Professional Documents
Culture Documents
Acs800 304 Suppl User Manualpdf Compress
Acs800 304 Suppl User Manualpdf Compress
Acs800 304 Suppl User Manualpdf Compress
Manual Supplement
ACS800-304 and ACS800-704 Diode Supply Modules (+V991)
ACS800 multidrive modules manuals
GENERAL DRIVE MANUALS Code (EN)
ACS800 Multidrive and Multidrive Modules Safety Instructions 3AFE64760432 1)
ACS800 Multidrive and Multidrive Modules Planning the Electrical 3AFE64783742 1)
Installation
ACS800 Multidrive Modules Planning the Cabinet Installation 3AFE64783572 1)
OPTION MANUALS
Manuals for Fieldbus Adapters, I/O Extension Modules etc. 3)
1)
Always included in the delivery
2) Included in the delivery with appropriate supply unit
3) Included in the delivery with appropriate program or option device
ACS800-304 and ACS800-704
Diode Supply Modules (+V991)
Manual Supplement
3AUA0000043435 Rev A
EN
EFFECTIVE: 03.09.2008
Safety instructions
Safety instructions
6
WARNING!
• Only qualified electricians are allowed to install and maintain the drive.
• The main switch on the cabinet door does not remove the voltage from the input
busbars of the drive. Before working on the drive, isolate the whole drive from
the supply.
• Never work on the drive, the motor cable or the motor when main power is
applied. After switching off the input power, always wait for 5 min to let the
intermediate circuit capacitors discharge before you start working on the drive,
the motor or the motor cable. Measure the voltage between terminals UDC+
and UDC- (L+ and L–) with a multimeter (impedance at least 1 Mohm) to
ensure that the drive is discharged before beginning work.
• Do not work on the control cables when power is applied to the drive or to the
external control circuits. Externally supplied control circuits may cause
dangerous voltages to exist inside the drive even when the main power of the
drive is switched off.
• Do not make any insulation or voltage withstand tests on the drive or drive
modules.
• When reconnecting the motor cable, always check that the phase order is
correct.
• When joining shipping splits (if any), check the cable connections at the joints
before switching on the supply voltage.
• Live parts on the inside of the doors are protected against direct contact.
Special attention shall be paid when handling metallic shrouds.
Note:
• The motor cable terminals on the drive are at a dangerously high voltage when
the input power is on, regardless of whether the motor is running or not.
• The Prevention of Unexpected Start function does not remove the voltage from
the main and auxiliary circuits.
Safety instructions
7
WARNING!
• Electrically conductive dust inside the unit may cause damage or lead to
malfunction. Make sure that dust from drilling does not enter the drive when
installing.
• Cooling fans may continue to rotate for a while after the disconnection of the
electrical supply.
Safety instructions
8
Grounding
These instructions are intended for all who are responsible for the grounding of the
drive. Incorrect grounding can cause physical injury, death or equipment malfunction
and increase electromagnetic interference.
WARNING!
• Ground the drive, the motor and adjoining equipment to ensure personnel
safety in all circumstances, and to reduce electromagnetic emission and pick-
up.
• Power cable shields are suitable for equipment grounding conductors only
when adequately sized to meet safety regulations.
WARNING!
• Handle the fibre optic cables with care. When unplugging optic cables, always
grab the connector, not the cable itself. Do not touch the ends of the fibres with
bare hands as the fibre is extremely sensitive to dirt. The minimum allowed
bend radius is 35 mm (1.4”).
Safety instructions
9
Operation
These warnings are intended for all who plan the operation of the drive or operate
the drive. Ignoring the instructions can cause physical injury or death or damage the
equipment.
WARNING!
• If the drive is equipped with an optional brake unit, make sure there are
inverters connected to the intermediate circuit before start. As a rule of thumb,
the sum capacitance of the inverters connected must be at least 30% of the
sum capacitance of all inverters.
• Do not open the DC switch fuse of an inverter when the inverter is running.
WARNING!
• Before adjusting the drive and putting it into service, make sure that the motor
and all driven equipment are suitable for operation throughout the speed range
provided by the drive. The drive can be adjusted to operate the motor at
speeds above and below the speed provided by connecting the motor directly
to the power line.
• Do not control the motor with the disconnecting device (means); instead, use
the control panel keys and , or commands via the I/O board of the drive.
