Professional Documents
Culture Documents
synchrophasorassistedadaptivereachsetting
synchrophasorassistedadaptivereachsetting
net/publication/224244752
CITATIONS READS
37 175
3 authors, including:
Seethalekshmi K. Sn Singh
Institute of Engineering & Technology - Lucknow Indian Institute of Technology Kanpur
35 PUBLICATIONS 485 CITATIONS 389 PUBLICATIONS 9,631 CITATIONS
Some of the authors of this publication are also working on these related projects:
Forecasting (Solar Power, Wind Power and Market Price ) View project
All content following this page was uploaded by Seethalekshmi K. on 14 December 2018.
Abstract—The operation of Flexible AC Transmission System out in the literature [2]–[8]. It deals with the change in the ap-
Controllers (FACTS) in the power transmission system pose a parent impedance measured by the relay in the presence of these
challenge to the distance relaying scheme. This paper suggests an controllers. The performance analysis in [3] utilizes a steady
adaptive scheme for estimating the trip boundaries of a distance
relay in presence of a Unified Power Flow Controller (UPFC), state voltage source model of the UPFC with fixed compensa-
utilizing a Generalized Regression Neural Network (GRNN). tion levels for studying the effects of location of the UPFC and
Initially, the impact of the UPFC on the relay’s trip boundary fault resistance on the distance relay operation. A more exhaus-
is studied for its automatic power flow control mode as well as tive analysis has been carried out in [4], [5] considering a de-
bypass mode of operation. The GRNN has been trained off-line tailed model of the UPFC. However, [3]–[5] do not discuss the
with the data generated from a detailed performance analysis
of the power system for various faults considering the effects strategies for mitigating the underreach/overreach issues in the
of the UPFC, fault resistance, and system loading conditions on distance relays.
the trip boundaries. This work has also proposed a strategy that The challenge in the distance protection in the presence of
computes the control parameters of the UPFC on-line, namely, FACTS controllers such as UPFC, is due to the variation of
series voltage and reactive current injections, utilizing the syn- its control parameters namely, the series voltage and reactive
chronized phasor measurements from Phasor Measurement Units
(PMUs). Pre-fault system states, including the control parameters current injections. These protection issues can be addressed ei-
of the UPFC and the apparent impedance measured by the relay ther through the development of dedicated schemes for fault
unit have been utilized by the GRNN for predicting the trip location in transmission lines provided with UPFC [6], [7] or
boundaries of the relay. The proposed scheme has considered through the adaptive prediction of trip boundaries of the conven-
Single Line-to-Ground (SLG), Double Line-to-Ground (LLG) and tional distance relays. The development of dedicated schemes
Three Phase-to-Ground (LLLG) faults and the effectiveness of the
scheme has been tested on 39-bus New England system and also [6], [7] has attracted much more attention as compared to the
on a 17-bus system, a reduced equivalent of practical Northern adaptive trip boundary prediction. As a typical distance relay
Regional Power Grid (NRPG) system in India. consists of fault detection, classification, measurement and trip
Index Terms—Distance relay, generalized regression neural net- region comparison units, replacing the fixed Mho/quadrilateral
work (GRNN), synchrophasor, trip boundary, unified power flow trip region comparison unit with an adaptive trip characteris-
controller (UPFC). tics is an effective option for dealing with the protection is-
sues in the presence of an UPFC. One such scheme has been
proposed by the authors’ in [8] and was demonstrated only for
I. INTRODUCTION Single-Line-to-Ground (SLG) fault.
This paper proposes a scheme to predict the trip boundaries of
a conventional distance relay in the presence of UPFC through
T HE introduction of Flexible AC Transmission System
(FACTS) [1] controllers in the power system opens
up new challenges to the line protection as they change the
the knowledge of the control parameters of the UPFC. It com-
putes the series voltage and reactive current injection by the
UPFC on-line with the help of synchronized phasor measure-
impedance of the lines dynamically. Consequently, distance
ments [9] and these parameters are utilized in the adaptive trip
relays, in the associated transmission system, will have an
boundary prediction. Additionally, the scheme also considers
overreaching or underreaching effect depending on the control
the fact that depending on the magnitude of the fault current,
modes of the FACTS controllers. Hence, determining the
the UPFC may change its status to bypass operating mode [10],
boundaries of operation of a distance relay, adaptively in the
where series voltage injection is zero.
presence of FACTS controllers, is a challenging task.
