Product datasheet

Specifications

Circuit breaker ComPacT


NSX100B, 25kA at 415VAC, TMD
trip unit 40A, 50 degrees C, 4
poles 3D
C10B6TM040C

Main
Range ComPacT new generation

Product Name ComPacT NSX new generation

Device Short Name NSX100B

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product Or Component Type Circuit breaker

Device Application Distribution

Poles Description 4P

Protected Poles Description 3D

Neutral Position Left

[In] Rated Current 40 A at 50 °C

[Ue] Rated Operational Voltage 690 V AC 50/60 Hz

Network Type AC

Network Frequency 50/60 Hz

Suitability For Isolation Yes conforming to EN/IEC 60947-2

Utilisation Category Category A

[Icu] Rated Ultimate Short-Circuit 40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Breaking Capacity 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2

Performance Level B 25 kA 415 V AC

Trip Unit Name TM-D

Trip Unit Technology Thermal-magnetic

Trip Unit Protection Functions LI

Control Type Toggle

Circuit Breaker Mounting Mode Fixed

Complementary
[Ui] Rated Insulation Voltage 800 V AC 50/60 Hz

[Uimp] Rated Impulse Withstand 8 kV


Voltage
[Ics] Rated Service Short-Circuit 40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Breaking Capacity 25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
7 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2

Mechanical Durability 50000 cycles

Excluding VAT, FCA Jabal Ali & are subject to change – check with your local distributor.

21 Mar 2024 1
Electrical Durability 50000 cycles at 440 V In/2
30000 cycles at 440 V In
20000 cycles at 690 V In/2
10000 cycles at 690 V In

Power Dissipation Per Pole 5.47 W

Mounting Support Backplate

Mounting Position Horizontal and vertical


Flat on the back

Upside Connection Front

Downside Connection Front

Connection Pitch 35 mm

Protection Type L : for overload protection (thermal)


I : for short-circuit protection (magnetic)

Trip Unit Rating 40 A at 50 °C

Long-Time Pick-Up Adjustment Adjustable


Type Ir (Thermal Protection)
[Ir] Long-Time Protection Pick-Up 0.7...1 x In
Adjustment Range
Long-Time Protection Delay Fixed
Adjustment Type Tr
[Tr] Long-Time Protection Delay 120…400 s at 1.5 x In
Adjustment Range 15 s at 6 x Ir

Neutral Protection Settings No protection (3D)

Instantaneous Protection Pick-Up Fixed


Adjustment Type Ii
[Ii] Instantaneous Protection Pick- 500 A
Up Adjustment Range
Earth-Leakage Protection Without

Number Of Slots For Electrical 5 slot(s)


Auxiliaries
Width (W) 140 mm

Height (H) 161 mm

Depth (D) 86 mm

Net Weight 2.4 kg

Environment
Standards EN/IEC 60947

Product Certifications CCC


EAC
Marine

Overvoltage Category Class II

Electrical Shock Protection Class Class II

Pollution Degree 3 conforming to IEC 60664-1

Ip Degree Of Protection IP40 conforming to IEC 60529

Ik Degree Of Protection IK07 conforming to IEC 62262

Ambient Air Temperature For -25…70 °C


Operation
Ambient Air Temperature For -50…85 °C
Storage
Relative Humidity 0…95 %

Operating Altitude 0...2000 m without derating


2000 m...5000 m with derating

2 21 Mar 2024
Packing Units
Unit Type Of Package 1 PCE

Number Of Units In Package 1 1

21 Mar 2024 3
Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right

Transparency RoHS/REACh

Well-being performance

 Mercury Free

 Rohs Exemption Information Yes

Certifications & Standards


Reach Regulation REACh Declaration

Eu Rohs Directive Compliant with Exemptions

China Rohs Regulation China RoHS declaration


Product out of China RoHS scope. Substance declaration for your information

Environmental Disclosure Product Environmental Profile

Circularity Profile End of Life Information

4 21 Mar 2024
Product datasheet
Specifications

Circuit breaker ComPacT


NSX100B, 25kA at 415VAC, TMD
trip unit 63A, 50 degrees C, 4
poles 3D
C10B6TM063C

Main
Range ComPacT new generation

Product Name ComPacT NSX new generation

Device Short Name NSX100B

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product Or Component Type Circuit breaker

Device Application Distribution

Poles Description 4P

Protected Poles Description 3D

Neutral Position Left

[In] Rated Current 63 A at 50 °C

[Ue] Rated Operational Voltage 690 V AC 50/60 Hz

Network Type AC

Network Frequency 50/60 Hz

Suitability For Isolation Yes conforming to EN/IEC 60947-2

Utilisation Category Category A

[Icu] Rated Ultimate Short-Circuit 40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Breaking Capacity 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2

Performance Level B 25 kA 415 V AC

Trip Unit Name TM-D

Trip Unit Technology Thermal-magnetic

Trip Unit Protection Functions LI

Control Type Toggle

Circuit Breaker Mounting Mode Fixed

Complementary
[Ui] Rated Insulation Voltage 800 V AC 50/60 Hz

[Uimp] Rated Impulse Withstand 8 kV


Voltage
[Ics] Rated Service Short-Circuit 40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Breaking Capacity 25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
7 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2

Mechanical Durability 50000 cycles

Excluding VAT, FCA Jabal Ali & are subject to change – check with your local distributor.

21 Mar 2024 1
Electrical Durability 50000 cycles at 440 V In/2
30000 cycles at 440 V In
20000 cycles at 690 V In/2
10000 cycles at 690 V In

Power Dissipation Per Pole 8.61 W

Mounting Support Backplate

Mounting Position Horizontal and vertical


Flat on the back

Upside Connection Front

Downside Connection Front

Connection Pitch 35 mm

Protection Type L : for overload protection (thermal)


I : for short-circuit protection (magnetic)

Trip Unit Rating 63 A at 50 °C

Long-Time Pick-Up Adjustment Adjustable


Type Ir (Thermal Protection)
[Ir] Long-Time Protection Pick-Up 0.7...1 x In
Adjustment Range
Long-Time Protection Delay Fixed
Adjustment Type Tr
[Tr] Long-Time Protection Delay 120…400 s at 1.5 x In
Adjustment Range 15 s at 6 x Ir

Neutral Protection Settings No protection (3D)

Instantaneous Protection Pick-Up Fixed


Adjustment Type Ii
[Ii] Instantaneous Protection Pick- 500 A
Up Adjustment Range
Earth-Leakage Protection Without

Number Of Slots For Electrical 5 slot(s)


Auxiliaries
Width (W) 140 mm

Height (H) 161 mm

Depth (D) 86 mm

Net Weight 2.4 kg

Environment
Standards EN/IEC 60947

Product Certifications CCC


EAC
Marine

Overvoltage Category Class II

Electrical Shock Protection Class Class II

Pollution Degree 3 conforming to IEC 60664-1

Ip Degree Of Protection IP40 conforming to IEC 60529

Ik Degree Of Protection IK07 conforming to IEC 62262

Ambient Air Temperature For -25…70 °C


Operation
Ambient Air Temperature For -50…85 °C
Storage
Relative Humidity 0…95 %

Operating Altitude 0...2000 m without derating


2000 m...5000 m with derating

2 21 Mar 2024
Packing Units
Unit Type Of Package 1 PCE

Number Of Units In Package 1 1

21 Mar 2024 3
Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right

Transparency RoHS/REACh

Well-being performance

 Mercury Free

 Rohs Exemption Information Yes

Certifications & Standards


Reach Regulation REACh Declaration

Eu Rohs Directive Compliant with Exemptions

China Rohs Regulation China RoHS declaration


Product out of China RoHS scope. Substance declaration for your information

Environmental Disclosure Product Environmental Profile

Circularity Profile End of Life Information

4 21 Mar 2024
Product datasheet
Specifications

Circuit breaker ComPacT


NSX100B, 25kA at 415VAC, TMD
trip unit 100A, 4 poles 3d
C10B6TM100

Main
Range ComPacT new generation

Product Name ComPacT NSX new generation

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Device Short Name NSX100B

Product Or Component Type Circuit breaker

Device Application Distribution

Poles Description 4P

Protected Poles Description 3D

Neutral Position Left

[In] Rated Current 100 A at 40 °C

[Ue] Rated Operational Voltage 690 V AC 50/60 Hz

Network Type AC

Network Frequency 50/60 Hz

Suitability For Isolation Yes conforming to EN/IEC 60947-2

Utilisation Category Category A

[Icu] Rated Ultimate Short-Circuit 40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Breaking Capacity 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2

Performance Level B 25 kA 415 V AC

Trip Unit Name TM-D

Trip Unit Technology Thermal-magnetic

Trip Unit Protection Functions LI

Control Type Toggle

Circuit Breaker Mounting Mode Fixed

Complementary
[Ui] Rated Insulation Voltage 800 V AC 50/60 Hz

[Uimp] Rated Impulse Withstand 8 kV


Voltage
[Ics] Rated Service Short-Circuit 40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Breaking Capacity 25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
7 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2

Mechanical Durability 50000 cycles

21 Mar 2024 1
Electrical Durability 50000 cycles at 440 V In/2
30000 cycles at 440 V In
20000 cycles at 690 V In/2
10000 cycles at 690 V In

Power Dissipation Per Pole 8.8 W

Mounting Support Backplate

Mounting Position Horizontal and vertical


Flat on the back

Upside Connection Front

Downside Connection Front

Connection Pitch 35 mm

Protection Type L : for overload protection (thermal)


I : for short-circuit protection (magnetic)

Trip Unit Rating 100 A at 40 °C

Long-Time Pick-Up Adjustment Adjustable


Type Ir (Thermal Protection)
[Ir] Long-Time Protection Pick-Up 0.7...1 x In
Adjustment Range
Long-Time Protection Delay Fixed
Adjustment Type Tr
[Tr] Long-Time Protection Delay 120…400 s at 1.5 x In
Adjustment Range 15 s at 6 x Ir

Neutral Protection Settings No protection (3D)

Instantaneous Protection Pick-Up Fixed


Adjustment Type Ii
[Ii] Instantaneous Protection Pick- 800 A
Up Adjustment Range
Earth-Leakage Protection Without

Number Of Slots For Electrical 5 slot(s)


Auxiliaries
Width (W) 140 mm

Height (H) 161 mm

Depth (D) 86 mm

Net Weight 2.4 kg

Environment
Standards EN/IEC 60947

Product Certifications CCC


EAC
Marine

Overvoltage Category Class II

Electrical Shock Protection Class Class II

Pollution Degree 3 conforming to IEC 60664-1

Ip Degree Of Protection IP40 conforming to IEC 60529

Ik Degree Of Protection IK07 conforming to IEC 62262

Ambient Air Temperature For -25…70 °C


Operation
Ambient Air Temperature For -50…85 °C
Storage
Relative Humidity 0…95 %

Operating Altitude 0...2000 m without derating


2000 m...5000 m with derating

2 21 Mar 2024
Packing Units
Unit Type Of Package 1 PCE

Number Of Units In Package 1 1

Package 1 Height 13.5 cm

Package 1 Width 14.5 cm

Package 1 Length 19 cm

Package 1 Weight 2.307 kg

Unit Type Of Package 2 CAR

Number Of Units In Package 2 6

Package 2 Height 23 cm

Package 2 Width 39 cm

Package 2 Length 49 cm

Package 2 Weight 14.7275 kg

Unit Type Of Package 3 PAL

Number Of Units In Package 3 48

Package 3 Height 107 cm

Package 3 Width 40 cm

Package 3 Length 60 cm

Package 3 Weight 122.82 kg

21 Mar 2024 3
Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right

Transparency RoHS/REACh

Well-being performance

 Mercury Free

 Rohs Exemption Information Yes

 Pvc Free

Certifications & Standards


Reach Regulation REACh Declaration

Eu Rohs Directive Compliant with Exemptions

China Rohs Regulation China RoHS declaration


Product out of China RoHS scope. Substance declaration for your information

Environmental Disclosure Product Environmental Profile

Circularity Profile End of Life Information

4 21 Mar 2024
Product datasheet
Specifications

Circuit breaker ComPacT


NSX160B, 25kA at 415VAC, TMD
trip unit 160A, 50 degrees C, 4
poles 3D
C16B6TM160C

Main
Range ComPacT new generation

Product Name ComPacT NSX new generation

Device Short Name NSX160B

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product Or Component Type Circuit breaker

Device Application Distribution

Poles Description 4P

Protected Poles Description 3D

Neutral Position Left

[In] Rated Current 160 A at 50 °C

[Ue] Rated Operational Voltage 690 V AC 50/60 Hz

Network Type AC

Network Frequency 50/60 Hz

Suitability For Isolation Yes conforming to EN/IEC 60947-2

Utilisation Category Category A

[Icu] Rated Ultimate Short-Circuit 40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Breaking Capacity 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2

Performance Level B 25 kA 415 V AC

Trip Unit Name TM-D

Trip Unit Technology Thermal-magnetic

Trip Unit Protection Functions LI

Control Type Toggle

Circuit Breaker Mounting Mode Fixed

Complementary
[Ui] Rated Insulation Voltage 800 V AC 50/60 Hz

[Uimp] Rated Impulse Withstand 8 kV


Voltage
[Ics] Rated Service Short-Circuit 40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Breaking Capacity 25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
15 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2

Mechanical Durability 40000 cycles

Excluding VAT, FCA Jabal Ali & are subject to change – check with your local distributor.