The maximum allowed number of charging cycles of the DC capacitors (i.e.
power-ups by applying power) is five in ten minutes.
Note:
• If an external source for start command is selected and it is ON, the drive (with
Standard Application Program) will start immediately after fault reset unless the
drive is configured for 3-wire (a pulse) start/stop.
• When the control location is not set to Local (L not shown in the status row of
the display), the stop key on the control panel will not stop the drive. To stop
the drive using the control panel, press the LOC/REM key and then the stop
key .
Safety instructions
10
WARNING! Do not work on the drive when the permanent magnet motor is rotating.
Also when the supply power is switched off, a rotating permanent magnet motor
feeds power to the intermediate circuit of the drive and also the supply connections
become live (even when the inverter is stopped!).
Operation
Do not run the motor above the rated speed. Motor overspeed leads to overvoltage
which may result in explosion of the capacitors in the intermediate circuit of the drive.
Application program
Controlling a permanent magnet motor is only allowed using the ACS800 Permanent
Magnet Synchronous Motor Drive Application Program, or using other application
programs in scalar control mode only.
Safety instructions
11
Table of contents
Safety instructions
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Usage of warnings and notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Installation and maintenance work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Fibre optic cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Permanent magnet motor drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Installation and maintenance work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Application program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Table of contents
Hardware description
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Main components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Module with charging choke . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Module with charging resistors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Charging resistors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Additional connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Diode supply module type code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Basic code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Option codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Program features
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Starting sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Settings at start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Charging circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Table of contents
12
Ordering codes
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Type equation table: Cabinet-installed units vs. modules vs. basic modules . . . . . . . . . . . . . . . . . 31
Ordering codes for diode supply modules and options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
AC fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
AC chokes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Table of contents
13
Dimensional drawings
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Module fixing hole sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Diode supply module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Control electronics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
RDCU Drive Control Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
APBU-44C branching unit for parallel connected DSUs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Boards
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
RMIO control board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
CMIB-01C Module Interface Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Interconnections between the boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
CMRB board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Table of contents
14
Table of contents
15
Compatibility
The manual supplement is compatible with the diode supply modules ACS800-304
and ACS800-704, intended for the user-defined cabinet installations. Some chapters
are also valid for the cabinet installed diode supply units AC800-307 and
ACS800-507.
This manual supplement contains documentation specific to ACS800-304 and
ACS800-704 diode supply modules with option code +V991 (included in the type
designation label). For the complete manuals, see ACS800-304 and ACS800-704
Diode Supply Modules User's Manual [3AFE64494023 (English)] and ACS800
Liquid-cooled Diode Supply Control Program Firmware Manual [3AFE68746299
(English)].
Safety instructions
Follow all safety instructions delivered with the drive.
• Read the complete safety instructions before you install, commission, or use
the drive. The complete safety instructions are given in ACS800 Multidrive Safety
Instructions [3AFE64760432 (English)].
• Read the software function specific warnings and notes before changing the
default settings of the function. For each function, the warnings and notes are
given in the section describing the related user-adjustable parameters.
• Read task specific safety instructions before starting the task. See the section
describing the task.
Reader
The reader of the manual supplement is expected to know the standard electrical
wiring practices, electronic components, and electrical schematic symbols.
Contents
• Safety instructions
• Hardware description
• Program features
• Actual signals and parameters
• Ordering codes
Product training
For information on ABB product training, navigate to www.abb.com/drives and select
Training courses.
Hardware description
Hardware description
18
Main components
Charging can be based either on charging choke or charging resistors. Main
components in both cases are shown below.
Main contactors
Charging contactor
DC fuses
DC busbars
Main choke
CINT board
CMIB board
Hardware description
19
DC fuses
CINT board
CMIB board
Fan
Hardware description
20
Charging resistors
Hardware description
21
Additional connections
Hardware description
22
Basic code
Digit no. Name Alternatives Description
Option codes
Heading Code Description
V991 Version 1 (includes current measurement based diagnostics)
Line options F250 Line contactor(s) inside
F253 Door Interlock Disconnect Switch (OETL)
F272 Internal charging
Hardware description
23
Program features
Starting sequence
During the starting sequence, the DC link is charged and the main contactor/breaker
is closed. When the routines have been completed, the DSU starts and operates
normally.
