Professional Documents
Culture Documents
CURVAS - UPC1
CURVAS - UPC1
Test Equipment
Type Serial Number
CMC356 FC672K
Hardware Check
Performed At Result Details
19/06/2024 16:24:16 Passed
Analog Outputs
Test Equipment Test Object
Display Connection
Device Connector
Name Terminal
CMC356 V A 1 V L1-E
FC672K 2 V L2-E
3 V L3-E
N
CMC356 V B 1 VE
FC672K N
CMC356 I A 1 I L1
FC672K 2 I L2
3 I L3
N
Binary/Analog Inputs
Test Equipment Test Object
Display Connection
Device Connector
Name Terminal
CMC356 1+ TRIP
FC672K 1-
2+ DISJ FE
2-
3+ 50BF
3-
4+ Bin. in 4
4-
5+ Bin. in 5
5-
6+ Bin. in 6
6-
7+ Bin. in 7
7-
8+ Bin. in 8
8-
9+ Bin. in 9
9-
10+ Bin. in 10
10-
1 Bin. in 11
2 Bin. in 12
N
1 / 51
Binary Outputs
Test Equipment Test Object
Display Connection
Device Connector
Name Terminal
CMC356 1+ Bin. out 1
FC672K 1-
2+ Bin. out 2
2-
3+ Bin. out 3
3-
4+ Bin. out 4
4-
11 Bin. out 5
12 Bin. out 6
13 Bin. out 7
14 Bin. out 8
N
Analog DC Inputs
Test Equipment Test Object
Display Connection
Device Connector
Name Terminal
CMC356 V+ V1
FC672K V-
I+ I1
I-
Sampled Values
Overview
Stream Enabled IED / Sampled Values ID Simulated Ethernet port
1 No Yes ETH2
2 No Yes ETH2
3 No Yes ETH2
Sample rate / number of ASDUs: n/a
Substation/Bay:
Substation: Substation Substation address: Substation address
Bay: bay Bay address: bay address
Device:
Name/description: SEL-311C Manufacturer: SEL
Device type: Distance protection Device address: feeder address
Serial/model number: serial no.
Additional info 1:
Additional info 2:
Nominal Values:
f nom: 60,00 Hz Number of phases: 3
V nom (secondary): 110,0 V V primary: 132,0 kV
I nom (secondary): 5,000 A I primary: 1,600 kA
2 / 51
Limits:
V max: 500,0 V I max: 75,00 A
Debounce/Deglitch Filters:
Debounce time: 3,000 ms Deglitch time: 0,00 s
Overload Detection:
Suppression time: 50,00 ms
SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Line Settings and Fault Locator
Description Name Value
Line Settings Line Settings
Pos-Seq Line Impedence Magnitude (Ohms secondary) Z1MAG Pos-Seq Line 1,39 Ohm
Impedence Magnitude (Ohms
secondary)
Pos-Seq Line Impedance Angle (degrees) Z1ANG Pos-Seq Line 67,72 °
Impedance Angle (degrees)
Zero-Seq Line Impedence Magnitude (Ohms secondary) Z0MAG Zero-Seq Line 5,14 Ohm
Impedence Magnitude (Ohms
secondary)
Zero-Seq Line Impedence Angle (degrees) Z0ANG Zero-Seq Line 75,06 °
Impedence Angle (degrees)
Line Length (unitless) LL Line Length (unitless) 10,00
Fault Locator Fault Locator
Fault locator enable Fault Locator Y
3 / 51
SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Phase Distance
Description Name Value
Enable Mho Phase Distance Elements E21P Enable Mho Phase 2
Distance Elements
CCVT Transient Detection Enable ECCVT CCVT Transient N
Detection Enable
Mho Phase Distance Element Reach Settings Mho Phase Distance Element
Reach Settings
Reach Zone1 (Ohm secondary) Z1P Reach Zone1 (Ohm 0,97 Ohm
secondary)
Reach Zone2 (Ohm secondary) Z2P Reach Zone2 (Ohm 1,67 Ohm
secondary)
Mho Phase Distance Overcurrent Fault Detector Settings Mho Phase Distance
Overcurrent Fault Detector
Settings
Phase-Phase Overcurrent Fault Detector Zone1 (Amps 50PP1 Phase-Phase 1,88 A
secondary) Overcurrent Fault Detector
Zone1 (Amps secondary)
Phase-Phase Overcurrent Fault Detector Zone2 (Amps 50PP2 Phase-Phase 1,88 A
secondary) Overcurrent Fault Detector
Zone2 (Amps secondary)
Phase-Phase Overcurrent Fault Detector Zone3 (Amps 50PP3 Phase-Phase 0,50 A
secondary) Overcurrent Fault Detector
Zone3 (Amps secondary)
Phase-Phase Overcurrent Fault Detector Zone4 (Amps 50PP4 Phase-Phase 0,50 A
secondary) Overcurrent Fault Detector
Zone4 (Amps secondary)
4 / 51
SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Ground Distance
5 / 51
Description Name Value
Enable Mho Ground Distance Elements E21MG Enable Mho Ground 2
Distance Elements
Reach Mho Ground Zone1 (Ohm secondary) Z1MG Mho Zone1 (Ohm 0,97 Ohm
secondary)
Reach Mho Ground Zone2 (Ohm secondary) Z2MG Mho Zone2 (Ohm 1,67 Ohm
secondary)
E21XG Enable Quad Ground Distance Elements E21XG Enable Quad Ground
Distance Elements
Enable Quad Ground Distance Elements E21XG Enable Quad Ground 2
Distance Elements
Reactance Zone1 Quad Ground (Ohm secondary) XG1 Quad Zone1 Reactance 0,90 Ohm
(Ohm secondary)
Reactance Zone2 Quad Ground (Ohm secondary) XG2 Quad Zone2 Reactance 1,54 Ohm
(Ohm secondary)
Resistance Zone1 Quad Ground (Ohm secondary) RG1 Quad Zone1 Resistance 5,00 Ohm
(Ohm secondary)
Resistance Zone2 Quad Ground (Ohm secondary) RG2 Quad Zone2 Resistance 8,00 Ohm
(Ohm secondary)
Quad Ground Polarizing Quantity XGPOL Quad Ground IG
Polarizing Quantity
None Homogeneous Correction Angle (degrees) TANG None Homogeneous 0,00 °
Correction Angle (degrees)
Quad and Mho Ground Distance Fault Detector Settings Quad and Mho Ground
Distance Fault Detector
Settings
Phase Overcurrent Fault Detector Zone1 for Ground Fault 50L1 Zone1 Phase Current 0,50 A
(Amps secondary) FD (Amps secondary)
Phase Overcurrent Fault Detector Zone2 for Ground Fault 50L2 Zone2 Phase Current 0,50 A
(Amps secondary) FD (Amps secondary)
Phase Overcurrent Fault Detector Zone3 for Ground Fault 50L3 Zone3 Phase Current 0,50 A
(Amps secondary) FD (Amps secondary)
Phase Overcurrent Fault Detector Zone4 for Ground Fault 50L4 Zone4 Phase Current 0,50 A
(Amps secondary) FD (Amps secondary)
Residual Current Fault Detector Zone1 for Ground Fault 50GZ1 Zone1 Residual 0,50 A
(Amps secondary) Current FD (Amps secondary)
Residual Current Fault Detector Zone2 for Ground Fault 50GZ2 Zone2 Residual 0,50 A
(Amps secondary) Current FD (Amps secondary)
Residual Current Fault Detector Zone3 for Ground Fault 50GZ3 Zone3 Residual 0,50 A
(Amps secondary) Current FD (Amps secondary)
Residual Current Fault Detector Zone4 for Ground Fault 50GZ4 Zone4 Residual 0,50 A
(Amps secondary) Current FD (Amps secondary)
Zero-Sequence Compensation Settings Zero-Sequence
Compensation Settings
Zone1 ZSC Factor Magnitude K0M1 Zone1 ZSC Factor 0,901
Magnitude
Zone1 ZSC Factor Angle K0A1 Zone1 ZSC Factor 10,04 °
Angle
Zone2,3,4 ZSC Factor Magnitude K0M Zone2,3,4 ZSC Factor 0,901
Magnitude
Zone2,3,4 ZSC Factor Angle K0A Zone2,3,4 ZSC Factor 10,04 °
Angle
Mho Phase Distance Element Time Delay Settings Mho Phase Distance Element
Time Delay Settings
Zone1 Phase Time Delay (cycles in 0.25 increments) Z1PD Zone1 Phase Time 0,00 cy
Delay (cycles in 0.25
increments)
Zone2 Phase Time Delay (cycles in 0.25 increments) Z2PD Zone2 Phase Time 24,00 cy
Delay (cycles in 0.25
increments)
Mho Ground Distance Element Time Delay Settings Mho Ground Distance
Element Time Delay Settings
Zone1 Ground Time Delay (cycles in 0.25 increments) Z1GD Zone1 Ground Time 0,00 cy
Delay (cycles in 0.25
increments)
Zone2 Ground Time Delay (cycles in 0.25 increments) Z2GD Zone2 Ground Time 24,00 cy
Delay (cycles in 0.25
increments)
Common Phase/Ground Dist. Element Time Delay Settings Common Phase/Ground Dist.