21 Mar 2024 1
Electrical Durability 40000 cycles at 440 V In/2
20000 cycles at 440 V In
15000 cycles at 690 V In/2
7500 cycles at 690 V In

Power Dissipation Per Pole 13.95 W

Mounting Support Backplate

Mounting Position Horizontal and vertical


Flat on the back

Upside Connection Front

Downside Connection Front

Connection Pitch 35 mm

Protection Type L : for overload protection (thermal)


I : for short-circuit protection (magnetic)

Trip Unit Rating 160 A at 50 °C

Long-Time Pick-Up Adjustment Adjustable


Type Ir (Thermal Protection)
[Ir] Long-Time Protection Pick-Up 0.7...1 x In
Adjustment Range
Long-Time Protection Delay Fixed
Adjustment Type Tr
[Tr] Long-Time Protection Delay 120…400 s at 1.5 x In
Adjustment Range 15 s at 6 x Ir

Neutral Protection Settings No protection (3D)

Instantaneous Protection Pick-Up Fixed


Adjustment Type Ii
[Ii] Instantaneous Protection Pick- 1250 A
Up Adjustment Range
Earth-Leakage Protection Without

Number Of Slots For Electrical 5 slot(s)


Auxiliaries
Width (W) 140 mm

Height (H) 161 mm

Depth (D) 86 mm

Net Weight 2.6 kg

Environment
Standards EN/IEC 60947

Product Certifications CCC


EAC
Marine

Overvoltage Category Class II

Electrical Shock Protection Class Class II

Pollution Degree 3 conforming to IEC 60664-1

Ip Degree Of Protection IP40 conforming to IEC 60529

Ik Degree Of Protection IK07 conforming to IEC 62262

Ambient Air Temperature For -25…70 °C


Operation
Ambient Air Temperature For -50…85 °C
Storage
Relative Humidity 0…95 %

Operating Altitude 0...2000 m without derating


2000 m...5000 m with derating

2 21 Mar 2024
Packing Units
Unit Type Of Package 1 PCE

Number Of Units In Package 1 1

21 Mar 2024 3
Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right

Transparency RoHS/REACh

Well-being performance

 Mercury Free

 Rohs Exemption Information Yes

Certifications & Standards


Reach Regulation REACh Declaration

Eu Rohs Directive Compliant with Exemptions

China Rohs Regulation China RoHS declaration


Product out of China RoHS scope. Substance declaration for your information

Environmental Disclosure Product Environmental Profile

Circularity Profile End of Life Information

4 21 Mar 2024
Product datasheet
Specifications

Circuit breaker ComPacT


NSX250B, 25kA at 415VAC,
MicroLogic 2.2 trip unit 250A, 4
poles 4d
C25B42D250

Main
Range ComPacT new generation

Product Name ComPacT NSX new generation

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Device Short Name NSX250B

Product Or Component Type Circuit breaker

Device Application Distribution

Poles Description 4P

Protected Poles Description 4D


3D + N/2
3D

Neutral Position Left

[In] Rated Current 250 A at 40 °C

[Ue] Rated Operational Voltage 690 V AC 50/60 Hz

Network Type AC

Network Frequency 50/60 Hz

Suitability For Isolation Yes conforming to EN/IEC 60947-2

Utilisation Category Category A

[Icu] Rated Ultimate Short-Circuit 40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Breaking Capacity 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2

Performance Level B 25 kA 415 V AC

Trip Unit Name MicroLogic 2.2

Trip Unit Technology Electronic

Trip Unit Protection Functions LSoI

Control Type Toggle

Circuit Breaker Mounting Mode Fixed

Complementary
[Ui] Rated Insulation Voltage 800 V AC 50/60 Hz

[Uimp] Rated Impulse Withstand 8 kV


Voltage
[Ics] Rated Service Short-Circuit 40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Breaking Capacity 25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
15 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2

Mechanical Durability 20000 cycles

21 Mar 2024 1
Electrical Durability 20000 cycles at 440 V In/2
10000 cycles at 440 V In
10000 cycles at 690 V In/2
5000 cycles at 690 V In

Power Dissipation Per Pole 17.6 W

Mounting Support Backplate

Mounting Position Horizontal and vertical


Flat on the back

Upside Connection Front

Downside Connection Front

Connection Pitch 35 mm

Protection Type L : for overload protection (long time)


So : for short time short-circuit protection with fixed delay
I : for instantaneous short-circuit protection

Trip Unit Rating 250 A at 40 °C

Long-Time Pick-Up Adjustment Adjustable 9 settings


Type Ir (Thermal Protection)
[Ir] Long-Time Protection Pick-Up 100...250 A
Adjustment Range
Long-Time Protection Delay Fixed
Adjustment Type Tr
[Tr] Long-Time Protection Delay 400 s at 1.5 x Ir
Adjustment Range 16 s at 6 x Ir
11 s at 7.2 x Ir

Neutral Protection Settings 0.5 x Ir (3D + N/2)


1 x Ir (4D)
No protection (3D)

Thermal Memory 20 minutes before and after tripping

Short-Time Protection Pick-Up Adjustable 9 settings


Adjustment Type Isd
[Isd] Short-Time Protection Pick- 1.5...10 x Ir
Up Adjustment Range
Short-Time Protection Delay Fixed
Adjustment Type Tsd
Instantaneous Protection Pick-Up Fixed
Adjustment Type Ii
[Ii] Instantaneous Protection Pick- 3000 A
Up Adjustment Range
Earth-Leakage Protection Without

Zone Selective Interlocking Zsi Without

Number Of Slots For Electrical 5 slot(s)


Auxiliaries
Local Signalling Flashing LED (green) for ready to operate
LED 105 % Ir (red) for overload
LED 90 % Ir (orange) for overload

Width (W) 140 mm

Height (H) 161 mm

Depth (D) 86 mm

Net Weight 2.8 kg

Environment
Standards EN/IEC 60947

Product Certifications CCC


EAC
Marine

2 21 Mar 2024
Overvoltage Category Class II

Electrical Shock Protection Class Class II

Pollution Degree 3 conforming to IEC 60664-1

Ip Degree Of Protection IP40 conforming to IEC 60529

Ik Degree Of Protection IK07 conforming to IEC 62262

Ambient Air Temperature For -25…70 °C


Operation
Ambient Air Temperature For -50…85 °C
Storage
Relative Humidity 0…95 %

Operating Altitude 0...2000 m without derating


2000 m...5000 m with derating

Packing Units
Unit Type Of Package 1 PCE

Number Of Units In Package 1 1

Package 1 Height 14.4 cm

Package 1 Width 14.7 cm

Package 1 Length 19.4 cm

Package 1 Weight 2.632 kg

Unit Type Of Package 2 S03

Number Of Units In Package 2 6

Package 2 Height 30.0 cm

Package 2 Width 30.0 cm

Package 2 Length 40.0 cm

Package 2 Weight 16.167 kg

21 Mar 2024 3
Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right

Transparency RoHS/REACh

Well-being performance

 Mercury Free

 Rohs Exemption Information Yes

Certifications & Standards


Reach Regulation REACh Declaration

Eu Rohs Directive Compliant with Exemptions

China Rohs Regulation China RoHS declaration


Product out of China RoHS scope. Substance declaration for your information

Environmental Disclosure Product Environmental Profile

Circularity Profile End of Life Information

4 21 Mar 2024
Product datasheet
Specifications

Circuit breaker ComPacT


NSX400F, 36kA at 415VAC,
MicroLogic 2.3 trip unit 400A, 4
poles 4d
C40F42D400

Main
Range ComPacT new generation

Product Name ComPacT NSX new generation

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Device Short Name NSX400F

Product Or Component Type Circuit breaker

Device Application Distribution

Poles Description 4P

Protected Poles Description 4D


3D + N/2
3D

Neutral Position Left

[In] Rated Current 400 A at 40 °C

[Ue] Rated Operational Voltage 690 V AC 50/60 Hz

Network Type AC

Network Frequency 50/60 Hz

Suitability For Isolation Yes conforming to EN/IEC 60947-2

Utilisation Category Category A

[Icu] Rated Ultimate Short-Circuit 40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Breaking Capacity 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
30 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
20 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
20 kA at 600 V AC 50/60 Hz conforming to UL 508

Performance Level F 36 kA 415 V AC

Trip Unit Name MicroLogic 2.3

Trip Unit Technology Electronic

Trip Unit Protection Functions LSoI

Control Type Toggle

Circuit Breaker Mounting Mode Fixed

Complementary
[Ui] Rated Insulation Voltage 800 V AC 50/60 Hz

[Uimp] Rated Impulse Withstand 8 kV


Voltage

21 Mar 2024 1
[Ics] Rated Service Short-Circuit 40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Breaking Capacity 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
30 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
10 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2

Mechanical Durability 15000 cycles

Electrical Durability 12000 cycles at 440 V In/2


6000 cycles at 440 V In
6000 cycles at 690 V In/2
3000 cycles at 690 V In

Power Dissipation Per Pole 19.2 W

Mounting Support Backplate

Mounting Position Horizontal and vertical


Flat on the back

Upside Connection Front

Downside Connection Front

Connection Pitch 45 mm

Protection Type L : for overload protection (long time)


So : for short time short-circuit protection with fixed delay
I : for instantaneous short-circuit protection

Trip Unit Rating 400 A at 40 °C

Long-Time Pick-Up Adjustment Adjustable 9 settings


Type Ir (Thermal Protection)
[Ir] Long-Time Protection Pick-Up 160…400 A
Adjustment Range
Long-Time Protection Delay Fixed
Adjustment Type Tr
[Tr] Long-Time Protection Delay 400 s at 1.5 x Ir
Adjustment Range 16 s at 6 x Ir
11 s at 7.2 x Ir

Neutral Protection Settings 0.5 x Ir (3D + N/2)


1 x Ir (4D)
No protection (3D)

Thermal Memory 20 minutes before and after tripping

Short-Time Protection Pick-Up Adjustable 9 settings


Adjustment Type Isd
[Isd] Short-Time Protection Pick- 1.5...10 x Ir
Up Adjustment Range
Short-Time Protection Delay Fixed
Adjustment Type Tsd
Instantaneous Protection Pick-Up Fixed
Adjustment Type Ii
[Ii] Instantaneous Protection Pick- 4800 A
Up Adjustment Range
Earth-Leakage Protection Without

Zone Selective Interlocking Zsi Without

Number Of Slots For Electrical 6 slot(s)


Auxiliaries
Local Signalling Flashing LED (green) for ready to operate
LED 105 % Ir (red) for overload
LED 90 % Ir (orange) for overload

Width (W) 185 mm

Height (H) 255 mm

Depth (D) 110 mm

Net Weight 7.9 kg

2 21 Mar 2024
Environment
Standards EN/IEC 60947

Product Certifications CCC


EAC
Marine

Overvoltage Category Class II

Electrical Shock Protection Class Class II

Pollution Degree 3 conforming to IEC 60664-1

Ip Degree Of Protection IP40 conforming to IEC 60529

Ik Degree Of Protection IK07 conforming to IEC 62262

Ambient Air Temperature For -25…70 °C


Operation
Ambient Air Temperature For -50…85 °C
Storage
Relative Humidity 0…95 %

Operating Altitude 0...2000 m without derating


2000 m...5000 m with derating

Packing Units
Unit Type Of Package 1 PCE

Number Of Units In Package 1 1

Package 1 Height 15.0 cm

Package 1 Width 20.0 cm

Package 1 Length 29.0 cm

Package 1 Weight 7.306 kg

Unit Type Of Package 2 S04

Number Of Units In Package 2 2

Package 2 Height 30.0 cm

Package 2 Width 40.0 cm

Package 2 Length 60.0 cm

Package 2 Weight 15.362 kg

21 Mar 2024 3
Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right

Transparency RoHS/REACh

Well-being performance

 Mercury Free

 Rohs Exemption Information Yes

 Pvc Free

 Halogen Free Plastic Parts Product

Certifications & Standards


Reach Regulation REACh Declaration

Eu Rohs Directive Compliant with Exemptions

China Rohs Regulation China RoHS declaration


Product out of China RoHS scope. Substance declaration for your information

Environmental Disclosure Product Environmental Profile

Circularity Profile End of Life Information

4 21 Mar 2024
Product datasheet
Specifications

miniature circuit breaker - iK60N -


1P - 2 A - C curve
A9K24102

Main
Device Application Distribution

Range Acti9

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product Name Acti9 iK60

Product Or Component Type Miniature circuit-breaker

Device Short Name iK60N

Poles Description 1P

Number Of Protected Poles 1

[In] Rated Current 2 A at 30 °C

Network Type AC

Trip Unit Technology Thermal-magnetic

Curve Code C

Breaking Capacity 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1

Suitability For Isolation Yes conforming to EN/IEC 60898-1

Standards EN/IEC 60898-1

Product Certifications SNI

Complementary
Network Frequency 50/60 Hz

Magnetic Tripping Limit 5...10 x In

[Ics] Rated Service Breaking 6000 A 100 % conforming to EN/IEC 60898-1 - 230 V AC 50/60 Hz
Capacity
Limitation Class 3 conforming to EN/IEC 60898-1