Settings at start-up
At the final testing of the drive at the factory, DC voltage undervoltage trip level is
adjusted to meet the application requirements. However, DC voltage undervoltage
trip level needs to be adjusted, if the input voltage is not 690 V.
Typically there is no reason to make other changes to the preliminary settings
or any other settings of the supply unit on field. However, if the RMIO control
board is replaced, or the parameter settings are reset to default values, check and
adjust this parameter:
Parameter Description Value
30.12 DC UNDERVOLT TRIP Undervoltage trip level See the parameter description on page 30.
Note: Voltage of the auxiliary voltage transformer must be set according to the
supply network.
Program features
24
Charging circuit
400 V AC … 690 V AC
K1–K2 R1
Charging circuit
F5…F7
K10 R1…R13
Program features
25
6231 6237
2737
Main Status Word (value 231
in hexadecimal)
1. START command
0.2...3.0 s
0.2 s
2. Charging contactor
(RO1)
3. Main contactor/breaker
(RO3)
4. Ready/Operating
Step Function
1. The supply unit receives the START command. Control via I/O: rising edge of digital
input DI2. Control via fieldbus: digital input DI2 = “1” and rising edge of Main Control
Word bit 0.
2. The supply unit closes the charging contactor control circuit (RO1).
3. The supply unit closes the main contactor/breaker and the cooling fan control circuit
(RO3) and receives the “main contactor on” acknowledgement (DI3) and the
“cooling air fan in operation” acknowledgement (DI1).
4. The supply unit is ready for loading in case the DC voltage level is acceptable
(charging is completed successfully).
0.2…3.0 s = Charging time. Charging time is shorter if the DC link is charged before start.
0.2 s = Start delay
Program features
26
07.01 MAIN CTRL WORD Status of the Main Control Word bits
08.01 MAIN STATUS WORD Status of the Main Status Word bits
Stopping
A stop signal from the three-position operating switch on the cabinet door stops the
DSU and opens the main contactor/breaker. The DSU can also be stopped from the
Stop ( )key on the control panel and from DriveWindow PC tool when in local
control mode (L on the panel display), or via fieldbus in remote control mode. These
controls also open the main contactor/breaker.
Note: It is recommended to stop the inverter units before diode supply units.
Program features
27
Program features
28
Loading commands
The form of the loading command for air-cooled diode supply modules is
L_ACS NRxxxx_x. Loading commands for each diode supply module type are listed
below.
400 V multidrive series
NR0205_3
NR0285_3
NR0405_3
NR0575_3
NR0785_3
NR1055_3
NR1585_3
NR2105_3
NR2535_3
500 V multidrive series
NR0255_5
NR0355_5
NR0495_5
NR0715_5
NR0995_5
NR1315_5
NR1975_5
NR2635_5
NR3295_5
690 V multidrive series
NR0325_7
NR0455_7
NR0645_7
NR0915_7
NR0345_7
NR0495_7
NR0685_7
NR0985_7
NR1375_7
NR1815_7
NR2725_7
NR3635_7
NR4545_7
00586755
Program features
29
Actual signals
No. Name/Value Description FbEq/T.
01 ACTUAL SIGNALS
01.31 FAN ON-TIME Running time of the drive cooling fan 1 = 10 h
h Time
Parameters
Index Name/selection Description FbEq/ Def
T.
16 SYSTEM CTR Parameter lock, parameter back-up etc.
INPUTS
16.01 DI3 FUNCTION Defines the purpose of DI3. 1=1 NOT USED
NOT USED (1) Not in use.
START IMP (2) Start impulse.
MBC ACK (3) Acknowledgement from main contactor.
30 FAULT Programmable protection functions
FUNCTIONS
30.12 DC UNDERVOLT Defines the intermediate circuit DC undervoltage fault trip limit. Default R 350/450/
TRIP trip limit is 360 VDC for 400 V units, 450 VDC for 500 V units and 600 V
600 VDC for 690 V units. In case a 690 VAC module is connected to
power line with lower voltage, set the undervoltage trip level according
to equation: 0.67 · 1.35 · Unet = 0.9 · Unet.
Note: This parameter also determines the DC voltage check limit
during charging.
Note: DC voltage undervoltage trip level needs to be adjusted, if the
input voltage is not 690 V.
