Hardware Configuration

Test Equipment
Type Serial Number
CMC356 FC672K

Hardware Check
Performed At Result Details
19/06/2024 16:24:16 Passed

Analog Outputs
Test Equipment Test Object
Display Connection
Device Connector
Name Terminal
CMC356 V A 1 V L1-E
FC672K 2 V L2-E
3 V L3-E
N
CMC356 V B 1 VE
FC672K N
CMC356 I A 1 I L1
FC672K 2 I L2
3 I L3
N

Binary/Analog Inputs
Test Equipment Test Object
Display Connection
Device Connector
Name Terminal
CMC356 1+ TRIP
FC672K 1-
2+ DISJ FE
2-
3+ 50BF
3-
4+ Bin. in 4
4-
5+ Bin. in 5
5-
6+ Bin. in 6
6-
7+ Bin. in 7
7-
8+ Bin. in 8
8-
9+ Bin. in 9
9-
10+ Bin. in 10
10-
1 Bin. in 11
2 Bin. in 12
N

1 / 51
Binary Outputs
Test Equipment Test Object
Display Connection
Device Connector
Name Terminal
CMC356 1+ Bin. out 1
FC672K 1-
2+ Bin. out 2
2-
3+ Bin. out 3
3-
4+ Bin. out 4
4-
11 Bin. out 5
12 Bin. out 6
13 Bin. out 7
14 Bin. out 8
N

Analog DC Inputs
Test Equipment Test Object
Display Connection
Device Connector
Name Terminal
CMC356 V+ V1
FC672K V-
I+ I1
I-

Sampled Values
Overview
Stream Enabled IED / Sampled Values ID Simulated Ethernet port
1 No Yes ETH2
2 No Yes ETH2
3 No Yes ETH2
Sample rate / number of ASDUs: n/a

Test Object - Device Settings

Substation/Bay:
Substation: Substation Substation address: Substation address
Bay: bay Bay address: bay address

Device:
Name/description: SEL-311C Manufacturer: SEL
Device type: Distance protection Device address: feeder address
Serial/model number: serial no.
Additional info 1:
Additional info 2:

Nominal Values:
f nom: 60,00 Hz Number of phases: 3
V nom (secondary): 110,0 V V primary: 132,0 kV
I nom (secondary): 5,000 A I primary: 1,600 kA

Residual Voltage/Current Factors:


VLN / VN: 1,732 IN / I nom: 1,000
VN (secondary): 36,66 V IN (secondary): 5,000 A
Residual Voltage 3 * V0 Residual Current -3 * I0
Direction: Direction:

2 / 51
Limits:
V max: 500,0 V I max: 75,00 A

Debounce/Deglitch Filters:
Debounce time: 3,000 ms Deglitch time: 0,00 s

Overload Detection:
Suppression time: 50,00 ms

Other Device Properties:


Drop-out time: 20,00 ms

Test Object - Custom Settings

SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ General Settings


Description Name Value
Relay Identifier Lables Relay Identifier Lables
Relay Identifier (30 chars) RID Relay Identifier (30 SEL-311C - UCP1
chars)
Terminal Identifier (30 chars) TID Terminal Identifier (30 SE ITACAIUNAS -
chars) BAY BY
Current and Potential Transformer Ratios Current and Potential
Transformer Ratios
Phase (IA,IB,IC) CT Ratio, CTR:1 CTR Phase (IA,IB,IC) CT 320
Ratio, CTR:1
Polarizing (IPOL) CT Ratio, CTRP:1 CTRP Polarizing (IPOL) CT 200
Ratio, CTRP:1
Phase (VA,VB,VC) PT Ratio, PTR:1 PTR Phase (VA,VB,VC) PT 1200,00
Ratio, PTR:1
Synch. Voltage (VS) PT Ratio, PTRS:1 PTRS Synch. Voltage (VS) 1200,00
PT Ratio, PTRS:1
Application Settings Application Settings
Application APP Application 311C
Advance Setting Enable EADVS Advance Setting Y
Enable

SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Line Settings and Fault Locator
Description Name Value
Line Settings Line Settings
Pos-Seq Line Impedence Magnitude (Ohms secondary) Z1MAG Pos-Seq Line 1,39 Ohm
Impedence Magnitude (Ohms
secondary)
Pos-Seq Line Impedance Angle (degrees) Z1ANG Pos-Seq Line 67,72 °
Impedance Angle (degrees)
Zero-Seq Line Impedence Magnitude (Ohms secondary) Z0MAG Zero-Seq Line 5,14 Ohm
Impedence Magnitude (Ohms
secondary)
Zero-Seq Line Impedence Angle (degrees) Z0ANG Zero-Seq Line 75,06 °
Impedence Angle (degrees)
Line Length (unitless) LL Line Length (unitless) 10,00
Fault Locator Fault Locator
Fault locator enable Fault Locator Y

3 / 51
SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Phase Distance
Description Name Value
Enable Mho Phase Distance Elements E21P Enable Mho Phase 2
Distance Elements
CCVT Transient Detection Enable ECCVT CCVT Transient N
Detection Enable
Mho Phase Distance Element Reach Settings Mho Phase Distance Element
Reach Settings
Reach Zone1 (Ohm secondary) Z1P Reach Zone1 (Ohm 0,97 Ohm
secondary)
Reach Zone2 (Ohm secondary) Z2P Reach Zone2 (Ohm 1,67 Ohm
secondary)
Mho Phase Distance Overcurrent Fault Detector Settings Mho Phase Distance
Overcurrent Fault Detector
Settings
Phase-Phase Overcurrent Fault Detector Zone1 (Amps 50PP1 Phase-Phase 1,88 A
secondary) Overcurrent Fault Detector
Zone1 (Amps secondary)
Phase-Phase Overcurrent Fault Detector Zone2 (Amps 50PP2 Phase-Phase 1,88 A
secondary) Overcurrent Fault Detector
Zone2 (Amps secondary)
Phase-Phase Overcurrent Fault Detector Zone3 (Amps 50PP3 Phase-Phase 0,50 A
secondary) Overcurrent Fault Detector
Zone3 (Amps secondary)
Phase-Phase Overcurrent Fault Detector Zone4 (Amps 50PP4 Phase-Phase 0,50 A
secondary) Overcurrent Fault Detector
Zone4 (Amps secondary)

4 / 51
SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Ground Distance

5 / 51
Description Name Value
Enable Mho Ground Distance Elements E21MG Enable Mho Ground 2
Distance Elements
Reach Mho Ground Zone1 (Ohm secondary) Z1MG Mho Zone1 (Ohm 0,97 Ohm
secondary)
Reach Mho Ground Zone2 (Ohm secondary) Z2MG Mho Zone2 (Ohm 1,67 Ohm
secondary)
E21XG Enable Quad Ground Distance Elements E21XG Enable Quad Ground
Distance Elements
Enable Quad Ground Distance Elements E21XG Enable Quad Ground 2
Distance Elements
Reactance Zone1 Quad Ground (Ohm secondary) XG1 Quad Zone1 Reactance 0,90 Ohm
(Ohm secondary)
Reactance Zone2 Quad Ground (Ohm secondary) XG2 Quad Zone2 Reactance 1,54 Ohm
(Ohm secondary)
Resistance Zone1 Quad Ground (Ohm secondary) RG1 Quad Zone1 Resistance 5,00 Ohm
(Ohm secondary)
Resistance Zone2 Quad Ground (Ohm secondary) RG2 Quad Zone2 Resistance 8,00 Ohm
(Ohm secondary)
Quad Ground Polarizing Quantity XGPOL Quad Ground IG
Polarizing Quantity
None Homogeneous Correction Angle (degrees) TANG None Homogeneous 0,00 °
Correction Angle (degrees)
Quad and Mho Ground Distance Fault Detector Settings Quad and Mho Ground
Distance Fault Detector
Settings
Phase Overcurrent Fault Detector Zone1 for Ground Fault 50L1 Zone1 Phase Current 0,50 A
(Amps secondary) FD (Amps secondary)
Phase Overcurrent Fault Detector Zone2 for Ground Fault 50L2 Zone2 Phase Current 0,50 A
(Amps secondary) FD (Amps secondary)
Phase Overcurrent Fault Detector Zone3 for Ground Fault 50L3 Zone3 Phase Current 0,50 A
(Amps secondary) FD (Amps secondary)
Phase Overcurrent Fault Detector Zone4 for Ground Fault 50L4 Zone4 Phase Current 0,50 A
(Amps secondary) FD (Amps secondary)
Residual Current Fault Detector Zone1 for Ground Fault 50GZ1 Zone1 Residual 0,50 A
(Amps secondary) Current FD (Amps secondary)
Residual Current Fault Detector Zone2 for Ground Fault 50GZ2 Zone2 Residual 0,50 A
(Amps secondary) Current FD (Amps secondary)
Residual Current Fault Detector Zone3 for Ground Fault 50GZ3 Zone3 Residual 0,50 A
(Amps secondary) Current FD (Amps secondary)
Residual Current Fault Detector Zone4 for Ground Fault 50GZ4 Zone4 Residual 0,50 A
(Amps secondary) Current FD (Amps secondary)
Zero-Sequence Compensation Settings Zero-Sequence
Compensation Settings
Zone1 ZSC Factor Magnitude K0M1 Zone1 ZSC Factor 0,901
Magnitude
Zone1 ZSC Factor Angle K0A1 Zone1 ZSC Factor 10,04 °
Angle
Zone2,3,4 ZSC Factor Magnitude K0M Zone2,3,4 ZSC Factor 0,901
Magnitude
Zone2,3,4 ZSC Factor Angle K0A Zone2,3,4 ZSC Factor 10,04 °
Angle
Mho Phase Distance Element Time Delay Settings Mho Phase Distance Element
Time Delay Settings
Zone1 Phase Time Delay (cycles in 0.25 increments) Z1PD Zone1 Phase Time 0,00 cy
Delay (cycles in 0.25
increments)
Zone2 Phase Time Delay (cycles in 0.25 increments) Z2PD Zone2 Phase Time 24,00 cy
Delay (cycles in 0.25
increments)
Mho Ground Distance Element Time Delay Settings Mho Ground Distance
Element Time Delay Settings
Zone1 Ground Time Delay (cycles in 0.25 increments) Z1GD Zone1 Ground Time 0,00 cy
Delay (cycles in 0.25
increments)
Zone2 Ground Time Delay (cycles in 0.25 increments) Z2GD Zone2 Ground Time 24,00 cy
Delay (cycles in 0.25
increments)
Common Phase/Ground Dist. Element Time Delay Settings Common Phase/Ground Dist.
Element Time Delay Settings
Zone1 Common Ph/Gr Time Delay (cycles in 0.25 Z1D Zone1 Common Ph/Gr 0,00 cy
increments) Time Delay (cycles in 0.25
increments)

6 / 51
Zone2 Common Ph/Gr Time Delay (cycles in 0.25 Z2D Zone2 Common Ph/Gr 24,00 cy
increments) Time Delay (cycles in 0.25
increments)

SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Phase Instantaneous Overcurrent
Description Name Value
Enable Phase Overcurrent Elements E50P Enable Phase 2
Overcurrent Elements
Level 1 (Amps secondary) 50P1P Level 1 (Amps 22,81 A
secondary)
Level 2 (Amps secondary) 50P2P Level 2 (Amps 1,88 A
secondary)
Phase Definite-Time Overcurrent Elements Phase Definite-Time
Overcurrent Elements
Level 1 (cycles in 0.25 increments) 67P1D Level 1 (cycles in 0.25 3,00 cy
increments)
Level 2 (cycles in 0.25 increments) 67P2D Level 2 (cycles in 0.25 0,00 cy
increments)

SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Residual Ground Instantaneous
Overcurrent
Description Name Value
Enable Residual Ground Overcurrent Elements E50G Enable Residual 1
Ground Overcurrent Elements
Level 1 (Amps secondary) 50G1P Level 1 (Amps 18,00 A
secondary)
Residual Ground Definite-Time Overcurrent Elements Residual Ground
Definite-Time Overcurrent
Elements
Level 1 (cycles in 0.25 increments) 67G1D Level 1 (cycles in 0.25 3,00 cy
increments)

SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Negative-Sequence Instantaneous


Overcurrent
Description Name Value
Enable Negative-Sequence Overcurrent Elements E50Q Enable N
Negative-Sequence
Overcurrent Elements
Residual Ground Definite-Time Overcurrent Elements Negative-Sequence
Definite-Time Overcurrent
Elements

SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Phase Time-Overcurrent


Description Name Value
Enable Phase Time-Overcurrent Elements E51P Enable Phase Y
Time-Overcurrent Elements
Pickup (Amps secondary) 51PP Pickup (Amps 1,87 A
secondary)
Curve 51PC Curve C1
Time Dial 51PTD Time Dial 0,14
Electromechanical Reset Delay 51PRS Electromechanical N
Reset Delay

SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Residual Ground Time-Overcurrent
Description Name Value
Enable Residual Ground Time-Overcurrent Elements E51G Enable Residual Y
Ground Time-Overcurrent
Elements
Pickup (Amps secondary) 51GP Pickup (Amps 0,50 A
secondary)
Curve 51GC Curve C1
Time Dial 51GTD Time Dial 0,20
Electromechanical Reset Delay 51GRS Electromechanical N
Reset Delay

7 / 51
SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Negative-Sequence
Time-Overcurrent
Description Name Value
Enable Negative-Sequence Time-Overcurrent Elements E51Q Enable Y
Negative-Sequence
Time-Overcurrent Elements
Pickup (Amps secondary) 51QP Pickup (Amps 2,20 A
secondary)
Curve 51QC Curve U3
Time Dial 51QTD Time Dial 3,00
Electromechanical Reset Delay 51QRS Electromechanical N
Reset Delay

SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Out of Step


Description Name Value
Enable Out of Step Elements EOOS Enable Out of Step N
Elements
Out of Step Elements Block Zone1 OOSB1 Block Zone1 N
Out of Step Elements Block Zone2 OOSB2 Block Zone2 N
Out of Step Elements Block Zone3 OOSB3 Block Zone3 N
Out of Step Elements Block Zone4 OOSB4 Block Zone4 N
Out of Step Block Time Delay (cycles in 0.25 increments) OSBD Out of Step Block 2,00 cy
Time Delay (cycles in 0.25
increments)
Enable Out of Step Tripping EOOST Enable Out of Step N
Tripping
Out of Step Zone6 Reactance-Top (Ohm secondary) X1T6 Out of Step Zone6 96,00 Ohm
Reactance-Top (Ohm
secondary)
Out of Step Zone5 Reactance-Top (Ohm secondary) X1T5 Out of Step Zone5 90,00 Ohm
Reactance-Top (Ohm
secondary)
Out of Step Zone6 Resisistance-Right (Ohm secondary) R1R6 Out of Step Zone6 70,00 Ohm
Resisistance-Right (Ohm
secondary)
Out of Step Zone5 Resisistance-Right (Ohm secondary) R1R5 Out of Step Zone5 65,00 Ohm
Resisistance-Right (Ohm
secondary)
Out of Step Zone6 Reactance-Bottom (Ohm secondary) X1B6 Out of Step Zone6 -96,00 Ohm
Reactance-Bottom (Ohm
secondary)
Out of Step Zone5 Reactance-Bottom (Ohm secondary) X1B5 Out of Step Zone5 -90,00 Ohm
Reactance-Bottom (Ohm
secondary)
Out of Step Zone6 Resistance-Left (Ohm secondary) R1L6 Out of Step Zone6 -70,00 Ohm
Resistance-Left (Ohm
secondary)
Out of Step Zone5 Resistance-Left (Ohm secondary) R1L5 Out of Step Zone5 -65,00 Ohm
Resistance-Left (Ohm
secondary)
Out of Step Positive Sequence Current Supervision (Amps 50ABCP Out of Step Positive 1,00 A
secondary) Sequence Current
Supervision (Amps
secondary)
Negative Sequence Current Unblock Delay (cycles in 0.25 UBD Negative Sequence 0,50 cy
increments) Current Unblock Delay
(cycles in 0.25 increments)
Out of Step Angle Change Unblock Rate UBOSBF Out of Step Angle 4,00
Change Unblock Rate

8 / 51
SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Load-Encroachment
Description Name Value
Enable Load-Encroachment Element ELOAD Enable Y
Load-Encroachment Element
Forward Load Impedance (Ohms secondary) ZLF Forward Load 32,00 Ohm
Impedance (Ohms
secondary)
Reverse Load Imoedance (Ohms secondary) ZLR Reverse Load 32,00 Ohm
Imoedance (Ohms
secondary)
Positive Forward Load Angle (degrees) PLAF Positive Forward Load 30,00 °
Angle (degrees)
Negative Forward Load Angle (degrees) NLAF Negative Forward Load -30,00 °
Angle (degrees)
Positive Reverse Load Angle (degrees) PLAR Positive Reverse Load 150,00 °
Angle (degrees)
Negative Reverse Load Angle (degrees) NLAR Negative Reverse Load 210,00 °
Angle (degrees)

SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Directional Elements


Description Name Value
E32 Enable Directional Elements E32 Enable Directional AUTO
Elements
ELOP Loss of Potential Enable ELOP Loss of Potential Y
Enable
Level3 Direction DIR3 Level3 Direction R
Level4 Direction DIR4 Level4 Direction F
Ground Directional Element Priority ORDER Ground Directional QVI
Element Priority

SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Voltage Elements


Description Name Value
Enable Voltage Elements EVOLT Enable Voltage Y
Elements
Phase Undervoltage Pickup (Volts secondary) 27P Phase Undervoltage +inf V
Pickup (Volts secondary)
Phase Overvoltage Pickup (Volts secondary) 59P Phase Overvoltage 79,67 V
Pickup (Volts secondary)
Zero-Seq. (3V0) Overvoltage Pickup (Volts secondary) 59N1P Zero-Seq. (3V0) +inf V
Overvoltage Pickup (Volts
secondary)
Zero-Seq. (3V0) Overvoltage Pickup (Volts secondary) 59N2P Zero-Seq. (3V0) +inf V
Overvoltage Pickup (Volts
secondary)
Neg.-Seq. (V2) Overvoltage Pickup (Volts secondary) 59QP Neg.-Seq. (V2) +inf V
Overvoltage Pickup (Volts
secondary)
Pos.-Seq. (V1) Overvoltage Pickup (Volts secondary) 59V1P Pos.-Seq. (V1) +inf V
Overvoltage Pickup (Volts
secondary)
Channel VS Undervoltage Pickup (Volts secondary) 27SP Channel VS +inf V
Undervoltage Pickup (Volts
secondary)
Channel VS Overvoltage Pickup (Volts secondary) 59SP Channel VS +inf V
Overvoltage Pickup (Volts
secondary)
Phase-Phase Undervoltage Pickup (Volts secondary) 27PP Phase-Phase +inf V
Undervoltage Pickup (Volts
secondary)
Phase-Phase Overvoltage Pickup (Volts secondary) 59PP Phase-Phase 161,00 V
Overvoltage Pickup (Volts
secondary)

9 / 51
SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Synchronism Check
Description Name Value
Enable Synchronism Check Elements E25 Enable Synchronism Y
Check Elements
Voltage Window - Low Threshold (Volts secondary) 25VLO Voltage Window - Low 59,00 V
Threshold (Volts secondary)
Voltage Window - High Threshold (Volts secondary) 25VHI Voltage Window - High 80,00 V
Threshold (Volts secondary)
Maximum Slip Frequency (Hz) 25SF Maximum Slip 0,050 Hz
Frequency (Hz)
Maximum Angle 1 (degrees) 25ANG1 Maximum Angle 1 25,00 °
(degrees)
Maximum Angle 2 (degrees) 25ANG2 Maximum Angle 2 40,00 °
(degrees)
Sync. Phase SYNCP Sync. Phase VB
Breaker Close Time for Angle Comp. TCLOSD Breaker Close Time 3,00 cy
for Angle Comp.

SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Frequency Elements


Description Name Value
Enable Frequency Elements E81 Enable Frequency N
Elements

SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Reclosing Relay


Description Name Value
Enable Reclosing Relay Elements E79 Enable Reclosing Relay 1
Elements
Open Interval 1 (cycles in 0.25 increments) 79OI1 Open Interval 1 (cycles 300,00 cy
in 0.25 increments)
Reset Time from Reclose Cycle (cycles in 0.25 increments) 79RSD Reset Time from 10800,00 cy
Reclose Cycle (cycles in 0.25
increments)
Reset Time from Lockout (cycles in 0.25 increments) 79RSLD Reset Time from 1800,00 cy
Lockout (cycles in 0.25
increments)
Reclose Supv. Time Limit (cycles in 0.25 increments) 79CLSD Reclose Supv. Time 480,00 cy
Limit (cycles in 0.25
increments)

SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Switch-Onto-Fault


Description Name Value
Enable Switch-Onto-Fault Elements ESOTF Enable Y
Switch-Onto-Fault Elements
Close Enable Time Delay (cycles in 0.25 increments) CLOEND Close Enable Time +inf cy
Delay (cycles in 0.25
increments)
52A Enable Time Delay (cycles in 0.25 increments) 52AEND 52A Enable Time 12,00 cy
Delay (cycles in 0.25
increments)
SOTF Duration (cycles in 0.25 increments) SOTFD SOTF Duration 12,00 cy
(cycles in 0.25 increments)

SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Comm. Assisted Trip Schemes
Description Name Value
Enable Communication Assisted Tripping Schemes ECOMM Enable N
Communication Assisted
Tripping Schemes

SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Zone1 Extension


Description Name Value
EZ1EXT Enable Zone1 Extension Elements EZ1EXT Enable Zone1 N
Extension Elements

10 / 51
SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Demand Metering
Description Name Value
Enable Demand Metering Method EDEM Enable Demand THM
Metering Method
Time Constant DMTC Time Constant 5
Phase Pickup (Amps secondary) PDEMP Phase Pickup (Amps 5,00 A
secondary)
Residual Ground Pickup (Amps secondary) GDEMP Residual Ground 1,50 A
Pickup (Amps secondary)
Negative-Sequence Pickup (Amps secondary) QDEMP Negative-Sequence 1,50 A
Pickup (Amps secondary)

SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Other Settings


Description Name Value
Minimum Trip Duration Time (cycles in 0.25 increments) TDURD Minimum Trip 5,00 cy
Duration Time (cycles in 0.25
increments)
Close Failure Time Delay (cycles in 0.25 increments) CFD Close Failure Time 10,00 cy
Delay (cycles in 0.25
increments)
3-Pole Open Time Delay (cycles in 0.25 increments) 3POD 3-Pole Open Time 1,50 cy
Delay (cycles in 0.25
increments)
Open Pole Option OPO Open Pole Option 52
Three Pole Open Undervoltage Pickup (Volts secondary) 27PO Three Pole Open 40,00 V
Undervoltage Pickup (Volts
secondary)
Load Detection Phase Pickup (Amps secondary) 50LP Load Detection Phase 0,25 A
Pickup (Amps secondary)

SEL 311C \ Relay Parameter Section \ Group 1 \ Logic 1 \ Trip/Comm.-Assisted Trip Logic
Description Name Value
Trip Logic Equations Trip Logic Equations
TR Direct Trip conditions M1PT+M2PT+M3PT+
Z1GT+Z2GT+Z3GT+
67P1T+67G1T+51PT
+51GT
TRCOMM M2P+Z2G
Communication-assisted trip
conditions
TRSOTF Switch-onto-fault trip M2P+Z2G+50P1
conditions
DTT Direct transfer trip 0
conditions.
ULTR Unlatch trip conditions !(M1P+M2P+M3P+Z1
G+Z2G+Z3G+67P1+6
7G1+51P+51G)

SEL 311C \ Relay Parameter Section \ Global \ General


Description Name Value
Setting Group Change Delay TGR Setting Group Change 0,00 cy
Delay
Nominal Frequency (Hz) NFREQ Nominal Frequency 60
(Hz)
Phase Rotation PHROT Phase Rotation ABC
Date Format DATE_F Date Format YMD
DC Battery LO Voltage Pickup (Vdc) DCLOP DC Battery LO 92,00 V
Voltage Pickup (Vdc)
DC Battery HI Voltage Pickup (Vdc) DCHIP DC Battery HI Voltage 138,00 V
Pickup (Vdc)

11 / 51
SEL 311C \ Additional Information \ General - General Information
Description Name Value
Manufacturer Manufacturer SEL
Device Model Device Model SEL-311C
Serial Number Serial Number serial no.
Device Address Device Address device address
Device type Device type Distance protection
Manufacturer HW code Hardware revision HW revision
Software revision Software revision Software revision
Substation Substation Substation
Substation Address Substation Address Substation address
Feeder Feeder feeder
Feeder Address Feeder Address feeder address
Bay Bay bay
Bay address Bay address bay address
Protected object name Protected object name Protected object
name
Description Description information
Location Location Location