[Ui] Rated Insulation Voltage 440 V AC 50/60 Hz conforming to EN/IEC 60898-1

[Uimp] Rated Impulse Withstand 4 kV conforming to EN/IEC 60898-1


Voltage
Contact Position Indicator No

Control Type Toggle

Local Signalling ON/OFF indication

Mounting Mode Clip-on

Mounting Support DIN rail

9 Mm Pitches 2

Height 85 mm

Width 18 mm

Mar 21, 2024 1


Depth 78.5 mm

Net Weight 100 g

Colour White

Mechanical Durability 20000 cycles

Electrical Durability 10000 cycles

Locking Options Description Padlocking device

Connections - Terminals Tunnel type terminal (top or bottom) 1…25 mm² rigid
Tunnel type terminal (top or bottom) 1…16 mm² flexible

Wire Stripping Length 14 mm for top or bottom connection

Tightening Torque 2 N.m top or bottom

Earth-Leakage Protection Without

Environment
Ip Degree Of Protection IP20 conforming to IEC 60529

Pollution Degree 2 conforming to EN/IEC 60898-1

Overvoltage Category II

Ambient Air Temperature For -25…60 °C


Operation
Ambient Air Temperature For -40…85 °C
Storage

Packing Units
Unit Type Of Package 1 PCE

Number Of Units In Package 1 1

Package 1 Height 2.000 cm

Package 1 Width 7.500 cm

Package 1 Length 9.500 cm

Package 1 Weight 112.000 g

Unit Type Of Package 2 BB1

Number Of Units In Package 2 12

Package 2 Height 8.500 cm

Package 2 Width 9.500 cm

Package 2 Length 22.000 cm

Package 2 Weight 1.399 kg

Unit Type Of Package 3 S03

Number Of Units In Package 3 132

Package 3 Height 30.000 cm

Package 3 Width 30.000 cm

Package 3 Length 40.000 cm

Package 3 Weight 15.745 kg

Contractual warranty
Warranty 12 months

2 Mar 21, 2024


Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right

Transparency RoHS/REACh

Well-being performance

 Mercury Free

 Rohs Exemption Information Yes

 Halogen Free Product

Certifications & Standards


Reach Regulation REACh Declaration

Eu Rohs Directive Compliant with Exemptions

China Rohs Regulation China RoHS declaration


Product out of China RoHS scope. Substance declaration for your information

Environmental Disclosure Product Environmental Profile

Weee The product must be disposed on European Union markets following specific waste
collection and never end up in rubbish bins

Circularity Profile No need of specific recycling operations

Mar 21, 2024 3


Product datasheet
Specifications

Easy9 RCBO 240V - 1P + N - 16A -


C curve - 6000 A - 30 mA
EZ9D56816

notification_critical_stroke Discontinued on: 2 Apr 2021

notification_critical_stroke Discontinued

Main
Range Easy9

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product Or Component Type Residual current breaker with overcurrent protection (RCBO)

Device Short Name Easy9 RCBO

Poles 1P + Ns

Neutral Position Left

[In] Rated Current 16 A

Earthing System TN

Network Type AC

Trip Unit Technology Thermal-magnetic

Curve Code C

Earth-Leakage Sensitivity 30 mA

Earth-Leakage Protection Time Instantaneous


Delay
Earth-Leakage Protection Class Type A

Breaking Capacity 6000 A Icn at 240 V AC 50 Hz conforming to BS EN 61009-1

Complementary
Device Application Distribution

Device Location In System Outgoer

Network Frequency 50 Hz

[Ue] Rated Operational Voltage 240 V AC 50 Hz

Magnetic Tripping Limit 3...5 x In

Residual Current Tripping Voltage dependent functional earth


Technology
Limitation Class 3

[Ui] Rated Insulation Voltage 500 V

[Uimp] Rated Impulse Withstand 4 kV


Voltage
Contact Position Indicator Yes

Control Type Toggle

Mounting Support DIN rail

9 Mm Pitches 2

Height 110 mm

21 Mar 2024 1
Width 18 mm

Depth 72 mm

Net Weight 180 g

Colour Grey (RAL 7035)

Mechanical Durability 10000 cycles

Electrical Durability 4000 cycles 240 V AC 50 Hz

Connections - Terminals Tunnel type terminal (top) 25 mm² rigid


Tunnel type terminal (bottom) 16 mm² rigid
Tunnel type terminal (bottom) 16 mm² flexible
Cable (top) 2 cable(s) flexible

Tightening Torque 2 N.m top or bottom

Earth-Leakage Protection Integrated

Environment
Standards BS EN 61009-1

Product Certifications CE

Overvoltage Category IV

Tropicalisation 2

Relative Humidity 95 % at 55 °C

Ambient Air Temperature For -15…60 °C


Operation
Ambient Air Temperature For -40…85 °C
Storage

Packing Units
Unit Type Of Package 1 PCE

Number Of Units In Package 1 1

Package 1 Height 7.5 cm

Package 1 Width 9.5 cm

Package 1 Length 1.8 cm

Package 1 Weight 211 g

Unit Type Of Package 2 S02

Number Of Units In Package 2 34

Package 2 Height 15 cm

Package 2 Width 30 cm

Package 2 Length 40 cm

Package 2 Weight 7174 g

Unit Type Of Package 3 P12

Number Of Units In Package 3 1088

Package 3 Height 70 cm

Package 3 Width 120 cm

Package 3 Length 80 cm

Package 3 Weight 229568 g

2 21 Mar 2024
Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right

Sustainable Packaging

Resource performance

 Sustainable Packaging

Well-being performance

 Mercury Free

 Rohs Exemption Information Yes

Reach Regulation REACh Declaration

Eu Rohs Directive Compliant with Exemptions

China Rohs Regulation China RoHS declaration


Product out of China RoHS scope. Substance declaration for your information

Weee The product must be disposed on European Union markets following specific waste
collection and never end up in rubbish bins

21 Mar 2024 3
Product datasheet
Specifications

Easy9 RCBO 240V - 1P + N - 20A -


C curve - 6000 A - 30 mA
EZ9D56820

notification_critical_stroke Discontinued on: 2 Apr 2021

notification_critical_stroke Discontinued

Main
Range Easy9

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product Or Component Type Residual current breaker with overcurrent protection (RCBO)

Device Short Name Easy9 RCBO

Poles 1P + Ns

Neutral Position Left

[In] Rated Current 20 A

Earthing System TN

Network Type AC

Trip Unit Technology Thermal-magnetic

Curve Code C

Earth-Leakage Sensitivity 30 mA

Earth-Leakage Protection Time Instantaneous


Delay
Earth-Leakage Protection Class Type A

Breaking Capacity 6000 A Icn at 240 V AC 50 Hz conforming to BS EN 61009-1

Complementary
Device Application Distribution

Device Location In System Outgoer

Network Frequency 50 Hz

[Ue] Rated Operational Voltage 240 V AC 50 Hz

Magnetic Tripping Limit 3...5 x In

Residual Current Tripping Voltage dependent functional earth


Technology
Limitation Class 3

[Ui] Rated Insulation Voltage 500 V

[Uimp] Rated Impulse Withstand 4 kV


Voltage
Contact Position Indicator Yes

Control Type Toggle

Mounting Support DIN rail

9 Mm Pitches 2

Height 110 mm

21 Mar 2024 1
Width 18 mm

Depth 72 mm

Net Weight 180 g

Colour Grey (RAL 7035)

Mechanical Durability 10000 cycles

Electrical Durability 4000 cycles 240 V AC 50 Hz

Connections - Terminals Tunnel type terminal (top) 25 mm² rigid


Tunnel type terminal (bottom) 16 mm² rigid
Tunnel type terminal (bottom) 16 mm² flexible
Cable (top) 2 cable(s) flexible

Tightening Torque 2 N.m top or bottom

Earth-Leakage Protection Integrated

Environment
Standards BS EN 61009-1

Product Certifications CE

Overvoltage Category IV

Tropicalisation 2

Relative Humidity 95 % at 55 °C

Ambient Air Temperature For -15…60 °C


Operation
Ambient Air Temperature For -40…85 °C
Storage

Packing Units
Unit Type Of Package 1 PCE

Number Of Units In Package 1 1

Package 1 Height 7.5 cm

Package 1 Width 9.5 cm

Package 1 Length 1.8 cm

Package 1 Weight 211 g

Unit Type Of Package 2 S02

Number Of Units In Package 2 34

Package 2 Height 15 cm

Package 2 Width 30 cm

Package 2 Length 40 cm

Package 2 Weight 7174 g

Unit Type Of Package 3 P12

Number Of Units In Package 3 1088

Package 3 Height 70 cm

Package 3 Width 120 cm

Package 3 Length 80 cm

Package 3 Weight 229568 g

2 21 Mar 2024
Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right

Sustainable Packaging

Resource performance

 Sustainable Packaging

Well-being performance

 Mercury Free

 Rohs Exemption Information Yes

Reach Regulation REACh Declaration

Eu Rohs Directive Compliant with Exemptions

China Rohs Regulation China RoHS declaration


Product out of China RoHS scope. Substance declaration for your information

Weee The product must be disposed on European Union markets following specific waste
collection and never end up in rubbish bins

21 Mar 2024 3
Product datasheet
Specifications

Earth-leakage VigiPacT add-on


protection module, ComPacT NSX
250, 200VAC to 440VAC, 30mA to
30A, 4 poles
LV429493

Main
Range Of Product ComPacT NSX100...250 new generation
ComPact NSX100...250

Device Short Name VigiPacT

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product Or Component Type Vigi add-on

Device Application Wiring

Range Compatibility ComPacT new generation ComPacT NSX250 new generation circuit breaker
ComPact ComPact NSX250 circuit breaker

Poles Description 4P

[In] Rated Current 250 A

Earth-Leakage Protection Class Class A


Class AC

Residual Earth-Leakage Sensitity Adjustable


Adjustment Type
Earth-Leakage Sensitivity 0.03 A for class A
0.1 A for class A
0.3 A for class A
0.5 A for class A
1 A for class A
3 A for class A
10 A for class AC
30 A for class AC

Residual Earth-Leakage Time Adjustable


Delay Adjustment Type
[Δt] Residual Earth-Leakage Time 0 ms
Delay Adjustment 60 ms
150 ms
300 ms
500 ms
800 ms
1.2 s
4s

Complementary
Network Type AC

Network Frequency 50/60 Hz

[Ue] Rated Operational Voltage 200...440 V AC 50/60 Hz conforming to IEC 60947-2

Earth-Leakage Protection With

Maximum Breaking Time 800 ms

Overvoltage Category IV

Environment
Electrical Shock Protection Class Class II

21 Mar 2024 1
Standards IEC 60947-2

Packing Units
Unit Type Of Package 1 PCE

Number Of Units In Package 1 1

Package 1 Height 13.5 cm

Package 1 Width 14.2 cm

Package 1 Length 17.2 cm

Package 1 Weight 1.34 kg

Unit Type Of Package 2 S04

Number Of Units In Package 2 12

Package 2 Height 30.0 cm

Package 2 Width 40.0 cm

Package 2 Length 60.0 cm

Package 2 Weight 16.52 kg

Unit Type Of Package 3 P12

Number Of Units In Package 3 48

Package 3 Height 42.0 cm

Package 3 Width 80.0 cm

Package 3 Length 120.0 cm

Package 3 Weight 78.0 kg

2 21 Mar 2024
Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right

Transparency RoHS/REACh

Well-being performance

 Mercury Free

 Rohs Exemption Information Yes

Certifications & Standards


Reach Regulation REACh Declaration

Eu Rohs Directive Compliant with Exemptions

China Rohs Regulation China RoHS declaration


Product out of China RoHS scope. Substance declaration for your information

Environmental Disclosure Product Environmental Profile

Weee The product must be disposed on European Union markets following specific waste
collection and never end up in rubbish bins

Circularity Profile End of Life Information

21 Mar 2024 3
Product datasheet
Specifications

Earth-leakage VigiPacT add-on


protection module. ComPacT NSX
400/630. 440 VAC to 550 VAC. 30
mA to 30 A. 4 poles
LV432467

Price: 26,787.42 ZAR

Main
Range Of Product ComPacT NSX400...630 new generation
ComPact NSX400...630

Device Short Name VigiPacT

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product Or Component Type Vigi add-on