Element Time Delay Settings
Zone1 Common Ph/Gr Time Delay (cycles in 0.25 Z1D Zone1 Common Ph/Gr 0,00 cy
increments) Time Delay (cycles in 0.25
increments)
6 / 51
Zone2 Common Ph/Gr Time Delay (cycles in 0.25 Z2D Zone2 Common Ph/Gr 24,00 cy
increments) Time Delay (cycles in 0.25
increments)
SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Phase Instantaneous Overcurrent
Description Name Value
Enable Phase Overcurrent Elements E50P Enable Phase 2
Overcurrent Elements
Level 1 (Amps secondary) 50P1P Level 1 (Amps 22,81 A
secondary)
Level 2 (Amps secondary) 50P2P Level 2 (Amps 1,88 A
secondary)
Phase Definite-Time Overcurrent Elements Phase Definite-Time
Overcurrent Elements
Level 1 (cycles in 0.25 increments) 67P1D Level 1 (cycles in 0.25 3,00 cy
increments)
Level 2 (cycles in 0.25 increments) 67P2D Level 2 (cycles in 0.25 0,00 cy
increments)
SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Residual Ground Instantaneous
Overcurrent
Description Name Value
Enable Residual Ground Overcurrent Elements E50G Enable Residual 1
Ground Overcurrent Elements
Level 1 (Amps secondary) 50G1P Level 1 (Amps 18,00 A
secondary)
Residual Ground Definite-Time Overcurrent Elements Residual Ground
Definite-Time Overcurrent
Elements
Level 1 (cycles in 0.25 increments) 67G1D Level 1 (cycles in 0.25 3,00 cy
increments)
SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Residual Ground Time-Overcurrent
Description Name Value
Enable Residual Ground Time-Overcurrent Elements E51G Enable Residual Y
Ground Time-Overcurrent
Elements
Pickup (Amps secondary) 51GP Pickup (Amps 0,50 A
secondary)
Curve 51GC Curve C1
Time Dial 51GTD Time Dial 0,20
Electromechanical Reset Delay 51GRS Electromechanical N
Reset Delay
7 / 51
SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Negative-Sequence
Time-Overcurrent
Description Name Value
Enable Negative-Sequence Time-Overcurrent Elements E51Q Enable Y
Negative-Sequence
Time-Overcurrent Elements
Pickup (Amps secondary) 51QP Pickup (Amps 2,20 A
secondary)
Curve 51QC Curve U3
Time Dial 51QTD Time Dial 3,00
Electromechanical Reset Delay 51QRS Electromechanical N
Reset Delay
8 / 51
SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Load-Encroachment
Description Name Value
Enable Load-Encroachment Element ELOAD Enable Y
Load-Encroachment Element
Forward Load Impedance (Ohms secondary) ZLF Forward Load 32,00 Ohm
Impedance (Ohms
secondary)
Reverse Load Imoedance (Ohms secondary) ZLR Reverse Load 32,00 Ohm
Imoedance (Ohms
secondary)
Positive Forward Load Angle (degrees) PLAF Positive Forward Load 30,00 °
Angle (degrees)
Negative Forward Load Angle (degrees) NLAF Negative Forward Load -30,00 °
Angle (degrees)
Positive Reverse Load Angle (degrees) PLAR Positive Reverse Load 150,00 °
Angle (degrees)
Negative Reverse Load Angle (degrees) NLAR Negative Reverse Load 210,00 °
Angle (degrees)
9 / 51
SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Synchronism Check
Description Name Value
Enable Synchronism Check Elements E25 Enable Synchronism Y
Check Elements
Voltage Window - Low Threshold (Volts secondary) 25VLO Voltage Window - Low 59,00 V
Threshold (Volts secondary)
Voltage Window - High Threshold (Volts secondary) 25VHI Voltage Window - High 80,00 V
Threshold (Volts secondary)
Maximum Slip Frequency (Hz) 25SF Maximum Slip 0,050 Hz
Frequency (Hz)
Maximum Angle 1 (degrees) 25ANG1 Maximum Angle 1 25,00 °
(degrees)
Maximum Angle 2 (degrees) 25ANG2 Maximum Angle 2 40,00 °
(degrees)
Sync. Phase SYNCP Sync. Phase VB
Breaker Close Time for Angle Comp. TCLOSD Breaker Close Time 3,00 cy
for Angle Comp.
SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Comm. Assisted Trip Schemes
Description Name Value
Enable Communication Assisted Tripping Schemes ECOMM Enable N
Communication Assisted
Tripping Schemes
10 / 51
SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Demand Metering
Description Name Value
Enable Demand Metering Method EDEM Enable Demand THM
Metering Method
Time Constant DMTC Time Constant 5
Phase Pickup (Amps secondary) PDEMP Phase Pickup (Amps 5,00 A
secondary)
Residual Ground Pickup (Amps secondary) GDEMP Residual Ground 1,50 A
Pickup (Amps secondary)
Negative-Sequence Pickup (Amps secondary) QDEMP Negative-Sequence 1,50 A
Pickup (Amps secondary)
SEL 311C \ Relay Parameter Section \ Group 1 \ Logic 1 \ Trip/Comm.-Assisted Trip Logic
Description Name Value
Trip Logic Equations Trip Logic Equations
TR Direct Trip conditions M1PT+M2PT+M3PT+
Z1GT+Z2GT+Z3GT+
67P1T+67G1T+51PT
+51GT
TRCOMM M2P+Z2G
Communication-assisted trip
conditions
TRSOTF Switch-onto-fault trip M2P+Z2G+50P1
conditions
DTT Direct transfer trip 0
conditions.
ULTR Unlatch trip conditions !(M1P+M2P+M3P+Z1
G+Z2G+Z3G+67P1+6
7G1+51P+51G)
11 / 51
SEL 311C \ Additional Information \ General - General Information
Description Name Value
Manufacturer Manufacturer SEL
Device Model Device Model SEL-311C
Serial Number Serial Number serial no.