0...1000 Undervoltage trip limit 1=1
32 PROTECTIONS These parameters are visible when password is set to 32.
32.01 CHARGE DELAY Defines the minimum time after which the main contactor is closed. R 0,8 s
0…20 s Real value
32.02 START DELAY Defines the time difference between charging contactor being opened R 0,2 s
and main contactor being closed.
0…7,5 s Real value
32.03 MBC TRIP Defines the time difference between main contactor being closed and R 0,5 s
DELAY “main contactor on” acknowledgement being received.
0…20 Real value
32.04 DI1 TRIP DELAY Defines the delay for DI1 supervision. The supervision function waits R 5s
the delay after detecting the event before tripping/generating alarm.
0…3600 s Real value
Ordering codes
Ordering codes
32
For description of the diode supply module, see chapter Hardware description. For
the ratings and no. of DSU modules under each unit, see ACS800-304 and ACS800-
704 technical data. For the illustration and dimension of one DSU module, see
chapter Dimensional drawings.
AC fuses
AC fuses (gG)
DSU module type Qty Type Rating Order code
400 V, 380...500 V, 525...690 V / 6-pulse Diode Supply Unit
ACS800-304-0325-7 3 OFAA3GG400 400 A, 690 V, DIN3 64729586
ACS800-304-0455-7 3 OFAA3GG500 500 A, 690 V, DIN3 64729632
ACS800-704-0645-7 6 OFAA3GG400 400 A, 690 V, DIN3 64729586
ACS800-704-0915-7 6 OFAA3GG500 500 A, 690 V, DIN3 64729632
ACS800-704-1375-7 12 OFAA3GG400 400 A, 690 V, DIN3 64729586
ACS800-704-1815-7 12 OFAA3GG500 500 A, 690 V, DIN3 64729632
ACS800-704-2725-7 18 OFAA3GG500 500 A, 690 V, DIN3 64729632
ACS800-704-3635-7 24 OFAA3GG500 500 A, 690 V, DIN3 64729632
ACS800-704-4545-7 30 OFAA3GG500 500 A, 690 V, DIN3 64729632
400 V, 380...500 V, 525...690 V / 12-pulse Diode Supply Unit
ACS800-704-0645-7 6 OFAA3GG400 400 A, 690 V, DIN3 64729586
ACS800-704-0915-7 6 OFAA3GG500 500 A, 690 V, DIN3 64729632
ACS800-704-1375-7 12 OFAA3GG400 400 A, 690 V, DIN3 64729586
ACS800-704-1815-7 12 OFAA3GG500 500 A, 690 V, DIN3 64729632
ACS800-704-2725-7 18 OFAA3GG500 500 A, 690 V, DIN3 64729632
ACS800-704-3635-7 24 OFAA3GG500 500 A, 690 V, DIN3 64729632
ACS800-704-4545-7 30 OFAA3GG500 500 A, 690 V, DIN3 64729632
00093148.XLS Rev H.13
Fuses protect the input cable and the diode-thyristor bridges of the DSU against
short circuits. Note that in the basic module size D4 there are two bridges in parallel.
Both bridges need to be fed through individual fuses.
Ordering codes
33
For more information on the protections, see ACS800 Multidrive Planning the
Electrical Installation [3AFE64783742 (English)].
Spare parts
Spare parts
Name Symbol Pcs Order code
Diode module V11…V13…V21…V23 6 68977223
CMIB-01 A43 1 68989809
CINT-01 A42 1 68989841
Current transducer T11…T13 1 64697811
NTC Resistor B1, B2 2 68879655
DC fuses F1, F3, F2, F4 4 68988900
Fan G1 1 68973708
Snubber Board A11, A13 1 64705563
CMRB-01C A44 1 3AUA0000037278
Charging contactor K10 1 64206087
Charging resistor R11, R12, R13 3 3AUA0000035399
Fuses for charging circuit F5, F6, F7 3 64717405
Contactor K1, K2 1 3AUA0000025476
OETL Q1 1 64607201
Auxiliary contact (Q1) 1 10000432
Fan transformer fuses -A44/F1, F2 2 68264251
AC chokes
AC chokes
Diode module type Order code Symbol Pcs
ACS800-304-0325-7+V991 64650971
ACS800-304-0455-7+V991 64650955
R1 1
ACS800-704-0645-7+V991 64650947
ACS800-704-0915-7+V991 64610813
Module
Module with charging resistors can be used as a spare part to replace the module
with charging choke.
