4 Column

maximum ultimate column load 867.23


column height 6.50
effective height 9.75
assume column size 350.00 350
slenderness ratio 27.86 therefore the column is slender
additional moments are BS 3.8.3
M1=0.05N*h 15.18
M2=k*N*h*(le/6)^2/2000 117.8
total moment 132.95
N/bh 7.08
Mu/bh^2 3.10
100As/bh 0.70 BS 8110 PART 3 CHART 34
min steel 0.40
Asc= 857.50
use 4 20mm
As, ac 1257mm^2
Links 8mm bar at 300 8mm 300mm
Note: vertical bars being 6m long need to
be reasonable stiff to avoid reinforcement 335mm^2
cage being too flexible
Column Bases
service load 619.45
SW column 19.91
SW base 30.00
669.35
use base 2.25 1
moment due to slender column say 50 50.00 assumed
soil pressure under base psb 158.56 105.88
note total pressure psb+pressure due to
223.56
contained water