Device Address Device Address device address
Device type Device type Distance protection
Manufacturer HW code Hardware revision HW revision
Software revision Software revision Software revision
Substation Substation Substation
Substation Address Substation Address Substation address
Feeder Feeder feeder
Feeder Address Feeder Address feeder address
Bay Bay bay
Bay address Bay address bay address
Protected object name Protected object name Protected object
name
Description Description information
Location Location Location
12 / 51
SEL 311C \ Additional Information \ Configuration details \ Trip logic \ Distance protection
Description Name Value
Phase distance Zone 1 used true
for direct tripping
Ground distance Zone 1 used true
for direct tripping
Phase distance Zone 2 used true
for direct tripping
Ground distance Zone 2 used true
for direct tripping
Phase distance Zone 3 used true
for direct tripping
Ground distance Zone 3 used true
for direct tripping
Phase distance Zone 4 used false
for direct tripping
Ground distance Zone 4 used false
for direct tripping
is "M1P" wordbit connected to a trip output? Instantanous trip of phase false
distance Zone 1
is "Z1G" wordbit connected to a trip output? Instantanous trip of ground false
distance Zone 1
Do Z1P and Z1G use common or independent timers? Timer selecion for phase and Independent timer for
ground distance Zone 1 phase and ground
Do Z2P and Z2G use common or independent timers? Timer selecion for phase and Independent timer for
ground distance Zone 2 phase and ground
Do Z3P and Z3G use common or independent timers? Timer selecion for phase and Independent timer for
ground distance Zone 3 phase and ground
13 / 51
SEL 311C \ Additional Information \ Relay Information \ Distance Protection - Distance
protection
Description Name Value
Rel. Tol Z at Line Angle (SIR<=60) Rel. Tol Z 5,00 %
Max. Trip time (according operating time curve at SIR=30) Max. operating time (cycle) - 2,00 cy
internal operation
Max. Trip time (according operating time curve at SIR=30) Max. operating time (ms) - 33,33 ms
internal operation
Rel. time tolerance Rel. t-Tolerance 5,00 %
Pick up / drop off ratio Pick Up / Drop Off Ratio 0,95
Abs. t-Tolerance Abs. t-Tolerance- internal 1,50 cy
operation
CB Configuration
Description Name Value
CB trip time CB trip time 50,00 ms
CB close time CB close time 100,00 ms
Times for 52a, 52b in percent of CB time 52a, 52b % of CB 20,00 %
General - Values:
TimeTolAbs: 0,03 s VT connection: n/a
TimeTolRel: 0,10 % CT starpoint connection: n/a
CurrentTolAbs: 0,05 Iref
CurrentTolRel: 3,00 %
Directional: No
14 / 51
Elements - Phase:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
Yes 51P C1 Standard Inverse 1,87 Iref 0,14 1,00 Non Directional
Yes 50/67P1 Definite Time 22,81 Iref 0,08 s 1,00 Non Directional
No 50/67P2 Definite Time 1,88 Iref 0,03 s 1,00 Non Directional
No 50/67P3 Definite Time 0,10 Iref 0,03 s 1,00 Non Directional
Elements - Residual:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
Yes 51G C1 Standard Inverse 0,50 Iref 0,20 1,00 Non Directional
Yes 50/67G1 Definite Time 18,00 0,08 s 1,00 Non Directional
Iref
No 50/67G2 Definite Time 0,10 Iref 0,03 s 1,00 Non Directional
No 50/67G3 Definite Time 0,10 Iref 0,03 s 1,00 Non Directional
No 50/67G4 Definite Time 0,10 Iref 0,03 s 1,00 Non Directional
Tolerances:
Tol. T rel.: 5,000 %
Tol. T abs. +: 29,00 ms Tol. T abs. -: 29,00 ms
Tol. Z rel.: 5,000 % Tol. Z abs.: 50,00 mΩ
Grounding factor:
kL mag.: 0,000000 kL angle: 0,000000°
Separate arc no
resistance:
Zone Settings:
Tol. T Tol. T
Label Type Fault loop Trip time Tol. T rel Tol. Z rel. Tol. Z abs
abs+ abs-
ZL1 Tripping L-L 33,33 ms 5,000 % 29,00 ms 29,00 ms 5,000 % 50,00 mΩ
ZL2 Tripping L-L 433,3 ms 5,000 % 29,00 ms 29,00 ms 5,000 % 50,00 mΩ
ZM1 Tripping L-E 33,33 ms 5,000 % 29,00 ms 29,00 ms 5,000 % 50,00 mΩ
ZM2 Tripping L-E 433,3 ms 5,000 % 29,00 ms 29,00 ms 5,000 % 50,00 mΩ
ZX1 Tripping L-E 33,33 ms 5,000 % 29,00 ms 29,00 ms 5,000 % 50,00 mΩ
ZX2 Tripping L-E 433,3 ms 5,000 % 29,00 ms 29,00 ms 5,000 % 50,00 mΩ
pos. Load non trip. L1-L2-L3 n/a n/a n/a n/a 5,000 % 1,600 Ω
Encroach
ment
neg. Load non trip. L1-L2-L3 n/a n/a n/a n/a 5,000 % 1,600 Ω
Encroach
ment
15 / 51
X/Ω
30
20
10
-10
-20
-30
Tolerances:
Tol. T rel.: 5,000 % Tol. S rel.: 5,000 %
Tol. T abs. +: 50,00 ms Tol. S abs.: 50,00 mVA
Tol. T abs. -: 0,00 s Angle tol.: 3,000 °
Voltage threshold:
Voltage threshold No Voltage threshold tol. rel.: 5,000 %
enabled:
Voltage threshold: 100,0 V Voltage threshold tol. 5,000 V
abs.:
Voltage threshold type: Undervoltage
Overcurrent threshold:
Overcurrent threshold No Overcurrent threshold tol. 5,000 %
enabled: rel.:
Overcurrent threshold: 1,000 A Overcurrent threshold tol. 250,0 mA
abs.:
Zone Settings:
QuickCMC:
Substation/Bay:
Substation: Substation Substation address: Substation address
Bay: bay Bay address: bay address
16 / 51
Device:
Name/description: SEL-311C Manufacturer: SEL
Device type: Distance protection Device address: feeder address
Serial/model number: serial no.
Additional info 1:
Additional info 2:
Nominal Values:
f nom: 60,00 Hz Number of phases: 3
V nom (secondary): 110,0 V V primary: 132,0 kV
I nom (secondary): 5,000 A I primary: 1,600 kA
Limits:
V max: 500,0 V I max: 75,00 A
Debounce/Deglitch Filters:
Debounce time: 3,000 ms Deglitch time: 0,00 s
Overload Detection:
Suppression time: 50,00 ms
17 / 51
SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Line Settings and Fault Locator
Description Name Value
Line Settings Line Settings
Pos-Seq Line Impedence Magnitude (Ohms secondary) Z1MAG Pos-Seq Line 1,39 Ohm
Impedence Magnitude (Ohms
secondary)
Pos-Seq Line Impedance Angle (degrees) Z1ANG Pos-Seq Line 67,72 °
Impedance Angle (degrees)
Zero-Seq Line Impedence Magnitude (Ohms secondary) Z0MAG Zero-Seq Line 5,14 Ohm
Impedence Magnitude (Ohms
secondary)
Zero-Seq Line Impedence Angle (degrees) Z0ANG Zero-Seq Line 75,06 °
Impedence Angle (degrees)
Line Length (unitless) LL Line Length (unitless) 10,00
Fault Locator Fault Locator
Fault locator enable Fault Locator Y
18 / 51
SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Ground Distance
19 / 51
Description Name Value
Enable Mho Ground Distance Elements E21MG Enable Mho Ground 2
Distance Elements
Reach Mho Ground Zone1 (Ohm secondary) Z1MG Mho Zone1 (Ohm 0,97 Ohm
secondary)
Reach Mho Ground Zone2 (Ohm secondary) Z2MG Mho Zone2 (Ohm 1,67 Ohm
secondary)
E21XG Enable Quad Ground Distance Elements E21XG Enable Quad Ground
Distance Elements
Enable Quad Ground Distance Elements E21XG Enable Quad Ground 2
Distance Elements
Reactance Zone1 Quad Ground (Ohm secondary) XG1 Quad Zone1 Reactance 0,90 Ohm
(Ohm secondary)
Reactance Zone2 Quad Ground (Ohm secondary) XG2 Quad Zone2 Reactance 1,54 Ohm
(Ohm secondary)
Resistance Zone1 Quad Ground (Ohm secondary) RG1 Quad Zone1 Resistance 5,00 Ohm
(Ohm secondary)
Resistance Zone2 Quad Ground (Ohm secondary) RG2 Quad Zone2 Resistance 8,00 Ohm
(Ohm secondary)
Quad Ground Polarizing Quantity XGPOL Quad Ground IG
Polarizing Quantity
None Homogeneous Correction Angle (degrees) TANG None Homogeneous 0,00 °
Correction Angle (degrees)
Quad and Mho Ground Distance Fault Detector Settings Quad and Mho Ground
Distance Fault Detector
Settings
Phase Overcurrent Fault Detector Zone1 for Ground Fault 50L1 Zone1 Phase Current 0,50 A
(Amps secondary) FD (Amps secondary)
Phase Overcurrent Fault Detector Zone2 for Ground Fault 50L2 Zone2 Phase Current 0,50 A
(Amps secondary) FD (Amps secondary)
Phase Overcurrent Fault Detector Zone3 for Ground Fault 50L3 Zone3 Phase Current 0,50 A
(Amps secondary) FD (Amps secondary)
Phase Overcurrent Fault Detector Zone4 for Ground Fault 50L4 Zone4 Phase Current 0,50 A
(Amps secondary) FD (Amps secondary)
Residual Current Fault Detector Zone1 for Ground Fault 50GZ1 Zone1 Residual 0,50 A
(Amps secondary) Current FD (Amps secondary)
Residual Current Fault Detector Zone2 for Ground Fault 50GZ2 Zone2 Residual 0,50 A
(Amps secondary) Current FD (Amps secondary)
Residual Current Fault Detector Zone3 for Ground Fault 50GZ3 Zone3 Residual 0,50 A
(Amps secondary) Current FD (Amps secondary)
Residual Current Fault Detector Zone4 for Ground Fault 50GZ4 Zone4 Residual 0,50 A
(Amps secondary) Current FD (Amps secondary)
Zero-Sequence Compensation Settings Zero-Sequence
Compensation Settings
Zone1 ZSC Factor Magnitude K0M1 Zone1 ZSC Factor 0,901
Magnitude
Zone1 ZSC Factor Angle K0A1 Zone1 ZSC Factor 10,04 °
Angle
Zone2,3,4 ZSC Factor Magnitude K0M Zone2,3,4 ZSC Factor 0,901
Magnitude
Zone2,3,4 ZSC Factor Angle K0A Zone2,3,4 ZSC Factor 10,04 °
Angle
Mho Phase Distance Element Time Delay Settings Mho Phase Distance Element
Time Delay Settings
Zone1 Phase Time Delay (cycles in 0.25 increments) Z1PD Zone1 Phase Time 0,00 cy
Delay (cycles in 0.25
increments)
Zone2 Phase Time Delay (cycles in 0.25 increments) Z2PD Zone2 Phase Time 24,00 cy
Delay (cycles in 0.25
increments)
Mho Ground Distance Element Time Delay Settings Mho Ground Distance
Element Time Delay Settings
Zone1 Ground Time Delay (cycles in 0.25 increments) Z1GD Zone1 Ground Time 0,00 cy
Delay (cycles in 0.25
increments)
Zone2 Ground Time Delay (cycles in 0.25 increments) Z2GD Zone2 Ground Time 24,00 cy
Delay (cycles in 0.25
increments)
Common Phase/Ground Dist. Element Time Delay Settings Common Phase/Ground Dist.