Device Application Wiring

Range Compatibility ComPacT new generation ComPacT NSX400 new generation circuit breaker
ComPacT new generation ComPacT NSX630 new generation circuit breaker
ComPact ComPact NSX400 circuit breaker
ComPact ComPact NSX630 circuit breaker

Poles Description 4P

[In] Rated Current 400 A


630 A

Earth-Leakage Protection Class Class A


Class AC

Residual Earth-Leakage Sensitity Adjustable


Adjustment Type
Earth-Leakage Sensitivity 0.03 A for class A
0.1 A for class A
0.3 A for class A
0.5 A for class A
1 A for class A
3 A for class A
10 A for class AC
30 A for class AC

Residual Earth-Leakage Time Adjustable


Delay Adjustment Type
[Δt] Residual Earth-Leakage Time 0 ms
Delay Adjustment 60 ms
150 ms
300 ms
500 ms
800 ms
1.2 s
4s

Complementary
Network Type AC

Network Frequency 50/60 Hz

[Ue] Rated Operational Voltage 440...550 V AC 50/60 Hz conforming to IEC 60947-2

Earth-Leakage Protection With

Maximum Breaking Time 800 ms

Overvoltage Category IV

Excluding VAT and subject to change. Please check with your local distributor through "Where to buy"

21 Mar 2024 1
Environment
Electrical Shock Protection Class Class II

Standards IEC 60947-2

Packing Units
Unit Type Of Package 1 PCE

Number Of Units In Package 1 1

Package 1 Height 14.0 cm

Package 1 Width 17.0 cm

Package 1 Length 20.0 cm

Package 1 Weight 3.356 kg

Unit Type Of Package 2 S03

Number Of Units In Package 2 3

Package 2 Height 30.0 cm

Package 2 Width 30.0 cm

Package 2 Length 40.0 cm

Package 2 Weight 10.468 kg

2 21 Mar 2024
Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right

Transparency RoHS/REACh

Well-being performance

 Mercury Free

 Rohs Exemption Information Yes

Certifications & Standards


Reach Regulation REACh Declaration

Eu Rohs Directive Compliant with Exemptions

China Rohs Regulation China RoHS declaration


Product out of China RoHS scope. Substance declaration for your information

Environmental Disclosure Product Environmental Profile

Weee The product must be disposed on European Union markets following specific waste
collection and never end up in rubbish bins

Circularity Profile End of Life Information

21 Mar 2024 3
Product datasheet
Specifications

Earth-leakage VigiPacT add-on


protection module, ComPacT NSX
100/160, 200VAC to 440VAC,
30mA to 30A, 4 poles
LV429489

EAN Code: 3606481298553

Main
Range Of Product ComPacT NSX100...250 new generation
ComPact NSX100...250

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Device Short Name VigiPacT

Product Or Component Type Vigi add-on

Device Application Wiring

Range Compatibility ComPacT new generation ComPacT NSX100 new generation circuit breaker
ComPacT new generation ComPacT NSX160 new generation circuit breaker
ComPact ComPact NSX100 circuit breaker
ComPact ComPact NSX160 circuit breaker

Poles Description 4P

[In] Rated Current 100 A


160 A

Earth-Leakage Protection Class Class A


Class AC

Residual Earth-Leakage Sensitity Adjustable


Adjustment Type
Earth-Leakage Sensitivity 0.03 A for class A
0.1 A for class A
0.3 A for class A
0.5 A for class A
1 A for class A
3 A for class A
10 A for class AC
30 A for class AC

Residual Earth-Leakage Time Adjustable


Delay Adjustment Type
[Δt] Residual Earth-Leakage Time 0 ms
Delay Adjustment 60 ms
150 ms
300 ms
500 ms
800 ms
1.2 s
4s

Complementary
Network Type AC

Network Frequency 50/60 Hz

[Ue] Rated Operational Voltage 200...440 V AC 50/60 Hz conforming to IEC 60947-2

Earth-Leakage Protection With

Maximum Breaking Time 800 ms

Overvoltage Category IV

21 Mar 2024 1
Environment
Electrical Shock Protection Class Class II

Standards IEC 60947-2

Packing Units
Unit Type Of Package 1 PCE

Number Of Units In Package 1 1

Package 1 Height 13.400 cm

Package 1 Width 14.500 cm

Package 1 Length 17.200 cm

Package 1 Weight 1.315 kg

Unit Type Of Package 2 S04

Number Of Units In Package 2 12

Package 2 Height 30.000 cm

Package 2 Width 40.000 cm

Package 2 Length 60.000 cm

Package 2 Weight 16.430 kg

Unit Type Of Package 3 P12

Number Of Units In Package 3 48

Package 3 Height 42.000 cm

Package 3 Width 80.000 cm

Package 3 Length 120.000 cm

Package 3 Weight 80.000 kg

Contractual warranty
Warranty 18 months

2 21 Mar 2024
Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right

Transparency RoHS/REACh

Well-being performance

 Mercury Free

 Rohs Exemption Information Yes

Certifications & Standards


Reach Regulation REACh Declaration

Eu Rohs Directive Compliant with Exemptions

China Rohs Regulation China RoHS declaration


Product out of China RoHS scope. Substance declaration for your information

Environmental Disclosure Product Environmental Profile

Weee The product must be disposed on European Union markets following specific waste
collection and never end up in rubbish bins

Circularity Profile End of Life Information

21 Mar 2024 3
Product datasheet
Specifications

Complete selector switch Easy


Harmony XA2, plastic, black,
22mm, long handle, 2 positions,
stay put, 1NO + 1NC
XA2EJ25

Main
Range Of Product Easy Harmony XA2

Product Or Component Type Complete selector switch

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Device Short Name XA2

Bezel Material Plastic

Mounting Diameter 22.5 mm

Complementary
Sale Per Indivisible Quantity 1

Fixing Center >= 30 x 40 mm (panel) - thickness: 1…5 mm

Fixing Mode Fixing nut: 2…2.4 N.m

Shape Of Signaling Unit Head Round

Type Of Operator stay put

Operator Profile Black long handle

Operator Position Information 2 positions 90°

Contacts Type And Composition 1 NO + 1 NC

Contact Operation Slow-break

Mechanical Durability 300000 cycles

Connections - Terminals , clamping capacity: <= 2 x 1.5 mm²


, clamping capacity: <= 1 x 2.5 mm²
, clamping capacity: >= 1 x 0.5 mm²
Faston terminals, connection size: 6.3 mm

Tightening Torque 0.8 N.m

Short-Circuit Protection 10 A fuse type gL conforming to IEC 60269-1

[Ith] Conventional Free Air 10 A (screw-clamp terminals)


Thermal Current
[Ui] Rated Insulation Voltage 600 V conforming to IEC 60947-1

[Uimp] Rated Impulse Withstand 6 kV conforming to IEC 60947-1


Voltage
[Ie] Rated Operational Current 3 A at 240 V, AC-15, A600
0.27 A at 250 V, DC-13, Q600

Electrical Durability 500000 cycles, AC-15, 3 A at 230 V, operating rate <60 cyc/mn, load factor: 0.5
conforming to IEC 60947-5-4
500000 cycles, DC-13, 0.2 A at 110 V, operating rate <60 cyc/mn, load factor: 0.5
conforming to IEC 60947-5-4

Electrical Reliability Λ < 10exp(-8) at 24 V

Width 30 mm

21 Mar 2024 1
Height 48.5 mm

Depth 68.2 mm

Net Weight 0.041 kg

Type Of Operator Stay put

Operator Profile Long handle

Head Type Standard

Cap/Operator Or Lens Colour Black

Environment
Protective Treatment TC

Ambient Air Temperature For -40…70 °C


Storage
Ambient Air Temperature For -25…55 °C
Operation
Overvoltage Category Class I conforming to IEC 536

Ip Degree Of Protection IP65 conforming to IEC 60529

Ik Degree Of Protection IK06 conforming to IEC 60529

Standards IEC 60947-5-1


IEC 60947-1
GB 14048.1
GB 14048.5

Product Certifications CE
CCC

Vibration Resistance 10 gn (f= 40…500 Hz) conforming to IEC 60068-2-6

Shock Resistance 120 gn (duration = 11 ms) for half sine wave acceleration conforming to IEC
60068-2-27

Packing Units
Unit Type Of Package 1 PCE

Number Of Units In Package 1 1

Package 1 Height 3.0 cm

Package 1 Width 5.0 cm

Package 1 Length 7.0 cm

Package 1 Weight 71.0 g

Unit Type Of Package 2 S02

Number Of Units In Package 2 100

Package 2 Height 15.0 cm

Package 2 Width 30.0 cm

Package 2 Length 40.0 cm

Package 2 Weight 7.15 kg

Unit Type Of Package 3 PAL

Number Of Units In Package 3 2000

Package 3 Height 60.0 cm

Package 3 Width 80.0 cm

Package 3 Length 90.0 cm

2 21 Mar 2024
Package 3 Weight 142.2 kg

21 Mar 2024 3
Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right

Transparency RoHS/REACh

Well-being performance

 Reach Free Of Svhc

 Mercury Free

 Rohs Exemption Information Yes

Certifications & Standards


Reach Regulation REACh Declaration

Eu Rohs Directive Pro-active compliance (Product out of EU RoHS legal scope)

EU RoHS Declaration

China Rohs Regulation China RoHS declaration

Environmental Disclosure Product Environmental Profile

Weee The product must be disposed on European Union markets following specific waste
collection and never end up in rubbish bins

Circularity Profile End of Life Information

4 21 Mar 2024
Product datasheet XA2EJ25

Dimensions Drawings

Dimensions

(e) Clamping thickness: 1 to 6 mm / 0.04 to 0.24 in.

21 Mar 2024 5
Product datasheet XA2EJ25

Mounting and Clearance

Panel Cut-out for Pushbuttons, Switches and Pilot Lights (Finished Holes, Ready for
Installation)

Connection by Screw Clamp Terminals

(1) Diameter on finished panel or support


(2) For selector switches and Emergency stop buttons, use of an anti-rotation plate type ZB5AZ902 is recommended.
(3) Ø22.5 mm recommended (Ø22.3 0+0.4) / Ø0.89 in. recommended (Ø0.88 in. 0+0.016)
Connections a in mm a in in. b in mm b in in.

By screw clamp terminals connector 40 1.57 30 1.18

By Faston connectors 45 1.77 32 1.26

Detail of Lug Recess

(1) Diameter on finished panel or support


(2) For selector switches and Emergency stop buttons, use of an anti-rotation plate type ZB5AZ902 is recommended.
(3) Ø22.5 mm recommended (Ø22.3 0+0.4) / Ø0.89 in. recommended (Ø0.88 in. 0+0.016)

6 21 Mar 2024
Product datasheet
Specifications

iC60N - miniature circuit breaker -


4P - 16A - C curve
A9F74416

Main
Device Application Distribution

Range Acti9

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product Name Acti9 iC60

Product Or Component Type Miniature circuit-breaker

Device Short Name IC60N

Poles Description 4P

Number Of Protected Poles 4

[In] Rated Current 16 A

Network Type DC
AC

Trip Unit Technology Thermal-magnetic

Curve Code C

Breaking Capacity 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1


36 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2
20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2
6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
36 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at <= 250 V DC conforming to EN/IEC 60947-2

Utilisation Category Category A conforming to EN 60947-2


Category A conforming to IEC 60947-2

Suitability For Isolation Yes conforming to EN 60898-1


Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2

Standards EN 60947-2
IEC 60898-1
EN 60898-1
IEC 60947-2

Complementary
Network Frequency 50/60 Hz

Magnetic Tripping Limit 8 x In +/- 20 %

Mar 21, 2024 1


[Ics] Rated Service Breaking 15 kA 75 % conforming to EN 60947-2 - 220...240 V AC 50/60 Hz
Capacity 7.5 kA 75 % conforming to EN 60947-2 - 380...415 V AC 50/60 Hz
4.5 kA 75 % conforming to EN 60947-2 - 440 V AC 50/60 Hz
15 kA 75 % conforming to IEC 60947-2 - 220...240 V AC 50/60 Hz
7.5 kA 75 % conforming to IEC 60947-2 - 380...415 V AC 50/60 Hz
4.5 kA 75 % conforming to IEC 60947-2 - 440 V AC 50/60 Hz
27 kA 75 % conforming to IEC 60947-2 - 12...133 V AC 50/60 Hz
27 kA 75 % conforming to EN 60947-2 - 12...133 V AC 50/60 Hz
6000 A 100 % conforming to EN 60898-1 - 400 V AC 50/60 Hz
6000 A 100 % conforming to IEC 60898-1 - 400 V AC 50/60 Hz
10 kA 100 % conforming to IEC 60947-2 - 180...250 V DC
10 kA 100 % conforming to EN 60947-2 - 180...250 V DC