The proposed scheme is based on Artificial Neural Network
An extensive analysis of the distance protection scheme, in
(ANN), which has found applications in adaptive reach settings
the presence of various FACTS controllers, has been carried
of the conventional distance relays [11], [12]. To adapt to the
changes in the system, external to the protected line, an adap-
Manuscript received February 28, 2011; revised May 29, 2011; accepted May
tive reach setting concept is presented using three Back Prop-
29, 2011. Date of publication July 05, 2011; date of current version August 24,
2011.This work was supported by the Department of Science and Technology, agation Neural Networks (BPNN) in [11] and by using three
New Delhi, India, under Project DST/EE/20100258. Radial Basis Function Neural Networks (RBFNN) in [12], uti-
The authors are with the Department of Electrical Engineering, Indian Insti-
lizing local signals. These ANN structures suffer from the draw-
tute of Technology Kanpur, Kanpur 208016, India (e-mail: seethalk@iitk.ac.in;
snsingh@iitk.ac.in; scs@iitk.ac.in). back that they require large training time for learning the several
Digital Object Identifier 10.1109/JSYST.2011.2158694 possible combinations of the operating scenarios of the system.
(11)
Define
(16)
(3)
Using (5), (6) and (7), series voltage injection of the UPFC can A. GRNN- An Overview
be calculated with the knowledge of the receiving end power GRNNs can model nonlinear functions and are shown to
flows, sending and receiving end voltage profiles and angular perform well in noisy environments, given enough data [13],
separations. In the above expressions, the power loss in the and its training is faster. Though GRNN is a feed forward net-
UPFC is neglected. work requiring supervised training, it is significantly different
Similarly, reactive current injection can also be calculated in architecture and algorithm to the BPNN. It involves one-pass
from the basic power flow equations [21]. neural network learning algorithm, which can be used for
estimating the continuous variables and does not require an it-
erative training procedure as in the BPNN. It approximates any
(8) arbitrary function between input and output vectors, drawing
Let the function estimate directly from the training data. Let “ ”
be a particular measured value of the random variable “ .” If
(9) a joint probability distribution between a set of variable “ ”
and a dependent variable “ ” exists, then the estimation of “ ,”
and given a particular realization of “ ,” is expressed as
(10) (18)
SEETHALEKSHMI et al.: SYNCHROPHASOR ASSISTED ADAPTIVE REACH SETTING 399
the line terminals. The advantage of the proposed scheme, com- study. Constraint imposed on the operation of the UPFC in auto-
pared to the differential protection scheme, is that this scheme matic power flow control is on the variation in the magnitude of
can very well be extended to the protection of the adjacent line its series injected voltage. The limits on series injection voltage
sections, which are falling in the zone 2 and the zone 3 limits are taken as 0–10% of the voltage value at the sending end and
of the relay. So, with the PMUs installed at both the ends of the the phase angle variation between 0–360 . In the bypass mode
line, the pre-fault information, which is utilized to obtain con- of operation of the UPFC, both the series and the shunt con-
trol settings of UPFC, can be used for identifying all the three trollers are bypassed; hence, the series injection voltage and the
trip zones of a conventional distance relay. reactive current injection by the UPFC are zero.
2) WAMS Architecture and Communication Requirements:
Modern distance relays such as SEL-421 of Schweitzer Engi- A. 39-Bus New England System
neering and D60 of General Electric are having PMU capability Placement of the UPFC in a network enhances the transmis-
to provide time stamped voltage and current phasors. Pre-fault sion capability of the interconnected system. From a system
system data, required by the proposed scheme, can be made point of view, though it is necessary to consider both the static
available at a frame rate of 60 frames per second in 60 Hz system as well as dynamic aspects for deriving a placement strategy for
and 50 frames per second in 50 Hz system [22] from the dis- a FACTS controller [19], this work has considered static Avail-
tance relays (or PMUs) installed in the line itself. This scheme able Transfer Capacity (ATC) enhancement as a criterion [24] to
can work with a “flat architecture” [15] based WAMS, in which decide the optimal placement of the UPFC. The UPFC is placed
relevant system data is transferred through the communication in line 16–17 as shown in Fig. 4, with shunt branch at bus 16. Ini-
system that ties the line terminals together. The communication tial reactive current injection of the UPFC is maintained at zero
delay in the present PMU based scheme does not pose a problem for all the cases as the system is having sufficient reactive power
in the scheme, as it deals with only pre-fault quantities at the support. However, the dynamic simulations have considered the
relay location. reactive current injection or absorption modes of the UPFC in
response to the faults. In the present study, a SLG fault, a LLG
fault and a LLLG fault, with fault resistance , have been sim-
V. SIMULATION RESULTS AND DISCUSSIONS
ulated on the line connecting buses 16 and 17. Distance relays
The effect of the dynamical changes in the UPFC settings are assumed to be located at stations 16 and 17.