Element Time Delay Settings
Zone1 Common Ph/Gr Time Delay (cycles in 0.25 Z1D Zone1 Common Ph/Gr 0,00 cy
increments) Time Delay (cycles in 0.25
increments)
20 / 51
Zone2 Common Ph/Gr Time Delay (cycles in 0.25 Z2D Zone2 Common Ph/Gr 24,00 cy
increments) Time Delay (cycles in 0.25
increments)
SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Phase Instantaneous Overcurrent
Description Name Value
Enable Phase Overcurrent Elements E50P Enable Phase 2
Overcurrent Elements
Level 1 (Amps secondary) 50P1P Level 1 (Amps 22,81 A
secondary)
Level 2 (Amps secondary) 50P2P Level 2 (Amps 1,88 A
secondary)
Phase Definite-Time Overcurrent Elements Phase Definite-Time
Overcurrent Elements
Level 1 (cycles in 0.25 increments) 67P1D Level 1 (cycles in 0.25 3,00 cy
increments)
Level 2 (cycles in 0.25 increments) 67P2D Level 2 (cycles in 0.25 0,00 cy
increments)
SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Residual Ground Instantaneous
Overcurrent
Description Name Value
Enable Residual Ground Overcurrent Elements E50G Enable Residual 1
Ground Overcurrent Elements
Level 1 (Amps secondary) 50G1P Level 1 (Amps 18,00 A
secondary)
Residual Ground Definite-Time Overcurrent Elements Residual Ground
Definite-Time Overcurrent
Elements
Level 1 (cycles in 0.25 increments) 67G1D Level 1 (cycles in 0.25 3,00 cy
increments)
SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Residual Ground Time-Overcurrent
Description Name Value
Enable Residual Ground Time-Overcurrent Elements E51G Enable Residual Y
Ground Time-Overcurrent
Elements
Pickup (Amps secondary) 51GP Pickup (Amps 0,50 A
secondary)
Curve 51GC Curve C1
Time Dial 51GTD Time Dial 0,20
Electromechanical Reset Delay 51GRS Electromechanical N
Reset Delay
21 / 51
SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Negative-Sequence
Time-Overcurrent
Description Name Value
Enable Negative-Sequence Time-Overcurrent Elements E51Q Enable Y
Negative-Sequence
Time-Overcurrent Elements
Pickup (Amps secondary) 51QP Pickup (Amps 2,20 A
secondary)
Curve 51QC Curve U3
Time Dial 51QTD Time Dial 3,00
Electromechanical Reset Delay 51QRS Electromechanical N
Reset Delay
22 / 51
SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Load-Encroachment
Description Name Value
Enable Load-Encroachment Element ELOAD Enable Y
Load-Encroachment Element
Forward Load Impedance (Ohms secondary) ZLF Forward Load 32,00 Ohm
Impedance (Ohms
secondary)
Reverse Load Imoedance (Ohms secondary) ZLR Reverse Load 32,00 Ohm
Imoedance (Ohms
secondary)
Positive Forward Load Angle (degrees) PLAF Positive Forward Load 30,00 °
Angle (degrees)
Negative Forward Load Angle (degrees) NLAF Negative Forward Load -30,00 °
Angle (degrees)
Positive Reverse Load Angle (degrees) PLAR Positive Reverse Load 150,00 °
Angle (degrees)
Negative Reverse Load Angle (degrees) NLAR Negative Reverse Load 210,00 °
Angle (degrees)
23 / 51
SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Synchronism Check
Description Name Value
Enable Synchronism Check Elements E25 Enable Synchronism Y
Check Elements
Voltage Window - Low Threshold (Volts secondary) 25VLO Voltage Window - Low 59,00 V
Threshold (Volts secondary)
Voltage Window - High Threshold (Volts secondary) 25VHI Voltage Window - High 80,00 V
Threshold (Volts secondary)
Maximum Slip Frequency (Hz) 25SF Maximum Slip 0,050 Hz
Frequency (Hz)
Maximum Angle 1 (degrees) 25ANG1 Maximum Angle 1 25,00 °
(degrees)
Maximum Angle 2 (degrees) 25ANG2 Maximum Angle 2 40,00 °
(degrees)
Sync. Phase SYNCP Sync. Phase VB
Breaker Close Time for Angle Comp. TCLOSD Breaker Close Time 3,00 cy
for Angle Comp.
SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Comm. Assisted Trip Schemes
Description Name Value
Enable Communication Assisted Tripping Schemes ECOMM Enable N
Communication Assisted
Tripping Schemes
24 / 51
SEL 311C \ Relay Parameter Section \ Group 1 \ Set 1 \ Demand Metering
Description Name Value
Enable Demand Metering Method EDEM Enable Demand THM
Metering Method
Time Constant DMTC Time Constant 5
Phase Pickup (Amps secondary) PDEMP Phase Pickup (Amps 5,00 A
secondary)
Residual Ground Pickup (Amps secondary) GDEMP Residual Ground 1,50 A
Pickup (Amps secondary)
Negative-Sequence Pickup (Amps secondary) QDEMP Negative-Sequence 1,50 A
Pickup (Amps secondary)
SEL 311C \ Relay Parameter Section \ Group 1 \ Logic 1 \ Trip/Comm.-Assisted Trip Logic
Description Name Value
Trip Logic Equations Trip Logic Equations
TR Direct Trip conditions M1PT+M2PT+M3PT+
Z1GT+Z2GT+Z3GT+
67P1T+67G1T+51PT
+51GT
TRCOMM M2P+Z2G
Communication-assisted trip
conditions
TRSOTF Switch-onto-fault trip M2P+Z2G+50P1
conditions
DTT Direct transfer trip 0
conditions.
ULTR Unlatch trip conditions !(M1P+M2P+M3P+Z1
G+Z2G+Z3G+67P1+6
7G1+51P+51G)
25 / 51
SEL 311C \ Additional Information \ General - General Information
Description Name Value
Manufacturer Manufacturer SEL
Device Model Device Model SEL-311C
Serial Number Serial Number serial no.
Device Address Device Address device address
Device type Device type Distance protection
Manufacturer HW code Hardware revision HW revision
Software revision Software revision Software revision
Substation Substation Substation
Substation Address Substation Address Substation address
Feeder Feeder feeder
Feeder Address Feeder Address feeder address
Bay Bay bay
Bay address Bay address bay address
Protected object name Protected object name Protected object
name
Description Description information
Location Location Location
26 / 51
SEL 311C \ Additional Information \ Configuration details \ Trip logic \ Distance protection
Description Name Value
Phase distance Zone 1 used true
for direct tripping
Ground distance Zone 1 used true
for direct tripping
Phase distance Zone 2 used true
for direct tripping
Ground distance Zone 2 used true
for direct tripping
Phase distance Zone 3 used true
for direct tripping
Ground distance Zone 3 used true
for direct tripping
Phase distance Zone 4 used false
for direct tripping
Ground distance Zone 4 used false
for direct tripping
is "M1P" wordbit connected to a trip output? Instantanous trip of phase false
distance Zone 1
is "Z1G" wordbit connected to a trip output? Instantanous trip of ground false
distance Zone 1
Do Z1P and Z1G use common or independent timers? Timer selecion for phase and Independent timer for
ground distance Zone 1 phase and ground
Do Z2P and Z2G use common or independent timers? Timer selecion for phase and Independent timer for
ground distance Zone 2 phase and ground
Do Z3P and Z3G use common or independent timers? Timer selecion for phase and Independent timer for
ground distance Zone 3 phase and ground
27 / 51
SEL 311C \ Additional Information \ Relay Information \ Distance Protection - Distance
protection
Description Name Value
Rel. Tol Z at Line Angle (SIR<=60) Rel. Tol Z 5,00 %
Max. Trip time (according operating time curve at SIR=30) Max. operating time (cycle) - 2,00 cy
internal operation
Max. Trip time (according operating time curve at SIR=30) Max. operating time (ms) - 33,33 ms
internal operation
Rel. time tolerance Rel. t-Tolerance 5,00 %
Pick up / drop off ratio Pick Up / Drop Off Ratio 0,95
Abs. t-Tolerance Abs. t-Tolerance- internal 1,50 cy
operation
CB Configuration
Description Name Value
CB trip time CB trip time 50,00 ms
CB close time CB close time 100,00 ms
Times for 52a, 52b in percent of CB time 52a, 52b % of CB 20,00 %
Test Module
Name: OMICRON QuickCMC Version: 4.30
Test Start: 18-jun-2024 15:06:39 Test End:
User Name: Manager:
Company:
Test Results
28 / 51
Comment
Summary
0 tests passed, 0 tests failed, 0 tests not assessed
No results available!
