CIVIL ENGINEERING DEPARTMENT

TRANSPORTATION ENGINEERING LABORATORY

No. CED/TEL/M.T/ / 17-18 Date: 00/01/2018


MATERIAL TESTING REPORT

1. Ref No. : AAI/SAP/AGM(E-C)/EXT OF RWY/Testing/DAC Mould/2016-17/132 Dtd- 26/11/2017


2. Name of Client : M/s. AGM (Engg- C)-II, Surat Airport Project, Surat.
3. Name of Agency : M/s. Relcon Infra Projects Ltd.
4. Report for : Test on Mould of DAC
5. Name of Work : Re-Carpeting / Strengthening & Extension of Runway 04/22 at Surat Airport, Surat.
6. Test Result :

Mix Parameters *
DAC
Bulk specific gravity Stability at Flow at Va, VFB,
Date Sample Gmm
of mould (Gmb) 60˚C, kN 60˚C, mm % %
No.
1. 2.342 10.55 3.45 2.447 4.29 73.25
25-11-

2. 2.345 11.58 3.72 2.449 4.25 73.35


17

3. 2.348 12.21 3.83 2.445 3.97 74.93

(Dr. Ashish Dhamaniya)


Assistant Professor &
TE- Lab in Charge, CED (Shri. A. J. Solanki)
Assistant Professor &
TE- Lab in Charge, CED (Dr. S.M. Yadav)
Prof. & Head, CED

TERMS AND CONDITIONS GOVERNING THE TEST REPORT ISSUED


1. Samples are not drawn by Transportation Engineering Laboratory, CED, S.V.N.I.T., Surat, unless otherwise
mentioned. The results are applicable only to the submitted sample. Endorsement of the products is neither
inferred nor implied.
2. The test report shall not be reproduced in full or part without the written approval of the Transportation
Engineering Laboratory, CED, S.V.N.I.T., Surat.
3. The test report in full or part shall not be used for promotional or publicity purpose without the written consent of
Transportation Engineering Laboratory, CED, S.V.N.I.T. Surat.
4. Perishable samples will be destroyed after testing, others after 07 Days from the date of issue of the report, unless
otherwise agreed with the customer or as required by the applicable regulations.
5. Any correction invalidates this test report.
6. Analysis report will be governed under Surat jurisdiction.