on the distance protection scheme has been studied on two test UPFC is assumed to be initially operating in the automatic
systems, namely 39-bus New England system and a 17-bus re- power flow control mode. For all the cases studied, reference
duced equivalent of Northern Region Power Grid (NRPG) net- power flow setting of the UPFC is MVA from bus 16
work. Test systems are modeled in SIMULINK [23]. Loads are to 17, which has been decided after analyzing the system for
modeled as constant impedance type for the transient studies. various loading scenarios and contingency cases such as outage
Dynamic model of the UPFC [23], has been considered in this of the line and generation units. However, this is only a sample
SEETHALEKSHMI et al.: SYNCHROPHASOR ASSISTED ADAPTIVE REACH SETTING 401
Fig. 5. Variation in the UPFC control parameters during SLG fault. (a): Vari-
ation in series voltage injection during fault. (b): Variation in reactive current
injection during fault.
setting for the study purpose and it can be decided by the utility
depending on the actual system requirements. Base case loading
of the system corresponds to a flow of MVA in the Fig. 6. Trip boundaries with the UPFC in 39-bus system. (a): Boundaries with
line, from bus 16 to bus 17 and the power flow is called as Pre UPFC in automatic power flow control mode. (b): Trip boundaries of the relay
with UPFC in bypass mode.
Controlled Power Flow (PCPF).
1) UPFC Transient Response in Power Flow Control Mode:
As stated in Section II, the series voltage injection undergoes from the relay location, with the fault resistance from 0.01 to
changes during fault conditions. Fig. 5(a) shows the change in 100 ohm. Fig. 6(a) shows the four trip boundaries indicated as
the series voltage injection, when a SLG fault takes place in “boundary a,” “b,” “c,” and “d.” Boundaries “a” and “c” corre-
the line 16–17 at 50% distance from the bus 16 with a fault spond to the fault distance of 95% and 2%, respectively, from
resistance of 10 ohm. The UPFC control is applied at for the relaying location, when the fault resistance is varied from
maintaining the power flow at the reference setting, followed by minimum to maximum value. Boundaries “b” and “d” corre-
a SLG fault applied at after attaining the required power spond to the maximum and minimum fault resistances, respec-
flow. In Fig. 5(a) series voltage injection has been increased to tively, where the distance at which fault occurs vary from 2%
0.06 p.u. at and following the SLG fault at to 95% of the line length. Plotted boundaries correspond to the
reduced to 0.055 p.u. impedance measured using FCDFT by taking the voltage and
Similar analysis has been done for the reactive current injec- current signals from the relay location.
tion from the UPFC. Fig. 5(b) shows the variation in the reactive In the bypass mode, both the series and the shunt controllers
current injection ( ) by the UPFC following the SLG fault. Fol- of the UPFC are bypassed within 1 cycle of the fault initiation
lowing the fault, increases to 1.0 p.u, due to which the mea- and steady state apparent impedance is measured for the SLG
sured value of the apparent impedance increases. However, the fault at various distances and fault resistances. Fig. 6(b) shows
influence of on the distance relay operation is dependent on the corresponding trip boundaries in various power flow condi-
the control mode of the UPFC. tions.
2) Apparent Impedance Boundaries for the 39-Bus System: For SLG, LLG and LLLG faults, variation in the trip bound-
Apparent impedance, measured at the relay point, is depen- aries of the distance relay located at bus 16, with the UPFC in
dent on the operating states of the system. This is illustrated in automatic power flow control mode, are shown in Fig. 7 along
Fig. 6(a) where trip boundaries of the relay under various power with the stepped zone trip characteristics of a conventional mho
flow conditions are shown with UPFC operating in automatic and quadrilateral relays. Settings of the mho and quadrilateral
power flow control mode. relays have been selected based on the standard practice of 85%
Towards realizing these trip boundaries of the relay at bus 16, of line impedance for zone 1, 120% for zone 2 and zone 3 set-
SLG fault is simulated at distances, ranging from 2% to 95% ting to cover the longest adjacent line section. From Fig. 7, it is
402 IEEE SYSTEMS JOURNAL, VOL. 5, NO. 3, SEPTEMBER 2011
TABLE I
DETAILS OF TRAINING CASES FOR 39-BUS SYSTEM
TABLE II
DETAILS OF TEST CASES FOR 39-BUS SYSTEM
Fig. 8. Trip boundaries predicted by the GRNN in 39-bus system. (a): for SLG
fault – Cases C and D. (b): for LLG fault – Cases C and B. (c): for LLLG fault
– Cases A and B.