Limitation Class 3 conforming to EN 60898-1


3 conforming to IEC 60898-1

[Ui] Rated Insulation Voltage 500 V AC 50/60 Hz conforming to EN 60947-2


500 V AC 50/60 Hz conforming to IEC 60947-2

[Uimp] Rated Impulse Withstand 6 kV conforming to EN 60947-2


Voltage 6 kV conforming to IEC 60947-2

Contact Position Indicator Yes

Control Type Toggle

Local Signalling Trip indicator

Mounting Mode Fixed

Mounting Support DIN rail

Comb Busbar And Distribution Top or bottom: YES


Block Compatibility
9 Mm Pitches 8

Height 85 mm

Width 72 mm

Depth 78.5 mm

Net Weight 0.5 kg

Colour White

Mechanical Durability 20000 cycles

Electrical Durability 10000 cycles

Connections - Terminals Single terminal (top or bottom) 1…25 mm² rigid


Single terminal (top or bottom) 1…16 mm² flexible

Wire Stripping Length 14 mm for top or bottom connection

Tightening Torque 2 N.m top or bottom

Earth-Leakage Protection Separate block

Environment
Ip Degree Of Protection IP20 conforming to IEC 60529
IP20 conforming to EN 60529

Pollution Degree 3 conforming to EN 60947-2


3 conforming to IEC 60947-2

Overvoltage Category IV

Tropicalisation 2 conforming to IEC 60068-1

Relative Humidity 95 % at 55 °C

Operating Altitude 0...2000 m

Ambient Air Temperature For -35…70 °C


Operation
Ambient Air Temperature For -40…85 °C
Storage

2 Mar 21, 2024


Packing Units
Unit Type Of Package 1 PCE

Number Of Units In Package 1 1

Package 1 Height 7.100 cm

Package 1 Width 7.300 cm

Package 1 Length 9.300 cm

Package 1 Weight 430.000 g

Unit Type Of Package 2 BB1

Number Of Units In Package 2 3

Package 2 Height 8.200 cm

Package 2 Width 10.000 cm

Package 2 Length 22.600 cm

Package 2 Weight 1.358 kg

Unit Type Of Package 3 S03

Number Of Units In Package 3 33

Package 3 Height 30.000 cm

Package 3 Width 30.000 cm

Package 3 Length 40.000 cm

Package 3 Weight 15.620 kg

Contractual warranty
Warranty 12 months

Mar 21, 2024 3


Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right

Transparency RoHS/REACh

Well-being performance

 Mercury Free

 Rohs Exemption Information Yes

 Halogen Free Product

Certifications & Standards


Reach Regulation REACh Declaration

Eu Rohs Directive Compliant with Exemptions

China Rohs Regulation China RoHS declaration


Product out of China RoHS scope. Substance declaration for your information

Environmental Disclosure Product Environmental Profile

Weee The product must be disposed on European Union markets following specific waste
collection and never end up in rubbish bins

Circularity Profile No need of specific recycling operations

4 Mar 21, 2024


Product datasheet
Specifications

Easy9 Residual Current Circuit


Breaker - 4P - 40A - 30 mA - AC
type - 400 V
EZ9R36440

Main
Range Of Product Easy9

Product Or Component Type Residual current circuit breaker (RCCB)

Device Short Name Easy9 RCCB

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Poles 4P

Neutral Position Left

[In] Rated Current 40 A

Network Type AC

Earth-Leakage Sensitivity 30 mA

Earth-Leakage Protection Time Instantaneous


Delay
Earth-Leakage Protection Class Type AC

Rated Breaking And Making 500 A


Capacity
Rated Conditional Short-Circuit Easy9 MCB: 6000 A 40 A
Current

Complementary
Device Location In System Outgoer

Network Frequency 50/60 Hz

[Ue] Rated Operational Voltage 400 V AC 50/60 Hz

Residual Current Tripping Voltage independent


Technology
[Ui] Rated Insulation Voltage 440 V AC

[Uimp] Rated Impulse Withstand 4 kV


Voltage
Surge Current 250 A

Contact Position Indicator Yes

Control Type Toggle

Mounting Mode Clip-on

Mounting Support DIN rail

Comb Busbar And Distribution Top: YES


Block Compatibility
Connection Pitch 18 mm between phases

9 Mm Pitches 8

Height 82 mm

Width 72 mm

Excluding VAT, FCA Jabal Ali & are subject to change – check with your local distributor.

21 Mar 2024 1
Depth 72 mm

Colour Grey (RAL 7035)

Mechanical Durability 5000 cycles

Electrical Durability AC: 2000 cycles 400 V AC 50/60 Hz

Connections - Terminals Tunnel type terminal (top or bottom) 1…35 mm² rigid
Tunnel type terminal (top or bottom) 1…25 mm² flexible

Tightening Torque 3.5 N.m top or bottom

Environment
Standards IEC 61008-1

Product Certifications CE

Ip Degree Of Protection IP20

Pollution Degree 2 conforming to IEC 61008-1

Tropicalisation 2

Relative Humidity 95 % at 55 °C

Ambient Air Temperature For -5…60 °C


Operation
Ambient Air Temperature For -40…85 °C
Storage

Packing Units
Unit Type Of Package 1 PCE

Number Of Units In Package 1 1

Package 1 Height 8 cm

Package 1 Width 8 cm

Package 1 Length 9 cm

Package 1 Weight 354 g

Unit Type Of Package 2 BB1

Number Of Units In Package 2 3

Package 2 Height 9.2 cm

Package 2 Width 9.7 cm

Package 2 Length 25.5 cm

Package 2 Weight 1.57 kg

Unit Type Of Package 3 S03

Number Of Units In Package 3 27

Package 3 Height 30 cm

Package 3 Width 30 cm

Package 3 Length 40 cm

Package 3 Weight 12.744 kg

2 21 Mar 2024
Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right

Transparency RoHS/REACh

Well-being performance

 Mercury Free

 Rohs Exemption Information Yes

 Halogen Free Plastic Parts & Cables


Product

Certifications & Standards


Reach Regulation REACh Declaration

Eu Rohs Directive Compliant with Exemptions

China Rohs Regulation China RoHS declaration


Product out of China RoHS scope. Substance declaration for your information

Environmental Disclosure Product Environmental Profile

Weee The product must be disposed on European Union markets following specific waste
collection and never end up in rubbish bins

Circularity Profile No need of specific recycling operations

21 Mar 2024 3
Product datasheet
Specifications

Monolithic pilot light, Easy


Harmony XA2, plastic, white,
22mm, integral LED, screw clamp
terminals, 220…230V AC, anti
interference
XA2EVM1LC

Main
Range Of Product Easy Harmony XA2

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product Or Component Type Monolithic pilot light

Device Short Name XA2

Mounting Diameter 22.5 mm

Shape Of Signaling Unit Head Round

Cap/Operator Or Lens Colour White

Light Source LED

Bulb Base Integral LED

[Us] Rated Supply Voltage 220...230 V AC 50/60 Hz

Complementary
Terminals Description Iso N°1 (X1-X2)PL

Device Mounting Fixing hole 22.3 +0.4/0 conforming to IEC 60947-5-1

Fixing Center >= 30 x 40 mm (support panel) metal - thickness: 1…6 mm


>= 30 x 40 mm (support panel) plastic - thickness: 2…6 mm

Fixing Mode Fixing nut beneath head recommended torque: 2.2 N.m (+/- 0.2 N.m)

Marking CCC
CE

[Us] Rated Supply Voltage 220...230 V

Connections - Terminals Screw clamp terminals, <= 2 x 1.5 mm² with cable end conforming to IEC 60947-1
Screw clamp terminals, 1 x 0.5...1 x 2.5 mm² without cable end conforming to IEC
60947-1

Shape Of Screw Head Cross compatible with Philips No 2 screwdriver


Slotted compatible with flat Ø 4 mm screwdriver
Slotted compatible with flat Ø 5.5 mm screwdriver

[Ui] Rated Insulation Voltage 400 V (pollution degree 3) conforming to IEC 60947-1

[Uimp] Rated Impulse Withstand 6 kV conforming to IEC 60947-1


Voltage
Signalling Type Steady

Supply Voltage Limits 0.8…1.2 V AC

Current Consumption <= 20 mA

Service Life 40000 h at rated voltage and 25 °C

Height 29 mm

Width 29 mm

21 Mar 2024 1
Depth 53 mm

Net Weight 0.02 kg

Environment
Ambient Air Temperature For -40…70 °C
Storage
Ambient Air Temperature For -25…70 °C
Operation
Overvoltage Category Class I conforming to IEC 536

Ip Degree Of Protection IP65 conforming to IEC 60529

Ik Degree Of Protection IK05

Standards GB 14048.5
IEC 60947-5-1
IEC 60947-1
GB 14048.1
IEC 60529
IEC 50102

Product Certifications CE
CCC

Vibration Resistance 5 gn (f= 12…500 Hz) conforming to IEC 60068-2-6

Shock Resistance 30 gn (duration = 11 ms) for half sine wave acceleration conforming to IEC
60068-2-27

Packing Units
Unit Type Of Package 1 PCE

Number Of Units In Package 1 1

Package 1 Height 5.300 cm

Package 1 Width 2.900 cm

Package 1 Length 2.900 cm

Package 1 Weight 21.000 g

Unit Type Of Package 2 BB1

Number Of Units In Package 2 10

Package 2 Height 8.000 cm

Package 2 Width 22.000 cm

Package 2 Length 29.500 cm

Package 2 Weight 216.000 kg

Unit Type Of Package 3 S02

Number Of Units In Package 3 160

Package 3 Height 15.000 cm

Package 3 Width 30.000 cm

Package 3 Length 40.000 cm

Package 3 Weight 5.800 kg

2 21 Mar 2024
Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right

Transparency RoHS/REACh

Well-being performance

 Reach Free Of Svhc

 Toxic Heavy Metal Free

 Mercury Free

 Rohs Exemption Information Yes

Certifications & Standards


Reach Regulation REACh Declaration

Eu Rohs Directive Pro-active compliance (Product out of EU RoHS legal scope)

EU RoHS Declaration

China Rohs Regulation China RoHS declaration

Environmental Disclosure Product Environmental Profile

Weee The product must be disposed on European Union markets following specific waste
collection and never end up in rubbish bins

Circularity Profile End of Life Information

21 Mar 2024 3
Product datasheet XA2EVM1LC

Dimensions Drawings

Dimensions

e : Calmping thickness:1 to 6 mm/0.04 to 0.24 in.

4 21 Mar 2024
Product datasheet XA2EVM1LC

Mounting and Clearance

Mounting

Diameter of Finished Fixing Holes

(1) Minimum value.


(2) 40 mm/1.58 in. for Emergency switching off pushbutton only.
(3) Standard value: Ø 22.3 (0; + 0.4) mm/Ø 0.88 (0; + 0.02) in.

21 Mar 2024 5
Product datasheet XA2EVM1LC

Connections and Schema

Wiring Diagram

(1) LED

6 21 Mar 2024
Product datasheet
Specifications

EASYLOGIC DM6200H VAF PF


DPM RS48 CL1.0
METSEDM6200HCL10RS

Main
Range EasyLogic

Product Name EasyLogic DM6X00H RS

Device Short Name DM6200H

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product Or Component Type VAF PF meter

Complementary
Device Application Remote monitoring

Type Of Measurement Current


Voltage
Frequency
RPM

Metering Type Unbalance current


Rotation speed
Average current Iavg
Average voltage Vavg
Unbalance voltage
Phase currents
Frequency
Calculated neutral current
Voltage U21, U32, U13, V1, V2, V3

Counter Functions ON hour counting


Power interruption

[Us] Rated Supply Voltage 48...277 V AC 45...65 Hz


48...277 V DC

Network Frequency 60 Hz
50 Hz

[In] Rated Current 1A


5A

Type Of Network 3P + N
3P
1P + N
2P + N
2P

Maximum Power Consumption In 4 VA at 240 V between phase and neutral


Va
Maximum Power Consumption In 2 W at 240 V
W
Display Type 8 segments LED

Display Colour Red

Messages Display Capacity 3 fields of 4 characters

Display Digits 12 digit(s) - 14.2 mm in height

Price is “List Price” and may be subject to a trade discount – check with your local distributor or retailer for actual price.