Ordering codes
34
Ordering codes
35
Ratings
Diode Supply Unit Consists of module … Nominal ratings Light overload use Heavy-duty use
type frame Icontmax Icontmax Imax SN Pcontmax In PN Ihd Phd
A [AC] A [DC] A [DC] [kVA] [kW] [ADC] [kW] [ADC] [kW]
400 V / 6-pulse Diode Supply Unit
ACS800-304-0325-7 ACS800-304-0325-7 D3 286 350 462 198 183 335 175 280 147
ACS800-304-0455-7 ACS800-304-0455-7 D3 408 500 700 283 262 480 251 400 210
ACS800-704-0645-7 ACS800-704-0645-7 D4 571 700 924 396 367 670 351 560 293
ACS800-704-0915-7 ACS800-704-0915-7 D4 816 1000 1400 566 524 960 503 800 419
ACS800-704-1375-7 ACS800-704-0645-7 2×D4 1143 1400 1848 792 733 1340 702 1120 587
ACS800-704-1815-7 ACS800-704-0915-7 2×D4 1518 1860 2604 1052 974 1790 938 1490 780
ACS800-704-2725-7 ACS800-704-0915-7 3×D4 2278 2790 3906 1578 1461 2685 1406 2230 1168
ACS800-704-3635-7 ACS800-704-0915-7 4×D4 3037 3720 5208 2104 1949 3580 1875 2980 1561
ACS800-704-4545-7 ACS800-704-0915-7 5×D4 3796 4650 6510 2630 2436 4475 2344 3720 1949
400 V / 12-pulse Diode Supply Unit
ACS800-704-0645-7 ACS800-704-0645-7 D4 571 700 924 396 367 670 351 560 293
ACS800-704-0915-7 ACS800-704-0915-7 D4 816 1000 1400 566 524 960 503 800 419
ACS800-704-1375-7 ACS800-704-0645-7 2×D4 1143 1400 1848 792 733 1340 702 1120 587
ACS800-704-1815-7 ACS800-704-0915-7 2×D4 1518 1860 2604 1052 974 1790 938 1490 780
ACS800-704-2725-7 ACS800-704-0915-7 3×D4 2278 2790 3906 1578 1461 2685 1406 2230 1168
ACS800-704-3635-7 ACS800-704-0915-7 4×D4 3037 3720 5208 2104 1949 3580 1875 2980 1561
ACS800-704-4545-7 ACS800-704-0915-7 5×D4 3796 4650 6510 2630 2436 4475 2344 3720 1949
380...500 / 6-pulse Diode Supply Unit
ACS800-304-0325-7 ACS800-304-0325-7 D3 286 350 462 247 229 335 219 280 183
ACS800-304-0455-7 ACS800-304-0455-7 D3 408 500 700 353 327 480 314 400 262
ACS800-704-0645-7 ACS800-704-0645-7 D4 571 700 924 495 458 670 439 560 367
ACS800-704-0915-7 ACS800-704-0915-7 D4 816 1000 1400 707 655 960 629 800 524
ACS800-704-1375-7 ACS800-704-0645-7 2×D4 1143 1400 1848 990 917 1340 877 1120 733
ACS800-704-1815-7 ACS800-704-0915-7 2×D4 1518 1860 2604 1315 1218 1790 1172 1490 976
ACS800-704-2725-7 ACS800-704-0915-7 3×D4 2278 2790 3906 1972 1827 2685 1758 2230 1460
ACS800-704-3635-7 ACS800-704-0915-7 4×D4 3037 3720 5208 2630 2436 3580 2344 2980 1951
ACS800-704-4545-7 ACS800-704-0915-7 5×D4 3796 4650 6510 3287 3045 4475 2930 3720 2436
380...500 V / 12-pulse Diode Supply Unit
ACS800-704-0645-7 ACS800-704-0645-7 D4 571 700 924 495 458 670 439 560 367
ACS800-704-0915-7 ACS800-704-0915-7 D4 816 1000 1400 707 655 960 629 800 524
ACS800-704-1375-7 ACS800-704-0645-7 2×D4 1143 1400 1848 990 917 1340 877 1120 733
ACS800-704-1815-7 ACS800-704-0915-7 2×D4 1518 1860 2604 1315 1218 1790 1172 1490 976
ACS800-704-2725-7 ACS800-704-0915-7 3×D4 2278 2790 3906 1972 1827 2685 1758 2230 1460
ACS800-704-3635-7 ACS800-704-0915-7 4×D4 3037 3720 5208 2630 2436 3580 2344 2980 1951
ACS800-704-4545-7 ACS800-704-0915-7 5×D4 3796 4650 6510 3287 3045 4475 2930 3720 2436
525...690 V / 6-pulse Diode Supply Unit
ACS800-304-0325-7 ACS800-304-0325-7 D3 286 350 462 341 316 335 303 280 253