Group:50P1
50P1:
Test Object - Overcurrent Parameters
General - Values:
TimeTolAbs: 0,03 s VT connection: n/a
TimeTolRel: 0,10 % CT starpoint connection: n/a
CurrentTolAbs: 0,05 Iref
CurrentTolRel: 3,00 %
Directional: No
Elements - Phase:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
No 51P C1 Standard Inverse 1,87 Iref 0,14 1,00 Non Directional
Yes 50/67P1 Definite Time 22,81 Iref 0,05 s 1,00 Non Directional
No 50/67P2 Definite Time 1,88 Iref 0,03 s 1,00 Non Directional
No 50/67P3 Definite Time 0,10 Iref 0,03 s 1,00 Non Directional
Elements - Residual:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
No 51G C1 Standard Inverse 0,50 Iref 0,20 1,00 Non Directional
No 50/67G1 Definite Time 18,00 0,08 s 1,00 Non Directional
Iref
No 50/67G2 Definite Time 0,10 Iref 0,03 s 1,00 Non Directional
No 50/67G3 Definite Time 0,10 Iref 0,03 s 1,00 Non Directional
No 50/67G4 Definite Time 0,10 Iref 0,03 s 1,00 Non Directional
Test Module
Name: OMICRON Overcurrent Version: 4.30
Test Start: 11-jun-2024 09:49:07 Test End: 11-jun-2024 09:49:37
User Name: Manager:
Company:
Test Settings:
29 / 51
Fault Model:
Time reference: Fault inception
Load current: 0,00 A
Load angle: n/a
Prefault time: 100,0 ms
Abs. max time: 240,0 s
Post fault time: 500,0 ms
Rel. max time: 100,0 %
Enable voltage output: No
Fault voltage LN (for all but two phase faults): n/a
Fault voltage LL (for two phase faults): n/a
Decaying DC active: No
Time constant: n/a
CB char min time: 50,00 ms
Thermal reset active: No
Thermal reset method: n/a
Thermal reset message: n/a
Shot Test:
Type Relative To Factor Magnitude Angle tnom tmin tmax
L1-L2 (---) n/a 23,50 A n/a 50,00 ms 20,83 ms 79,17 ms
L1-L2 (---) n/a 24,00 A n/a 50,00 ms 20,83 ms 79,17 ms
L1-L2 (---) n/a 24,50 A n/a 50,00 ms 20,83 ms 79,17 ms
L1-L2 (---) n/a 25,00 A n/a 50,00 ms 20,83 ms 79,17 ms
L1-L2 (---) n/a 25,50 A n/a 50,00 ms 20,83 ms 79,17 ms
L1-L2 (---) n/a 26,00 A n/a 50,00 ms 20,83 ms 79,17 ms
L2-L3 (---) n/a 23,50 A n/a 50,00 ms 20,83 ms 79,17 ms
L2-L3 (---) n/a 24,00 A n/a 50,00 ms 20,83 ms 79,17 ms
L2-L3 (---) n/a 24,50 A n/a 50,00 ms 20,83 ms 79,17 ms
L2-L3 (---) n/a 25,00 A n/a 50,00 ms 20,83 ms 79,17 ms
L2-L3 (---) n/a 25,50 A n/a 50,00 ms 20,83 ms 79,17 ms
L2-L3 (---) n/a 26,00 A n/a 50,00 ms 20,83 ms 79,17 ms
L3-L1 (---) n/a 23,50 A n/a 50,00 ms 20,83 ms 79,17 ms
L3-L1 (---) n/a 24,00 A n/a 50,00 ms 20,83 ms 79,17 ms
L3-L1 (---) n/a 24,50 A n/a 50,00 ms 20,83 ms 79,17 ms
L3-L1 (---) n/a 25,00 A n/a 50,00 ms 20,83 ms 79,17 ms
L3-L1 (---) n/a 25,50 A n/a 50,00 ms 20,83 ms 79,17 ms
L3-L1 (---) n/a 26,00 A n/a 50,00 ms 20,83 ms 79,17 ms
L1-L2-L3 (---) n/a 23,50 A n/a 50,00 ms 20,83 ms 79,17 ms
L1-L2-L3 (---) n/a 24,00 A n/a 50,00 ms 20,83 ms 79,17 ms
L1-L2-L3 (---) n/a 24,50 A n/a 50,00 ms 20,83 ms 79,17 ms
L1-L2-L3 (---) n/a 25,00 A n/a 50,00 ms 20,83 ms 79,17 ms
L1-L2-L3 (---) n/a 25,50 A n/a 50,00 ms 20,83 ms 79,17 ms
L1-L2-L3 (---) n/a 26,00 A n/a 50,00 ms 20,83 ms 79,17 ms
Binary Outputs:
Name State
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
Binary Inputs:
Trigger Logic: And
Name Trigger State
TRIP 1
Bin. in 3 X
30 / 51
Shot Test Results:
Type Relative To Factor Magnitude Angle tnom tact Deviation Overload Result
L1-L2 (---) n/a 23,50 A n/a 50,00 ms 74,40 ms 48,80 % No Passed
L1-L2 (---) n/a 24,00 A n/a 50,00 ms 75,90 ms 51,80 % No Passed
L1-L2 (---) n/a 24,50 A n/a 50,00 ms 74,00 ms 48,00 % No Passed
L1-L2 (---) n/a 25,00 A n/a 50,00 ms 73,20 ms 46,40 % No Passed
L1-L2 (---) n/a 25,50 A n/a 50,00 ms 73,20 ms 46,40 % No Passed
L1-L2 (---) n/a 26,00 A n/a 50,00 ms 74,40 ms 48,80 % No Passed
L2-L3 (---) n/a 23,50 A n/a 50,00 ms 74,20 ms 48,40 % No Passed
L2-L3 (---) n/a 24,00 A n/a 50,00 ms 76,90 ms 53,80 % No Passed
L2-L3 (---) n/a 24,50 A n/a 50,00 ms 74,70 ms 49,40 % No Passed
L2-L3 (---) n/a 25,00 A n/a 50,00 ms 73,60 ms 47,20 % No Passed
L2-L3 (---) n/a 25,50 A n/a 50,00 ms 73,50 ms 47,00 % No Passed
L2-L3 (---) n/a 26,00 A n/a 50,00 ms 76,30 ms 52,60 % No Passed
L3-L1 (---) n/a 23,50 A n/a 50,00 ms 75,80 ms 51,60 % No Passed
L3-L1 (---) n/a 24,00 A n/a 50,00 ms 74,10 ms 48,20 % No Passed
L3-L1 (---) n/a 24,50 A n/a 50,00 ms 76,40 ms 52,80 % No Passed
L3-L1 (---) n/a 25,00 A n/a 50,00 ms 74,20 ms 48,40 % No Passed
L3-L1 (---) n/a 25,50 A n/a 50,00 ms 76,90 ms 53,80 % No Passed
L3-L1 (---) n/a 26,00 A n/a 50,00 ms 75,00 ms 50,00 % No Passed
L1-L2-L3 (---) n/a 23,50 A n/a 50,00 ms 71,20 ms 42,40 % No Passed
L1-L2-L3 (---) n/a 24,00 A n/a 50,00 ms 72,60 ms 45,20 % No Passed
L1-L2-L3 (---) n/a 24,50 A n/a 50,00 ms 71,10 ms 42,20 % No Passed
L1-L2-L3 (---) n/a 25,00 A n/a 50,00 ms 73,90 ms 47,80 % No Passed
L1-L2-L3 (---) n/a 25,50 A n/a 50,00 ms 73,60 ms 47,20 % No Passed
L1-L2-L3 (---) n/a 26,00 A n/a 50,00 ms 74,40 ms 48,80 % No Passed
L1-L2 n/a
10000,00
1000,00
100,00
10,00
t/s
1,00
0,10
L2-L3 n/a
10000,00
1000,00
100,00
10,00
t/s
1,00
0,10
31 / 51
Charts for Fault Types:
Angle
Type
L3-L1 n/a
10000,00
1000,00
100,00
10,00
t/s
1,00
0,10
L1-L2-L3 n/a
10000,00
1000,00
100,00
10,00
t/s
1,00
0,10
Test State:
24 out of 24 points tested.
