Professional Documents
Culture Documents
37
37
F= Fan
SM= Sewing M/C
M/C= Machine
FEED FROM TOB-03 EXH= Exhaust Fan
Unit-02(Sheet No-01) EL= Emergency light
FINISHING SECTION TRF= Top Roof Fan
CTP= Cooling tower pump
TP= Tank Pump
DP= Deep Pump
400V
4X1cX300RM NYY (TP&N)
2x1cx150RM NYY ECC
DB-37,UNIT-2,FINISHING SECTION-2
1000A TP
MCCB
Set Point-480A
R Y B
CU BUSBAR 3X1cX70RM NYY (TP)
TP- (42mmX10mm)-756A TOTAL CONNECTED
V A LOAD - 90.78 KW
N- (30mmX6mm)-324A
E- (30mmX6mm)-324A CT=250/5A
R-1 Y-2 B-3 R-4 Y-5 B-6 R-7 Y-8 B-9 R10 RYB-11 RYB-12 RYB-13 RYB-14 RYB-15 RYB-16
2X1cX1.5RM BYA(SP+N)
2X1cX1.5RM BYA(SP+N)
2X1cX2.5RM BYA(SP+N)
2X1cX2.5RM BYA(SP+N)
2X1cX2.5RM BYA(SP+N)
2X1cX2.5RM BYA(SP+N)
2X1cX4.5RM BYA(SP+N)
1X1cX4RM BYA(ECC)
SPARE 2-NOS EXHUST FAN BRUCKNER
AC-1 TON AC-2 TON 8-Nos Light(25W) 8-Nos Light(25W) 8-Nos Light(25W) 8-Nos Light(25W) 6-Nos Light(25W) 40-Nos Light(25W) 30-Nos Light(25W) TARNING M/C SPARE SPARE
(2X3000W)=6KW M/C-1
(1x2400W)=2.4KW (1x2400W)=2.4KW (8X25W)=0.4KW (8X25W)=0.4KW (8X25W)=0.4KW (8X25W)=0.4KW (6X25W)=0.15KW 8-Nos Light(100W) 6-Nos Light(100W) LOAD=4KW Exhaust Fan is Protected LOAD=135KW
AC Protected By a AC Protected By a L1558-L1565 L1566-L1573 L1574-L1581 L1582-L1589 L1590-L1595 (40X25W)+(8X100W)=1.8KW (30X25W)+(6X100W)=1.35KW by a 5A Thermal Overload
10A Circuit Breaker 10A Circuit Breaker L1596-L1643 L1644-L1679 relay with 50A Magnetic
AC-44 AC-45 Contractor
EXH-01,EXh-02
Checked by :
Technical Team of Divine Group Ltd. DIVINE GROUP LTD. SINGLE LINE DIAGRAM (SLD) Page No-68
.