ACS800-304-0455-7 ACS800-304-0455-7 D3 408 500 700 488 452 480 434 400 361
ACS800-704-0645-7 ACS800-704-0645-7 D4 571 700 924 683 632 670 605 560 506
ACS800-704-0915-7 ACS800-704-0915-7 D4 816 1000 1400 976 904 960 867 800 723
ACS800-704-1375-7 ACS800-704-0645-7 2×D4 1143 1400 1848 1366 1265 1340 1211 1120 1012
ACS800-704-1815-7 ACS800-704-0915-7 2×D4 1518 1860 2604 1815 1681 1790 1617 1490 1346
ACS800-704-2725-7 ACS800-704-0915-7 3×D4 2278 2790 3906 2722 2521 2685 2426 2230 2015
ACS800-704-3635-7 ACS800-704-0915-7 4×D4 3037 3720 5208 3629 3361 3580 3235 2980 2693
ACS800-704-4545-7 ACS800-704-0915-7 5×D4 3796 4650 6510 4537 4202 4475 4043 3720 3361
Diode Supply Unit Consists of module … Nominal ratings Light overload use Heavy-duty use
type frame Icontmax Icontmax Imax SN Pcontmax In PN Ihd Phd
A [AC] A [DC] A [DC] [kVA] [kW] [ADC] [kW] [ADC] [kW]
525...690 V / 12-pulse Diode Supply Unit
ACS800-704-0645-7 ACS800-704-0645-7 D4 571 700 924 683 632 670 605 560 506
ACS800-704-0915-7 ACS800-704-0915-7 D4 816 1000 1400 976 904 960 867 800 723
ACS800-704-1375-7 ACS800-704-0645-7 2×D4 1143 1400 1848 1366 1265 1340 1211 1120 1012
ACS800-704-1815-7 ACS800-704-0915-7 2×D4 1518 1860 2604 1815 1681 1790 1617 1490 1346
ACS800-704-2725-7 ACS800-704-0915-7 3×D4 2278 2790 3906 2722 2521 2685 2426 2230 2015
ACS800-704-3635-7 ACS800-704-0915-7 4×D4 3037 3720 5208 3629 3361 3580 3235 2980 2693
ACS800-704-4545-7 ACS800-704-0915-7 5×D4 3796 4650 6510 4537 4202 4475 4043 3720 3361
00184674.xls / A
Nominal ratings
Icont.max continuous rms input (AC) or output (DC) current. No overload capability at 40°C.
Imax maximum output current. Available for 10 s at start, otherwise as long as allowed by module temperature.
Pcont.max nominal output power
Light-overload use (10% overload capability) ratings
IN continuous rms current. 10% overload is allowed for one minute every 5 minutes.
PN output power in light overload use
Heavy-duty use (50% overload capability) ratings
Ihd continuous rms current. 50% overload is allowed for one minute every 5 minutes.
Phd output power in heavy duty-use
AC fuses
Check that the operating time of the fuse is below 0.5 seconds. The operating time
depends on the fuse type, supply network impedance and the cross-sectional area,
material and length of the supply cable. The fuses must be of the “non-time delay”
type. See also ACS800 Multidrive Planning the Electrical Installation
[3AFE64783742 (English)].
Note 1: Larger fuses must not be used.
Note 2: Fuses from other manufacturers can be used if they meet the ratings.
Note 3: The recommended fuses are for branch circuit protection per NEC as
required for the UL approval.
Note 4: Use one fuse per each input terminal of the DSU module (i.e. six fuses per
D4 module, three fuses per D3 module).
AC fuse (gG)
OFAA3GG400 /
Type
OFAA3GG500
400 A, 690 V, DIN 3 /
Rating
500 A, 690 V, DIN 3
Internal DC fuses
All DSU modules: Ferraz-Shawmut screw fuse PC71UD10C 700TF, 700 A/1000 V,
DIN1
(Bussmann screw fuse, 170M 4908, 700 A / 1000 V, DIN1)
1)
Dual-cable screw lug. Included in delivery as standard.