24 points passed.
0 points failed.
Test passed
50P1 - DISPARO:
Test Object - Overcurrent Parameters
General - Values:
TimeTolAbs: 0,03 s VT connection: n/a
TimeTolRel: 0,10 % CT starpoint connection: n/a
CurrentTolAbs: 0,05 Iref
CurrentTolRel: 3,00 %
Directional: No
Elements - Phase:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
No 51P C1 Standard Inverse 1,87 Iref 0,14 1,00 Non Directional
Yes 50/67P1 Definite Time 22,81 Iref 0,05 s 1,00 Non Directional
No 50/67P2 Definite Time 1,88 Iref 0,03 s 1,00 Non Directional
No 50/67P3 Definite Time 0,10 Iref 0,03 s 1,00 Non Directional
32 / 51
Elements - Residual:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
No 51G C1 Standard Inverse 0,50 Iref 0,20 1,00 Non Directional
No 50/67G1 Definite Time 18,00 0,08 s 1,00 Non Directional
Iref
No 50/67G2 Definite Time 0,10 Iref 0,03 s 1,00 Non Directional
No 50/67G3 Definite Time 0,10 Iref 0,03 s 1,00 Non Directional
No 50/67G4 Definite Time 0,10 Iref 0,03 s 1,00 Non Directional
Test Module
Name: OMICRON Overcurrent Version: 4.30
Test Start: 13-jun-2024 11:14:15 Test End: 13-jun-2024 11:14:20
User Name: Manager:
Company:
Test Settings:
Fault Model:
Time reference: Fault inception
Load current: 0,00 A
Load angle: n/a
Prefault time: 100,0 ms
Abs. max time: 240,0 s
Post fault time: 500,0 ms
Rel. max time: 100,0 %
Enable voltage output: No
Fault voltage LN (for all but two phase faults): n/a
Fault voltage LL (for two phase faults): n/a
Decaying DC active: No
Time constant: n/a
CB char min time: 50,00 ms
Thermal reset active: No
Thermal reset method: n/a
Thermal reset message: n/a
Shot Test:
Type Relative To Factor Magnitude Angle tnom tmin tmax
L1-L2 (---) n/a 24,00 A n/a 50,00 ms 20,83 ms 79,17 ms
Binary Outputs:
Name State
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
Binary Inputs:
Trigger Logic: And
Name Trigger State
TRIP 1
Bin. in 3 X
33 / 51
Shot Test Results:
Type Relative To Factor Magnitude Angle tnom tact Deviation Overload Result
L1-L2 (---) n/a 24,00 A n/a 50,00 ms 74,50 ms 49,00 % No Passed
L1-L2 n/a
10000,00
1000,00
100,00
10,00
t/s
1,00
0,10
Test State:
1 out of 1 points tested.
1 points passed.
0 points failed.
Test passed
Group end:50P1
Group:50P2 - SOTF
SOTF:
Test Settings
State PRE FALTA POS
V L1-E 63,50 V 63,50 V 63,50 V
0,00 ° 0,00 ° 0,00 °
60,000 Hz 60,000 Hz 60,000 Hz
V L2-E 63,50 V 63,50 V 63,50 V
-120,00 ° -120,00 ° -120,00 °
60,000 Hz 60,000 Hz 60,000 Hz
34 / 51
V L3-E 63,50 V 63,50 V 63,50 V
120,00 ° 120,00 ° 120,00 °
60,000 Hz 60,000 Hz 60,000 Hz
I L1 0,00 A 5,000 A 0,00 A
0,00 ° 0,00 ° 0,00 °
60,000 Hz 60,000 Hz 60,000 Hz
I L2 0,00 A 5,000 A 0,00 A
-120,00 ° -120,00 ° -120,00 °
60,000 Hz 60,000 Hz 60,000 Hz
I L3 0,00 A 5,000 A 0,00 A
120,00 ° 120,00 ° 120,00 °
60,000 Hz 60,000 Hz 60,000 Hz
V(2)-1 63,50 V 0,00 V 63,50 V
0,00 ° 0,00 ° 0,00 °
60,000 Hz 60,000 Hz 60,000 Hz
Bin. out 1 0 0 0
Bin. out 2 0 0 0
Bin. out 3 0 0 0
Bin. out 4 0 0 0
Max. State Time 1,000 s
Trigger Logic OR OR OR
TRIP X 1 1
DISJ FE 1 X X
User interaction no no no
CMGPS trigger no no no
IRIG-B/PTP no no no
trigger
Pulses / 1 1 1
seconds
Delay after Tr. 0,00 s 0,00 s 0,00 s
On trigger jump no no no
to test end
Diagrams +90° +90° +90°
-90°V32,0 A
288,7 -90°V32,0 A
288,7 -90°V32,0 A
288,7
Comment
Test Module
Name: OMICRON State Sequencer Version: 4.30
Test Start: Test End:
User Name: Manager:
Company:
Test Results
Time Assessment
Ignore
Name Start Stop Tnom Tdev- Tdev+ Tact Tdev Assess
before
SOTF FALTA FALTA TRIP 0>1 50,00 ms 50,00 ms 50,00 ms o
Assess: + .. Passed x .. Failed o .. Not assessed
35 / 51
PRE POS
FALTA
CMC356 V A/V
80
60
40
20 t/s
0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1
0
-20
-40
-60
-80
CMC356 I A/A
6
2 t/s
0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1
0
-2
-4
-6
I L1 I L2 I L3
CMC356 V B/V
80
60
40
20 t/s
0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1
0
-20
-40
-60
-80
V(2)-1
Bin. out 1
Bin. out 2
Bin. out 3
Bin. out 4
0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1
t/s
36 / 51
PRE POS
FALTA
TRIP
DISJ FE
50BF
Bin. in 4
Bin. in 5
Bin. in 6
Bin. in 7
Bin. in 8
Bin. in 9
Bin. in 10
0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1
t/s
Cursor Data
Time Signal Value
Cursor 1 0,00 s <none> n/a
Cursor 2 1,20 s <none> n/a
C2 - C1 1,20 s n/a
Event recorder
Time Type Signal name Slope
Test State:
No results available!