Mar 21, 2024 1


Communication Of Data Instantaneous and demand values
Revolution speed
All counters
Reading of measurements

Tamperproof Of Settings Protected by access code

Sampling Rate 32 samples/cycle

Measurement Current 5…6000 mA

Signal Current 0.005...10 A (impedance 0.3 MOhm)6 x

Measurement Voltage 46…277 V AC 50...60 Hz between phase and neutral


80…480 V AC 50...60 Hz between phases
277…999000 V AC 50...60 Hz with external VT

Frequency Measurement Range 45…65 Hz

Number Of Inputs 2

Measurement Accuracy Frequency +/- 0.05 %


Power factor +/- 0.01
Current +/- 1 %
Voltage +/- 1 %

Accuracy Class Class 1

Demand Intervals 1s

Local Signalling Green LED: activity


Red LED: output signal 1...9999000 pulse/ k_h (kWh, kVAh, kVARh)

Communication Port Protocol Modbus at 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps even/odd or none - 2-wire,
insulation 2500 V

Communication Port Support Screw terminal block: RS485

Material Polycarbonate

Flame Retardance V-0 conforming to UL 94

Mounting Mode Flush-mounted

Mounting Support Framework

Installation Category III

Type Of Installation Indoor installation

Measurement Category Category III 480 V

Electrical Insulation Class Class II

Connections - Terminals Current circuit: screw clamp terminals (bottom) 2.08…3.31 mm² cable(s)
Voltage circuit: screw clamp terminals (top) 0.82…3.31 mm² cable(s)
Control circuit: screw clamp terminals (top) 0.82…3.31 mm² cable(s)
Communication: screw clamp terminals (bottom) 0.33…3.31 mm² cable(s)

Tightening Torque Current circuit: 0.9…1 N.m Philips No 2 screwdriver


Voltage circuit: 0.9…1 N.m Philips No 2 screwdriver
Control circuit: 0.9…1 N.m Philips No 2 screwdriver
Communication: 0.5…0.6 N.m Philips no 1 screwdriver

Wire Stripping Length Current circuit: 3.68 mm


Voltage circuit: 7 mm
Control circuit: 7 mm
Communication: 7 mm

Standards IEC 61010-1:ed. 3


UL 61010-1:ed. 3

Product Certifications CE conforming to IEC 61010-1


CULus conforming to UL 61010-1
CULus conforming to CSA C22.2 No 61010-1
C-Tick

Width 96 mm

2 Mar 21, 2024


Depth 13 mm outside:
49 mm panel:

Height 96 mm

Net Weight 300 g

Environment
Electromagnetic Compatibility Electrostatic discharge conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test conforming to IEC
61000-4-3
Electrical fast transient/burst immunity test conforming to IEC 61000-4-4
Surge immunity test conforming to IEC 61000-4-5
Conducted RF disturbances conforming to IEC 61000-4-6
Magnetic field at power frequency conforming to IEC 61000-4-8
Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
Emission tests conforming to FCC part 15 class A
Emission tests conforming to FCC part 15 Subpart C
Emission tests conforming to FCC part 15 Subpart E

Overvoltage Category III

Ip Degree Of Protection IP51 front: conforming to IEC 60529


IP30 body: conforming to IEC 60529

Relative Humidity 5…95 % at 50 °C

Pollution Degree 2

Ambient Air Temperature For -10…60 °C


Operation
Ambient Air Temperature For -20…70 °C
Storage
Operating Altitude <= 2000 m

Service Life 7 year(s)

Packing Units
Unit Type Of Package 1 PCE

Number Of Units In Package 1 1

Package 1 Height 8.905 cm

Package 1 Width 11.903 cm

Package 1 Length 12.229 cm

Package 1 Weight 360 g

Unit Type Of Package 2 S03

Number Of Units In Package 2 18

Package 2 Height 30 cm

Package 2 Width 30 cm

Package 2 Length 40 cm

Package 2 Weight 6480 g

Unit Type Of Package 3 P12

Number Of Units In Package 3 288

Package 3 Height 75 cm

Package 3 Width 80 cm

Package 3 Length 120 cm

Package 3 Weight 133.5 kg

Mar 21, 2024 3


Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right

Transparency RoHS/REACh

Well-being performance

 Mercury Free

 Rohs Exemption Information Yes

Certifications & Standards


Reach Regulation REACh Declaration

Eu Rohs Directive Compliant with Exemptions

China Rohs Regulation China RoHS declaration

Environmental Disclosure Product Environmental Profile

Circularity Profile End of Life Information

4 Mar 21, 2024


Product datasheet
Specifications

Miniature circuit-breaker, Acti9


iC60N, 2P, 16 A, C curve, 6000 A
(IEC 60898-1), 10 kA (IEC
60947-2)
A9F74216

EAN Code: 3606480079566

Main
Device Application Distribution

Range Acti9

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product Name Acti9 iC60

Product Or Component Type Miniature circuit-breaker

Device Short Name IC60N

Poles Description 2P

Number Of Protected Poles 2

[In] Rated Current 16 A

Network Type AC
DC

Trip Unit Technology Thermal-magnetic

Curve Code C

Breaking Capacity 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1


36 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at <= 125 V DC conforming to EN/IEC 60947-2
10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2
20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2
6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
36 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2

Utilisation Category Category A conforming to EN 60947-2


Category A conforming to IEC 60947-2

Suitability For Isolation Yes conforming to EN 60898-1


Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2

Standards IEC 60898-1


EN 60898-1
IEC 60947-2
EN 60947-2

Complementary
Network Frequency 50/60 Hz

Magnetic Tripping Limit 8 x In +/- 20 %

21 Mar 2024 1
[Ics] Rated Service Breaking 15 kA 75 % conforming to EN 60947-2 - 220...240 V AC 50/60 Hz
Capacity 7.5 kA 75 % conforming to EN 60947-2 - 380...415 V AC 50/60 Hz
4.5 kA 75 % conforming to EN 60947-2 - 440 V AC 50/60 Hz
15 kA 75 % conforming to IEC 60947-2 - 220...240 V AC 50/60 Hz
7.5 kA 75 % conforming to IEC 60947-2 - 380...415 V AC 50/60 Hz
4.5 kA 75 % conforming to IEC 60947-2 - 440 V AC 50/60 Hz
27 kA 75 % conforming to IEC 60947-2 - 12...133 V AC 50/60 Hz
27 kA 75 % conforming to EN 60947-2 - 12...133 V AC 50/60 Hz
6000 A 100 % conforming to EN 60898-1 - 400 V AC 50/60 Hz
6000 A 100 % conforming to IEC 60898-1 - 400 V AC 50/60 Hz
10 kA 100 % conforming to IEC 60947-2 - 72...125 V DC
10 kA 100 % conforming to EN 60947-2 - 72...125 V DC

Limitation Class 3 conforming to EN 60898-1


3 conforming to IEC 60898-1

[Ui] Rated Insulation Voltage 500 V AC 50/60 Hz conforming to EN 60947-2


500 V AC 50/60 Hz conforming to IEC 60947-2

[Uimp] Rated Impulse Withstand 6 kV conforming to EN 60947-2


Voltage 6 kV conforming to IEC 60947-2

Contact Position Indicator Yes

Control Type Toggle

Local Signalling Trip indicator

Mounting Mode Fixed

Mounting Support DIN rail

Comb Busbar And Distribution Top or bottom: YES


Block Compatibility
9 Mm Pitches 4

Height 85 mm

Width 36 mm

Depth 78.5 mm

Net Weight 0.25 kg

Colour White

Mechanical Durability 20000 cycles

Electrical Durability 10000 cycles

Connections - Terminals Single terminal (top or bottom) 1…25 mm² rigid


Single terminal (top or bottom) 1…16 mm² flexible

Wire Stripping Length 14 mm for top or bottom connection

Tightening Torque 2 N.m top or bottom

Earth-Leakage Protection Separate block

Environment
Ip Degree Of Protection IP20 conforming to IEC 60529
IP20 conforming to EN 60529

Pollution Degree 3 conforming to EN 60947-2


3 conforming to IEC 60947-2

Overvoltage Category IV

Tropicalisation 2 conforming to IEC 60068-1

Relative Humidity 95 % at 55 °C

Operating Altitude 0...2000 m

Ambient Air Temperature For -35…70 °C


Operation
Ambient Air Temperature For -40…85 °C
Storage

2 21 Mar 2024
Packing Units
Unit Type Of Package 1 PCE

Number Of Units In Package 1 1

Package 1 Height 7.5 cm

Package 1 Width 3.5 cm

Package 1 Length 9.5 cm

Package 1 Weight 217 g

Unit Type Of Package 2 BB1

Number Of Units In Package 2 6

Package 2 Height 8 cm

Package 2 Width 9.5 cm

Package 2 Length 22.5 cm

Package 2 Weight 1.401 kg

Unit Type Of Package 3 S03

Number Of Units In Package 3 66

Package 3 Height 30 cm

Package 3 Width 30 cm

Package 3 Length 40 cm

Package 3 Weight 15.851 kg

Contractual warranty
Warranty 18 months

21 Mar 2024 3
Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right

Transparency RoHS/REACh

Well-being performance

 Mercury Free

 Rohs Exemption Information Yes

 Halogen Free Product

Certifications & Standards


Reach Regulation REACh Declaration

Eu Rohs Directive Compliant with Exemptions

China Rohs Regulation China RoHS declaration


Product out of China RoHS scope. Substance declaration for your information

Environmental Disclosure Product Environmental Profile

Weee The product must be disposed on European Union markets following specific waste
collection and never end up in rubbish bins

Circularity Profile No need of specific recycling operations

4 21 Mar 2024
Product datasheet
Specifications

Spacial CRN plain door with


mount.plate. H800xW600xD300
IP66 IK10 RAL7035..
NSYCRN86300P

Main
Range Spacial

Product Name Spacial CRN

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Application Multi-purpose

Category Compact enclosure

Enclosure Nominal Height 800 mm

Enclosure Nominal Width 600 mm

Enclosure Nominal Depth 300 mm

Installation Accessory Type Wall-mounting

Device Composition 1 body


1 cable gland plate
1 door with lock
1 mounting plate

Door Type Plain

Mounting Plate Description Plain

Complementary
Body Type Back welded with double profile forming a protected sealed area
Sides made from a single folded section

Number Of Doors Front face: 1 door(s)

Door Opening Side Reversible (120 °)

Lock Type 3 mm double-bar lock

Type Of Gland Plate Standard

Accessibility For Operation Front

Removable Parts Door by hinges


Cable gland plate by screws
Mounting plate by fixing element

Material Enclosure: steel


Mounting plate: galvanised steel

Surface Finish Enclosure: epoxy-polyester powder

Colour Enclosure: grey (RAL 7035)

Standards IEC 62208

Product Certifications UL
cUL
DNV-GL

Net Weight 29.62 kg

Mar 21, 2024 1


Environment
Ip Degree Of Protection IP66 conforming to IEC 60529

Ik Degree Of Protection IK10 conforming to IEC 62262

Packing Units
Unit Type Of Package 1 PCE

Number Of Units In Package 1 1

Package 1 Height 32.500 cm

Package 1 Width 60.000 cm

Package 1 Length 81.000 cm

Package 1 Weight 29.813 kg

Unit Type Of Package 2 PAM

Number Of Units In Package 2 12

Package 2 Height 220.000 cm

Package 2 Width 100.000 cm

Package 2 Length 120.000 cm

Package 2 Weight 370.756 kg

Contractual warranty
Warranty 18 months

2 Mar 21, 2024


Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right

Transparency RoHS/REACh

Well-being performance

 Mercury Free

 Rohs Exemption Information Yes

Certifications & Standards


Reach Regulation REACh Declaration

Eu Rohs Directive Pro-active compliance (Product out of EU RoHS legal scope)

China Rohs Regulation China RoHS declaration


Product out of China RoHS scope. Substance declaration for your information

Environmental Disclosure Product Environmental Profile

Circularity Profile No need of specific recycling operations

Mar 21, 2024 3


Product datasheet
Specifications

Spacial CRN plain door with


mount.plate. H1000xW800xD250
IP66 IK10 RAL7035..
NSYCRN108250P

Main
Range Spacial

Product Name Spacial CRN

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Application Multi-purpose

Category Compact enclosure

Enclosure Nominal Height 1000 mm

Enclosure Nominal Width 800 mm

Enclosure Nominal Depth 250 mm

Installation Accessory Type Wall-mounting

Device Composition 1 body


1 door with lock
1 mounting plate
2 cable gland plate: bottom

Door Type Plain

Mounting Plate Description Plain

Complementary
Body Type Back welded with double profile forming a protected sealed area
Sides made from a single folded section

Number Of Doors Front face: 1 door(s)

Door Opening Side Reversible (120 °)

Lock Type 3 mm double-bar lock

Type Of Gland Plate Standard

Accessibility For Operation Front

Removable Parts Door by hinges


Cable gland plate by screws
Mounting plate by fixing element

Material Enclosure: steel


Mounting plate: galvanised steel

Surface Finish Enclosure: epoxy-polyester powder

Colour Enclosure: grey (RAL 7035)

Standards IEC 62208

Product Certifications cUL


UL
DNV-GL

Net Weight 42 kg

Mar 21, 2024 1


AD
Environment
Ip Degree Of Protection IP66 conforming to IEC 60529

Ik Degree Of Protection IK10 conforming to IEC 62262

Packing Units
Unit Type Of Package 1 PCE

Number Of Units In Package 1 1

Package 1 Height 26.500 cm

Package 1 Width 81.000 cm

Package 1 Length 101.000 cm

Package 1 Weight 43.747 kg

Unit Type Of Package 2 PAM

Number Of Units In Package 2 8

Package 2 Height 220.000 cm

Package 2 Width 100.000 cm

Package 2 Length 120.000 cm

Package 2 Weight 362.976 kg

Contractual warranty
Warranty 18 months

2 Mar 21, 2024


AD
Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right

Transparency RoHS/REACh

Well-being performance

 Mercury Free

 Rohs Exemption Information Yes

Certifications & Standards


Reach Regulation REACh Declaration

Eu Rohs Directive Pro-active compliance (Product out of EU RoHS legal scope)

China Rohs Regulation China RoHS declaration


Product out of China RoHS scope. Substance declaration for your information

Environmental Disclosure Product Environmental Profile

Circularity Profile No need of specific recycling operations

Mar 21, 2024 3


AD
Product datasheet
Specifications

Spacial CRNG plain door w/o


mount.plate. H1200xW800xD300
IP66 IK10 RAL7035
NSYCRNG128300

notification_critical_stroke Discontinued on: Oct 4, 2023

Discontinued
notification_critical_stroke To be end-of-service on: Sep 3, 2026
notification_critical_stroke

Main
Range Spacial

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product Name Spacial CRNG

Application Multi-purpose

Category Compact enclosure

Enclosure Nominal Height 1200 mm

Enclosure Nominal Width 800 mm

Enclosure Nominal Depth 300 mm

Installation Accessory Type Wall-mounting

Device Composition 1 body


1 door
1 lock
2 cable gland plate: bottom

Door Type Plain

Mounting Plate Description Without mounting plate

Complementary
Body Type Single piece body

Number Of Doors Front face: 1 door(s)

Door Opening Side Reversible (120 °)

Lock Type 3 points lock, 5 mm double-bar

Type Of Gland Plate Standard

Accessibility For Operation Front

Removable Parts Door by hinges


Cable gland plate by screws

Material Body: steel

Surface Finish Epoxy-polyester powder

Colour Grey (RAL 7035)

Standards IEC 62208

Product Certifications cUL


UL

Net Weight 44.2 kg

Price is “List Price” and may be subject to a trade discount – check with your local distributor or retailer for actual price.

