Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

FEED FROM TOB-04

Unit-02 (Sheet No-02) L= Light


KNITTING SECTION F= Fan
SM= Sewing M/C
M/C= Machine
EXH= Exhaust Fan
EL= Emergency light
TRF= Top Roof Fan
400V CTP= Cooling tower pump
4X1CX185 RM , NYY (TP&N) TP= Tank Pump
1X1CX185 RM NYY ECC DP= Deep Pump

DB-30, UNIT-2, KNITTING SECTION


320A TP
MCCB
Set Point-281 A

R Y B
CU BUSBAR
3X1CX35RM NYY (TP)
TP- (40mmX6mm)-432A
N- (25mmX3mm)-135A V A TOTAL CONNECTED
E- (25mmX3mm)-135A
CT=160/5A LOAD - 66.482 KW

R-1 Y-2 B-3 R-4 Y-5 B-6 R-7 Y-8 B-9 Y-10 RYB-11 RYB-12 RYB-13 RYB-14 RYB-15 RYB-16 RYB-17 RYB-18

1X1cX4RM BYA (DOOR)


6A SP 6A SP 6A SP 32A SP 16A SP 16A SP 125A TP 40A TP 125A TP 125A TP 100A TP 63A TP 50A TP 150A TP
16A SP 16A SP 16A SP 16A SP
MCB MCB MCB MCB MCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB
MCB MCB MCB MCB MCB SET - 125A SET - 34A SET - 106A SET - 125A SET - 70A SET - 44A SET - 35A SET - 112A
2X1cX2.5RM BYA (SP&N)
1X1cX2.5RM BYAF (ECC)

4X1cX25RM NYY (TP&N)

4X1cX25RM NYY (TP&N)

4X1cX25RM NYY (TP&N)

4X1cX25RM NYY (TP&N)

4X1cX25RM NYY (TP&N)


1X1cX25RM NYY (ECC)

1X1cX25RM NYY (ECC)

1X1cX25RM NYY (ECC)

1X1cX25RM NYY (ECC)

1X1cX25RM NYY (ECC)


SPARE OFFICE ROOM SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE 3rd Floor Garments 4th Floor Cutting 1st Floor Garments 2nd Floor Garments SPARE 5th Floor Store SPARE SPARE
24-Nos Light(25W) DB-12 DB-11 DB-20 DB-19 DB-06
5-Nos FAN(80W) load=51.221KW load=15.198KW load=51.47KW load=50.63KW load=33.89KW
(24X25W)+(5X100W)=1KW SHEET NO-15 SHEET NO-14 SHEET NO-23 SHEET NO-22 SHEET NO-09
L1431-L1454,F375-F379

PROJECT: DIVINE TEXTILE LTD.


Drawn by : Technical Team of Divine Group Ltd. Date : 19.11.2023
RSC ID:11327

Checked by :
Technical Team of Divine Group Ltd. DIVINE GROUP LTD. SINGLE LINE DIAGRAM (SLD) Sheet No. 42
.