Group:50BF
50BF:
Test Settings
State PRE FALTA 50BF POS
V L1-E 66,40 V 66,40 V 66,40 V 66,40 V
0,00 ° 0,00 ° 0,00 ° 0,00 °
60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz
V L2-E 66,40 V 66,40 V 66,40 V 66,40 V
-120,00 ° -120,00 ° -120,00 ° -120,00 °
60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz
37 / 51
V L3-E 66,40 V 66,40 V 66,40 V 66,40 V
120,00 ° 120,00 ° 120,00 ° 120,00 °
60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz
I L1 0,00 A 5,000 A 5,000 A 0,00 A
0,00 ° 0,00 ° 0,00 ° 0,00 °
60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz
I L2 0,00 A 5,000 A 5,000 A 0,00 A
-120,00 ° -120,00 ° -120,00 ° -120,00 °
60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz
I L3 0,00 A 5,000 A 5,000 A 0,00 A
120,00 ° 120,00 ° 120,00 ° 120,00 °
60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz
V(2)-1 0,00 V 63,50 V 63,50 V 63,50 V
0,00 ° 0,00 ° 0,00 ° 0,00 °
60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz
Bin. out 1 0 0 0 0
Bin. out 2 0 0 0 0
Bin. out 3 0 0 0 0
Bin. out 4 0 0 0 0
Max. State Time 1,000 s 1,000 s
Trigger Logic OR OR
TRIP 1 X
50BF X 1
User interaction no no no no
CMGPS trigger no no no no
IRIG-B/PTP no no no no
trigger
Pulses / 1 1 1 1
seconds
Delay after Tr. 0,00 s 0,00 s 0,00 s 0,00 s
On trigger jump no no no no
to test end
Diagrams +90° +90° +90° +90°
-90°V32,0 A
288,7 -90°V32,0 A
288,7 -90°V32,0 A
288,7 -90°V32,0 A
288,7
Comment
Test Module
Name: OMICRON State Sequencer Version: 4.30
Test Start: 13-jun-2024 16:23:26 Test End: 13-jun-2024 16:23:31
User Name: Manager:
Company:
Test Results
Time Assessment
Ignore
Name Start Stop Tnom Tdev- Tdev+ Tact Tdev Assess
before
50BF 50BF 50BF 50BF 0>1 200,0 ms 50,00 ms 50,00 ms 200,5 ms 500,0 μs +
Assess: + .. Passed x .. Failed o .. Not assessed
38 / 51
PRE 50BF
FALTA POS
CMC356 V A/V
75
50
25 t/s
0,25 0,50 0,75 1,00 1,25 1,50 1,75 2,00 2,25 2,50 2,75
0
-25
-50
-75
-100
V L1-E V L2-E V L3-E
CMC356 I A/A
6
2 t/s
0,25 0,50 0,75 1,00 1,25 1,50 1,75 2,00 2,25 2,50 2,75
0
-2
-4
-6
I L1 I L2 I L3
CMC356 V B/V
80
60
40
20 t/s
0,25 0,50 0,75 1,00 1,25 1,50 1,75 2,00 2,25 2,50 2,75
0
-20
-40
-60
-80
V(2)-1
Bin. out 1
Bin. out 2
Bin. out 3
Bin. out 4
0,25 0,50 0,75 1,00 1,25 1,50 1,75 2,00 2,25 2,50 2,75
t/s
39 / 51
PRE 50BF
FALTA POS
TRIP
DISJ FE
50BF
Bin. in 4
Bin. in 5
Bin. in 6
Bin. in 7
Bin. in 8
Bin. in 9
Bin. in 10
0,25 0,50 0,75 1,00 1,25 1,50 1,75 2,00 2,25 2,50 2,75
t/s
Cursor Data
Time Signal Value
Cursor 1 0,00 s <none> n/a
Cursor 2 3,19 s <none> n/a
C2 - C1 3,19 s n/a
Event recorder
Time Type Signal name Slope
1,993 s Input TRIP 0>1
2,193 s Input 50BF 0>1
2,235 s Input TRIP 1>0
2,275 s Input 50BF 1>0
Test State:
Test passed
Group end:50BF
Group:59
59P:
Test Settings
State PRE FALTA POS
V L1-E 63,50 V 81,00 V 63,50 V
0,00 ° 0,00 ° 0,00 °
60,000 Hz 60,000 Hz 60,000 Hz
V L2-E 63,50 V 66,40 V 63,50 V
-120,00 ° -120,00 ° -120,00 °
60,000 Hz 60,000 Hz 60,000 Hz
V L3-E 63,50 V 66,40 V 63,50 V
120,00 ° 120,00 ° 120,00 °
60,000 Hz 60,000 Hz 60,000 Hz
I L1 0,00 A 0,00 A 0,00 A
0,00 ° 0,00 ° 0,00 °
60,000 Hz 60,000 Hz 60,000 Hz
I L2 0,00 A 0,00 A 0,00 A
-120,00 ° -120,00 ° -120,00 °
60,000 Hz 60,000 Hz 60,000 Hz
40 / 51
I L3 0,00 A 0,00 A 0,00 A
120,00 ° 120,00 ° 120,00 °
60,000 Hz 60,000 Hz 60,000 Hz
V(2)-1 0,00 V 0,00 V 0,00 V
0,00 ° 0,00 ° 0,00 °
60,000 Hz 60,000 Hz 60,000 Hz
Bin. out 1 0 0 0
Bin. out 2 0 0 0
Bin. out 3 0 0 0
Bin. out 4 0 0 0
Max. State Time 1,000 s 1,000 s
Trigger Logic OR
TRIP 1
User interaction no no no
CMGPS trigger no no no
IRIG-B/PTP no no no
trigger
Pulses / 1 1 1
seconds
Delay after Tr. 0,00 s 0,00 s 0,00 s
On trigger jump no no no
to test end
Diagrams +90° +90° +90°
288,7
-90°V32,0 A 288,7
-90°V32,0 A 288,7
-90°V32,0 A
Comment
Test Module
Name: OMICRON State Sequencer Version: 4.30
Test Start: 13-jun-2024 16:48:45 Test End: 13-jun-2024 16:48:54
User Name: Manager:
Company:
Test Results
Time Assessment
Ignore
Name Start Stop Tnom Tdev- Tdev+ Tact Tdev Assess
before
59P FALTA FALTA TRIP 0>1 5,000 s 50,00 ms 50,00 ms 5,029 s 28,60 ms +
Assess: + .. Passed x .. Failed o .. Not assessed
41 / 51
PRE POS
FALTA
CMC356 V A/V
100
75
50
25 t/s
1,0 2,0 3,0 4,0 5,0 6,0
0
-25
-50
-75
-100
-125
V L1-E V L2-E V L3-E
CMC356 I A/mA
75
50
25 t/s
1,0 2,0 3,0 4,0 5,0 6,0
0
-25
-50
-75
-100
I L1 I L2 I L3
CMC356 V B/mV
75
50
25 t/s
1,0 2,0 3,0 4,0 5,0 6,0
0
-25
-50
-75
-100
V(2)-1
Bin. out 1
Bin. out 2
Bin. out 3
Bin. out 4
42 / 51
PRE POS
FALTA
TRIP
DISJ FE
50BF
Bin. in 4
Bin. in 5
Bin. in 6
Bin. in 7
Bin. in 8
Bin. in 9
Bin. in 10
Cursor Data
Time Signal Value
Cursor 1 0,00 s <none> n/a
Cursor 2 7,03 s <none> n/a
C2 - C1 7,03 s n/a
Event recorder
Time Type Signal name Slope
6,029 s Input TRIP 0>1
6,113 s Input TRIP 1>0
Test State:
Test passed
59PP:
Test Settings
State PRE FALTA POS
V L1-E 63,50 V 170,0 V 63,50 V
0,00 ° 0,00 ° 0,00 °
60,000 Hz 60,000 Hz 60,000 Hz
V L2-E 63,50 V 170,0 V 63,50 V
-120,00 ° -120,00 ° -120,00 °
60,000 Hz 60,000 Hz 60,000 Hz
V L3-E 63,50 V 170,0 V 63,50 V
120,00 ° 120,00 ° 120,00 °
60,000 Hz 60,000 Hz 60,000 Hz
I L1 0,00 A 0,00 A 0,00 A
0,00 ° 0,00 ° 0,00 °
60,000 Hz 60,000 Hz 60,000 Hz
I L2 0,00 A 0,00 A 0,00 A
-120,00 ° -120,00 ° -120,00 °
60,000 Hz 60,000 Hz 60,000 Hz
I L3 0,00 A 0,00 A 0,00 A
120,00 ° 120,00 ° 120,00 °
60,000 Hz 60,000 Hz 60,000 Hz
V(2)-1 0,00 V 0,00 V 0,00 V
0,00 ° 0,00 ° 0,00 °
60,000 Hz 60,000 Hz 60,000 Hz
43 / 51
Bin. out 1 0 0 0
Bin. out 2 0 0 0
Bin. out 3 0 0 0
Bin. out 4 0 0 0
Max. State Time 1,000 s 1,000 s
Trigger Logic OR
TRIP 1
User interaction no no no
CMGPS trigger no no no
IRIG-B/PTP no no no
trigger
Pulses / 1 1 1
seconds
Delay after Tr. 0,00 s 0,00 s 0,00 s
On trigger jump no no no
to test end
Diagrams +90° +90° +90°
288,7
-90°V32,0 A 288,7
-90°V32,0 A 288,7
-90°V32,0 A
Comment
Test Module
Name: OMICRON State Sequencer Version: 4.30
Test Start: 13-jun-2024 16:52:13 Test End: 13-jun-2024 16:52:17
User Name: Manager:
Company:
Test Results
Time Assessment
Ignore
Name Start Stop Tnom Tdev- Tdev+ Tact Tdev Assess
before
59PP FALTA FALTA TRIP 0>1 0,00 s 50,00 ms 50,00 ms 12,60 ms 12,60 ms +
Assess: + .. Passed x .. Failed o .. Not assessed
PRE POS
FALTA
CMC356 V A/V
200
150
100
50 t/s
0,25 0,50 0,75 1,00 1,25 1,50 1,75
0
-50
-100
-150
-200
-250
V L1-E V L2-E V L3-E
44 / 51
PRE POS
FALTA
CMC356 I A/mA
75
50
25 t/s
0,25 0,50 0,75 1,00 1,25 1,50 1,75
0
-25