Mar 21, 2024 1


Environment
Ip Degree Of Protection IP66 conforming to IEC 60529

Ik Degree Of Protection IK10 conforming to IEC 62262

Packing Units
Unit Type Of Package 1 PCE

Number Of Units In Package 1 1

Package 1 Height 35.5 cm

Package 1 Width 82.5 cm

Package 1 Length 122.0 cm

Package 1 Weight 44.2 kg

Unit Type Of Package 2 PAL

Number Of Units In Package 2 4

Package 2 Height 178.0 cm

Package 2 Width 80.0 cm

Package 2 Length 122.5 cm

Package 2 Weight 176.8 kg

Contractual warranty
Warranty 18 months

2 Mar 21, 2024


Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right

Transparency RoHS/REACh

Well-being performance

 Mercury Free

 Rohs Exemption Information Yes

Certifications & Standards


Reach Regulation REACh Declaration

Eu Rohs Directive Pro-active compliance (Product out of EU RoHS legal scope)

China Rohs Regulation China RoHS declaration


Product out of China RoHS scope. Substance declaration for your information

Environmental Disclosure Product Environmental Profile

Circularity Profile No need of specific recycling operations

Mar 21, 2024 3


Product data sheet
Specifications

Spacial CRNG plain door w/o


mount.plate. H1400xW1000xD300
IP55 IK10 RAL7035
NSYCRNG1410300D

notification_critical_stroke Discontinued on: Sep 6, 2023

notification_critical_stroke Discontinued Product availability: Non-Stock - Not normally stocked in


distribution facility

Main
Range Spacial

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product Name Spacial CRNG

Application Multi-purpose

Category Compact enclosure

Enclosure Nominal Height 55.12 in (1400 mm)

Enclosure Nominal Width 39.37 in (1000 mm)

Enclosure Nominal Depth 11.81 in (300 mm)

Installation Accessory Type Wall-mounting

Device Composition 1 body


1 lock
2 cable gland plate bottom
2 door

Door Type Solid

Mounting Plate Description Without mounting plate

Complementary
Body Type Single piece body

Number Of Doors Front face 2

Door Opening Side Reversible 120 °)

Lock Type 3 points lock, 5 mm double-bar

Type Of Gland Plate Standard

Accessibility For Operation Front

Removable Parts Door by hinges


Cable gland plate by screws

Material Body steel

Surface Finish epoxy-polyester powder

Color Gray RAL 7035)

Standards IEC 62208

Product Certifications cUL


UL

Net Weight 197.31 lb(US) (89.5 kg)

Price is “List Price” and may be subject to a trade discount – check with your local distributor or retailer for actual price.

Mar 21, 2024 1


Environment
Ip Degree Of Protection IP55 IEC 60529

Ik Degree Of Protection IK10 IEC 62262

Ordering and shipping details


Category US10ES180034

Discount Schedule 0ES1

Gtin 3606480298332

Returnability Yes

Country Of Origin FR

Packing Units
Unit Type Of Package 1 PCE

Number Of Units In Package 1 1

Package 1 Height 14.17 in (36.0 cm)

Package 1 Width 40.55 in (103.0 cm)

Package 1 Length 60.24 in (153.0 cm)

Package 1 Weight 178.57 lb(US) (81.0 kg)

Contractual warranty
Warranty 18 months

2 Mar 21, 2024


Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right

Transparency RoHS/REACh

Well-being performance

 Mercury Free

 Rohs Exemption Information Yes

Certifications & Standards


Reach Regulation REACh Declaration

Eu Rohs Directive Pro-active compliance (Product out of EU RoHS legal scope)

China Rohs Regulation China RoHS declaration


Product out of China RoHS scope. Substance declaration for your information.

Environmental Disclosure Product Environmental Profile

Circularity Profile No need of specific recycling operations

Mar 21, 2024 3


Product datasheet
Specifications

TeSys D contactor - 4P(4 NO) -


AC-1 - <= 440 V 40 A - 220 V AC
50/60 Hz coil
LC1DT40M7

Main
Range TeSys
TeSys Deca

Range Of Product TeSys Deca

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product Or Component Type Contactor

Device Short Name LC1D

Contactor Application Resistive load

Utilisation Category AC-1


AC-3
AC-3e
AC-4

Poles Description 4P

[Ue] Rated Operational Voltage Power circuit: <= 690 V AC 25...400 Hz


Power circuit: <= 300 V DC

[Ie] Rated Operational Current 40 A (at <60 °C) at <= 440 V AC AC-1 for power circuit

[Uc] Control Circuit Voltage 220 V AC 50/60 Hz

Complementary
Compatibility Code LC1D

Pole Contact Composition 4 NO

Protective Cover With

[Ith] Conventional Free Air 10 A (at 60 °C) for signalling circuit


Thermal Current 40 A (at 60 °C) for power circuit

Irms Rated Making Capacity 140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
450 A at 440 V for power circuit conforming to IEC 60947

Rated Breaking Capacity 450 A at 440 V for power circuit conforming to IEC 60947

[Icw] Rated Short-Time Withstand 50 A 40 °C - 10 min for power circuit


Current 120 A 40 °C - 1 min for power circuit
240 A 40 °C - 10 s for power circuit
380 A 40 °C - 1 s for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit

Associated Fuse Rating 10 A gG for signalling circuit conforming to IEC 60947-5-1


63 A gG at <= 690 V coordination type 1 for power circuit
40 A gG at <= 690 V coordination type 2 for power circuit

Average Impedance 2 mOhm - Ith 40 A 50 Hz for power circuit

Power Dissipation Per Pole 3.2 W AC-1

Price is “List Price” and may be subject to a trade discount – check with your local distributor or retailer for actual price.

Mar 21, 2024 1


[Ui] Rated Insulation Voltage Power circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Signalling circuit: 690 V conforming to IEC 60947-1
Signalling circuit: 600 V CSA certified
Signalling circuit: 600 V UL certified
Power circuit: 690 V conforming to IEC 60947-4-1

Overvoltage Category III

Pollution Degree 3

[Uimp] Rated Impulse Withstand 6 kV conforming to IEC 60947


Voltage
Safety Reliability Level B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO
13849-1

Mechanical Durability 15 Mcycles

Electrical Durability 1.4 Mcycles 40 A AC-1 at Ue <= 440 V

Control Circuit Type AC at 50/60 Hz

Coil Technology Without built-in suppressor module

Control Circuit Voltage Limits 0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz


0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz
0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz
1...1.1 Uc (60…70 °C):operational AC 50/60 Hz

Inrush Power In Va 70 VA 60 Hz cos phi 0.75 (at 20 °C)


70 VA 50 Hz cos phi 0.75 (at 20 °C)

Hold-In Power Consumption In Va 7.5 VA 60 Hz cos phi 0.3 (at 20 °C)


7 VA 50 Hz cos phi 0.3 (at 20 °C)

Heat Dissipation 2…3 W at 50/60 Hz

Operating Time 4...19 ms opening


12...22 ms closing

Maximum Operating Rate 3600 cyc/h 60 °C

Connections - Terminals Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with
cable end
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without
cable end
Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without
cable end
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable
end
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without
cable end
Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without
cable end
Power circuit: screw clamp terminals 1 2.5…10 mm² - cable stiffness: flexible without
cable end
Power circuit: screw clamp terminals 2 2.5…10 mm² - cable stiffness: flexible without
cable end
Power circuit: screw clamp terminals 1 2.5…10 mm² - cable stiffness: flexible with
cable end
Power circuit: screw clamp terminals 2 2.5…10 mm² - cable stiffness: flexible with
cable end
Power circuit: screw clamp terminals 1 2.5…16 mm² - cable stiffness: solid without
cable end
Power circuit: screw clamp terminals 2 2.5…16 mm² - cable stiffness: solid without
cable end

Tightening Torque Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
Power circuit: 1.8 N.m - on screw clamps terminals - with screwdriver flat Ø 6 mm
Power circuit: 1.8 N.m - on screw clamps terminals - with screwdriver Philips No 2
Power circuit: 1.8 N.m - on screw clamp terminals - with screwdriver pozidriv No 2

Auxiliary Contact Composition 1 NO + 1 NC

Auxiliary Contacts Type type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1


type mirror contact 1 NC conforming to IEC 60947-4-1

2 Mar 21, 2024


Signalling Circuit Frequency 25...400 Hz

Minimum Switching Voltage 17 V for signalling circuit

Minimum Switching Current 5 mA for signalling circuit

Insulation Resistance > 10 MOhm for signalling circuit

Non-Overlap Time 1.5 ms on de-energisation between NC and NO contact


1.5 ms on energisation between NC and NO contact

Mounting Support Rail


Plate

Environment
Standards CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
IEC 60335-1

Product Certifications UL
LROS (Lloyds register of shipping)
CCC
BV
RINA
DNV
GL
GOST
CSA

Ip Degree Of Protection IP20 front face conforming to IEC 60529

Protective Treatment TH conforming to IEC 60068-2-30

Climatic Withstand conforming to IACS E10 exposure to damp heat


conforming to IEC 60947-1 Annex Q category D exposure to damp heat

Permissible Ambient Air -40…60 °C


Temperature Around The Device 60…70 °C with derating

Operating Altitude 0...3000 m

Fire Resistance 850 °C conforming to IEC 60695-2-1

Flame Retardance V1 conforming to UL 94

Mechanical Robustness Vibrations contactor open (2 Gn, 5...300 Hz)


Vibrations contactor closed (4 Gn, 5...300 Hz)
Shocks contactor closed (15 Gn for 11 ms)
Shocks contactor open (8 Gn for 11 ms)

Height 91 mm

Width 45 mm

Depth 99 mm

Net Weight 0.425 kg

Packing Units
Unit Type Of Package 1 PCE

Number Of Units In Package 1 1

Package 1 Height 5.400 cm

Package 1 Width 9.400 cm

Package 1 Length 12.000 cm

Package 1 Weight 467.000 g

Mar 21, 2024 3


Unit Type Of Package 2 S02

Number Of Units In Package 2 16

Package 2 Height 15.000 cm

Package 2 Width 30.000 cm

Package 2 Length 40.000 cm

Package 2 Weight 8.019 kg

Contractual warranty
Warranty 18 months

4 Mar 21, 2024


Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right

Transparency RoHS/REACh

Well-being performance

 Reach Free Of Svhc

 Toxic Heavy Metal Free

 Mercury Free

 Rohs Exemption Information Yes

 Pvc Free

Certifications & Standards


Reach Regulation REACh Declaration

Eu Rohs Directive Compliant

EU RoHS Declaration

China Rohs Regulation China RoHS declaration


Pro-active China RoHS declaration (out of China RoHS legal scope)

Environmental Disclosure Product Environmental Profile

Weee The product must be disposed on European Union markets following specific waste
collection and never end up in rubbish bins

Circularity Profile End of Life Information

Mar 21, 2024 5


Product datasheet
Specifications

Acti 9 iID - RCCB - 4P - 25A -


30mA - type AC
A9R41425

Main
Range Acti9

Product Name Acti9 iID

Product Or Component Type Residual current circuit breaker (RCCB)

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Device Short Name iID

Poles Description 4P

Neutral Position Left

[In] Rated Current 25 A

Network Type AC

Earth-Leakage Sensitivity 30 mA

Earth-Leakage Protection Time Instantaneous


Delay
Earth-Leakage Protection Class Type AC

Complementary
Device Location In System Outgoer

Network Frequency 50/60 Hz

[Ue] Rated Operational Voltage 380...415 V AC 50/60 Hz

Residual Current Tripping Voltage independent


Technology
Rated Breaking And Making Idm 1500 A
Capacity Im 1500 A

Rated Conditional Short-Circuit 10 kA


Current
[Ui] Rated Insulation Voltage 500 V AC 50/60 Hz

[Uimp] Rated Impulse Withstand 6 kV


Voltage
Surge Current 250 A

Contact Position Indicator Yes

Control Type Toggle

Mounting Mode Clip-on

Mounting Support DIN rail

9 Mm Pitches 8

Height 91 mm

Width 72 mm

Depth 73.5 mm

Price is “List Price” and may be subject to a trade discount – check with your local distributor or retailer for actual price.