VI. CONCLUSION
In this paper, a new scheme based on Generalized Regres-
sion Neural Network (GRNN) has been proposed to predict the
trip boundaries of a distance relay in an adaptive manner, in the
presence of UPFC. Data sets have been generated for training
the GRNN through an extensive analysis of the system for var-
ious types of faults viz. Single-Line-to-Ground (SLG), Double-
Line-to-Ground (LLG) and Three- Phase-to-Ground (LLLG)
faults, with the UPFC in automatic power flow control mode
as well as in the bypass mode of operation. GRNN has been
trained with the pre-fault system states, control parameters of
the UPFC, impedance measured by the relay unit and operating
status of the UPFC as inputs. Control settings of the UPFC have
been calculated with the aid of synchro phasor measurements,
Fig. 10. Variation in trip boundaries with changes in “ ” injection of the assumed to be available from the Phasor Measurement Units
UPFC (NRPG system). (PMUs) placed at the ends of the line. The test results show
that, with a single GRNN for each type of fault, the trip region
can be accurately recognized for automatic power flow control
as well as the bypass modes of operation of the UPFC. Trip
boundaries for the relay in the presence of UPFC are compared
with that of the conventional mho and quadrilateral character-
istics which clearly indicate the need of replacing the conven-
tional settings with adaptive settings. Also, the performance of
GRNN has been found superior to that with a Back Propagation
Neural Network (BPNN) for generating the trip boundary. By
replacing the fixed type relay settings with the proposed adap-
tive settings, the capability of the conventional distance relay
can be enhanced to cope up with the dynamic variation in the
line impedance in the presence of the UPFC.
ACKNOWLEDGMENT
The authors wish to thank Department of Science and Tech-
Fig. 11. Trip boundaries generated by GRNN for NRPG system for SLG fault.
nology, New Delhi, India for providing support to carry out this
TABLE III research work.
DETAILS OF TEST CASES FOR NRPG SYSTEM.
REFERENCES
[1] N. G. Hingorani and L. Gyugyi, Understanding FACTS: Concepts &
Technology of Flexible AC Transmission Systems. New York: IEEE,
2000.
[2] F. A. Albasri, T. S. Sidhu, and R. K. Verma, “Performance comparison
of distance protection schemes for shunt-FACTS compensated trans-
mission lines,” IEEE Trans. Power Del., vol. 22, no. 4, pp. 2116–2125,
2007.
[3] P. K. Dash, A. K. Pradhan, G. Panda, and A. C. Liew, “Adaptive relay
setting for flexible AC transmission systems (FACTS),” IEEE Trans.
Power Del., vol. 15, no. 1, pp. 38–43, 2000.
sponding to each power flow condition, varying reactive power [4] X. Zhou, H. Wang, R. K. Aggarwal, and P. Beaumont, “Performance
injection from the shunt branch ( ) is considered. evaluation of a distance relay as applied to a transmission system with
2) Test Results for the NRPG System: Testing patterns consist UPFC,” IEEE Trans. Power Del., vol. 21, no. 3, pp. 1137–1147, 2006.
[5] M. Khederzadeh, “UPFC operating characteristics impact on transmis-
of all the four categories i.e., UPFC in power flow control mode sion line distance protection,” in Proc. IEEE PES General Meeting,
with minimal, negative and positive injections along with the Pittsburgh, PA, Jul. 2008, pp. 1–6.
UPFC in bypass mode of operation. PCPF in the test case has [6] S. R. Samantaray, “Decision tree-based fault zone identification and
fault classification in flexible AC transmissions-based transmission
been taken as MVA, which is slightly outside the line,” Proc. IET Gen. Transm. Distrib., vol. 3, no. 5, pp. 425–436,
range of the PCPF values used for training the GRNN. Details 2009.
of the test cases are given in Table III and the performance of [7] S. R. Samantaray, L. N. Tripathy, and P. K. Dash, “Differential
equation-based fault locator for unified power flow controller-based
the GRNN is shown in Fig. 11. It is seen that the GRNN is able transmission line using synchronized phasor measurements,” Proc.
to approximate the function in an acceptable way. IET Gen. Transm. Distrib., vol. 3, no. 1, pp. 86–98, 2009.