-50
-75
-100
I L1 I L2 I L3
CMC356 V B/mV
75
50
25 t/s
0,25 0,50 0,75 1,00 1,25 1,50 1,75
0
-25
-50
-75
-100
V(2)-1
Bin. out 1
Bin. out 2
Bin. out 3
Bin. out 4
TRIP
DISJ FE
50BF
Bin. in 4
Bin. in 5
Bin. in 6
Bin. in 7
Bin. in 8
Bin. in 9
Bin. in 10
Cursor Data
Time Signal Value
Cursor 1 0,00 s <none> n/a
Cursor 2 2,01 s <none> n/a
C2 - C1 2,01 s n/a
Event recorder
45 / 51
Time Type Signal name Slope
1,013 s Input TRIP 0>1
1,097 s Input TRIP 1>0
Test State:
Test passed
Group end:59
Group:25
25:
Test Settings
State State 1 State 2 State 3 State 4 State 5
V L1-E 66,40 V 66,40 V 66,40 V 66,40 V 66,40 V
0,00 ° 0,00 ° 0,00 ° 0,00 ° 0,00 °
60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz
V L2-E 66,40 V 66,40 V 66,40 V 66,40 V 66,40 V
-120,00 ° -120,00 ° -120,00 ° -120,00 ° -120,00 °
60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz
V L3-E 66,40 V 66,40 V 66,40 V 66,40 V 66,40 V
120,00 ° 120,00 ° 120,00 ° 120,00 ° 120,00 °
60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz
I L1 0,00 A 0,00 A 0,00 A 0,00 A 0,00 A
0,00 ° 0,00 ° 0,00 ° 0,00 ° 0,00 °
60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz
I L2 0,00 A 0,00 A 0,00 A 0,00 A 0,00 A
-120,00 ° -120,00 ° -120,00 ° -120,00 ° -120,00 °
60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz
I L3 0,00 A 0,00 A 0,00 A 0,00 A 0,00 A
120,00 ° 120,00 ° 120,00 ° 120,00 ° 120,00 °
60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz
VE 0,00 V 66,40 V 66,40 V 66,40 V 40,00 V
0,00 ° -120,00 ° -50,00 ° -120,00 ° -120,00 °
60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz
Bin. out 1 0 0 0 0 0
Bin. out 2 0 0 0 0 0
Bin. out 3 0 0 0 0 0
Bin. out 4 0 0 0 0 0
Max. State Time
Trigger Logic
User interaction yes yes yes yes yes
CMGPS trigger no no no no no
IRIG-B/PTP no no no no no
trigger
Pulses / 1 1 1 1 1
seconds
Delay after Tr. 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s
On trigger jump no no no no no
to test end
Diagrams +90° +90° +90° +90° +90°
288,7
-90°V32,0 A 288,7
-90°V32,0 A 288,7
-90°V32,0 A 288,7
-90°V32,0 A 288,7
-90°V32,0 A
Comment
Test Module
Name: OMICRON State Sequencer Version: 4.30
Test Start: Test End:
46 / 51
User Name: Manager:
Company:
Test Results
Time Assessment
Ignore
Name Start Stop Tnom Tdev- Tdev+ Tact Tdev Assess
before
o
Assess: + .. Passed x .. Failed o .. Not assessed
CMC356 V A/V
75
50
25 t/s
0,5 1,0 1,5 2,0 2,5 3,0 3,5 4,0 4,5
0
-25
-50
-75
-100
V L1-E V L2-E V L3-E
CMC356 I A/mA
75
50
25 t/s
0,5 1,0 1,5 2,0 2,5 3,0 3,5 4,0 4,5
0
-25
-50
-75
-100
I L1 I L2 I L3
CMC356 V B/V
75
50
25 t/s
0,5 1,0 1,5 2,0 2,5 3,0 3,5 4,0 4,5
0
-25
-50
-75
-100
VE
47 / 51
State 1 State 3 State 5
State 2 State 4
Bin. out 1
Bin. out 2
Bin. out 3
Bin. out 4
TRIP
DISJ FE
50BF
Bin. in 4
Bin. in 5
Bin. in 6
Bin. in 7
Bin. in 8
Bin. in 9
Bin. in 10
Cursor Data
Time Signal Value
Cursor 1 0,00 s <none> n/a
Cursor 2 5,00 s <none> n/a
C2 - C1 5,00 s n/a
Event recorder
Time Type Signal name Slope
Test State:
No results available!
Group end:25
Group:79
79T:
Test Settings
State State 1 State 2 State 3 State 4 State 5 State 6 State 7
V L1-E 66,40 V 17,05 V 66,40 V 66,40 V 17,05 V 66,40 V 66,40 V
0,00 ° 0,00 ° 0,00 ° 0,00 ° 0,00 ° 0,00 ° 0,00 °
60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz
V L2-E 66,40 V 63,50 V 66,40 V 66,40 V 63,50 V 66,40 V 66,40 V
-120,00 ° -120,00 ° -120,00 ° -120,00 ° -120,00 ° -120,00 ° -120,00 °
60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz
V L3-E 66,40 V 63,50 V 66,40 V 66,40 V 63,50 V 66,40 V 66,40 V
120,00 ° 120,00 ° 120,00 ° 120,00 ° 120,00 ° 120,00 ° 120,00 °
60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz
I L1 100,0 mA 5,000 A 0,00 A 100,0 mA 5,000 A 0,00 A 100,0 mA
0,00 ° -80,00 ° 0,00 ° 0,00 ° -80,00 ° 0,00 ° 0,00 °
60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz
I L2 100,0 mA 0,00 A 0,00 A 100,0 mA 0,00 A 0,00 A 100,0 mA
-120,00 ° 0,00 ° -120,00 ° -120,00 ° 0,00 ° -120,00 ° -120,00 °
60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz
48 / 51
I L3 100,0 mA 0,00 A 0,00 A 100,0 mA 0,00 A 0,00 A 100,0 mA
120,00 ° 0,00 ° 120,00 ° 120,00 ° 0,00 ° 120,00 ° 120,00 °
60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz
VE 66,40 V 66,40 V 66,40 V 66,40 V 66,40 V 66,40 V 66,40 V
-120,00 ° -120,00 ° -120,00 ° -120,00 ° -120,00 ° -120,00 ° -120,00 °
60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz 60,000 Hz
Bin. out 1 0 0 0 0 0 0 0
Bin. out 2 0 0 0 0 0 0 0
Bin. out 3 0 0 0 0 0 0 0
Bin. out 4 0 0 0 0 0 0 0
Max. State Time 3,000 s 3,000 s
Trigger Logic OR OR OR OR
DISJ FE 0 1 0 1
User interaction yes no no no no no no
CMGPS trigger no no no no no no no
IRIG-B/PTP no no no no no no no
trigger
Pulses / 1 1 1 1 1 1 1
seconds
Delay after Tr. 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s
On trigger jump no no no no no no no
to test end
Diagrams +90° +90° +90° +90° +90° +90° +90°
288,7
-90°V32,0 A 288,7
-90°V32,0 A 288,7
-90°V32,0 A 288,7
-90°V32,0 A 288,7
-90°V32,0 A 288,7
-90°V32,0 A 288,7
-90°V32,0 A
Comment
Test Module
Name: OMICRON State Sequencer Version: 4.30
Test Start: 29-jun-2024 14:50:05 Test End: 29-jun-2024 14:50:45
User Name: Manager:
Company:
Test Results
Time Assessment
Ignore
Name Start Stop Tnom Tdev- Tdev+ Tact Tdev Assess
before
REL1 State 2 State 3 State 4 10,00 s 300,0 ms 300,0 ms 10,19 s 193,7 ms +
REL2 State 5 State 6 State 7 20,00 s 300,0 ms 300,0 ms 20,19 s 193,2 ms +
Assess: + .. Passed x .. Failed o .. Not assessed
49 / 51
State 1
3 State 5 State 7
State 2 State 4 State 6
CMC356 V A/V
75
50
25 t/s
5 10 15 20 25 30 35
0
-25
-50
-75
-100
V L1-E V L2-E V L3-E
CMC356 I A/A
6
2 t/s
5 10 15 20 25 30 35
0
-2
-4
-6
I L1 I L2 I L3
CMC356 V B/V
75
50
25 t/s
5 10 15 20 25 30 35
0
-25
-50
-75
-100
VE
Bin. out 1
Bin. out 2
Bin. out 3
Bin. out 4
5 10 15 20 25 30 35
t/s
50 / 51
State 1
3 State 5 State 7
State 2 State 4 State 6
TRIP
DISJ FE
50BF
Bin. in 4
Bin. in 5
Bin. in 6
Bin. in 7
Bin. in 8
Bin. in 9
Bin. in 10
5 10 15 20 25 30 35
t/s
Cursor Data
Time Signal Value
Cursor 1 0,00 s <none> n/a
Cursor 2 37,80 s <none> n/a
C2 - C1 37,80 s n/a
Event recorder
Time Type Signal name Slope
0,00 s Input DISJ FE 0>1
1,345 s Input TRIP 0>1
1,370 s Input DISJ FE 1>0
1,493 s Input TRIP 1>0
11,56 s Input DISJ FE 0>1
14,59 s Input TRIP 0>1
14,61 s Input DISJ FE 1>0
14,73 s Input TRIP 1>0
34,80 s Input DISJ FE 0>1
Test State:
Test passed
Group end:79
51 / 51