Mar 21, 2024 1


Net Weight 0.37 kg

Colour White

Mechanical Durability 20000 cycles

Electrical Durability AC-1: 15000 cycles

Locking Options Description Padlocking device

Connections - Terminals Single terminal top or bottom 1…35 mm² rigid


Single terminal top or bottom 1…25 mm² flexible
Single terminal top or bottom 1…25 mm² flexible with ferrule

Wire Stripping Length 14 mm for top or bottom connection

Tightening Torque 3.5 N.m top or bottom

Environment
Standards EN/IEC 61008-1
EN/IEC 61008-2-1

Ip Degree Of Protection IP20 conforming to IEC 60529


IP40 (modular enclosure) conforming to IEC 60529

Pollution Degree 3

Electromagnetic Compatibility 8/20 µs impulse withstand, 250 A conforming to EN/IEC 61008-1

Ambient Air Temperature For -5…60 °C


Operation
Ambient Air Temperature For -40…85 °C
Storage

Packing Units
Unit Type Of Package 1 PCE

Number Of Units In Package 1 1

Package 1 Height 8.5 cm

Package 1 Width 7.5 cm

Package 1 Length 10.0 cm

Package 1 Weight 358.0 g

Unit Type Of Package 2 S03

Number Of Units In Package 2 27

Package 2 Height 30.0 cm

Package 2 Width 30.0 cm

Package 2 Length 40.0 cm

Package 2 Weight 10.226 kg

Contractual warranty
Warranty 18 months

2 Mar 21, 2024


Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right

Transparency RoHS/REACh

Well-being performance

 Mercury Free

 Rohs Exemption Information Yes

 Halogen Free Plastic Parts Product

Certifications & Standards


Reach Regulation REACh Declaration

Eu Rohs Directive Compliant with Exemptions

China Rohs Regulation China RoHS declaration


Product out of China RoHS scope. Substance declaration for your information

Environmental Disclosure Product Environmental Profile

Weee The product must be disposed on European Union markets following specific waste
collection and never end up in rubbish bins

Circularity Profile No need of specific recycling operations

Mar 21, 2024 3


Product datasheet
Specifications

miniature circuit breaker - iK60N -


2P - 6 A - C curve
A9K24206

Main
Device Application Distribution

Range Acti9

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product Name Acti9 iK60

Product Or Component Type Miniature circuit-breaker

Device Short Name iK60N

Poles Description 2P

Number Of Protected Poles 2

[In] Rated Current 6 A at 30 °C

Network Type AC

Trip Unit Technology Thermal-magnetic

Curve Code C

Breaking Capacity 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1

Suitability For Isolation Yes conforming to EN/IEC 60898-1

Standards EN/IEC 60898-1

Complementary
Network Frequency 50/60 Hz

Magnetic Tripping Limit 5...10 x In

[Ics] Rated Service Breaking 6000 A 100 % conforming to EN/IEC 60898-1 - 230 V AC 50/60 Hz
Capacity
Limitation Class 3 conforming to EN/IEC 60898-1

[Ui] Rated Insulation Voltage 440 V AC 50/60 Hz conforming to EN/IEC 60898-1

[Uimp] Rated Impulse Withstand 4 kV conforming to EN/IEC 60898-1


Voltage
Contact Position Indicator No

Control Type Toggle

Local Signalling ON/OFF indication

Mounting Mode Clip-on

Mounting Support DIN rail

9 Mm Pitches 4

Height 85 mm

Width 36 mm

Depth 78.5 mm

21 Mar 2024 1
Net Weight 200 g

Colour White

Mechanical Durability 20000 cycles

Electrical Durability 10000 cycles

Locking Options Description Padlocking device

Connections - Terminals Tunnel type terminal (top or bottom) 1…25 mm² rigid
Tunnel type terminal (top or bottom) 1…16 mm² flexible

Wire Stripping Length 14 mm for top or bottom connection

Tightening Torque 2 N.m top or bottom

Earth-Leakage Protection Without

Environment
Ip Degree Of Protection IP20 conforming to IEC 60529

Pollution Degree 2 conforming to EN/IEC 60898-1

Overvoltage Category II

Ambient Air Temperature For -25…60 °C


Operation
Ambient Air Temperature For -40…85 °C
Storage

Packing Units
Unit Type Of Package 1 PCE

Number Of Units In Package 1 1

Package 1 Height 3.500 cm

Package 1 Width 7.500 cm

Package 1 Length 9.000 cm

Package 1 Weight 195.000 g

Unit Type Of Package 2 BB1

Number Of Units In Package 2 6

Package 2 Height 8.500 cm

Package 2 Width 10.000 cm

Package 2 Length 22.000 cm

Package 2 Weight 1.225 kg

Unit Type Of Package 3 S03

Number Of Units In Package 3 66

Package 3 Height 30.000 cm

Package 3 Width 30.000 cm

Package 3 Length 40.000 cm

Package 3 Weight 13.904 kg

Contractual warranty
Warranty 12 months

2 21 Mar 2024
Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right

Transparency RoHS/REACh

Well-being performance

 Reach Free Of Svhc

 Toxic Heavy Metal Free

 Mercury Free

 Rohs Exemption Information Yes

Certifications & Standards


Reach Regulation REACh Declaration

Eu Rohs Directive Compliant

EU RoHS Declaration

China Rohs Regulation China RoHS declaration


Pro-active China RoHS declaration (out of China RoHS legal scope)

Environmental Disclosure Product Environmental Profile

Weee The product must be disposed on European Union markets following specific waste
collection and never end up in rubbish bins

Circularity Profile No need of specific recycling operations

21 Mar 2024 3
Product datasheet
Specifications

Easy9 RCBO 240V - 1P + N - 20A -


C curve - 6000 A - 30 mA
EZ9D56820

notification_critical_stroke Discontinued on: 2 Apr 2021

notification_critical_stroke Discontinued

Main
Range Easy9

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product Or Component Type Residual current breaker with overcurrent protection (RCBO)

Device Short Name Easy9 RCBO

Poles 1P + Ns

Neutral Position Left

[In] Rated Current 20 A

Earthing System TN

Network Type AC

Trip Unit Technology Thermal-magnetic

Curve Code C

Earth-Leakage Sensitivity 30 mA

Earth-Leakage Protection Time Instantaneous


Delay
Earth-Leakage Protection Class Type A

Breaking Capacity 6000 A Icn at 240 V AC 50 Hz conforming to BS EN 61009-1

Complementary
Device Application Distribution

Device Location In System Outgoer

Network Frequency 50 Hz

[Ue] Rated Operational Voltage 240 V AC 50 Hz

Magnetic Tripping Limit 3...5 x In

Residual Current Tripping Voltage dependent functional earth


Technology
Limitation Class 3

[Ui] Rated Insulation Voltage 500 V

[Uimp] Rated Impulse Withstand 4 kV


Voltage
Contact Position Indicator Yes

Control Type Toggle

Mounting Support DIN rail

9 Mm Pitches 2

Height 110 mm

21 Mar 2024 1
Width 18 mm

Depth 72 mm

Net Weight 180 g

Colour Grey (RAL 7035)

Mechanical Durability 10000 cycles

Electrical Durability 4000 cycles 240 V AC 50 Hz

Connections - Terminals Tunnel type terminal (top) 25 mm² rigid


Tunnel type terminal (bottom) 16 mm² rigid
Tunnel type terminal (bottom) 16 mm² flexible
Cable (top) 2 cable(s) flexible

Tightening Torque 2 N.m top or bottom

Earth-Leakage Protection Integrated

Environment
Standards BS EN 61009-1

Product Certifications CE

Overvoltage Category IV

Tropicalisation 2

Relative Humidity 95 % at 55 °C

Ambient Air Temperature For -15…60 °C


Operation
Ambient Air Temperature For -40…85 °C
Storage

Packing Units
Unit Type Of Package 1 PCE

Number Of Units In Package 1 1

Package 1 Height 7.5 cm

Package 1 Width 9.5 cm

Package 1 Length 1.8 cm

Package 1 Weight 211 g

Unit Type Of Package 2 S02

Number Of Units In Package 2 34

Package 2 Height 15 cm

Package 2 Width 30 cm

Package 2 Length 40 cm

Package 2 Weight 7174 g

Unit Type Of Package 3 P12

Number Of Units In Package 3 1088

Package 3 Height 70 cm

Package 3 Width 120 cm

Package 3 Length 80 cm

Package 3 Weight 229568 g

2 21 Mar 2024
Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right

Sustainable Packaging

Resource performance

 Sustainable Packaging

Well-being performance

 Mercury Free

 Rohs Exemption Information Yes

Reach Regulation REACh Declaration

Eu Rohs Directive Compliant with Exemptions

China Rohs Regulation China RoHS declaration


Product out of China RoHS scope. Substance declaration for your information

Weee The product must be disposed on European Union markets following specific waste
collection and never end up in rubbish bins

21 Mar 2024 3
Product datasheet
Specifications

Easy9 RCBO 240V - 1P + N - 40A -


C curve - 6000 A - 30 mA
EZ9D56840

notification_critical_stroke Discontinued on: 2 Apr 2021

notification_critical_stroke Discontinued

Main
Range Easy9

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product Or Component Type Residual current breaker with overcurrent protection (RCBO)

Device Short Name Easy9 RCBO

Poles 1P + Ns

Neutral Position Left

[In] Rated Current 40 A

Earthing System TN

Network Type AC

Trip Unit Technology Thermal-magnetic

Curve Code C

Earth-Leakage Sensitivity 30 mA

Earth-Leakage Protection Time Instantaneous


Delay
Earth-Leakage Protection Class Type A

Breaking Capacity 6000 A Icn at 240 V AC 50 Hz conforming to BS EN 61009-1

Complementary
Device Application Distribution

Device Location In System Outgoer

Network Frequency 50 Hz

[Ue] Rated Operational Voltage 240 V AC 50 Hz

Magnetic Tripping Limit 3...5 x In

Residual Current Tripping Voltage dependent functional earth


Technology
Limitation Class 3

[Ui] Rated Insulation Voltage 500 V

[Uimp] Rated Impulse Withstand 4 kV


Voltage
Surge Current 250 A

Contact Position Indicator Yes

Control Type Toggle

Mounting Support DIN rail

9 Mm Pitches 2

21 Mar 2024 1
Height 110 mm

Width 18 mm

Depth 72 mm

Net Weight 180 g

Colour Grey (RAL 7035)

Mechanical Durability 10000 cycles

Electrical Durability 4000 cycles 240 V AC 50 Hz

Connections - Terminals Tunnel type terminal (top) 25 mm² rigid


Tunnel type terminal (bottom) 16 mm² rigid
Tunnel type terminal (bottom) 16 mm² flexible
Cable (top) 2 cable(s) flexible

Tightening Torque 2 N.m top or bottom

Earth-Leakage Protection Integrated

Environment
Standards BS EN 61009-1

Product Certifications CE

Overvoltage Category IV

Tropicalisation 2

Relative Humidity 95 % at 55 °C

Ambient Air Temperature For -15…60 °C


Operation
Ambient Air Temperature For -40…85 °C
Storage

Packing Units
Unit Type Of Package 1 PCE

Number Of Units In Package 1 1

Package 1 Height 7.5 cm

Package 1 Width 9.5 cm

Package 1 Length 1.8 cm

Package 1 Weight 211 g

Unit Type Of Package 2 S02

Number Of Units In Package 2 34

Package 2 Height 15 cm

Package 2 Width 30 cm

Package 2 Length 40 cm

Package 2 Weight 7174 g

Unit Type Of Package 3 P12

Number Of Units In Package 3 1088

Package 3 Height 70 cm

Package 3 Width 120 cm

Package 3 Length 80 cm

Package 3 Weight 229568 g

2 21 Mar 2024
Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right

Sustainable Packaging

Resource performance

 Sustainable Packaging

Well-being performance

 Mercury Free

 Rohs Exemption Information Yes

Reach Regulation REACh Declaration

Eu Rohs Directive Compliant with Exemptions

China Rohs Regulation China RoHS declaration


Product out of China RoHS scope. Substance declaration for your information

Weee The product must be disposed on European Union markets following specific waste
collection and never end up in rubbish bins