Power Grid Company of Bangladesh Ltd.

Head Office: Avenue-3, Juhurul Islam City,


Aftabnagor, Badda, Dhaka-1212.
Design & Quality Control (Transmission Line)
Emergency
Very
Confidential

Record Number: 27.21.0000.411.49.042.21.559 Date: 1/7/2024


Subject: Drawing of 230k V OPGW Fittings from Jiangsu
Zhongtian Technology Co., Ltd., China (Power
Grid Network Strengthening Project under
PGCB; Contract Number: PGCB/GtoG/01. Signing
Date: 10th October, 2016)
Reference: CCCE-ETERN-FEPEC Consortium Letter No:
CEF/PGCB/G2G/PGNSP/TL-2618; Dated: 13/06/2024
(TLD Recieved on Date: 24/06/2024)
Dear Sir,
We are pleased to mention the following comment for the purpose indicated below:
In case of any modification other than those desired are carried out, the same shall be
highlighted clearly in the Drawing/Document with full justification thereof and resubmitted for
approval.
Approval/Comments/Information conveyed herein neither relieves the contractor of his
contractual obligation and his responsibilities for correctness of dimensions, material of
constructions, weight, quantities, design details, assemble fits, performance particulars and
conformity of the supplies with the Statutory Laws of Bangladesh as may be applicable, nor does
it limit the Employer’s right under the contract.”

SL Drawing/ Sheet Enclos


Descript ion of Drawing/ Document s Rev. St at us
No. Document No. No. ed
Approved
01 Tension set for 230kV OPGW JSF-49055-6 - A wit h Yes
comment
Joint Box for 230kV OPGW-OPGW on JSH-XJ29132- 1-
02 - A Comment s No
Tower 19
JSH-XJ29132-
03 Joint Box for 230kV OPGW-OFC on Tower - A Comment s No
1/20
Vibrat ion Damper for 230kV OPGW (Type: JSH-XJ29132- 1-
04 - A Comment s No
4D-20) 20
Armor rods of Vibrat ion Damper for 230kV JSH-XJ29132- 1-
05 - A Comment s No
OPGW 21

. ১
Comments:
1) T ension set for 230kV OP GW:
T his approval supersedes the corresponding earlier approval given vide P GCB's letter No:
27.21.0000.411.49.001.17.654; Dated: 13/08/2018.

2) Joint Box for 230kV OP GW-OP GW on T ower and OFC on tower:


T he joint boxes shall consist of an external steel or die cast aluminium housing and provide
protection to IEC 60529 IP 447, and an internal die cast aluminium or high impact plastic ABS
box to IEC 60529 IP 54 as per the specification of the Contract.

3) Vibration Damper for 230kV OP GW:


i) Installation torque, messenger cable size and individual dimension and weight of the
masses shall be mentioned.
ii) Messenger cable shall be made from high tensile steel wire having a minimum tensile
strength of 1220 N/mm2.
iii) T he messenger cable shall comprise a suitable number of high tensile steel wire strands,
(minimum number 19).
iv) Damper study report along with placement chart shall be submitted by the contractor.
v) T he clamping range of clamp shall be mentioned.

4) Armor rods of Vibration Damper for 230kV OP GW:


Number of rod shall be mentioned in the drawing of armor rods.

5) Downlead clamp for 230kV OP GW drawing shall be submitted by the Contractor.

Issued by:

03- 07- 2024

Sardar Mohammad Zafrul


Hasan
Project Director(CE) (Additional) Superintending Engineer
Power Grid Network Strengthening Email: se.tld@pgcb.gov.bd
Project (G2G)
পাওয়ার ি ড কা ািন অব বাংলােদশ িলঃ

Record Number: Date: 1/7/2024


27.21.0000.411.49.042.21.559/1(3)

Copy for kind information and necessary action,


1) Chief Engineer (Additional), Planning & Design (P&D), Power Grid
Company of Bangladesh Ltd
2) Md. Sazedur Rahman, Project Manager, CCCE-ETERN-FEPEC
Consortium
3) Office File/ Master File, TLD & QC, PGCB Ltd.

. ২
03- 07- 2024

Md. Shoeb Hasan


িনব াহী েকৗশলী

. ৩

You might also like