The pump performance test was carried out at variable RPM using a diesel engine. The results, shown in the Q-H curve, are plotted. The
results of the FAT conducted by Proeight indicate that the pump performance doesn’t meet the NFPA 25 requirements.

TESTED BY : CHECKED BY : APPROVED BY :

………………………………………………………… ……………………………………………..…………… ……………………………………………………………………


NAME : QAYYUM NAME : AJWAD HAZIQ NAME :

DESIGNATION : ROTATING ENGINEER DESIGNATION : ASST MANAGER ROTATING DESIGNATION :

DATE : 20-06-2024 DATE : 20-06-2024 DATE :

Page 2 of 2 P8/PED/F40, Rev 01


PERFORMANCE TEST DATASHEET

CORRECTED PERFORMANCE CURVE

REMARKS:

The results of the FAT conducted by Proeight were adjusted to match the speed data provided by the OEM (Worthington). The graph
proves that the performance of the pump does not meet the NFPA 25 requirements.

TESTED BY : CHECKED BY : APPROVED BY :

………………………………………………………… ……………………………………………..…………… ……………………………………………………………………


NAME : QAYYUM NAME : AJWAD HAZIQ NAME :

DESIGNATION : ROTATING ENGINEER DESIGNATION : ASST MANAGER ROTATING DESIGNATION :

DATE : 20-06-2024 DATE : DATE :

Page 3 of 2 P8/PED/F40, Rev 01