SEL 311C \ Additional Information \ Power System Data \ VT's


Description Name Value
Line to Neutral Voltage Secondary Nominal Voltage 63,50 V
L-N

SEL 311C \ Additional Information \ Power System Data \ CT's


Description Name Value
Secondary Nominal Current 5A

SEL 311C \ Additional Information \ Configuration details


Description Name Value
Test with loss-of-potential condition? Test overcurrent as backup true

SEL 311C \ Additional Information \ Configuration details \ Trip logic


Description Name Value
Override Trip Logic Evaluation Override Trip Logic false
Evaluation

12 / 51
SEL 311C \ Additional Information \ Configuration details \ Trip logic \ Distance protection
Description Name Value
Phase distance Zone 1 used true
for direct tripping
Ground distance Zone 1 used true
for direct tripping
Phase distance Zone 2 used true
for direct tripping
Ground distance Zone 2 used true
for direct tripping
Phase distance Zone 3 used true
for direct tripping
Ground distance Zone 3 used true
for direct tripping
Phase distance Zone 4 used false
for direct tripping
Ground distance Zone 4 used false
for direct tripping
is "M1P" wordbit connected to a trip output? Instantanous trip of phase false
distance Zone 1
is "Z1G" wordbit connected to a trip output? Instantanous trip of ground false
distance Zone 1
Do Z1P and Z1G use common or independent timers? Timer selecion for phase and Independent timer for
ground distance Zone 1 phase and ground
Do Z2P and Z2G use common or independent timers? Timer selecion for phase and Independent timer for
ground distance Zone 2 phase and ground
Do Z3P and Z3G use common or independent timers? Timer selecion for phase and Independent timer for
ground distance Zone 3 phase and ground

SEL 311C \ Additional Information \ Configuration details \ Trip logic \ Overcurrent


Description Name Value
Phase overcurrent level 1 Definite time
Phase overcurrent level 2 Not used for tripping
Phase overcurrent level 3 Not used for tripping
Residual overcurrent level 1 Definite time
Directional
Residual overcurrent level 2 Not used for tripping
Residual overcurrent level 3 Not used for tripping
Residual overcurrent level 4 Not used for tripping
Negative sequence Not used for tripping
overcurrent level 1
Negative sequence Not used for tripping
overcurrent level 2
Negative sequence Not used for tripping
overcurrent level 3
Negative sequence Not used for tripping
overcurrent level 4
is this element connected to a trip output? Phase time overcurrent true
"51PT"
is this element connected to a trip output? Residual time overcurrent true
"51GT"
is this element connected to a trip output? Negative sequence time false
overcurrent "51QT"

SEL 311C \ Additional Information \ Circuit Breaker Information


Description Name Value
52ab Percentage 52ab Percentage 20,00 %
CB Trip Time CB Trip Time 50,00 ms
CB Close Time CB Close Time 100,00 ms
t-Tolerance abs t-Tolerance abs 0,00 ms
t-Tolerance rel t-Tolerance rel 5,00 %

SEL 311C \ Additional Information \ Relay Information \ Output contacts


Description Name Value
Contact operatating time Contact operatating time 4,00 ms

13 / 51
SEL 311C \ Additional Information \ Relay Information \ Distance Protection - Distance
protection
Description Name Value
Rel. Tol Z at Line Angle (SIR<=60) Rel. Tol Z 5,00 %
Max. Trip time (according operating time curve at SIR=30) Max. operating time (cycle) - 2,00 cy
internal operation
Max. Trip time (according operating time curve at SIR=30) Max. operating time (ms) - 33,33 ms
internal operation
Rel. time tolerance Rel. t-Tolerance 5,00 %
Pick up / drop off ratio Pick Up / Drop Off Ratio 0,95
Abs. t-Tolerance Abs. t-Tolerance- internal 1,50 cy
operation

SEL 311C \ Additional Information \ Relay Information \ Distance Protection \ Fault


Detectors
Description Name Value
Rel. I-Tolerance 3,00 %
Abs. I-Tolerance 0,05 A

SEL 311C \ Additional Information \ Relay Information \ Overcurrent Protection \ Time


Overcurrent Elements
Description Name Value
abs. current tolerance 0,05 A
rel. current tolerance 3,00 %
abs. time tolerance 1,75 cy
rel. time tolerance 0,10 %
Pickup/Drop off ratio 1,00

SEL 311C \ Additional Information \ Relay Information \ Overcurrent Protection \ Definite


Time/Instantaneous Elements
Description Name Value
abs. current tolerance 0,05 A
rel. current tolerance 3,00 %
abs. time tolerance 1,75 cy
rel. time tolerance 0,10 %
Pickup/Drop off ratio 1,00
Max operating time - internal 1,50 cy
operation

SEL 311C \ Additional Information \ Test Tolerance


Description Name Value
Global Test Tolerance Test Tolerance 2,00 %

Test Object - Other RIO Functions

CB Configuration
Description Name Value
CB trip time CB trip time 50,00 ms
CB close time CB close time 100,00 ms
Times for 52a, 52b in percent of CB time 52a, 52b % of CB 20,00 %

Test Object - Overcurrent Parameters

General - Values:
TimeTolAbs: 0,03 s VT connection: n/a
TimeTolRel: 0,10 % CT starpoint connection: n/a
CurrentTolAbs: 0,05 Iref
CurrentTolRel: 3,00 %
Directional: No

14 / 51
Elements - Phase:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
Yes 51P C1 Standard Inverse 1,87 Iref 0,14 1,00 Non Directional
Yes 50/67P1 Definite Time 22,81 Iref 0,08 s 1,00 Non Directional
No 50/67P2 Definite Time 1,88 Iref 0,03 s 1,00 Non Directional
No 50/67P3 Definite Time 0,10 Iref 0,03 s 1,00 Non Directional

Elements - Residual:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
Yes 51G C1 Standard Inverse 0,50 Iref 0,20 1,00 Non Directional
Yes 50/67G1 Definite Time 18,00 0,08 s 1,00 Non Directional
Iref
No 50/67G2 Definite Time 0,10 Iref 0,03 s 1,00 Non Directional
No 50/67G3 Definite Time 0,10 Iref 0,03 s 1,00 Non Directional
No 50/67G4 Definite Time 0,10 Iref 0,03 s 1,00 Non Directional

Elements - Negative Sequence:


Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
No 51Q U3 Very Inverse 0,73 Iref 3,00 1,00 Non Directional
No 50/67Q1 Definite Time 0,10 Iref 0,03 s 1,00 Non Directional
No 50/67Q2 Definite Time 0,10 Iref 0,03 s 1,00 Non Directional
No 50/67Q3 Definite Time 0,10 Iref 0,03 s 1,00 Non Directional
No 50/67Q4 Definite Time 0,10 Iref 0,03 s 1,00 Non Directional

Test Object - Distance Settings


System parameters:
Line length: 1,390 Ω Line angle: 67,72 °
PT connection: at line CT starpoint: Dir. line
Impedance correction no
1A/I nom:
Impedances in primary no
values:

Tolerances:
Tol. T rel.: 5,000 %
Tol. T abs. +: 29,00 ms Tol. T abs. -: 29,00 ms
Tol. Z rel.: 5,000 % Tol. Z abs.: 50,00 mΩ

Grounding factor:
kL mag.: 0,000000 kL angle: 0,000000°
Separate arc no
resistance:

Zone Settings:
Tol. T Tol. T
Label Type Fault loop Trip time Tol. T rel Tol. Z rel. Tol. Z abs
abs+ abs-
ZL1 Tripping L-L 33,33 ms 5,000 % 29,00 ms 29,00 ms 5,000 % 50,00 mΩ
ZL2 Tripping L-L 433,3 ms 5,000 % 29,00 ms 29,00 ms 5,000 % 50,00 mΩ
ZM1 Tripping L-E 33,33 ms 5,000 % 29,00 ms 29,00 ms 5,000 % 50,00 mΩ
ZM2 Tripping L-E 433,3 ms 5,000 % 29,00 ms 29,00 ms 5,000 % 50,00 mΩ
ZX1 Tripping L-E 33,33 ms 5,000 % 29,00 ms 29,00 ms 5,000 % 50,00 mΩ
ZX2 Tripping L-E 433,3 ms 5,000 % 29,00 ms 29,00 ms 5,000 % 50,00 mΩ
pos. Load non trip. L1-L2-L3 n/a n/a n/a n/a 5,000 % 1,600 Ω
Encroach
ment
neg. Load non trip. L1-L2-L3 n/a n/a n/a n/a 5,000 % 1,600 Ω
Encroach
ment

15 / 51
X/Ω

30

20

10

-10

-20

-30

-40 -30 -20 -10 0 10 20 30


R/Ω

Test Object - Power Settings


System parameters:
CT starpoint: Towards line

Reference for relative power data:


Reference: Nominal CT*VT
Nominal reference power: 0,00 VA

Tolerances:
Tol. T rel.: 5,000 % Tol. S rel.: 5,000 %
Tol. T abs. +: 50,00 ms Tol. S abs.: 50,00 mVA
Tol. T abs. -: 0,00 s Angle tol.: 3,000 °

Voltage threshold:
Voltage threshold No Voltage threshold tol. rel.: 5,000 %
enabled:
Voltage threshold: 100,0 V Voltage threshold tol. 5,000 V
abs.:
Voltage threshold type: Undervoltage

Overcurrent threshold:
Overcurrent threshold No Overcurrent threshold tol. 5,000 %
enabled: rel.:
Overcurrent threshold: 1,000 A Overcurrent threshold tol. 250,0 mA
abs.:

Zone Settings:

QuickCMC:

Test Object - Device Settings

Substation/Bay:
Substation: Substation Substation address: Substation address
Bay: bay Bay address: bay address

16 / 51
Device:
Name/description: SEL-311C Manufacturer: SEL
Device type: Distance protection Device address: feeder address
Serial/model number: serial no.
Additional info 1:
Additional info 2:

Nominal Values:
f nom: 60,00 Hz Number of phases: 3
V nom (secondary): 110,0 V V primary: 132,0 kV
I nom (secondary): 5,000 A I primary: 1,600 kA

Residual Voltage/Current Factors:


VLN / VN: 1,732 IN / I nom: 1,000
VN (secondary): 36,66 V IN (secondary): 5,000 A
Residual Voltage 3 * V0 Residual Current -3 * I0
Direction: Direction:

Limits:
V max: 500,0 V I max: 75,00 A

Debounce/Deglitch Filters:
Debounce time: 3,000 ms Deglitch time: 0,00 s

Overload Detection:
Suppression time: 50,00 ms

Other Device Properties:


Drop-out time: 20,00 ms

Test Object - Custom Settings

SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ General Settings


Description Name Value
Relay Identifier Lables Relay Identifier Lables
Relay Identifier (30 chars) RID Relay Identifier (30 SEL-311C - UCP1
chars)
Terminal Identifier (30 chars) TID Terminal Identifier (30 SE ITACAIUNAS -
chars) BAY BY
Current and Potential Transformer Ratios Current and Potential
Transformer Ratios
Phase (IA,IB,IC) CT Ratio, CTR:1 CTR Phase (IA,IB,IC) CT 320
Ratio, CTR:1
Polarizing (IPOL) CT Ratio, CTRP:1 CTRP Polarizing (IPOL) CT 200
Ratio, CTRP:1
Phase (VA,VB,VC) PT Ratio, PTR:1 PTR Phase (VA,VB,VC) PT 1200,00
Ratio, PTR:1
Synch. Voltage (VS) PT Ratio, PTRS:1 PTRS Synch. Voltage (VS) 1200,00
PT Ratio, PTRS:1
Application Settings Application Settings
Application APP Application 311C
Advance Setting Enable EADVS Advance Setting Y
Enable

17 / 51
SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Line Settings and Fault Locator
Description Name Value
Line Settings Line Settings
Pos-Seq Line Impedence Magnitude (Ohms secondary) Z1MAG Pos-Seq Line 1,39 Ohm
Impedence Magnitude (Ohms
secondary)
Pos-Seq Line Impedance Angle (degrees) Z1ANG Pos-Seq Line 67,72 °
Impedance Angle (degrees)
Zero-Seq Line Impedence Magnitude (Ohms secondary) Z0MAG Zero-Seq Line 5,14 Ohm
Impedence Magnitude (Ohms
secondary)
Zero-Seq Line Impedence Angle (degrees) Z0ANG Zero-Seq Line 75,06 °
Impedence Angle (degrees)
Line Length (unitless) LL Line Length (unitless) 10,00
Fault Locator Fault Locator
Fault locator enable Fault Locator Y

SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Phase Distance


Description Name Value
Enable Mho Phase Distance Elements E21P Enable Mho Phase 2
Distance Elements
CCVT Transient Detection Enable ECCVT CCVT Transient N
Detection Enable
Mho Phase Distance Element Reach Settings Mho Phase Distance Element
Reach Settings
Reach Zone1 (Ohm secondary) Z1P Reach Zone1 (Ohm 0,97 Ohm
secondary)
Reach Zone2 (Ohm secondary) Z2P Reach Zone2 (Ohm 1,67 Ohm
secondary)
Mho Phase Distance Overcurrent Fault Detector Settings Mho Phase Distance
Overcurrent Fault Detector
Settings
Phase-Phase Overcurrent Fault Detector Zone1 (Amps 50PP1 Phase-Phase 1,88 A
secondary) Overcurrent Fault Detector
Zone1 (Amps secondary)
Phase-Phase Overcurrent Fault Detector Zone2 (Amps 50PP2 Phase-Phase 1,88 A
secondary) Overcurrent Fault Detector
Zone2 (Amps secondary)
Phase-Phase Overcurrent Fault Detector Zone3 (Amps 50PP3 Phase-Phase 0,50 A
secondary) Overcurrent Fault Detector
Zone3 (Amps secondary)
Phase-Phase Overcurrent Fault Detector Zone4 (Amps 50PP4 Phase-Phase 0,50 A
secondary) Overcurrent Fault Detector
Zone4 (Amps secondary)

18 / 51
SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Ground Distance

19 / 51
Description Name Value
Enable Mho Ground Distance Elements E21MG Enable Mho Ground 2
Distance Elements
Reach Mho Ground Zone1 (Ohm secondary) Z1MG Mho Zone1 (Ohm 0,97 Ohm
secondary)
Reach Mho Ground Zone2 (Ohm secondary) Z2MG Mho Zone2 (Ohm 1,67 Ohm
secondary)
E21XG Enable Quad Ground Distance Elements E21XG Enable Quad Ground
Distance Elements
Enable Quad Ground Distance Elements E21XG Enable Quad Ground 2
Distance Elements
Reactance Zone1 Quad Ground (Ohm secondary) XG1 Quad Zone1 Reactance 0,90 Ohm
(Ohm secondary)
Reactance Zone2 Quad Ground (Ohm secondary) XG2 Quad Zone2 Reactance 1,54 Ohm
(Ohm secondary)
Resistance Zone1 Quad Ground (Ohm secondary) RG1 Quad Zone1 Resistance 5,00 Ohm
(Ohm secondary)
Resistance Zone2 Quad Ground (Ohm secondary) RG2 Quad Zone2 Resistance 8,00 Ohm
(Ohm secondary)
Quad Ground Polarizing Quantity XGPOL Quad Ground IG
Polarizing Quantity
None Homogeneous Correction Angle (degrees) TANG None Homogeneous 0,00 °
Correction Angle (degrees)
Quad and Mho Ground Distance Fault Detector Settings Quad and Mho Ground
Distance Fault Detector
Settings
Phase Overcurrent Fault Detector Zone1 for Ground Fault 50L1 Zone1 Phase Current 0,50 A
(Amps secondary) FD (Amps secondary)
Phase Overcurrent Fault Detector Zone2 for Ground Fault 50L2 Zone2 Phase Current 0,50 A
(Amps secondary) FD (Amps secondary)
Phase Overcurrent Fault Detector Zone3 for Ground Fault 50L3 Zone3 Phase Current 0,50 A
(Amps secondary) FD (Amps secondary)
Phase Overcurrent Fault Detector Zone4 for Ground Fault 50L4 Zone4 Phase Current 0,50 A
(Amps secondary) FD (Amps secondary)
Residual Current Fault Detector Zone1 for Ground Fault 50GZ1 Zone1 Residual 0,50 A
(Amps secondary) Current FD (Amps secondary)
Residual Current Fault Detector Zone2 for Ground Fault 50GZ2 Zone2 Residual 0,50 A
(Amps secondary) Current FD (Amps secondary)
Residual Current Fault Detector Zone3 for Ground Fault 50GZ3 Zone3 Residual 0,50 A
(Amps secondary) Current FD (Amps secondary)
Residual Current Fault Detector Zone4 for Ground Fault 50GZ4 Zone4 Residual 0,50 A
(Amps secondary) Current FD (Amps secondary)
Zero-Sequence Compensation Settings Zero-Sequence
Compensation Settings
Zone1 ZSC Factor Magnitude K0M1 Zone1 ZSC Factor 0,901
Magnitude
Zone1 ZSC Factor Angle K0A1 Zone1 ZSC Factor 10,04 °
Angle
Zone2,3,4 ZSC Factor Magnitude K0M Zone2,3,4 ZSC Factor 0,901
Magnitude
Zone2,3,4 ZSC Factor Angle K0A Zone2,3,4 ZSC Factor 10,04 °
Angle
Mho Phase Distance Element Time Delay Settings Mho Phase Distance Element
Time Delay Settings
Zone1 Phase Time Delay (cycles in 0.25 increments) Z1PD Zone1 Phase Time 0,00 cy
Delay (cycles in 0.25
increments)
Zone2 Phase Time Delay (cycles in 0.25 increments) Z2PD Zone2 Phase Time 24,00 cy
Delay (cycles in 0.25
increments)
Mho Ground Distance Element Time Delay Settings Mho Ground Distance
Element Time Delay Settings
Zone1 Ground Time Delay (cycles in 0.25 increments) Z1GD Zone1 Ground Time 0,00 cy
Delay (cycles in 0.25
increments)
Zone2 Ground Time Delay (cycles in 0.25 increments) Z2GD Zone2 Ground Time 24,00 cy
Delay (cycles in 0.25
increments)
Common Phase/Ground Dist. Element Time Delay Settings Common Phase/Ground Dist.
Element Time Delay Settings
Zone1 Common Ph/Gr Time Delay (cycles in 0.25 Z1D Zone1 Common Ph/Gr 0,00 cy
increments) Time Delay (cycles in 0.25
increments)

20 / 51
Zone2 Common Ph/Gr Time Delay (cycles in 0.25 Z2D Zone2 Common Ph/Gr 24,00 cy
increments) Time Delay (cycles in 0.25
increments)

SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Phase Instantaneous Overcurrent
Description Name Value
Enable Phase Overcurrent Elements E50P Enable Phase 2
Overcurrent Elements
Level 1 (Amps secondary) 50P1P Level 1 (Amps 22,81 A
secondary)
Level 2 (Amps secondary) 50P2P Level 2 (Amps 1,88 A
secondary)
Phase Definite-Time Overcurrent Elements Phase Definite-Time
Overcurrent Elements
Level 1 (cycles in 0.25 increments) 67P1D Level 1 (cycles in 0.25 3,00 cy
increments)
Level 2 (cycles in 0.25 increments) 67P2D Level 2 (cycles in 0.25 0,00 cy
increments)

SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Residual Ground Instantaneous
Overcurrent
Description Name Value
Enable Residual Ground Overcurrent Elements E50G Enable Residual 1
Ground Overcurrent Elements
Level 1 (Amps secondary) 50G1P Level 1 (Amps 18,00 A
secondary)
Residual Ground Definite-Time Overcurrent Elements Residual Ground
Definite-Time Overcurrent
Elements
Level 1 (cycles in 0.25 increments) 67G1D Level 1 (cycles in 0.25 3,00 cy
increments)

SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Negative-Sequence Instantaneous


Overcurrent
Description Name Value
Enable Negative-Sequence Overcurrent Elements E50Q Enable N
Negative-Sequence
Overcurrent Elements
Residual Ground Definite-Time Overcurrent Elements Negative-Sequence
Definite-Time Overcurrent
Elements

SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Phase Time-Overcurrent


Description Name Value
Enable Phase Time-Overcurrent Elements E51P Enable Phase Y
Time-Overcurrent Elements
Pickup (Amps secondary) 51PP Pickup (Amps 1,87 A
secondary)
Curve 51PC Curve C1
Time Dial 51PTD Time Dial 0,14
Electromechanical Reset Delay 51PRS Electromechanical N
Reset Delay

SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Residual Ground Time-Overcurrent
Description Name Value
Enable Residual Ground Time-Overcurrent Elements E51G Enable Residual Y
Ground Time-Overcurrent
Elements
Pickup (Amps secondary) 51GP Pickup (Amps 0,50 A
secondary)
Curve 51GC Curve C1
Time Dial 51GTD Time Dial 0,20
Electromechanical Reset Delay 51GRS Electromechanical N
Reset Delay

21 / 51
SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Negative-Sequence
Time-Overcurrent
Description Name Value
Enable Negative-Sequence Time-Overcurrent Elements E51Q Enable Y
Negative-Sequence
Time-Overcurrent Elements
Pickup (Amps secondary) 51QP Pickup (Amps 2,20 A
secondary)
Curve 51QC Curve U3
Time Dial 51QTD Time Dial 3,00
Electromechanical Reset Delay 51QRS Electromechanical N
Reset Delay

SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Out of Step


Description Name Value
Enable Out of Step Elements EOOS Enable Out of Step N
Elements
Out of Step Elements Block Zone1 OOSB1 Block Zone1 N
Out of Step Elements Block Zone2 OOSB2 Block Zone2 N
Out of Step Elements Block Zone3 OOSB3 Block Zone3 N
Out of Step Elements Block Zone4 OOSB4 Block Zone4 N
Out of Step Block Time Delay (cycles in 0.25 increments) OSBD Out of Step Block 2,00 cy
Time Delay (cycles in 0.25
increments)
Enable Out of Step Tripping EOOST Enable Out of Step N
Tripping
Out of Step Zone6 Reactance-Top (Ohm secondary) X1T6 Out of Step Zone6 96,00 Ohm
Reactance-Top (Ohm
secondary)
Out of Step Zone5 Reactance-Top (Ohm secondary) X1T5 Out of Step Zone5 90,00 Ohm
Reactance-Top (Ohm
secondary)
Out of Step Zone6 Resisistance-Right (Ohm secondary) R1R6 Out of Step Zone6 70,00 Ohm
Resisistance-Right (Ohm
secondary)
Out of Step Zone5 Resisistance-Right (Ohm secondary) R1R5 Out of Step Zone5 65,00 Ohm
Resisistance-Right (Ohm
secondary)
Out of Step Zone6 Reactance-Bottom (Ohm secondary) X1B6 Out of Step Zone6 -96,00 Ohm
Reactance-Bottom (Ohm
secondary)
Out of Step Zone5 Reactance-Bottom (Ohm secondary) X1B5 Out of Step Zone5 -90,00 Ohm
Reactance-Bottom (Ohm
secondary)
Out of Step Zone6 Resistance-Left (Ohm secondary) R1L6 Out of Step Zone6 -70,00 Ohm
Resistance-Left (Ohm
secondary)
Out of Step Zone5 Resistance-Left (Ohm secondary) R1L5 Out of Step Zone5 -65,00 Ohm
Resistance-Left (Ohm
secondary)
Out of Step Positive Sequence Current Supervision (Amps 50ABCP Out of Step Positive 1,00 A
secondary) Sequence Current
Supervision (Amps
secondary)
Negative Sequence Current Unblock Delay (cycles in 0.25 UBD Negative Sequence 0,50 cy
increments) Current Unblock Delay
(cycles in 0.25 increments)
Out of Step Angle Change Unblock Rate UBOSBF Out of Step Angle 4,00
Change Unblock Rate

22 / 51
SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Load-Encroachment
Description Name Value
Enable Load-Encroachment Element ELOAD Enable Y
Load-Encroachment Element
Forward Load Impedance (Ohms secondary) ZLF Forward Load 32,00 Ohm
Impedance (Ohms
secondary)
Reverse Load Imoedance (Ohms secondary) ZLR Reverse Load 32,00 Ohm
Imoedance (Ohms
secondary)
Positive Forward Load Angle (degrees) PLAF Positive Forward Load 30,00 °
Angle (degrees)
Negative Forward Load Angle (degrees) NLAF Negative Forward Load -30,00 °
Angle (degrees)
Positive Reverse Load Angle (degrees) PLAR Positive Reverse Load 150,00 °
Angle (degrees)
Negative Reverse Load Angle (degrees) NLAR Negative Reverse Load 210,00 °
Angle (degrees)

SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Directional Elements


Description Name Value
E32 Enable Directional Elements E32 Enable Directional AUTO
Elements
ELOP Loss of Potential Enable ELOP Loss of Potential Y
Enable
Level3 Direction DIR3 Level3 Direction R
Level4 Direction DIR4 Level4 Direction F
Ground Directional Element Priority ORDER Ground Directional QVI
Element Priority

SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Voltage Elements


Description Name Value
Enable Voltage Elements EVOLT Enable Voltage Y
Elements
Phase Undervoltage Pickup (Volts secondary) 27P Phase Undervoltage +inf V
Pickup (Volts secondary)
Phase Overvoltage Pickup (Volts secondary) 59P Phase Overvoltage 79,67 V
Pickup (Volts secondary)
Zero-Seq. (3V0) Overvoltage Pickup (Volts secondary) 59N1P Zero-Seq. (3V0) +inf V
Overvoltage Pickup (Volts
secondary)
Zero-Seq. (3V0) Overvoltage Pickup (Volts secondary) 59N2P Zero-Seq. (3V0) +inf V
Overvoltage Pickup (Volts
secondary)
Neg.-Seq. (V2) Overvoltage Pickup (Volts secondary) 59QP Neg.-Seq. (V2) +inf V
Overvoltage Pickup (Volts
secondary)
Pos.-Seq. (V1) Overvoltage Pickup (Volts secondary) 59V1P Pos.-Seq. (V1) +inf V
Overvoltage Pickup (Volts
secondary)
Channel VS Undervoltage Pickup (Volts secondary) 27SP Channel VS +inf V
Undervoltage Pickup (Volts
secondary)
Channel VS Overvoltage Pickup (Volts secondary) 59SP Channel VS +inf V
Overvoltage Pickup (Volts
secondary)
Phase-Phase Undervoltage Pickup (Volts secondary) 27PP Phase-Phase +inf V
Undervoltage Pickup (Volts
secondary)
Phase-Phase Overvoltage Pickup (Volts secondary) 59PP Phase-Phase 161,00 V
Overvoltage Pickup (Volts
secondary)

23 / 51
SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Synchronism Check
Description Name Value
Enable Synchronism Check Elements E25 Enable Synchronism Y
Check Elements
Voltage Window - Low Threshold (Volts secondary) 25VLO Voltage Window - Low 59,00 V
Threshold (Volts secondary)
Voltage Window - High Threshold (Volts secondary) 25VHI Voltage Window - High 80,00 V
Threshold (Volts secondary)
Maximum Slip Frequency (Hz) 25SF Maximum Slip 0,050 Hz
Frequency (Hz)
Maximum Angle 1 (degrees) 25ANG1 Maximum Angle 1 25,00 °
(degrees)
Maximum Angle 2 (degrees) 25ANG2 Maximum Angle 2 40,00 °
(degrees)
Sync. Phase SYNCP Sync. Phase VB
Breaker Close Time for Angle Comp. TCLOSD Breaker Close Time 3,00 cy
for Angle Comp.

SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Frequency Elements


Description Name Value
Enable Frequency Elements E81 Enable Frequency N
Elements

SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Reclosing Relay


Description Name Value
Enable Reclosing Relay Elements E79 Enable Reclosing Relay 1
Elements
Open Interval 1 (cycles in 0.25 increments) 79OI1 Open Interval 1 (cycles 300,00 cy
in 0.25 increments)
Reset Time from Reclose Cycle (cycles in 0.25 increments) 79RSD Reset Time from 10800,00 cy
Reclose Cycle (cycles in 0.25
increments)
Reset Time from Lockout (cycles in 0.25 increments) 79RSLD Reset Time from 1800,00 cy
Lockout (cycles in 0.25
increments)
Reclose Supv. Time Limit (cycles in 0.25 increments) 79CLSD Reclose Supv. Time 480,00 cy
Limit (cycles in 0.25
increments)

SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Switch-Onto-Fault


Description Name Value
Enable Switch-Onto-Fault Elements ESOTF Enable Y
Switch-Onto-Fault Elements
Close Enable Time Delay (cycles in 0.25 increments) CLOEND Close Enable Time +inf cy
Delay (cycles in 0.25
increments)
52A Enable Time Delay (cycles in 0.25 increments) 52AEND 52A Enable Time 12,00 cy
Delay (cycles in 0.25
increments)
SOTF Duration (cycles in 0.25 increments) SOTFD SOTF Duration 12,00 cy
(cycles in 0.25 increments)

SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Comm. Assisted Trip Schemes
Description Name Value
Enable Communication Assisted Tripping Schemes ECOMM Enable N
Communication Assisted
Tripping Schemes

SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Zone1 Extension


Description Name Value
EZ1EXT Enable Zone1 Extension Elements EZ1EXT Enable Zone1 N
Extension Elements

24 / 51
SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Demand Metering
Description Name Value
Enable Demand Metering Method EDEM Enable Demand THM
Metering Method
Time Constant DMTC Time Constant 5
Phase Pickup (Amps secondary) PDEMP Phase Pickup (Amps 5,00 A
secondary)
Residual Ground Pickup (Amps secondary) GDEMP Residual Ground 1,50 A
Pickup (Amps secondary)
Negative-Sequence Pickup (Amps secondary) QDEMP Negative-Sequence 1,50 A
Pickup (Amps secondary)

SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Other Settings


Description Name Value
Minimum Trip Duration Time (cycles in 0.25 increments) TDURD Minimum Trip 5,00 cy
Duration Time (cycles in 0.25
increments)
Close Failure Time Delay (cycles in 0.25 increments) CFD Close Failure Time 10,00 cy
Delay (cycles in 0.25
increments)
3-Pole Open Time Delay (cycles in 0.25 increments) 3POD 3-Pole Open Time 1,50 cy
Delay (cycles in 0.25
increments)
Open Pole Option OPO Open Pole Option 52
Three Pole Open Undervoltage Pickup (Volts secondary) 27PO Three Pole Open 40,00 V
Undervoltage Pickup (Volts
secondary)
Load Detection Phase Pickup (Amps secondary) 50LP Load Detection Phase 0,25 A
Pickup (Amps secondary)

SEL 311C \ Relay Parameter Section \ Group 1 \ Logic 1 \ Trip/Comm.-Assisted Trip Logic
Description Name Value
Trip Logic Equations Trip Logic Equations
TR Direct Trip conditions M1PT+M2PT+M3PT+
Z1GT+Z2GT+Z3GT+
67P1T+67G1T+51PT
+51GT
TRCOMM M2P+Z2G
Communication-assisted trip
conditions
TRSOTF Switch-onto-fault trip M2P+Z2G+50P1
conditions
DTT Direct transfer trip 0
conditions.
ULTR Unlatch trip conditions !(M1P+M2P+M3P+Z1
G+Z2G+Z3G+67P1+6
7G1+51P+51G)

SEL 311C \ Relay Parameter Section \ Global \ General


Description Name Value
Setting Group Change Delay TGR Setting Group Change 0,00 cy
Delay
Nominal Frequency (Hz) NFREQ Nominal Frequency 60
(Hz)
Phase Rotation PHROT Phase Rotation ABC
Date Format DATE_F Date Format YMD
DC Battery LO Voltage Pickup (Vdc) DCLOP DC Battery LO 92,00 V
Voltage Pickup (Vdc)
DC Battery HI Voltage Pickup (Vdc) DCHIP DC Battery HI Voltage 138,00 V
Pickup (Vdc)

25 / 51
SEL 311C \ Additional Information \ General - General Information
Description Name Value
Manufacturer Manufacturer SEL
Device Model Device Model SEL-311C
Serial Number Serial Number serial no.
Device Address Device Address device address
Device type Device type Distance protection
Manufacturer HW code Hardware revision HW revision
Software revision Software revision Software revision
Substation Substation Substation
Substation Address Substation Address Substation address
Feeder Feeder feeder
Feeder Address Feeder Address feeder address
Bay Bay bay
Bay address Bay address bay address
Protected object name Protected object name Protected object
name
Description Description information
Location Location Location

SEL 311C \ Additional Information \ Power System Data \ VT's


Description Name Value
Line to Neutral Voltage Secondary Nominal Voltage 63,50 V
L-N

SEL 311C \ Additional Information \ Power System Data \ CT's


Description Name Value
Secondary Nominal Current 5A

SEL 311C \ Additional Information \ Configuration details


Description Name Value
Test with loss-of-potential condition? Test overcurrent as backup true

SEL 311C \ Additional Information \ Configuration details \ Trip logic


Description Name Value
Override Trip Logic Evaluation Override Trip Logic false
Evaluation

26 / 51
SEL 311C \ Additional Information \ Configuration details \ Trip logic \ Distance protection
Description Name Value
Phase distance Zone 1 used true
for direct tripping
Ground distance Zone 1 used true
for direct tripping
Phase distance Zone 2 used true
for direct tripping
Ground distance Zone 2 used true
for direct tripping
Phase distance Zone 3 used true
for direct tripping
Ground distance Zone 3 used true
for direct tripping
Phase distance Zone 4 used false
for direct tripping
Ground distance Zone 4 used false
for direct tripping
is "M1P" wordbit connected to a trip output? Instantanous trip of phase false
distance Zone 1
is "Z1G" wordbit connected to a trip output? Instantanous trip of ground false
distance Zone 1
Do Z1P and Z1G use common or independent timers? Timer selecion for phase and Independent timer for
ground distance Zone 1 phase and ground
Do Z2P and Z2G use common or independent timers? Timer selecion for phase and Independent timer for
ground distance Zone 2 phase and ground
Do Z3P and Z3G use common or independent timers? Timer selecion for phase and Independent timer for
ground distance Zone 3 phase and ground

SEL 311C \ Additional Information \ Configuration details \ Trip logic \ Overcurrent


Description Name Value
Phase overcurrent level 1 Definite time
Phase overcurrent level 2 Not used for tripping
Phase overcurrent level 3 Not used for tripping
Residual overcurrent level 1 Definite time
Directional
Residual overcurrent level 2 Not used for tripping
Residual overcurrent level 3 Not used for tripping
Residual overcurrent level 4 Not used for tripping
Negative sequence Not used for tripping
overcurrent level 1
Negative sequence Not used for tripping
overcurrent level 2
Negative sequence Not used for tripping
overcurrent level 3
Negative sequence Not used for tripping
overcurrent level 4
is this element connected to a trip output? Phase time overcurrent true
"51PT"
is this element connected to a trip output? Residual time overcurrent true
"51GT"
is this element connected to a trip output? Negative sequence time false
overcurrent "51QT"

SEL 311C \ Additional Information \ Circuit Breaker Information


Description Name Value
52ab Percentage 52ab Percentage 20,00 %
CB Trip Time CB Trip Time 50,00 ms
CB Close Time CB Close Time 100,00 ms
t-Tolerance abs t-Tolerance abs 0,00 ms
t-Tolerance rel t-Tolerance rel 5,00 %

SEL 311C \ Additional Information \ Relay Information \ Output contacts


Description Name Value
Contact operatating time Contact operatating time 4,00 ms

27 / 51
SEL 311C \ Additional Information \ Relay Information \ Distance Protection - Distance
protection
Description Name Value
Rel. Tol Z at Line Angle (SIR<=60) Rel. Tol Z 5,00 %
Max. Trip time (according operating time curve at SIR=30) Max. operating time (cycle) - 2,00 cy
internal operation
Max. Trip time (according operating time curve at SIR=30) Max. operating time (ms) - 33,33 ms
internal operation
Rel. time tolerance Rel. t-Tolerance 5,00 %
Pick up / drop off ratio Pick Up / Drop Off Ratio 0,95
Abs. t-Tolerance Abs. t-Tolerance- internal 1,50 cy
operation

SEL 311C \ Additional Information \ Relay Information \ Distance Protection \ Fault


Detectors
Description Name Value
Rel. I-Tolerance 3,00 %
Abs. I-Tolerance 0,05 A

SEL 311C \ Additional Information \ Relay Information \ Overcurrent Protection \ Time


Overcurrent Elements
Description Name Value
abs. current tolerance 0,05 A
rel. current tolerance 3,00 %
abs. time tolerance 1,75 cy
rel. time tolerance 0,10 %
Pickup/Drop off ratio 1,00

SEL 311C \ Additional Information \ Relay Information \ Overcurrent Protection \ Definite


Time/Instantaneous Elements
Description Name Value
abs. current tolerance 0,05 A
rel. current tolerance 3,00 %
abs. time tolerance 1,75 cy
rel. time tolerance 0,10 %
Pickup/Drop off ratio 1,00
Max operating time - internal 1,50 cy
operation

SEL 311C \ Additional Information \ Test Tolerance


Description Name Value
Global Test Tolerance Test Tolerance 2,00 %

Test Object - Other RIO Functions

CB Configuration
Description Name Value
CB trip time CB trip time 50,00 ms
CB close time CB close time 100,00 ms
Times for 52a, 52b in percent of CB time 52a, 52b % of CB 20,00 %

Test Module
Name: OMICRON QuickCMC Version: 4.30
Test Start: 18-jun-2024 15:06:39 Test End:
User Name: Manager:
Company:

Test Results
28 / 51
Comment

Summary
0 tests passed, 0 tests failed, 0 tests not assessed
No results available!