1)
Branching boards needed and control panels of types CDP-312 and LMD.
Charging
Maximum charging 200 mF / 690 V for single charging when starting from cold
Nominal charging capacity 28 kWs (e.g. 64 mF / 690 V AC network, 7×R8i)
Six straight charging of DC link are allowed when starting from cold, delay between
chargings 7 seconds
Average charging interval minimum is 2 minutes
Degree of Plain module: IP20, Cabinet: IP20, IP21, IP22, IP42 or IP54
Protection
Ambient conditions
The unit is to be used in a heated indoor controlled environment.
Operation Storage Transportation
Altitude above sea level 0…1000 m - -
1000…2000: 1% derating - -
for every 100 m
Max. 4000 m ASL
Temperature 0…+50°C -40…+70°C -40…+70°C
+40…+50°C derating 1% /
1°C above 40°C
Relative humidity 5…95%, no condensation 5…95% 5…95%
allowed
Vibration (IEC 60068-2-6) 10…58 Hz, 0.075 mm
displacement amplitude
58…150 Hz 10 m/s2
Vibration (Marine 3…13.8 Hz 1.0 mm
Classification, DNV) displacement amplitude
13.8…100 Hz 7 m/s2
Shock (IEC-60068-2-6) Not allowed max. 100 m/s2 18 ms max. 100 m/s2 18 ms
Free fall (IEC-60068-2-6) Not allowed 25 mm 25 mm
Atmospheric pressure 70 to 106 kPa 70 to 106 kPa 60 to 106 kPa
(0.7 to 1.05 atmospheres) (0.7 to 1.05 atmospheres) (0.6 to 1.05 atmospheres)
Contamination (IEC-721-3-3) Class 3C2 - chemical gases Class 1C2 - chemical gases Class 2C2 - chemical gases
Class 3S2 - solid particles Class 1S2 - solid particles Class 2S2 - solid particles
Cooling
Method Centrifugal fan
Max. 190 l/s, noise < 65 dB
Free space See dimensional drawings
Air flow See type specific figures
Net air inlet / module 0.117 m2 (IP20)
Net air outlet / module 0.065 m2 (IP20)
Recommended IP22/42 filter AIR TEX G-150 by Luftfilter
material
Recommended IP54 filter airComp 300-50 (47 mm) by Luftfilter
material
Average temperature rise of < 29°C
cooling air
Materials
Module enclosure 2 mm sheet steel
Flat busbars Tin plated copper or aluminium
Fire safety of materials Insulating materials & non-metallic items: Mostly self-extinctive
(IEC-332-1)
Package Plywood. Bands PP or steel.
Disposal According to the general ABB drives specification
Standards
See ACS800 Multidrive and ACS800 Multidrive Modules Planning the Electrical Installation [3AFE64783742 (English)].
Markings
See ACS800 Multidrive and ACS800 Multidrive Modules Planning the Electrical Installation [3AFE64783742 (English)].