Test results indicate that the proposed GRNN architecture is [8] K. Seethalekshmi, S. N. Singh, and S. C. Srivastava, “Adaptive dis-
tance relaying scheme in presence of UPFC using WAMS,” in Proc.
able to track the relay trip boundaries utilizing the pre-fault op- IEEE Power Systems Conf. Exposition, Seattle, WA, Mar. 2009, pp.
erating conditions and the control settings of the UPFC. 1–6.
SEETHALEKSHMI et al.: SYNCHROPHASOR ASSISTED ADAPTIVE REACH SETTING 405
[9] A. G. Phadke, “Synchronized phasor measurement in power systems,” K. Seethalekshmi (S’09) received the B.Tech
IEEE Comput. Applicat. Power, vol. 6, no. 2, pp. 10–15, 1993. degree from Regional Engineering College, Calicut,
[10] L. Gyugyi et al., “Operation of the unified power flow controller Kerala, India, the M. Tech. degree from the College
(UPFC) under practical constraints,” IEEE Trans. Power Del., vol. 13, of Engineering, Trivandrum, Kerala, and is currently
no. 2, pp. 630–639, 1998. pursuing the Ph.D. in the Department of Electrical
[11] K. K. Li, L. L. Lai, and A. K. David, “Stand alone intelligent digital Engineering, Indian Institute of Technology Kanpur.
distance relay,” IEEE Trans. Power Syst., vol. 15, no. 1, pp. 137–142, Her research interests include wide area monitoring
2000. systems, synchrophasor applications in power
[12] B. R. Bhalija and R. P. Maheshwari, “High- resistance faults on two system protection and control, and optimal power
terminal parallel transmission lines: analysis, simulation studies, and flow.
an adaptive distance relaying scheme,” IEEE Trans. Power Del., vol.
22, no. 2, pp. 801–812, 2007.
[13] D. F. Specht, “A general regression neural network,” IEEE Trans.
Neural Netw., vol. 2, no. 6, pp. 568–576, 1991.
[14] M. A. Pai, Energy Function Analysis for Power System Stability. S. N. Singh (SM’02) received M.Tech and Ph.D. de-
London, U.K.: Kluwer, 1989. grees from the Indian Institute of Technology Kanpur
[15] Northern Regional Load Dispatch Center Website, [Online]. Available: in 1989 and 1995, respectively.
http://nrldc.org Presently, he is Professor in the Department of
[16] M. Arunachalam, G. Lal, C. G. Rajiv, and M. M. B. Narayanan, “Per- Electrical Engineering, Indian Institute of Tech-
formance verification of TCSC control and protection equipment using nology Kanpur. His research interests include
RTDS,” in 15th Power Systems Computation Conf., Liege, Aug. 2005. power system restructuring, FACTS, power system
[17] T. Jain, S. N. Singh, and S. C. Srivastava, “Dynamic ATC enhancement optimization and control, wind power, etc. He is a
through optimal placement of FACTS controllers,” Elect. Power Syst. Fellow of IE (India) and IETE (India).
Res., vol. 79, no. 11, pp. 1473–1482, 2009.
[18] B. Xu and A. Abur, “State estimation of systems with UPFCs using
the interior point method,” IEEE Trans. Power Del., vol. 19, no. 3, pp.
1635–1641, 2004.
[19] J. Bertsch, C. Carnal, D. Karlsson, J. Mcdaniel, and K. Vu, “Wide-area
S. C. Srivastava (SM’91) received the Ph.D. degree
protection and power system utilization,” Proc. IEEE, vol. 93, no. 5,
in electrical engineering from the Indian Institute of
pp. 997–1003, 2005.
Technology Delhi.
[20] G. Shaoyun, “Optimal Power System Operation and Control Incorpo-
Presently, he is Professor in the Department of
rating FACTS Devices,” Ph.D., Hong Kong Polytechnic Univ., Dept.
Electrical Engineering, Indian Institute of Tech-
Elect. Eng., Hong Kong, 1998.
nology Kanpur. His research interests include
[21] K. Fukunaga, Introduction to Statistical Pattern Recognitions. New
synchrophasor technology, stability and controls,
York: Academic, 1972.
and technical issues in electricity markets. He is a
[22] IEEE Standard for Synchrophasors for Power Systems, IEEE Std. C37.
Fellow of INAE (India), IE (India) and IETE (India).
118, 2005.
[23] SimPowerSystems 4 – Reference Manual. Natick, MA, The Math-
Works, Inc., 2007.
[24] S. Kim, J. Lim, and S. Moon, “Enhancement of power system security
level through the power flow control of UPFC,” in Proc. IEEE PES
Summer Meeting, Seattle, WA, Jul. 2000, pp. 38–43.