Group:50P1

50P1:
Test Object - Overcurrent Parameters
General - Values:
TimeTolAbs: 0,03 s VT connection: n/a
TimeTolRel: 0,10 % CT starpoint connection: n/a
CurrentTolAbs: 0,05 Iref
CurrentTolRel: 3,00 %
Directional: No

Elements - Phase:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
No 51P C1 Standard Inverse 1,87 Iref 0,14 1,00 Non Directional
Yes 50/67P1 Definite Time 22,81 Iref 0,05 s 1,00 Non Directional
No 50/67P2 Definite Time 1,88 Iref 0,03 s 1,00 Non Directional
No 50/67P3 Definite Time 0,10 Iref 0,03 s 1,00 Non Directional

Elements - Residual:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
No 51G C1 Standard Inverse 0,50 Iref 0,20 1,00 Non Directional
No 50/67G1 Definite Time 18,00 0,08 s 1,00 Non Directional
Iref
No 50/67G2 Definite Time 0,10 Iref 0,03 s 1,00 Non Directional
No 50/67G3 Definite Time 0,10 Iref 0,03 s 1,00 Non Directional
No 50/67G4 Definite Time 0,10 Iref 0,03 s 1,00 Non Directional

Elements - Negative Sequence:


Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
No 51Q U3 Very Inverse 0,73 Iref 3,00 1,00 Non Directional
No 50/67Q1 Definite Time 0,10 Iref 0,03 s 1,00 Non Directional
No 50/67Q2 Definite Time 0,10 Iref 0,03 s 1,00 Non Directional
No 50/67Q3 Definite Time 0,10 Iref 0,03 s 1,00 Non Directional
No 50/67Q4 Definite Time 0,10 Iref 0,03 s 1,00 Non Directional

Test Module
Name: OMICRON Overcurrent Version: 4.30
Test Start: 11-jun-2024 09:49:07 Test End: 11-jun-2024 09:49:37
User Name: Manager:
Company:

Test Settings:

29 / 51
Fault Model:
Time reference: Fault inception
Load current: 0,00 A
Load angle: n/a
Prefault time: 100,0 ms
Abs. max time: 240,0 s
Post fault time: 500,0 ms
Rel. max time: 100,0 %
Enable voltage output: No
Fault voltage LN (for all but two phase faults): n/a
Fault voltage LL (for two phase faults): n/a
Decaying DC active: No
Time constant: n/a
CB char min time: 50,00 ms
Thermal reset active: No
Thermal reset method: n/a
Thermal reset message: n/a

Shot Test:
Type Relative To Factor Magnitude Angle tnom tmin tmax
L1-L2 (---) n/a 23,50 A n/a 50,00 ms 20,83 ms 79,17 ms
L1-L2 (---) n/a 24,00 A n/a 50,00 ms 20,83 ms 79,17 ms
L1-L2 (---) n/a 24,50 A n/a 50,00 ms 20,83 ms 79,17 ms
L1-L2 (---) n/a 25,00 A n/a 50,00 ms 20,83 ms 79,17 ms
L1-L2 (---) n/a 25,50 A n/a 50,00 ms 20,83 ms 79,17 ms
L1-L2 (---) n/a 26,00 A n/a 50,00 ms 20,83 ms 79,17 ms
L2-L3 (---) n/a 23,50 A n/a 50,00 ms 20,83 ms 79,17 ms
L2-L3 (---) n/a 24,00 A n/a 50,00 ms 20,83 ms 79,17 ms
L2-L3 (---) n/a 24,50 A n/a 50,00 ms 20,83 ms 79,17 ms
L2-L3 (---) n/a 25,00 A n/a 50,00 ms 20,83 ms 79,17 ms
L2-L3 (---) n/a 25,50 A n/a 50,00 ms 20,83 ms 79,17 ms
L2-L3 (---) n/a 26,00 A n/a 50,00 ms 20,83 ms 79,17 ms
L3-L1 (---) n/a 23,50 A n/a 50,00 ms 20,83 ms 79,17 ms
L3-L1 (---) n/a 24,00 A n/a 50,00 ms 20,83 ms 79,17 ms
L3-L1 (---) n/a 24,50 A n/a 50,00 ms 20,83 ms 79,17 ms
L3-L1 (---) n/a 25,00 A n/a 50,00 ms 20,83 ms 79,17 ms
L3-L1 (---) n/a 25,50 A n/a 50,00 ms 20,83 ms 79,17 ms
L3-L1 (---) n/a 26,00 A n/a 50,00 ms 20,83 ms 79,17 ms
L1-L2-L3 (---) n/a 23,50 A n/a 50,00 ms 20,83 ms 79,17 ms
L1-L2-L3 (---) n/a 24,00 A n/a 50,00 ms 20,83 ms 79,17 ms
L1-L2-L3 (---) n/a 24,50 A n/a 50,00 ms 20,83 ms 79,17 ms
L1-L2-L3 (---) n/a 25,00 A n/a 50,00 ms 20,83 ms 79,17 ms
L1-L2-L3 (---) n/a 25,50 A n/a 50,00 ms 20,83 ms 79,17 ms
L1-L2-L3 (---) n/a 26,00 A n/a 50,00 ms 20,83 ms 79,17 ms

Binary Outputs:
Name State
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0

Binary Inputs:
Trigger Logic: And
Name Trigger State
TRIP 1
Bin. in 3 X

30 / 51
Shot Test Results:
Type Relative To Factor Magnitude Angle tnom tact Deviation Overload Result
L1-L2 (---) n/a 23,50 A n/a 50,00 ms 74,40 ms 48,80 % No Passed
L1-L2 (---) n/a 24,00 A n/a 50,00 ms 75,90 ms 51,80 % No Passed
L1-L2 (---) n/a 24,50 A n/a 50,00 ms 74,00 ms 48,00 % No Passed
L1-L2 (---) n/a 25,00 A n/a 50,00 ms 73,20 ms 46,40 % No Passed
L1-L2 (---) n/a 25,50 A n/a 50,00 ms 73,20 ms 46,40 % No Passed
L1-L2 (---) n/a 26,00 A n/a 50,00 ms 74,40 ms 48,80 % No Passed
L2-L3 (---) n/a 23,50 A n/a 50,00 ms 74,20 ms 48,40 % No Passed
L2-L3 (---) n/a 24,00 A n/a 50,00 ms 76,90 ms 53,80 % No Passed
L2-L3 (---) n/a 24,50 A n/a 50,00 ms 74,70 ms 49,40 % No Passed
L2-L3 (---) n/a 25,00 A n/a 50,00 ms 73,60 ms 47,20 % No Passed
L2-L3 (---) n/a 25,50 A n/a 50,00 ms 73,50 ms 47,00 % No Passed
L2-L3 (---) n/a 26,00 A n/a 50,00 ms 76,30 ms 52,60 % No Passed
L3-L1 (---) n/a 23,50 A n/a 50,00 ms 75,80 ms 51,60 % No Passed
L3-L1 (---) n/a 24,00 A n/a 50,00 ms 74,10 ms 48,20 % No Passed
L3-L1 (---) n/a 24,50 A n/a 50,00 ms 76,40 ms 52,80 % No Passed
L3-L1 (---) n/a 25,00 A n/a 50,00 ms 74,20 ms 48,40 % No Passed
L3-L1 (---) n/a 25,50 A n/a 50,00 ms 76,90 ms 53,80 % No Passed
L3-L1 (---) n/a 26,00 A n/a 50,00 ms 75,00 ms 50,00 % No Passed
L1-L2-L3 (---) n/a 23,50 A n/a 50,00 ms 71,20 ms 42,40 % No Passed
L1-L2-L3 (---) n/a 24,00 A n/a 50,00 ms 72,60 ms 45,20 % No Passed
L1-L2-L3 (---) n/a 24,50 A n/a 50,00 ms 71,10 ms 42,20 % No Passed
L1-L2-L3 (---) n/a 25,00 A n/a 50,00 ms 73,90 ms 47,80 % No Passed
L1-L2-L3 (---) n/a 25,50 A n/a 50,00 ms 73,60 ms 47,20 % No Passed
L1-L2-L3 (---) n/a 26,00 A n/a 50,00 ms 74,40 ms 48,80 % No Passed

Charts for Fault Types:


Angle
Type

L1-L2 n/a

10000,00
1000,00
100,00
10,00
t/s

1,00
0,10

22,5 25,0 27,5 30,0 32,5 35,0 37,5 40,0 42,5


I/A

Charts for Fault Types:


Angle
Type

L2-L3 n/a

10000,00
1000,00
100,00
10,00
t/s

1,00
0,10

22,5 25,0 27,5 30,0 32,5 35,0 37,5 40,0 42,5


I/A

31 / 51
Charts for Fault Types:
Angle
Type

L3-L1 n/a

10000,00
1000,00
100,00
10,00
t/s

1,00
0,10

22,5 25,0 27,5 30,0 32,5 35,0 37,5 40,0 42,5


I/A

Charts for Fault Types:


Angle
Type

L1-L2-L3 n/a

10000,00
1000,00
100,00
10,00
t/s

1,00
0,10

22,5 25,0 27,5 30,0 32,5 35,0 37,5 40,0 42,5


I/A

Test State:
24 out of 24 points tested.
24 points passed.
0 points failed.

Test passed

50P1 - DISPARO:
Test Object - Overcurrent Parameters

General - Values:
TimeTolAbs: 0,03 s VT connection: n/a
TimeTolRel: 0,10 % CT starpoint connection: n/a
CurrentTolAbs: 0,05 Iref
CurrentTolRel: 3,00 %
Directional: No

Elements - Phase:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
No 51P C1 Standard Inverse 1,87 Iref 0,14 1,00 Non Directional
Yes 50/67P1 Definite Time 22,81 Iref 0,05 s 1,00 Non Directional
No 50/67P2 Definite Time 1,88 Iref 0,03 s 1,00 Non Directional
No 50/67P3 Definite Time 0,10 Iref 0,03 s 1,00 Non Directional

32 / 51
Elements - Residual:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
No 51G C1 Standard Inverse 0,50 Iref 0,20 1,00 Non Directional
No 50/67G1 Definite Time 18,00 0,08 s 1,00 Non Directional
Iref
No 50/67G2 Definite Time 0,10 Iref 0,03 s 1,00 Non Directional
No 50/67G3 Definite Time 0,10 Iref 0,03 s 1,00 Non Directional
No 50/67G4 Definite Time 0,10 Iref 0,03 s 1,00 Non Directional

Elements - Negative Sequence:


Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
No 51Q U3 Very Inverse 0,73 Iref 3,00 1,00 Non Directional
No 50/67Q1 Definite Time 0,10 Iref 0,03 s 1,00 Non Directional
No 50/67Q2 Definite Time 0,10 Iref 0,03 s 1,00 Non Directional
No 50/67Q3 Definite Time 0,10 Iref 0,03 s 1,00 Non Directional
No 50/67Q4 Definite Time 0,10 Iref 0,03 s 1,00 Non Directional

Test Module
Name: OMICRON Overcurrent Version: 4.30
Test Start: 13-jun-2024 11:14:15 Test End: 13-jun-2024 11:14:20
User Name: Manager:
Company:

Test Settings:

Fault Model:
Time reference: Fault inception
Load current: 0,00 A
Load angle: n/a
Prefault time: 100,0 ms
Abs. max time: 240,0 s
Post fault time: 500,0 ms
Rel. max time: 100,0 %
Enable voltage output: No
Fault voltage LN (for all but two phase faults): n/a
Fault voltage LL (for two phase faults): n/a
Decaying DC active: No
Time constant: n/a
CB char min time: 50,00 ms
Thermal reset active: No
Thermal reset method: n/a
Thermal reset message: n/a

Shot Test:
Type Relative To Factor Magnitude Angle tnom tmin tmax
L1-L2 (---) n/a 24,00 A n/a 50,00 ms 20,83 ms 79,17 ms

Binary Outputs:
Name State
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0

Binary Inputs:
Trigger Logic: And
Name Trigger State
TRIP 1
Bin. in 3 X

33 / 51
Shot Test Results:
Type Relative To Factor Magnitude Angle tnom tact Deviation Overload Result
L1-L2 (---) n/a 24,00 A n/a 50,00 ms 74,50 ms 49,00 % No Passed

Charts for Fault Types:


Angle
Type

L1-L2 n/a

10000,00
1000,00
100,00
10,00
t/s

1,00
0,10

22,5 25,0 27,5 30,0 32,5 35,0 37,5 40,0 42,5


I/A

Test State:
1 out of 1 points tested.
1 points passed.
0 points failed.