Dimensional drawings
Dimensional drawings
42
Dimensional drawings
43
(2 of 3)
Dimensional drawings
44
(3 of 3)
Dimensional drawings
45
Control electronics
Dimensional drawings
46
1 2 3 4 5 6 7 8
6 9 6
5 9
B A P B U -4 4 C B O A R D
V 1 V 2 1
C H 1 C H 5
V 2 V 2 2
D
V 3 V 2 3
C H 2 C H 6
V 4 V 2 4
E
V 5 V 2 5
C H 3 C H 7
V 6 V 2 6
V 7 V 2 7
C H 4 C H 8
F V 8 V 2 8
V 9 V 2 9
C N T L 1 C H 9
V 1 0 V 3 0
G
V 1 1 C N T L 2 V 3 1 2 7 5
O R C H 1 0
V 1 2 D D C S (P C ) V 3 2
H V 3 3
V 1 3
T R IG G E R C H 1 1
V 1 4 V 3 4
V 3 5
0 1
C H 1 2 E F 2
S 1
3 4 5
B C D
D D C S V 3 6 8 9 A
6
J N O D E 0 1
E F 2
S 2 A D D R
3 4 5
A P E B -8 4 C
B C D
6
8 9 A
D IP
1 2
1
T E
O P T P W
S T 1
R (V 1 1 )
X A P B U -4 4 C
3
S 3 T E S T 2 (4 C H )
4
M O D E 1
5
M O D E 2
A P B U -4 4 C E
O N
6
6 B A T T E R Y
K O N O F F (1 2 C H )
B A R C O D E L A B E L
L O G IC V E R S IO N
R X D T X D S W IT C H B A T T E R Y
B A T P W R O N W H E N B R IN G IN G
U N IT IN T O U S E
1 2 4 V A
2 G N D 2 4 V D C
X 1
3 2 4 V B IN
L 4 G N D
6 4 6 8 8 3 9 1
D R A W N 0 5 .1 1 .2 0 0 2 T .F . R E F E R S A C S 8 0 0 M D
A B B O y C H E C K 0 6 .0 9 .2 0 0 4 M .T
A P B U -4 4 C F IL E 0 0 2 1 9 0 1 8 .D S F
M D r iv e s , S y s te m A C
A P P R O V 0 6 .0 9 .2 0 0 4 P P C S B R A N C H IN G & D A T A L O G G E R U N IT , 4 C H S H E E T 1 / 2
I.T . R E V
H e ls in k i, F in la n d D IM E N S IO N D R A W IN G
R E V IS E D D R A W IN G 3 A F E 6 4 6 9 6 9 4 7 B 64696947-B
Dimensional drawings
47
Boards
Boards
48
5'&2;
&+
&+ 50,2
'5,9(
&21752//(5
&+ ,2%2$5'
56
),(/'%86
RU
,202'8/( $Q\%XV6
>@ &+
9
9
836
9
,202'8/(
$Q\%XV6
>@
9
33&6 ''&6
0ELWV 3&
$3%8
RU
$3%8
$3(%
33&6
0ELWV ,19
8SZDUGV,'&,'&8&
08;,6807(037(03
9 9
&+*
&+*
&+*
)$1
&217
,680
)$1
)$1
&217
&217
,'&
,'&
,680
,680
,'&
,'&
,'&
,'&
0$;
7
7
7
7
7
7
SFV
)$1
&+*
)$1
&+*
&217
&217
&217
,8 ,: ,9 [7 ,8 ,: ,9 [7 ,8 ,: ,9 [7
,9 ,8 ,: ,9 ,8 ,: ,9 ,8 ,:
Boards
49
CMRB board
Boards
50
Boards
51
Analogue outputs
Two programmable current outputs: 0 (4) to 20 mA, RL < 700 ohm
Resolution 0.1% (10 bit)
Inaccuracy ±1% (Full Scale Range) at 25 °C (77 °F). Temperature coefficient: ±200 ppm/°C
(±111 ppm/°F) max.
Digital inputs
With Standard Control Program six programmable digital inputs (common ground:
24 V DC, -15% to +20%) and a start interlock input. Group isolated, can be divided in
two isolated groups (see Isolation and grounding diagram below).
Thermistor input: 5 mA, < 1.5 kohm “1” (normal temperature), > 4 kohm “0”
(high temperature), open circuit “0” (high temperature).
Internal supply for digital inputs (+24 V DC): short-circuit proof. An external 24 V DC
supply can be used instead of the internal supply.
Insulation test voltage 500 V AC, 1 min
Logical thresholds < 8 V DC “0”, > 12 V DC “1”
Input current DI1 to DI 5: 10 mA, DI6: 5 mA
Filtering time constant 1 ms
Relay outputs
Three programmable relay outputs
Switching capacity 8 A at 24 V DC or 250 V AC, 0.4 A at 120 V DC
Minimum continuous current 5 mA rms at 24 V DC
Maximum continuous current 2 A rms
Insulation test voltage 4 kV AC, 1 minute
The terminals on the RMIO board as well as on the optional modules attachable to the board fulfil the Protective Extra
Low Voltage (PELV) requirements stated in EN 50178 provided that the external circuits connected to the terminals also
fulfil the requirements and the installation site is below 2000 m (6562 ft).
9 AO1+
10 AO1-
11 AO2+
12 AO2-
X22
1 DI1
2 DI2
3 DI3
4 DI4
Jumper J1 settings:
9 DGND1
Note: These diagrams do not necessarily match the delivery specific circuit
diagrams of a tailor-made cabinet-installed unit.