Test passed

Group end:50P1

Group:50P2 - SOTF

SOTF:

Test Settings
State PRE FALTA POS
V L1-E 63,50 V 63,50 V 63,50 V
0,00 ° 0,00 ° 0,00 °
60,000 Hz 60,000 Hz 60,000 Hz
V L2-E 63,50 V 63,50 V 63,50 V
-120,00 ° -120,00 ° -120,00 °
60,000 Hz 60,000 Hz 60,000 Hz

34 / 51
V L3-E 63,50 V 63,50 V 63,50 V
120,00 ° 120,00 ° 120,00 °
60,000 Hz 60,000 Hz 60,000 Hz
I L1 0,00 A 5,000 A 0,00 A
0,00 ° 0,00 ° 0,00 °
60,000 Hz 60,000 Hz 60,000 Hz
I L2 0,00 A 5,000 A 0,00 A
-120,00 ° -120,00 ° -120,00 °
60,000 Hz 60,000 Hz 60,000 Hz
I L3 0,00 A 5,000 A 0,00 A
120,00 ° 120,00 ° 120,00 °
60,000 Hz 60,000 Hz 60,000 Hz
V(2)-1 63,50 V 0,00 V 63,50 V
0,00 ° 0,00 ° 0,00 °
60,000 Hz 60,000 Hz 60,000 Hz
Bin. out 1 0 0 0
Bin. out 2 0 0 0
Bin. out 3 0 0 0
Bin. out 4 0 0 0
Max. State Time 1,000 s
Trigger Logic OR OR OR
TRIP X 1 1
DISJ FE 1 X X
User interaction no no no
CMGPS trigger no no no
IRIG-B/PTP no no no
trigger
Pulses / 1 1 1
seconds
Delay after Tr. 0,00 s 0,00 s 0,00 s
On trigger jump no no no
to test end
Diagrams +90° +90° +90°

180° 0° 180° 0° 180° 0°

-90°V32,0 A
288,7 -90°V32,0 A
288,7 -90°V32,0 A
288,7

Comment

Test Module
Name: OMICRON State Sequencer Version: 4.30
Test Start: Test End:
User Name: Manager:
Company:

Test Results

Time Assessment
Ignore
Name Start Stop Tnom Tdev- Tdev+ Tact Tdev Assess
before
SOTF FALTA FALTA TRIP 0>1 50,00 ms 50,00 ms 50,00 ms o
Assess: + .. Passed x .. Failed o .. Not assessed

35 / 51
PRE POS
FALTA

CMC356 V A/V
80
60
40
20 t/s
0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1
0
-20
-40
-60
-80

V L1-E V L2-E V L3-E

CMC356 I A/A
6

2 t/s
0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1
0

-2

-4

-6

I L1 I L2 I L3

CMC356 V B/V
80
60
40
20 t/s
0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1
0
-20
-40
-60
-80

V(2)-1

Bin. out 1
Bin. out 2
Bin. out 3
Bin. out 4

0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1
t/s

36 / 51
PRE POS
FALTA

TRIP
DISJ FE
50BF
Bin. in 4
Bin. in 5
Bin. in 6
Bin. in 7
Bin. in 8
Bin. in 9
Bin. in 10

0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1
t/s

Cursor Data
Time Signal Value
Cursor 1 0,00 s <none> n/a
Cursor 2 1,20 s <none> n/a
C2 - C1 1,20 s n/a

Event recorder
Time Type Signal name Slope

Test State:
No results available!

Group end:50P2 - SOTF

Group:50BF

50BF:

Test Settings
State PRE FALTA 50BF POS
V L1-E 66,40 V 66,40 V 66,40 V 66,40 V
0,00 ° 0,00 ° 0,00 ° 0,00 °
60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz
V L2-E 66,40 V 66,40 V 66,40 V 66,40 V
-120,00 ° -120,00 ° -120,00 ° -120,00 °
60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz

37 / 51
V L3-E 66,40 V 66,40 V 66,40 V 66,40 V
120,00 ° 120,00 ° 120,00 ° 120,00 °
60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz
I L1 0,00 A 5,000 A 5,000 A 0,00 A
0,00 ° 0,00 ° 0,00 ° 0,00 °
60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz
I L2 0,00 A 5,000 A 5,000 A 0,00 A
-120,00 ° -120,00 ° -120,00 ° -120,00 °
60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz
I L3 0,00 A 5,000 A 5,000 A 0,00 A
120,00 ° 120,00 ° 120,00 ° 120,00 °
60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz
V(2)-1 0,00 V 63,50 V 63,50 V 63,50 V
0,00 ° 0,00 ° 0,00 ° 0,00 °
60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz
Bin. out 1 0 0 0 0
Bin. out 2 0 0 0 0
Bin. out 3 0 0 0 0
Bin. out 4 0 0 0 0
Max. State Time 1,000 s 1,000 s
Trigger Logic OR OR
TRIP 1 X
50BF X 1
User interaction no no no no
CMGPS trigger no no no no
IRIG-B/PTP no no no no
trigger
Pulses / 1 1 1 1
seconds
Delay after Tr. 0,00 s 0,00 s 0,00 s 0,00 s
On trigger jump no no no no
to test end
Diagrams +90° +90° +90° +90°

180° 0° 180° 0° 180° 0° 180° 0°

-90°V32,0 A
288,7 -90°V32,0 A
288,7 -90°V32,0 A
288,7 -90°V32,0 A
288,7

Comment

Test Module
Name: OMICRON State Sequencer Version: 4.30
Test Start: 13-jun-2024 16:23:26 Test End: 13-jun-2024 16:23:31
User Name: Manager:
Company:

Test Results

Time Assessment
Ignore
Name Start Stop Tnom Tdev- Tdev+ Tact Tdev Assess
before
50BF 50BF 50BF 50BF 0>1 200,0 ms 50,00 ms 50,00 ms 200,5 ms 500,0 μs +
Assess: + .. Passed x .. Failed o .. Not assessed

38 / 51
PRE 50BF
FALTA POS

CMC356 V A/V

75

50

25 t/s
0,25 0,50 0,75 1,00 1,25 1,50 1,75 2,00 2,25 2,50 2,75
0

-25

-50

-75

-100
V L1-E V L2-E V L3-E

CMC356 I A/A
6

2 t/s
0,25 0,50 0,75 1,00 1,25 1,50 1,75 2,00 2,25 2,50 2,75
0

-2

-4

-6

I L1 I L2 I L3

CMC356 V B/V
80
60
40
20 t/s
0,25 0,50 0,75 1,00 1,25 1,50 1,75 2,00 2,25 2,50 2,75
0
-20
-40
-60
-80

V(2)-1

Bin. out 1
Bin. out 2
Bin. out 3
Bin. out 4

0,25 0,50 0,75 1,00 1,25 1,50 1,75 2,00 2,25 2,50 2,75
t/s

39 / 51
PRE 50BF
FALTA POS

TRIP
DISJ FE
50BF
Bin. in 4
Bin. in 5
Bin. in 6
Bin. in 7
Bin. in 8
Bin. in 9
Bin. in 10

0,25 0,50 0,75 1,00 1,25 1,50 1,75 2,00 2,25 2,50 2,75
t/s

Cursor Data
Time Signal Value
Cursor 1 0,00 s <none> n/a
Cursor 2 3,19 s <none> n/a
C2 - C1 3,19 s n/a

Event recorder
Time Type Signal name Slope
1,993 s Input TRIP 0>1
2,193 s Input 50BF 0>1
2,235 s Input TRIP 1>0
2,275 s Input 50BF 1>0

Test State:
Test passed

Group end:50BF
Group:59

59P:

Test Settings
State PRE FALTA POS
V L1-E 63,50 V 81,00 V 63,50 V
0,00 ° 0,00 ° 0,00 °
60,000 Hz 60,000 Hz 60,000 Hz
V L2-E 63,50 V 66,40 V 63,50 V
-120,00 ° -120,00 ° -120,00 °
60,000 Hz 60,000 Hz 60,000 Hz
V L3-E 63,50 V 66,40 V 63,50 V
120,00 ° 120,00 ° 120,00 °
60,000 Hz 60,000 Hz 60,000 Hz
I L1 0,00 A 0,00 A 0,00 A
0,00 ° 0,00 ° 0,00 °
60,000 Hz 60,000 Hz 60,000 Hz
I L2 0,00 A 0,00 A 0,00 A
-120,00 ° -120,00 ° -120,00 °
60,000 Hz 60,000 Hz 60,000 Hz

40 / 51
I L3 0,00 A 0,00 A 0,00 A
120,00 ° 120,00 ° 120,00 °
60,000 Hz 60,000 Hz 60,000 Hz
V(2)-1 0,00 V 0,00 V 0,00 V
0,00 ° 0,00 ° 0,00 °
60,000 Hz 60,000 Hz 60,000 Hz
Bin. out 1 0 0 0
Bin. out 2 0 0 0
Bin. out 3 0 0 0
Bin. out 4 0 0 0
Max. State Time 1,000 s 1,000 s
Trigger Logic OR
TRIP 1
User interaction no no no
CMGPS trigger no no no
IRIG-B/PTP no no no
trigger
Pulses / 1 1 1
seconds
Delay after Tr. 0,00 s 0,00 s 0,00 s
On trigger jump no no no
to test end
Diagrams +90° +90° +90°

180° 0° 180° 0° 180° 0°

288,7
-90°V32,0 A 288,7
-90°V32,0 A 288,7
-90°V32,0 A

Comment

Test Module
Name: OMICRON State Sequencer Version: 4.30
Test Start: 13-jun-2024 16:48:45 Test End: 13-jun-2024 16:48:54
User Name: Manager:
Company:

Test Results
Time Assessment
Ignore
Name Start Stop Tnom Tdev- Tdev+ Tact Tdev Assess
before
59P FALTA FALTA TRIP 0>1 5,000 s 50,00 ms 50,00 ms 5,029 s 28,60 ms +
Assess: + .. Passed x .. Failed o .. Not assessed

41 / 51
PRE POS
FALTA

CMC356 V A/V
100
75
50
25 t/s
1,0 2,0 3,0 4,0 5,0 6,0
0
-25
-50
-75
-100
-125
V L1-E V L2-E V L3-E

CMC356 I A/mA

75
50
25 t/s
1,0 2,0 3,0 4,0 5,0 6,0
0
-25
-50
-75
-100
I L1 I L2 I L3

CMC356 V B/mV

75
50
25 t/s
1,0 2,0 3,0 4,0 5,0 6,0
0
-25
-50
-75
-100
V(2)-1

Bin. out 1
Bin. out 2
Bin. out 3
Bin. out 4

1,0 2,0 3,0 4,0 5,0 6,0


t/s

42 / 51
PRE POS
FALTA

TRIP
DISJ FE
50BF
Bin. in 4
Bin. in 5
Bin. in 6
Bin. in 7
Bin. in 8
Bin. in 9
Bin. in 10

1,0 2,0 3,0 4,0 5,0 6,0


t/s

Cursor Data
Time Signal Value
Cursor 1 0,00 s <none> n/a
Cursor 2 7,03 s <none> n/a
C2 - C1 7,03 s n/a

Event recorder
Time Type Signal name Slope
6,029 s Input TRIP 0>1
6,113 s Input TRIP 1>0

Test State:
Test passed

59PP:

Test Settings
State PRE FALTA POS
V L1-E 63,50 V 170,0 V 63,50 V
0,00 ° 0,00 ° 0,00 °
60,000 Hz 60,000 Hz 60,000 Hz
V L2-E 63,50 V 170,0 V 63,50 V
-120,00 ° -120,00 ° -120,00 °
60,000 Hz 60,000 Hz 60,000 Hz
V L3-E 63,50 V 170,0 V 63,50 V
120,00 ° 120,00 ° 120,00 °
60,000 Hz 60,000 Hz 60,000 Hz
I L1 0,00 A 0,00 A 0,00 A
0,00 ° 0,00 ° 0,00 °
60,000 Hz 60,000 Hz 60,000 Hz
I L2 0,00 A 0,00 A 0,00 A
-120,00 ° -120,00 ° -120,00 °
60,000 Hz 60,000 Hz 60,000 Hz
I L3 0,00 A 0,00 A 0,00 A
120,00 ° 120,00 ° 120,00 °
60,000 Hz 60,000 Hz 60,000 Hz
V(2)-1 0,00 V 0,00 V 0,00 V
0,00 ° 0,00 ° 0,00 °
60,000 Hz 60,000 Hz 60,000 Hz

43 / 51
Bin. out 1 0 0 0
Bin. out 2 0 0 0
Bin. out 3 0 0 0
Bin. out 4 0 0 0
Max. State Time 1,000 s 1,000 s
Trigger Logic OR
TRIP 1
User interaction no no no
CMGPS trigger no no no
IRIG-B/PTP no no no
trigger
Pulses / 1 1 1
seconds
Delay after Tr. 0,00 s 0,00 s 0,00 s
On trigger jump no no no
to test end
Diagrams +90° +90° +90°

180° 0° 180° 0° 180° 0°

288,7
-90°V32,0 A 288,7
-90°V32,0 A 288,7
-90°V32,0 A

Comment

Test Module
Name: OMICRON State Sequencer Version: 4.30
Test Start: 13-jun-2024 16:52:13 Test End: 13-jun-2024 16:52:17
User Name: Manager:
Company:

Test Results

Time Assessment
Ignore
Name Start Stop Tnom Tdev- Tdev+ Tact Tdev Assess
before
59PP FALTA FALTA TRIP 0>1 0,00 s 50,00 ms 50,00 ms 12,60 ms 12,60 ms +
Assess: + .. Passed x .. Failed o .. Not assessed

PRE POS
FALTA

CMC356 V A/V

200
150
100
50 t/s
0,25 0,50 0,75 1,00 1,25 1,50 1,75
0
-50
-100
-150
-200
-250
V L1-E V L2-E V L3-E

44 / 51
PRE POS
FALTA

CMC356 I A/mA

75
50
25 t/s
0,25 0,50 0,75 1,00 1,25 1,50 1,75
0
-25
-50
-75
-100
I L1 I L2 I L3

CMC356 V B/mV

75
50
25 t/s
0,25 0,50 0,75 1,00 1,25 1,50 1,75
0
-25
-50
-75
-100
V(2)-1

Bin. out 1
Bin. out 2
Bin. out 3
Bin. out 4

0,25 0,50 0,75 1,00 1,25 1,50 1,75


t/s

TRIP
DISJ FE
50BF
Bin. in 4
Bin. in 5
Bin. in 6
Bin. in 7
Bin. in 8
Bin. in 9
Bin. in 10

0,25 0,50 0,75 1,00 1,25 1,50 1,75


t/s

Cursor Data
Time Signal Value
Cursor 1 0,00 s <none> n/a
Cursor 2 2,01 s <none> n/a
C2 - C1 2,01 s n/a

Event recorder

45 / 51
Time Type Signal name Slope
1,013 s Input TRIP 0>1
1,097 s Input TRIP 1>0

Test State:
Test passed

Group end:59
Group:25

25:

Test Settings
State State 1 State 2 State 3 State 4 State 5
V L1-E 66,40 V 66,40 V 66,40 V 66,40 V 66,40 V
0,00 ° 0,00 ° 0,00 ° 0,00 ° 0,00 °
60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz
V L2-E 66,40 V 66,40 V 66,40 V 66,40 V 66,40 V
-120,00 ° -120,00 ° -120,00 ° -120,00 ° -120,00 °
60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz
V L3-E 66,40 V 66,40 V 66,40 V 66,40 V 66,40 V
120,00 ° 120,00 ° 120,00 ° 120,00 ° 120,00 °
60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz
I L1 0,00 A 0,00 A 0,00 A 0,00 A 0,00 A
0,00 ° 0,00 ° 0,00 ° 0,00 ° 0,00 °
60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz
I L2 0,00 A 0,00 A 0,00 A 0,00 A 0,00 A
-120,00 ° -120,00 ° -120,00 ° -120,00 ° -120,00 °
60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz
I L3 0,00 A 0,00 A 0,00 A 0,00 A 0,00 A
120,00 ° 120,00 ° 120,00 ° 120,00 ° 120,00 °
60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz
VE 0,00 V 66,40 V 66,40 V 66,40 V 40,00 V
0,00 ° -120,00 ° -50,00 ° -120,00 ° -120,00 °
60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz
Bin. out 1 0 0 0 0 0
Bin. out 2 0 0 0 0 0
Bin. out 3 0 0 0 0 0
Bin. out 4 0 0 0 0 0
Max. State Time
Trigger Logic
User interaction yes yes yes yes yes
CMGPS trigger no no no no no
IRIG-B/PTP no no no no no
trigger
Pulses / 1 1 1 1 1
seconds
Delay after Tr. 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s
On trigger jump no no no no no
to test end
Diagrams +90° +90° +90° +90° +90°

180° 0° 180° 0° 180° 0° 180° 0° 180° 0°

288,7
-90°V32,0 A 288,7
-90°V32,0 A 288,7
-90°V32,0 A 288,7
-90°V32,0 A 288,7
-90°V32,0 A

Comment

Test Module
Name: OMICRON State Sequencer Version: 4.30
Test Start: Test End:

46 / 51
User Name: Manager:
Company:

Test Results
Time Assessment
Ignore
Name Start Stop Tnom Tdev- Tdev+ Tact Tdev Assess
before
o
Assess: + .. Passed x .. Failed o .. Not assessed

State 1 State 3 State 5


State 2 State 4

CMC356 V A/V

75

50

25 t/s
0,5 1,0 1,5 2,0 2,5 3,0 3,5 4,0 4,5
0

-25

-50

-75

-100
V L1-E V L2-E V L3-E

CMC356 I A/mA

75
50
25 t/s
0,5 1,0 1,5 2,0 2,5 3,0 3,5 4,0 4,5
0
-25
-50
-75
-100
I L1 I L2 I L3

CMC356 V B/V

75

50

25 t/s
0,5 1,0 1,5 2,0 2,5 3,0 3,5 4,0 4,5
0

-25

-50

-75

-100
VE

47 / 51
State 1 State 3 State 5
State 2 State 4

Bin. out 1
Bin. out 2
Bin. out 3
Bin. out 4

0,5 1,0 1,5 2,0 2,5 3,0 3,5 4,0 4,5


t/s

TRIP
DISJ FE
50BF
Bin. in 4
Bin. in 5
Bin. in 6
Bin. in 7
Bin. in 8
Bin. in 9
Bin. in 10

0,5 1,0 1,5 2,0 2,5 3,0 3,5 4,0 4,5


t/s

Cursor Data
Time Signal Value
Cursor 1 0,00 s <none> n/a
Cursor 2 5,00 s <none> n/a
C2 - C1 5,00 s n/a

Event recorder
Time Type Signal name Slope

Test State:
No results available!

Group end:25

Group:79

79T:

Test Settings
State State 1 State 2 State 3 State 4 State 5 State 6 State 7
V L1-E 66,40 V 17,05 V 66,40 V 66,40 V 17,05 V 66,40 V 66,40 V
0,00 ° 0,00 ° 0,00 ° 0,00 ° 0,00 ° 0,00 ° 0,00 °
60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz
V L2-E 66,40 V 63,50 V 66,40 V 66,40 V 63,50 V 66,40 V 66,40 V
-120,00 ° -120,00 ° -120,00 ° -120,00 ° -120,00 ° -120,00 ° -120,00 °
60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz
V L3-E 66,40 V 63,50 V 66,40 V 66,40 V 63,50 V 66,40 V 66,40 V
120,00 ° 120,00 ° 120,00 ° 120,00 ° 120,00 ° 120,00 ° 120,00 °
60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz
I L1 100,0 mA 5,000 A 0,00 A 100,0 mA 5,000 A 0,00 A 100,0 mA
0,00 ° -80,00 ° 0,00 ° 0,00 ° -80,00 ° 0,00 ° 0,00 °
60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz
I L2 100,0 mA 0,00 A 0,00 A 100,0 mA 0,00 A 0,00 A 100,0 mA
-120,00 ° 0,00 ° -120,00 ° -120,00 ° 0,00 ° -120,00 ° -120,00 °
60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz

48 / 51
I L3 100,0 mA 0,00 A 0,00 A 100,0 mA 0,00 A 0,00 A 100,0 mA
120,00 ° 0,00 ° 120,00 ° 120,00 ° 0,00 ° 120,00 ° 120,00 °
60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz
VE 66,40 V 66,40 V 66,40 V 66,40 V 66,40 V 66,40 V 66,40 V
-120,00 ° -120,00 ° -120,00 ° -120,00 ° -120,00 ° -120,00 ° -120,00 °
60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz
Bin. out 1 0 0 0 0 0 0 0
Bin. out 2 0 0 0 0 0 0 0
Bin. out 3 0 0 0 0 0 0 0
Bin. out 4 0 0 0 0 0 0 0
Max. State Time 3,000 s 3,000 s
Trigger Logic OR OR OR OR
DISJ FE 0 1 0 1
User interaction yes no no no no no no
CMGPS trigger no no no no no no no
IRIG-B/PTP no no no no no no no
trigger
Pulses / 1 1 1 1 1 1 1
seconds
Delay after Tr. 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s
On trigger jump no no no no no no no
to test end
Diagrams +90° +90° +90° +90° +90° +90° +90°

180° 0° 180° 0° 180° 0° 180° 0° 180° 0° 180° 0° 180° 0°

288,7
-90°V32,0 A 288,7
-90°V32,0 A 288,7
-90°V32,0 A 288,7
-90°V32,0 A 288,7
-90°V32,0 A 288,7
-90°V32,0 A 288,7
-90°V32,0 A

Comment

Test Module
Name: OMICRON State Sequencer Version: 4.30
Test Start: 29-jun-2024 14:50:05 Test End: 29-jun-2024 14:50:45
User Name: Manager:
Company:

Test Results
Time Assessment
Ignore
Name Start Stop Tnom Tdev- Tdev+ Tact Tdev Assess
before
REL1 State 2 State 3 State 4 10,00 s 300,0 ms 300,0 ms 10,19 s 193,7 ms +
REL2 State 5 State 6 State 7 20,00 s 300,0 ms 300,0 ms 20,19 s 193,2 ms +
Assess: + .. Passed x .. Failed o .. Not assessed

49 / 51
State 1
3 State 5 State 7
State 2 State 4 State 6

CMC356 V A/V

75

50

25 t/s
5 10 15 20 25 30 35
0

-25

-50

-75

-100
V L1-E V L2-E V L3-E

CMC356 I A/A
6

2 t/s
5 10 15 20 25 30 35
0

-2

-4

-6

I L1 I L2 I L3

CMC356 V B/V

75

50

25 t/s
5 10 15 20 25 30 35
0

-25

-50

-75

-100
VE

Bin. out 1
Bin. out 2
Bin. out 3
Bin. out 4

5 10 15 20 25 30 35
t/s

50 / 51
State 1
3 State 5 State 7
State 2 State 4 State 6

TRIP
DISJ FE
50BF
Bin. in 4
Bin. in 5
Bin. in 6
Bin. in 7
Bin. in 8
Bin. in 9
Bin. in 10

5 10 15 20 25 30 35
t/s

Cursor Data
Time Signal Value
Cursor 1 0,00 s <none> n/a
Cursor 2 37,80 s <none> n/a
C2 - C1 37,80 s n/a

Event recorder
Time Type Signal name Slope
0,00 s Input DISJ FE 0>1
1,345 s Input TRIP 0>1
1,370 s Input DISJ FE 1>0
1,493 s Input TRIP 1>0
11,56 s Input DISJ FE 0>1
14,59 s Input TRIP 0>1
14,61 s Input DISJ FE 1>0
14,73 s Input TRIP 1>0
34,80 s Input DISJ FE 0>1

Test State:
Test passed

Group end:79

51 / 51